CDS303 Setting VFD

The document provides configuration settings for a frequency converter including language, motor speed unit, operating state at power-up, reference range, minimum reference, digital input/output modes, relay functions, analog output scaling, oil return management settings like running time and boost duration.

Uploaded by

Mohd Fauzi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views1 page

CDS303 Setting VFD

The document provides configuration settings for a frequency converter including language, motor speed unit, operating state at power-up, reference range, minimum reference, digital input/output modes, relay functions, analog output scaling, oil return management settings like running time and boost duration.

Uploaded by

Mohd Fauzi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CDS303

PGR REVISED
0-01 Language [0] English
0-02 Motor Speed Unit [0] RPM
0-04 Operating State at Power-up (Hand) [1] Restarts the frequency converter with a saved local reference, after the
[1] Forced stop, ref=old mains voltage reappears and after pressing [Hand On].
[2] Forced stop, ref=0
0-40 [Hand on] Key on LCP [0] Disabled
1-00 Configuration Mode [0]
[0] Speed open loop
[3] Process
3-00 Reference Range [0] For positive values only
[0]Min. - Max
3-02 Minimum Reference [0] Enter the minimum reference. The minimum reference is the lowest
value obtainable by summing all references. Minimum reference is active
only when 3-00 Reference Range is set to [0] Min.- Max..
5-00 Digital In/Out Mode [0] Action on positive directional pulses.
[0] PNP
5-10 Terminal 18 Digital Input [8] Start
5-11 Terminal 19 Digital Input [0] No operation
5-14 Terminal 32 Digital Input [0] No operation
5-15 Terminal 33 Digital Input [0] No operation
5-40 Relay 2 - Function Relay [9] Alarm
6-50 Terminal 42 Output [137] Speed 4-20mA
6-51 Terminal 42 Output Min Scale 0% Scale for the minimum output (0 or 4 mA) of the analog signal at terminal
42. Set the value to be the percentage of the full range of the variable
selected in 6-50 Terminal 42 Output.
28-10 Oil Return Management [1] The oil return mechanism is active. [1] The oil return
[0] Off - No function mechanism is
[1] On - Oil return mechanism is active. active.
28-11 Low-Speed Running Time 60 min Running at low speeds for extended periods may result in inadequate oil Def 60
[1 – 1440 min] return to the compressor crankcase. Set this parameter to the maximum
running time the compressor is allowed to run at a speed below 3000
RPM/50 Hz. An oil return boost is performed each time the compressor
has been running at a low speed for this maximum time.
28-13 Boost Duration 30 s An oil return boost is performed at fixed time intervals to complement Default 30s
[10 – 120 s ] the oil return boosts triggered by inadequate flow speeds (28-11 Low-
Speed Running Time). The fixed interval boosts ensure that oil return
boosts are performed even when no boosts have occurred due to low
flow