CDS303 Setting VFD
CDS303 Setting VFD
PGR REVISED
0-01 Language [0] English
0-02 Motor Speed Unit [0] RPM
0-04 Operating State at Power-up (Hand) [1] Restarts the frequency converter with a saved local reference, after the
[1] Forced stop, ref=old mains voltage reappears and after pressing [Hand On].
[2] Forced stop, ref=0
0-40 [Hand on] Key on LCP [0] Disabled
1-00 Configuration Mode [0]
[0] Speed open loop
[3] Process
3-00 Reference Range [0] For positive values only
[0]Min. - Max
3-02 Minimum Reference [0] Enter the minimum reference. The minimum reference is the lowest
value obtainable by summing all references. Minimum reference is active
only when 3-00 Reference Range is set to [0] Min.- Max..
5-00 Digital In/Out Mode [0] Action on positive directional pulses.
[0] PNP
5-10 Terminal 18 Digital Input [8] Start
5-11 Terminal 19 Digital Input [0] No operation
5-14 Terminal 32 Digital Input [0] No operation
5-15 Terminal 33 Digital Input [0] No operation
5-40 Relay 2 - Function Relay [9] Alarm
6-50 Terminal 42 Output [137] Speed 4-20mA
6-51 Terminal 42 Output Min Scale 0% Scale for the minimum output (0 or 4 mA) of the analog signal at terminal
42. Set the value to be the percentage of the full range of the variable
selected in 6-50 Terminal 42 Output.
28-10 Oil Return Management [1] The oil return mechanism is active. [1] The oil return
[0] Off - No function mechanism is
[1] On - Oil return mechanism is active. active.
28-11 Low-Speed Running Time 60 min Running at low speeds for extended periods may result in inadequate oil Def 60
[1 – 1440 min] return to the compressor crankcase. Set this parameter to the maximum
running time the compressor is allowed to run at a speed below 3000
RPM/50 Hz. An oil return boost is performed each time the compressor
has been running at a low speed for this maximum time.
28-13 Boost Duration 30 s An oil return boost is performed at fixed time intervals to complement Default 30s
[10 – 120 s ] the oil return boosts triggered by inadequate flow speeds (28-11 Low-
Speed Running Time). The fixed interval boosts ensure that oil return
boosts are performed even when no boosts have occurred due to low
flow