CP TD12/15

Technical Data
CP TD12/15 Technical Data

© OMICRON electronics GmbH 2019. All rights reserved.


This technical data was extracted from the following manual: ENU 1226 05 01
All rights including translation reserved. Reproduction of any kind, for example, photocopying,
microfilming, optical character recognition and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON.
The document content represents the technical status at the time of writing and is subject to change
without prior notice.
We have done our best to ensure that the information given in this document is useful, accurate and
entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may
be present.
OMICRON translates this document from the source language English into a number of other
languages. Any translation of this document is done for local requirements, and in the event of a dispute
between the English and a non-English version, the English version of this document shall govern.

2 OMICRON
Technical data

1 Technical data
1.1 Technical data of the CP TD12/15 in combination with
the Control device
1.1.1 High-voltage output
Conditions: Signals below 45 Hz with reduced values possible. Capacitive linear loads.
Table 1-1: CP TD12 – High-voltage output

Terminal U THD I max S max t max


300 mA 3600 VA > 2 min
High-voltage output 0...12 kV AC <2%
100 mA 1200 VA > 60 min

Table 1-2: CP TD15 – High-voltage output

Terminal U THD I max S max t max


300 mA 4500 VA1 > 2 min
High-voltage output 0...15 kV AC <2%
100 mA 1500 VA > 60 min
1. Depending on Control device and power supply

1.1.2 Measurements
Test frequencies
Table 1-3: Test frequencies

Range Typical accuracy1


15...400 Hz error < 0.005 % of reading
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Only CPC 100 and CPC 80: TanDelta test card: Column "Hz" of the results table
Special displays in the frequency column "Hz" and their meanings:

*50 Hz (*60 Hz) Measurement mode suppressing the mains frequency interferences; doubles
the measurement time.
!30 Hz The selected test voltage is not available in Automatic measurement (applies to
frequencies below 45 Hz only).
?xx Hz Results with reduced accuracy, e.g., in case of a low testing voltage, influences
of partial discharge etc.

OMICRON 3
CP TD12/15 Technical Data

Filter for selective measurements


Conditions: f = 15 ... 400 Hz
Table 1-4: Filter for selective measurements

Filter Bandwidth Measurement time Stop band specification (attenuation)


f0 ± 5 Hz 2.2 s > 110 dB at fx = f 0 ± (5 Hz or more)
f0 ± 10 Hz 1.2 s > 110 dB at fx = f 0 ± (10 Hz or more)
f0 ± 20 Hz 0.9 s > 110 dB at fx = f 0 ± (20 Hz or more)

Test current (RMS, selective)


Table 1-5: Test current

Terminal Range Typical accuracy1 Conditions


IN A or error < 0.3 % of reading + 100 nA Ix < 8 mA
0...5 A AC
IN B2 error < 0.5 % of reading Ix > 8 mA
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
2. IN A (red) or IN B (blue), depending on the mode.

Test voltage (RMS, selective)


Table 1-6: CP TD12 – Test voltage

Condition: U > 2 kV
Range Typical accuracy1
2 kV...12 kV AC error < 0.3 % of reading + 1 V
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Table 1-7: CP TD15 – Test voltage

Condition: U > 2 kV
Range Typical accuracy1
2 kV...15 kV AC error < 0.3 % of reading + 1 V
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

4 OMICRON
Technical data

Capacitance Cp (equivalent parallel circuit)


Table 1-8: Capacitance Cp

Range Typical accuracy1 Conditions


error < 0.05 % of reading + 0.1 pF Ix < 8 mA, Utest = 2 kV...10 kV
1 pF...3 µF
error < 0.2 % of reading Ix > 8 mA, Utest = 2 kV...10 kV
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Dissipation factor DF (tan δ)


Table 1-9: Dissipation factor DF

Range Typical accuracy1 Conditions


f = 45...70 Hz, I < 8 mA,
0...10 % (capacitive) error < 0.1 % of reading + 0.005 % 2
Utest = 2 kV...10 kV
0...10000 % error < 0.5 % of reading + 0.02 % Utest = 2 kV...10 kV
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
2. Reduced accuracy of DF at mains frequency or its harmonics. Mains frequency suppression available by precisely selecting
a mains frequency of *50Hz or *60Hz in the "Hz" column.

Power factor PF (cos ϕ )


Table 1-10: Power factor Pf

Range Typical accuracy1 Conditions

2 f = 45...70 Hz, I < 8 mA,


0...10 % (capacitive) error < 0.1 % of reading + 0.005 % Utest = 2 kV...10 kV

0...100 % error < 0.5 % of reading + 0.02 % Utest = 2 kV...10 kV

1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
2. Reduced accuracy of PF at mains frequency or its harmonics. Mains frequency suppression available by precisely selecting
a mains frequency of *50Hz or *60Hz in the "Hz" column.

Phase angle ϕ
Table 1-11: Phase angle ϕ

Range Typical accuracy1 Conditions


-90 °...+90 ° error < 0.01 ° Utest = 2 kV...10 kV
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

OMICRON 5
CP TD12/15 Technical Data

Impedance Z
Table 1-12: Impedance Z

Range Typical accuracy1 Conditions


1 kΩ...1200 MΩ error < 0.5 % of reading Utest = 2 kV...10 kV
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Inductance Lx (equivalent serial circuit)


Table 1-13: Inductance Lx

Range Typical accuracy1


1 H...1000 kH error < 0.3 % of reading
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Quality factor QF
Table 1-14: Quality factor QF

Range Typical accuracy1


0...1000 error < 0.5 % of reading + 0.2 %
> 1000 error < 5 % of reading
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Power P, Q, S (selective)
Table 1-15: CP TD12 – Power P, Q, S

Range Typical accuracy1


0...3.6 kW error < 0.5 % of reading + 1 mW
0...3.6 kVAR error < 0.5 % of reading + 1 mVAR
0...3.6 kVA error < 0.5 % of reading + 1 mVA
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.

Table 1-16: CP TD15 – Power P, Q, S

Range Typical accuracy1


0...4.5 kW2 error < 0.5 % of reading + 1 mW

0...4.5 kVAR2 error < 0.5 % of reading + 1 mVAR

0...4.5 kVA2 error < 0.5 % of reading + 1 mVA

1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
2. Depending on Control device and power supply

6 OMICRON
Technical data

1.2 Mechanical data

Table 1-17: Mechanical data


Characteristic Rating
Dimensions CP TD12/15 460 × 317 × 223 mm
(W × H × D) 18.1 × 12.5 × 8.8 inches
Weight CP TD12 23 kg / 51 lb
CP TD15 24 kg / 53 lb

1.3 Environmental Conditions


Table 1-18: Climate
Characteristic Rating
Operating –10…+55 ºC / +14…+131 ºF
Temperature Storage and –20…+70 ºC / –4…+158 ºF
transportation
Max. altitude 2000 m
Relative humidity 5…95 %; no condensation, tested according to IEC 60068-2-78

Table 1-19: Noise Immunity

Characteristic Rating
Noise Immunity Electrostatic: 15 mA induced noise into any test lead without losing measurement
accuracy at maximum interference to specimen current of 20:1
Electromagnetic: 500 µT, at 60 Hz in any direction

OMICRON 7
CP TD12/15 Technical Data

1.4 Standards
Table 1-20: Standards conformity
Safety
Safety IEC / EN / UL 61010-1

EMC
EMC IEC/EN 61326-1 (industrial electromagnetic environment)
FCC subpart B of part 15, class A
Other
Shock IEC 60068-2-27 (operating), 15 g/11 ms, half-sinusoid
Vibration IEC 60068-2-6 (operating), 10...150 Hz, acceleration 2 g
continuous (20 m/s2); 10 cycles per axis
Humidity IEC/EN 60068-2-78 (5…95 % relative humidity, no condensation)

8 OMICRON