Technical Data
CP TD12/15 Technical Data
2 OMICRON
Technical data
1 Technical data
1.1 Technical data of the CP TD12/15 in combination with
the Control device
1.1.1 High-voltage output
Conditions: Signals below 45 Hz with reduced values possible. Capacitive linear loads.
Table 1-1: CP TD12 – High-voltage output
1.1.2 Measurements
Test frequencies
Table 1-3: Test frequencies
Only CPC 100 and CPC 80: TanDelta test card: Column "Hz" of the results table
Special displays in the frequency column "Hz" and their meanings:
*50 Hz (*60 Hz) Measurement mode suppressing the mains frequency interferences; doubles
the measurement time.
!30 Hz The selected test voltage is not available in Automatic measurement (applies to
frequencies below 45 Hz only).
?xx Hz Results with reduced accuracy, e.g., in case of a low testing voltage, influences
of partial discharge etc.
OMICRON 3
CP TD12/15 Technical Data
Condition: U > 2 kV
Range Typical accuracy1
2 kV...12 kV AC error < 0.3 % of reading + 1 V
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
Condition: U > 2 kV
Range Typical accuracy1
2 kV...15 kV AC error < 0.3 % of reading + 1 V
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
4 OMICRON
Technical data
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
2. Reduced accuracy of PF at mains frequency or its harmonics. Mains frequency suppression available by precisely selecting
a mains frequency of *50Hz or *60Hz in the "Hz" column.
Phase angle ϕ
Table 1-11: Phase angle ϕ
OMICRON 5
CP TD12/15 Technical Data
Impedance Z
Table 1-12: Impedance Z
Quality factor QF
Table 1-14: Quality factor QF
Power P, Q, S (selective)
Table 1-15: CP TD12 – Power P, Q, S
1. "Typical accuracy" means at temperatures of 23 °C ± 5 K, after a warm-up time of more than 25 min, and in a frequency range
of 45 Hz to 65 Hz, 98 % of all units have an accuracy which is better than specified.
2. Depending on Control device and power supply
6 OMICRON
Technical data
Characteristic Rating
Noise Immunity Electrostatic: 15 mA induced noise into any test lead without losing measurement
accuracy at maximum interference to specimen current of 20:1
Electromagnetic: 500 µT, at 60 Hz in any direction
OMICRON 7
CP TD12/15 Technical Data
1.4 Standards
Table 1-20: Standards conformity
Safety
Safety IEC / EN / UL 61010-1
EMC
EMC IEC/EN 61326-1 (industrial electromagnetic environment)
FCC subpart B of part 15, class A
Other
Shock IEC 60068-2-27 (operating), 15 g/11 ms, half-sinusoid
Vibration IEC 60068-2-6 (operating), 10...150 Hz, acceleration 2 g
continuous (20 m/s2); 10 cycles per axis
Humidity IEC/EN 60068-2-78 (5…95 % relative humidity, no condensation)
8 OMICRON