Power Cable Design, Construction, Testing
Power Cable Design, Construction, Testing
Power Cable Design, Construction, Testing
TESTING
1
POWER CABLE DESIGN, CONSTRUCTION, TESTING
1.0 INTRODUCTION:
Before of the introduction of Power cables power supply is to be extended from source to
any equipment through an Over head conductors made of Copper or Aluminium
Conductors. Later came and are used to extend the power supply from source to an
equipment such as Transformers, Motors, Distribution Panels etc. Initially power cables
were used for Medium & Low voltage application. However due to improving in the
manufacturing Technology and in particular insulation of cables, Power cables are
extensively used in EHV Transmission lines.
The following are the advantages in using Power Cables against Overhead conductor.
1) Greater freedom from interruption of service such as from Thunder storm,
Severe weather Conditions, Short Circuits Earth Faults due to Flashovers,
breaking of Conductors, Insulators, Objects falling across the lines etc.
2) Less liability of accidents to public.
3) Avoidance ugly appearance of overhead lines.
However the cost of installation of Power Cable is higher than Over Head Lines.
2
b) XLPE Cable.
3 core PVC Insulated 3 1/2 core PVC insulated 4 core PVC insulated
Un armoured armoured un armoured
H H H H H
I I I I I
-- C--C--C-- C--C
I I I I I
H H H H H
H H H
I I I I
-- C-- C --C -- C
H H I H
H H I H
-- C-- C --C -- C
I -- H -- I -- H
5.1 LV Power cables sizing is carried out in order to meet the continuous load current and
short circuit conditions.
3
5.2 Eg for a motor feeder of rated 0.55 KW.
Considering 1 run of 4 core x 2.5 Sq mm XLPE, copper cable is used to feed to 415 v load
rated 0.55 KW.
a) Running Voltage drop Calculation:-
Motor actual rated KW
Running Current (I) required to = --------------------------------- Amps.
fed power to motor √ x 0.415 x 0.85 x 0.9
0.55
= ---------------------------- = 1 amp.
√3 x 0.415 x 0.85 x 0.9
A.C Resistance (R) at 90 0 C = 9.48 Ohm/Kms ----------from the table of Cable Manufacturer.
Reactance (X) at 50 Hz = 0.0985 Ohm/ Kms ----------- from the table of Cable Manufacturer.
Load power Factor (Cos Ø) = 0.85.(during Motor running condition).
Load power Factor (Cos Ø) = 0.30.(during starting of Motor.).
(R Cos Ø + X Sin Ø)
Voltage Drop = √ 3 x I x ----------------------------- x L Volts
(N x 1000)
Maximum allowable Voltage drop during running condition = 3 % of rated voltage i.e. 415
V +/- 3 % = 427.5 or 402.5 volts.
So the maximum distance that can be laid 3 x 415
for this KW rating at 415 Volts is = ------------------------- = 889.28 mtrs.
100 x 0.014
(R Cos Ø + X Sin Ø)
Voltage Drop = √ 3 x I x ----------------------------- x L Volts
(N x 1000)
Maximum allowable Voltage drop during running condition = % of rated voltage i.e. 415 V
+/- 10 % = 456.5 or 373.5 volts.
4
So the maximum distance that can be laid
10 x 415
for this KW rating at 415 Volts is = ------------------------- = 1360 mtrs.
100 x 0.0305
c) Calculation for De rated current:-
Current de rating of a given size of XLPE cable per run in free air at ambient temp at 40
deg C from Manufacturer's data sheet, two stage de rating factor is applied.
i) Temperature De rating Factor:
Temperature de rating factor (Kt)for 50 deg C ambient temp = 0.89 (as per XLPE
insulated LT Power Cable Catalogue.
ii) Group de rating Factor:
Group De rating factor (Kg) is taken as = 0.68 (Empirical Value).
Overall de rating factor K = Kt x Kg = 0.89 x 0.68 = 0.6.
5
Here the fuse provides protection against short circuit. Hence the energy experienced by
the cable during short circuit condition must be more than the 'Let Through ' energy
allowed by fuse before it melts on a short circuit fault.
The short circuit Current Rating of 4c 2.5 sq mm cable is 0.36Ka for 1 sec.
So the derived value of max energy the cable can withstand under SC fault = 0.36 x 0.36 =
0.1296 KA2 - sec.
For 0.55 KW motor HRC fuse rating as per table is 4 amps & let through energy is 0.01
KA2 - sec. Hence 1 4C 2.5 sq mm for a distance of 889 mtrs, cable used is in order.
The selection of for HT cable is that the max value of 'Let Through' energy of HT fuse during
6
short ckt, as mentioned in Table - 1 & 2 has to be less than the energy that the cable can
withstand during a short ckt fault. By comparing the respective values mentioned in Table 1 7
2 it can be said that 50 mm 2 XLPE HT Cable is suitable for use in Vacuum contactor feeders
backed up by an HT fuse rated equal or less than 630 amps.
(R Cos Ø + X Sin Ø)
Voltage Drop (dv) = √ 3 x I x ----------------------------- x L Volts
(N x 1000)
Where ,
dv= Voltage drop in cable (in Volts).
750
Running Current (I) = ---------------------------- Amps.
√ 3 3.3 x 0.85 x 0.9
= 171.5 Amps.
A.C Resistance (R) at 90 deg C = 0.16 Ω/Kms.
Reactance (X) at 50 Hz = 0.0737 Ω/Kms.
No of runs of Cable being used.= 1
Load P.f (Cos Ø) = 0.85 during running , Sin Ø= 0.53
Load P.f (Cos Ø) = 0.3 during starting.
70.5
% Voltage drop = --------- x 100 = 2.1 % i.e ≤ 3 % Hence OK.
during running 3300
285
% Voltage drop = --------- x 100 = 8.6 % i.e ≤ 10 % Hence OK.
during starting 3300
c) Type Tests:-
i) Conductor Resistance Test
ii) Annealing Test [For Copper]
iii) Tensile strength Test [For Aluminium]
iv) Wrapping Test [For Aluminium]
v) Thickness of Insulation & Sheath.
vi) Tensile Strength & Elongation Test of Insulation & Sheath.
vii) Ageing in air Oven of Insulation & Sheath.
viii) Shrinkage Test of Insulation & Sheath.
ix) Hot Deformation Test of Insulation & Outer Sheath.
x) Heat Shock Test of Insulation & Outer Sheath.
xi) Loss of Mass Test of Insulation & Outer Sheath.
xii) Oxygen & Temperature Index Test
xii) Smoke Density Test
xiv) HCL Gas Generation Test
xv) Insulation Resistance Test.
xvi) High Voltage Test [water Immersion & at Room temperature]
xvii) Flammability Test.
d) Optional Tests - The constitute optional tests: following shall
1) Cold bend test,
2) Cold impact test, and
3) Armour resistance test ( for other than mining cables ).
4) Additional Ageing Test.
10