PD Monitoring System Manual ENU
PD Monitoring System Manual ENU
PD Monitoring System Manual ENU
2
Contents
Contents
Limitation of Liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Principle Use According to Regulations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Orderly Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operator Qualifications and Safety Standards. . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety Rules for the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1 The Monitoring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
1.1 Designated Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.2 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.3 Monitoring System Design for Rotating Machines with the OMS 600 . . . . . . . . 16
1.4 Monitoring System Design for Short Cable Links with the OMS 600. . . . . . . . . 18
1.5 Normalization Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.6 Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2 Operating the Monitoring Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.1 Put the Monitoring Server into Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.1.1 Connect the Monitoring Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.1.2 Operator Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.1.3 Log On to Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.2 Start the Monitoring Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.3 Access the Monitoring Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.3.1 Access the Monitoring Web Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.3.2 Access the Monitoring Web Application Locally . . . . . . . . . . . . . . . . . . . . . . . . 38
3 Monitoring Software Argos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
3.1 Header . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.2 Task Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.2.1 Assets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.2.2 Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.2.3 Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3.2.4 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3.3 Charts and Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
3
Operation Manual for Rotating Machine PD Monitoring
4
Contents
5
Operation Manual for Rotating Machine PD Monitoring
6
Limitation of Liability
Limitation of Liability
This warranty is made in lieu of all other warranties, representations or
conditions, whether expressed or implied, including, without limitation,
merchantability or fitness for a specific purpose. The remedy set forth herein
shall be the sole, exclusive remedy with respect to OMICRON Energy
Solution GmbH products. No person is authorized to make any other warranty
or representation concerning the performance of OMICRON Energy
Solution GmbH products or extend or enlarge the warranty contained herein.
Under no circumstances will OMICRON Energy Solution GmbH be liable for any
direct, indirect, special incidental or consequential damages, even if OMICRON
Energy Solution GmbH is notified of the possibility of such damages, including,
but not limited to, any loss of revenue, loss of profit, or loss of data, whether
based upon any alleged breach of warranty, representation or condition,
contract, or any other conduct including negligence (intentional or otherwise).
OMICRON Energy Solution GmbH shall not be liable for any claims made by a
third party or made by you for a third party.
If this warranty is applied in a jurisdiction that does not allow exclusions or
limitations of liabilities as defined above, only those limitations and exclusions
that are not allowed under the jurisdiction shall be void, and all other limitations
and exclusions shall remain in force. Some jurisdictions may grant the end user
purchaser other rights, which this warranty does not limit.
7
Operation Manual for Rotating Machine PD Monitoring
8
Using This Manual
Symbol Description
Caution: Equipment damage or loss of data possible
9
Operation Manual for Rotating Machine PD Monitoring
10
Safety Instructions
Safety Instructions
Before operating the Monitoring System or the system components, read the
safety instructions in this manual carefully. Do not operate the Monitoring
System without understanding all safety instructions. If you do not understand
the safety information completely, contact OMICRON Energy Solution GmbH
before proceeding.
Orderly Measures
The following orderly measures apply to using the Monitoring System:
• The Operation Manual for Rotating Machine PD Monitoring always has to be
available on site where the Monitoring System is operated.
• The users of the Monitoring System must read this manual before working
with the Monitoring System and observe the safety, installation, and
operation instructions therein when operating the Monitoring System.
• Do not modify, extend, or adapt any component of the Monitoring System.
• Operate the Monitoring System only with original system components.
• Only OMICRON Energy Solution GmbH personnel or personnel trained and
certified by OMICRON Energy Solution GmbH are allowed to commission
and configure the Monitoring System.
11
Operation Manual for Rotating Machine PD Monitoring
12
Safety Instructions
Operation
Observe the following safety instructions when operating the Monitoring
System:
• When putting the Monitoring System into operation, follow the instructions in
1 "The Monitoring System" on page 15.
• Do not insert any objects (for example, screwdrivers) into the input or output
sockets.
• Operate the Monitoring System only under ambient conditions specified in
the "Technical Data" chapters of the respective system components.
• Do not operate the Monitoring System in the presence of explosives, gas, or
vapors.
• Opening the housing of the system components invalidates all warranty
claims, if not explicitly allowed in this manual.
• If the Monitoring System or any of the system components does not seem to
function properly, turn the Monitoring System off, if feasible, and contact the
OMICRON Energy Solution GmbH technical support.
13
Operation Manual for Rotating Machine PD Monitoring
14
The Monitoring System
15
Operation Manual for Rotating Machine PD Monitoring
The acquisition units have two optical ports to support the FO ring architecture:
a receive port and a transmit port. The measurement data is sent through the
transmit port over the patch panels to the receive port of the next networked
acquisition units. Finally, the control unit located in the connection panel in the
server cabinet is connected to the monitoring server through USB 2.0 interface
to convert the FO network protocol.
The PD data transmitted by the control unit is processed by the monitoring
software and displayed as apparent charge magnitude. Based on the expert
knowledge, a special filtering technique and analyzing algorithms are
implemented in the monitoring software and the Monitoring System displays the
apparent charge magnitude and other important parameters necessary for the
determination of the asset insulation status.
16
The Monitoring System
17
Operation Manual for Rotating Machine PD Monitoring
B2
B1 B7
B3 B4
B8
B9
B5
B6
18
The Monitoring System
19
Operation Manual for Rotating Machine PD Monitoring
4. Connect a calibrator (for example, the CAL 542) to one of the phases,
connecting one lead to the relevant phase and the second one to ground
(main grounding of the machine).
20
The Monitoring System
Stator
winding
U PD sensor
Star point
Line
V PD sensor
W PD sensor
Stator core-
frame
Capacitive Inductive
coupler coupler
Figure 1-4 Example of the normalization scheme with the machine star
point connected straight to ground
21
Operation Manual for Rotating Machine PD Monitoring
The following figure shows a snapshot of the Calibration tab, the standard
pattern acquired during normalization and the normalization pulse (example
coming from a lab test).
1.6 Cleaning
Warning: Before cleaning the Monitoring System and its accessories, always
disconnect the devices.
To clean the Monitoring System and its accessories, use a cloth dampened with
isopropanol alcohol.
22
Operating the Monitoring Server
23
Operation Manual for Rotating Machine PD Monitoring
Figure 2-1 Rear view of the OMS 801 LARGE - HP DL380 G7 monitoring
server
24
Operating the Monitoring Server
25
Operation Manual for Rotating Machine PD Monitoring
OMS 801 MEDIUM The following figure shows the connections of the OMS 801 MEDIUM -
- HP ML110 G7 HP ML110 G7 monitoring server.
Figure 2-2 Rear view of the OMS 801 MEDIUM - HP ML110 G7 monitoring
server
26
Operating the Monitoring Server
27
Operation Manual for Rotating Machine PD Monitoring
OMS 801 SMALL - The following figures show the connections of the OMS 801 SMALL -
HP EliteBook HP EliteBook 8760w monitoring server.
8760w
Left view
Right view
Figure 2-3 Side views of the OMS 801 SMALL - HP EliteBook 8760w
monitoring server
28
Operating the Monitoring Server
29
Operation Manual for Rotating Machine PD Monitoring
Front view
Rear view
Figure 2-4 Front and rear views of the OMS 801 SMALL -
HP EliteBook 8760w monitoring server
Table 2-6 OMS 801 SMALL - HP EliteBook 8760w Front and Rear Panel
Connections and Indicators
Identifier Description
1 Wireless-LAN LED indicator
2 Power/standby LED indicator
3 Battery charging LED indicator
4 HDD/ODD activity / HP 3D DriveGuard LED indicator
5 Display release latch
6 Secure digital/MMC slot
7 Stereo speakers
8 RJ-11/modem port
9 Vents
10 Power connector
30
Operating the Monitoring Server
The following table shows the technical data of the OMS 801 SMALL -
HP EliteBook 8760w monitoring server.
31
Operation Manual for Rotating Machine PD Monitoring
OMS 801 The following figures show the connections of the OMS 801 X-SMALL -
X-SMALL - HP EliteBook 8570p monitoring server.
HP EliteBook
8570p
Right view
Rear view
Figure 2-5 Right and rear views of the OMS 801 X-SMALL -
HP EliteBook 8570p monitoring server
32
Operating the Monitoring Server
The following table shows the technical data of the OMS 801 X-SMALL -
HP EliteBook 8570p monitoring server.
Caution: Do not change the server name. Changing the server name can
cause serious problems.
The web application provided through the OMICRON Energy Solution GmbH
monitoring software suite intensively uses services and frameworks installed on
the server. We cannot guarantee that changes done by updates do not have
adverse impacts on software functionality.
33
Operation Manual for Rotating Machine PD Monitoring
Caution: Do not hard reset the server if not necessary. Though the setup is
resistant to database corruption, it is not immune. Unfinished writes might harm
the system (“sync problem”).
34
Operating the Monitoring Server
35
Operation Manual for Rotating Machine PD Monitoring
Remote Desktop All precreated user accounts are allowed to remotely connect to the monitoring
Connection server with proper credentials.
With the use of the Remote Desktop Protocol (RDP), you can access the
Microsoft Terminal Services of the monitoring server by using mstsc.exe
included in the Windows operating system or other RDP clients.
Note: To start and stop the monitoring software, Administrator credentials are
necessary.
36
Operating the Monitoring Server
You can verify the status of the system by using the services.msc process (see
the following figure). This is a Windows program called Services. You can
search this program by using the search box under Windows Start Menu.
37
Operation Manual for Rotating Machine PD Monitoring
By using the web access, detailed information about the monitored system
(current and historical data) can be supervised. With standard web browsers (for
example, Internet Explorer) operators and supervisors can log on to the
Monitoring System from various locations and machines inside the trusted
network.
38
Monitoring Software Argos
In the following sections the elements and parts of the Argos GUI are described
and their effect on the monitoring process is explained.
3.1 Header
The header displays the project/customer and location names. In addition, it
provides access to the user specific system settings.
39
Operation Manual for Rotating Machine PD Monitoring
To set the user specific system settings, click Settings in the header to open the
Settings dialog box.
With Available Values, you can select the values to be displayed in the
visualization panel and with View Default Value, you can select the values to
be displayed in the navigation bar. You can select one or more of the following
values: PD Events, QAvg, QIec and VRms.
Under Language, you can select the language of the Argos GUI.
By clicking Change Password in the navigation bar, you can change the
password.
40
Monitoring Software Argos
You must confirm all operations by clicking Save. After that, the system will take
over the changes and continue to operate with the new settings.
Note: In some cases the Monitoring System needs up to one minute to take over
the changes. In this case refresh the GUI in the browser after one minute.
3.2.1 Assets
The Assets tab provides an overview of the status of all monitored assets and
currently measured values. In the navigation bar on the left site of the Argos
workspace, all assets are listed with asset name (for example, Generator 1,
Generator 2, …) and asset location (for example, G1, G2, …). Next to the asset,
the highest measured value is displayed and colored according to its status:
• Green measured value within the normal range.
• Yellow measured value violates the warning threshold.
• Red measured value violates the alert threshold.
• Grey no value available or value out of date
41
Operation Manual for Rotating Machine PD Monitoring
The red squares with numbers next to the asset name ( 1 ) represent the
number of warnings or alerts registered at this location. The square next to the
Assets tab (Asset 1) gives an overall sum of warnings or alerts registered on
all assets. By clicking on one of these squares, the Alert History table with list
of warnings or alerts will appear.
The Alert History table shows the names of location alerts, time stamp of
occurrence, alert type and confirmation status of these alerts. All alerts can also
be sorted using these attributes by clicking on the appropriate column name.
You can confirm the alert by clicking Confirm to acknowledge the alert but the
42
Monitoring Software Argos
confirmation does not delete the alert from the database. Since alerts occurring
during a certain time span are summarized, you can see the details related to
these alerts, by clicking the + symbol as shown in the following figure.
You can configure the following features of the Alert History table to get more
information (see also "User Interface" on page 66):
• Number of elements shown on one page of the table defined by the general
setting Default Grid Page Size
• Determine whether the confirmed alerts should be displayed in the table by
using Display Confirmed Alerts
• Date of the displayed alerts by using Display Alerts From Date
43
Operation Manual for Rotating Machine PD Monitoring
If you expand the table in the visualization panel by clicking the + symbol, you
can see the current values for each measuring point.
Figure 3-10 Current measured quantities for each measuring point (cables)
44
Monitoring Software Argos
By clicking the location name in the navigation bar, a schematic view of the
location and the setup of the Monitoring System and sensors appear in the
visualization panel (see the following figure, green arrow). You can navigate
form one to another location by clicking the location name in the navigation bar
on the left site.
Figure 3-11 Asset view with view ports and links to monitoring trend charts
This figure displays also three view ports showing the newest measured values
for each measurement point (phase) of the particular asset. The table includes
the location name (for example, L1, L2, and L3) and the measured values (for
example, PDEvent, Qiec, and so on).
By clicking Charts, you can display a trend diagram of the values acquired
within the continuous monitoring mode. For usage of this diagram, see
3.3 "Charts and Diagrams" on page 69.
There are two additional buttons on the upper right corner of the visualization
panel: Historical Charts and Alert History. By clicking Alert History, you can
display a list with all warning and alert entries described earlier. By clicking
45
Operation Manual for Rotating Machine PD Monitoring
Historical Charts, you can display a trend diagram showing the data acquired
during the periodic monitoring mode. For Handling and usage of these
diagrams, see 3.3 "Charts and Diagrams" on page 69.
3.2.2 Devices
The Devices tab provides various monitoring setting options and shows the
measuring configuration of all acquisition units of each channel.
46
Monitoring Software Argos
The configuration area in the navigation bar is divided into the periodic (red
rectangle) and the continuous measurement setting modes (blue rectangle).
Figure 3-13 Devices tab: configuration of the periodic monitoring mode for
all channels of one device (generators)
47
Operation Manual for Rotating Machine PD Monitoring
After clicking Generator 1 or Cable 1/C1 in the periodic configuration area, the
configurations will be divided into three major areas: Schedules, Rules, and
Configuration:
• Schedules determine how frequently the measurement and data storage
should be performed (for example, every 5 minutes). Click Edit, and then
click the calender symbol to open a schedule setting window for easy
and convenient time setting. You can choose a time-based or calendar-
based selection.
48
Monitoring Software Argos
These configurations are general for all channels of one measuring location. By
clicking on one channel you can see and/or create individual configurations valid
for this channel only.
Since the bandwidth of the PD frequency-domain filter can differ between the
channels, set this variable for each channel individually as shown in the
following figures.
49
Operation Manual for Rotating Machine PD Monitoring
By clicking in the continuous configuration area, you can access the general
configuration for the continuous monitoring mode with the Schedules, Rules,
and Configuration areas as for the continuous mode. These configurations are
valid for all channels.
Acquisition time has three different configuration types:
• Default: Only one per device, settings apply to all measurements of this
device. Acquisition time must be 0.
• Continuous: Only one per device, settings apply to all continuous
measurements of this device. Acquisition time must be 0.
• Periodic: Multiple configurations per device are possible. Acquisition time
specifies the duration of value acquisition within the periodic measurement.
The periodic configuration is used to accumulate data for histograms like
3 PARD or PRPD.
50
Monitoring Software Argos
51
Operation Manual for Rotating Machine PD Monitoring
In analogy to the periodic mode, the configurations of the continuous mode are
individual for each channel. After clicking one channel, you can see and/or
create individual configurations valid for this channel only. You can change and
delete the configurations by clicking Edit and Delete respectively. To add new
configurations, click Create.
Device Error If the Monitoring System and/or an acquisition unit fail(s), a notification sign ( 1 )
appears next to the Device tab.
The notification sign indicates the number of the currently active system errors.
After clicking the notification sign, a table with the error detail history
(Alert History) with the date, time and short description of the current errors will
appear as shown in Figure 3-20 "System and device error history" on page 52.
Since the cause of the malfunctioning of the entire Monitoring System can be
software- or hardware-related, the notification of alerts is divided (see
Figure 3-20 "System and device error history") into:
• System alerts: Weak or no connection between the system components,
server outage or bad performance, software components error (Argos core,
database, web service)
• Device alerts: Outage of one or more acquisition units or channels
As soon as an error is repaired, the sign will vanish and the entry will be removed
from the Alert History table.
52
Monitoring Software Argos
The Monitoring System error messages are defined according to the error status
as shown in the following table.
53
Operation Manual for Rotating Machine PD Monitoring
54
Monitoring Software Argos
3.2.3 Reporting
On the Reporting tab you can export the measured results for a selected time
range and for a selected location. You can save reports in Microsoft Excel,
Microsoft Word or in pdf format.
The Argos customizable report generator module provides the following
features:
• Remarks
• Time range selection (date from, date until)
• Selection of location for which a report should be generated
• Full support of Microsoft Excel, Microsoft Word and pdf format
• Support of direct printing from the report generator module
55
Operation Manual for Rotating Machine PD Monitoring
56
Monitoring Software Argos
3.2.4 Configuration
Caution: Misconfiguration of the Configuration settings can seriously impact
the measurement and the system performance. Wrong handling may cause
system outage and error. Only the Admin user should make settings on the
Configuration tab.
57
Operation Manual for Rotating Machine PD Monitoring
Click Edit to rename and either activate or deactivate an asset (see the following
figure). In case of a shutdown of one or more assets, you can interrupt the data
acquisition on this asset by selecting the Active check box.
58
Monitoring Software Argos
Each location must have a type (for example, winding termination) and a name.
A location can be assigned to only one asset.
• Measuring Points are places within a location where sensors are attached.
In case of a 3-phase rotating machine, there are usually three measuring
points, phase windings, which are assigned to one of the phases. Like
59
Operation Manual for Rotating Machine PD Monitoring
60
Monitoring Software Argos
• Device describes the name and type of the acquisition unit used for
monitoring.
• Channels shows a list with the name, type and number of used channels of
the acquisition units (see the following figure).
Again, each channel must have a unique channel number, name, and it has to
be assigned to a particular measuring point (figure 3 26).
Measurements With Measurements, you can configure measurements, jobs, schedules and
rules which are the same options as on the Devices tab (see 3.2.2 "Devices" on
page 46). After clicking Configuration, Jobs, Schedules, or Rules in the
navigation bar, the visualization panel will display a table with an overview of the
configured elements. You can change and delete the elements by clicking Edit
and Delete respectively (if permission is granted by the user role). To add new
elements, click Create at the bottom of the table.
61
Operation Manual for Rotating Machine PD Monitoring
System
User
Management
After clicking Details, a window (see Figure 3-35 "User details" on page 63) with
user details such as email, roles, log and activity protocol will appear.
• Admin user account can be used for setting up and maintaining the system.
• Administrators can be divided into three roles: Administrator, Operator and
User´s Administrator. These roles allow complete configuration control over
the entire system, including creation of new users, resetting the user
passwords, and locking/unlocking the user accounts.
• Omicron user has the same rights and roles as the Admin user but with a
different access account to the system.
• Operator user is a person who works with computers on a daily basis, for
example, the asset system engineer. In general, operators observe the
62
Monitoring Software Argos
measured data, alert and warning logs and system status massages. This
user is allowed to set (edit and delete) the measurement configuration as
described in 3.2.2 "Devices" on page 46 and "Measurements" on page 61,
but is not allowed to configure the system as described in "Topology" on
page 58.
2. In the Create User dialog box, enter the name (for example, Asset
Engineer), email, and password for the new user. You can also assign a
certain role to the user.
3. Click Save to create the user. If you want to create a new role for this user,
follow the next steps.
63
Operation Manual for Rotating Machine PD Monitoring
In the Create Role dialog box, type the role name (for example, PD Engineer),
and then click Save. The new role will appear in the Roles table.
6. In the Roles table, click Settings to set the available values accessible to
this role, for example, QAvg and QIec.
64
Monitoring Software Argos
7. In the Users table (see Figure 3-34 "User administration" on page 62), click
Edit next to the new user (Asset Engineer).
8. In the Edit Asset Engineer dialog box, select PD Engineer, and then click
Save.
9. In the Users table, click Details next to the new user to see the credentials
of the Asset Engineer user (see the following figure) who is not allowed to
change anything in the system or measurement configuration because the
user account was not added neither to the Operator nor Administrator roles.
This user account is only allowed to see the PD related values, such as QIec
and QAvg.
65
Operation Manual for Rotating Machine PD Monitoring
User Interface With User Interface, you can configure the layout of the GUI by using the
following elements: Settings, View Templates, and View Ports (see the
following figure).
With Settings, the Admin user can configure the user interface such as the
application name and project name displayed in the header.
Available Values define the values to be displayed on the Assets tab.
You can configure the following features of the Alert History (see 3.2.1 "Assets"
on page 41):
• The size of the Alert History table or the number of rows can be configured
by using Default Grid Page Size. The default value is 10.
• Whether the already confirmed alerts should be displayed by using
Display Confirmed Alerts.
• The date since when the alerts should be shown by using
Display Alerts From Date.
66
Monitoring Software Argos
View Templates are used to display the appropriate image for a location in the
Assets tab. The Argos GUI supports several types of locations with a particular
view template. You can find the appropriated images under:
C:\[Argos installationfolder]\Web\Content\templates\location\themes\default\
[ViewTemplateName].
In the same folder an image.map must be provided. The image.map is a file
describing how many view ports the image supports.
Caution: Misconfiguration of the View Ports settings can seriously impact the
measurement and the system performance. Wrong handling may cause
system outage and error. Although the Operator user is allowed to access
these settings, it is recommended that only the Admin user changes the
configuration and settings in this domain.
With View Ports, you can configure view ports. View ports are areas of an
image in the view template.
View ports
67
Operation Manual for Rotating Machine PD Monitoring
Exports With PD Measurements under Exports, you can export the measured values
(QIec, QAvg, Vrms, PDEvents) in CSV format (comma-separated values). CSV file
stores data (numbers and text) in plain text form. As a result, such a file is easily
readable and can be opened by any spreadsheet program.
68
Monitoring Software Argos
With Locations, you can select which asset data should be exported, and with
From and Until, you can determine the time period of acquired data.
Note: From and Until are related to UTC Coordinated Universal Time which
may have time offset to the local server time.
Once the data is exported and saved to a local hard drive, it can be copied and
post processed with any spreadsheet (see the following figure) or diagram
calculating program (for example, Gnumeric, Microsoft Excel, Lotus, and so on).
69
Operation Manual for Rotating Machine PD Monitoring
Vertical Y-axis labeling is provided for each of the axes where voltage, charge
and impulse quantity are quantified. The horizontal X-axis plots the actual date
and time at which the quantities were measured (see Figure 3-47 "Charts for the
continuous measurement mode").
70
Monitoring Software Argos
The display panel contains all setting elements that control the curve and
visualizations for all values of the selected channel. Display properties, such as
curve and background color can be individually configured.
You can interrupt constant updating of the chart by clicking Pause in the top-left
corner of the window. Next to this button there is a drop-down menu where you
can select how many values are to be displayed in the diagram; there is a
minimum of 10 or a maximal of 100 points. Next to this menu there is another
drop-down menu where you can select the background color of the diagram
between bright grey and dark grey.
71
Operation Manual for Rotating Machine PD Monitoring
Below the diagram there is a field with a variety of selection options that control
the graph panel. With Asset, Location, Measuring Point, and Values, you can
determine which curves from each source should be displayed.
You can also display the threshold limit for this location by checking the
Thresholds box and change the color of the curves by clicking the colored box.
Curves can be removed by clicking Remove and added by using Add at any
time (see lower-right corner of the window).
By using the symbols in the top-right corner of the diagram, you can print
the graph or save it as a PNG, SVG or JPEG image. The system sets the name
of the graph according to the time range of the data display.
you can also select any other time window for the data trend using the standard
time selection options shown in the following figure.
By using the two slider cursors below the diagrams, you can zoom into a
particular diagram area of interest.
72
Monitoring Software Argos
You can also zoom into a particular area of the diagram using the drag and drop
function. To do this, draw a rectangle by clicking and dragging the mouse across
the desired area of the screen. The selected area will be displayed in an
enlarged view.
The ruler function is also implemented in the trend view and appears every time
the mouse curser crosses a curve field.
To show the diagrams (PRPD, 3PARD, 3D PRPD), you can click one of the dots
in the desired time stamp in the curve. You can also select different diagrams
and change and adapt its resolution.
73
Operation Manual for Rotating Machine PD Monitoring
Each diagram can be printed and saved in different formats as described earlier
in this chapter by clicking the symbol in upper-right corner of the diagram
window.
The system sets the name of the diagram according to the diagram type, asset,
location and measuring point name and the time stamp of the diagram
acquisition. PNG is the default format of the saved diagram.
74
Monitoring Software Argos
3.4 Backup
In order to recover recorded data and system configuration after system failure
(for example, server hard disk failure), it is important to store different files and
folders in a secure location outside the Argos server. This can be accomplished
be using either a portable hard disk connected via USB interface or a direct
network connection.
3.4.1 Database
Database backups are created each night and backups older than two days are
removed automatically. The database backup contains all measured data and
the Argos software configuration. It is strongly recommended to create an
external copy of the database backup on a regular basis.
75
Operation Manual for Rotating Machine PD Monitoring
76
System Components
4 System Components
4.1 Monitoring Server
The monitoring server runs the monitoring software Argos and provides
configuration and control features for setting the Monitoring System parameters
according to the specific needs of the monitored high-voltage equipment. For
detailed information, see 2.1.1 "Connect the Monitoring Server" on page 24.
The technical data of the monitoring server depends on the server hardware life
cycle and customer demand. The main differentiation is explained in
2.1.1 "Connect the Monitoring Server" on page 24.
77
Operation Manual for Rotating Machine PD Monitoring
78
OMS 600 Module
79
Operation Manual for Rotating Machine PD Monitoring
80
OMS 600 Module
Each acquisition unit is equipped with two LEDs for displaying the unit’s status.
The red LED indicates both the power supply status and the status of the fiber-
optic link. A flashing red LED indicates that the acquisition unit is powered and
ready to be connected to the computer. If the acquisition unit is connected to a
computer and the computer is running the MPD & MI software, the red LED
stops flashing and instead remains continuously on. This indicates that the
acquisition unit has a good connection to the computer and that it can receive
data on the fiber-optic link.
As soon as the computer has detected and configured all connected acquisition
units, the green LED on each unit turns on. This indicates that the acquisition
unit is ready to perform measurements.
The following tables show the technical data of the splice module
81
Operation Manual for Rotating Machine PD Monitoring
82
OMS 600 Module
Table 4-5 Technical Data of the OMS 600 Acquisition Unit (3 Channels)
Characteristic Rating
System noise <15 fC
Maximum double pulse resolution <200 ns
Maximum pulse rate 1.5×106 pulses/s
per fiber-optic network
PD event resolution <2 ns
Time domain
Integration range 100 ns…8 µs
Frequency domain
Center frequency 0 Hz…32 MHz free adjustable
Bandwidth (standard) 9 kHz, 40 kHz, 100 kHz, 160 kHz,
300 kHz, 650 kHz, 1 MHz, 1.5 MHz
Bandwidth (with broadband filters) 9 kHz, 30 kHz, 100 kHz, 300 kHz,
1 MHz, 3 MHz
V input
Frequency range 0 Hz…4.3 kHz
Impedance 1 µF//1 MΩ
Voltage 33 Vrms (max.)
Dynamic range 102 dB
PD input
Frequency range 0 Hz…20 MHz
Impedance 50 Ω
Voltage 10 Vrms (max.)
Dynamic range 132 dB (overall)
70 dB (per input range)
83
Operation Manual for Rotating Machine PD Monitoring
84
OMS 600 Module
Figure 4-4 The drilling template for the OMS 600 module
85
Operation Manual for Rotating Machine PD Monitoring
86
OMS 600 Module
87
Operation Manual for Rotating Machine PD Monitoring
4. Wrap the fiber-optic cable around the splice module, connect the OMS 600
module, and then fix the fiber-optic cable with a cable tie to the splice module.
Note: The fiber-optic connection to the OMS 600 module is system specific.
For more information, see the Fiber-Optic Plan shipped with the Monitoring
System.
88
OMS 600 Module
5. Fix the PD sensor cable with the flat wrenches 19 mm and 20 mm to the
OMS 600 housing.
7. Fix the power cable to the OMS 600 with the flat wrenches 19 mm, 20 mm,
27 mm and 30 mm.
Warning: Observe the safety instructions and safety rules (see "Safety
Instructions" on page 11).
Power cable*
Fiber-optic inlet
Fiber-optic outlet
Power cable*
*For example, ÖLFLEX® ROBUST 200 (PG16 clamping range 9…14 mm or PG M16×1.5
clamping range 4.5…10 mm)
89
Operation Manual for Rotating Machine PD Monitoring
8. Connect the power cable to the PCB terminal block with the slotted
screwdriver 0.6×3.5 mm.
Warning: Observe the safety instructions and safety rules (see "Safety
Instructions" on page 11).
Note: Fix the power cable with the zip tie as shown in the figure.
9. Fix the grounding cable to the OMS 600 housing with the cross screwdriver
PZ1 (5 mm).
10.Close the OMS 600 housing with the cross screwdriver PZ1 (5 mm).
Note: Ensure that the gasket is intact and in place.
90
MCT 110 High-Frequency Current Transformer
91
Operation Manual for Rotating Machine PD Monitoring
4.3.1 Characteristics
The main characteristics of the MCT 110 HFCT include:
• Very high sensitivity and therefore a very good signal-to-noise-ratio
• Big inner hole for large ground connections
92
MCT 110 High-Frequency Current Transformer
The following table shows the technical data of the MCT 110 HFCT.
93
Operation Manual for Rotating Machine PD Monitoring
94
MCT 120 High-Frequency Current Transformer
95
Operation Manual for Rotating Machine PD Monitoring
4.4.1 Characteristics
The main characteristics of the MCT 120 include:
• Clamp-on construction enabling installation without opening the (ground)
connection
• Very high sensitivity and therefore a very good signal-to-noise-ratio
• Big inner hole for large ground connections
0 mm gap
0.2 mm gap
0.4 mm gap
0.6 mm gap
Figure 4-8 Frequency response of the MCT 120 (typical transfer function)
96
MCT 120 High-Frequency Current Transformer
The following table shows the technical data of the MCT 120.
97
Operation Manual for Rotating Machine PD Monitoring
98
MCC 112 Coupling Capacitor
TNC connector
Ground
M6 bolt
99
Operation Manual for Rotating Machine PD Monitoring
4.5.1 Characteristics
The main characteristics of the MCC 112 coupling capacitor include:
• Decoupling of PD pulses at safe grounding connections
• Very good signal-to-noise ratio due to the high sensitivity of the MCC 112
• Overvoltage protection at the sensor output (TNC plug)
The following table shows the technical data of the MCC 112 coupling capacitor.
100
MCC 112 Coupling Capacitor
Table 4-10 Technical Data of the MCC 112 Coupling Capacitor (continued)
Characteristic Rating
Connector TNC
High-voltage side connection M12 cap nut
Additional grounding M6 knurled screw
Overall height 250 mm
Diameter 150 mm
Weight 4.5 kg
101
Operation Manual for Rotating Machine PD Monitoring
102
MCC 124 Coupling Capacitor
TNC connector
Ground
M6 bolt
103
Operation Manual for Rotating Machine PD Monitoring
4.6.1 Characteristics
The main characteristics of the MCC 124 coupling capacitor include:
• Decoupling of PD pulses at safe grounding connections
• Very good signal-to-noise ratio due to the high sensitivity of the MCC 124
• Overvoltage protection at the sensor output (TNC plug)
The following table shows the technical data of the MCC 124 coupling capacitor.
104
MCC 124 Coupling Capacitor
Table 4-11 Technical Data of the MCC 124 Coupling Capacitor (continued)
Characteristic Rating
Connector TNC
High-voltage side connection M12 cap nut
Additional grounding M6 knurled screw
Overall height 250 mm
Diameter 150 mm
Weight 4.5 kg
105
Operation Manual for Rotating Machine PD Monitoring
106
MCU 502 Controller
4.7.1 Overview
The MCU 502 controller is shown in the following figure.
Blue LED
Figure 4-13 Front and rear views of the MCU 502 fiber-optic controller
The MCU 502 controller is equipped with a blue LED that indicates the status of
the controller. When the LED lights continuously, the controller is connected to
a computer, has good power, and has been configured for use on the computer.
A flashing LED indicates a hardware or software problem with the MCU 502
controller or the connected computer. In this case, contact OMICRON Energy
Solution GmbH technical support.
107
Operation Manual for Rotating Machine PD Monitoring
108
CAL 542 Charge Calibrator
4.8.1 Battery
The CAL 542 charge calibrator is powered by a 9 V lithium battery. The battery’s
lifetime (under ordinary conditions) is more than 10 years. If the CAL 542
displays Low Bat, you must replace the battery. You can replace the original
battery with a new one of type PP3-Lithium or IEC-6LR61-Lithium or
ANSI-1604LC.
To replace the battery:
1. Remove the silicone covers of the CAL 542 by shifting them outward.
2. Remove the four screws on the front panel, and then remove the front panel.
3. Remove the upper two screws on the rear panel, and then remove the rear
panel.
4. Remove the top cover of the CAL 542.
109
Operation Manual for Rotating Machine PD Monitoring
110
Troubleshooting
5 Troubleshooting
5.1 Problems with the System
5.1.1 Problems at System Startup
The monitoring server does not start at all:
• Make sure that the power cable of the monitoring server is properly
connected.
• If the problem persists, contact the OMICRON Energy Solution GmbH
technical support (see "Support" on page 115).
At system startup no acquisition unit is recognized or some acquisition units are
not recognized by the Monitoring System:
• Make sure that the power at the lost acquisition unit is properly connected
and switch on. The power is on if the LEDs inside the OMS 600 is flashing
red or lights permanently green. For more Information, see 4.2 "OMS 600
Module" on page 79.
• If the units are still powered but the LEDs are off check the power of the
primary switcher. The output voltage is supplied with 12 V DC voltage.
• If the 12 V DC supply is active the acquisition unit is defective and must be
replaced. Contact the OMICRON Energy Solution GmbH technical support
(see "Support" on page 115).
• If the 12 V DC voltage is not available and the supply power is on the fuse
or the primary switcher is defective.
• Check the fiber-optic network and the connection from the MCU 502
controller and the connection from the OMS 600 acquisition units to the
following lost acquisition unit.
• If the acquisition units are working restart the Monitoring System or the
OMICRON Monitoring Services and follow the steps described in 2.2 "Start
the Monitoring Software" on page 36.
You cannot log on to the system:
If you entered three times a wrong user name or password the logon is blocked
for several minutes. Wait and then try again with correct user name and
password.
111
Operation Manual for Rotating Machine PD Monitoring
2. The control software shows which disk is still in operation and which disk
failed. Replace the defective disk by a new one of the same size and brand.
112
Troubleshooting
3. After you replaced the defective disk and restarted the system the control
software detects that still one disk is missing but a new one is available.
5. In the Rebuild Volume dialog box, click the Rebuild button to start the
rebuild process.
113
Operation Manual for Rotating Machine PD Monitoring
114
Support
Support
When you are working with our products we want to provide you with the
greatest possible benefits. If you need any support, we are here to assist you!
OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495
115
Operation Manual for Rotating Machine PD Monitoring
116
Index
Index M
MCC 112 coupling capacitor 17, 18, 99–101
MCC 124 coupling capacitor 17, 18, 103–105
Numerics MCU 502 controller 17, 18, 107–108
monitoring
3D PRPD 48, 73 continuous 45, 50, 70
3PARD 15, 48, 70, 73 periodic 46, 70, 72
monitoring server 15, 16, 17, 18, 23–34, 37, 38, 77,
C 111
monitoring software 15, 17, 18, 36–38, 39–76, 112,
cable 114
fiber-optic 114 MPD & MI software 19, 76, 81
FO-MM 17, 18
grounding 17, 18
power 17, 18, 111 O
sensor 17, 18 OMS 600 acquisition unit 17, 18, 79–90
triaxial 15
CAL 542 charge calibrator 109–110
P
F partial discharge 9
patch panel 15, 16, 17, 18
fiber-optic power cable 17, 18, 111
cable 114 PRPD 48, 69, 70, 73
network 15, 111
FO-MM cable 17, 18
S
G safety
instructions 12
grounding cable 17, 18 internal 12
standards 12
I safety rules 11
sensor cable 17, 18
iLO 25, 27, 35 server cabinet 15, 16
short cable links 18
standards
K safety 12
system startup 111
KVM 23, 25, 27, 35
L T
triaxial cable 15
limitation of liability 7
logon 35, 37, 53, 111
U
USB interface 16, 75
117
Operation Manual for Rotating Machine PD Monitoring
118