RuggedSwitchTM RSG2100

eRSTP
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports eRSTP

eRSTP eRSTP ZPL


TM

Zero-Packet-Loss™

eRSTP
eRSTP eRSTP
eRSTP

eRSTP
TM
The RuggedSwitch™ RSG2100 is an industrially hardened, RuggedRated for Reliability in Harsh Environments
fully managed, modular, Ethernet switch specifically designed .Immunity to EMI and heavy electrical surges
to operate reliably in electrically harsh and climatically . Zero-Packet-Loss™ Technology
demanding utility substation and industrial environments. . Meets IEEE 1613 Class 2 (electric utility substations)
The RSG2100's superior ruggedized hardware design . Exceeds IEC 61850-3 (electric utility substations)
coupled with the embedded Rugged Operating System . Exceeds IEC 61800-3 (variable speed drive systems)
(ROS™) provides improved system reliability and advanced . Exceeds IEC 61000-6-2 (generic industrial)
cyber security and networking features making it ideally . Exceeds NEMA TS-2 (traffic control equipment)
suited for creating secure Ethernet networks for mission- .-40 to +85°C operating temperature (no fans)
critical, real-time, control applications. .Conformal coated printed circuit boards (optional)
.18 AWG galvanized steel enclosure
The RSG2100's modular flexibility offers 10BaseFL /100BaseFX .Hazardous Location Certification: Class 1 Division 2
/1000BaseX fiber and 10/100/1000BaseTX copper port
combinations. Optional front or rear mount connectors make the Rugged Operating System (ROSTM) Features
RSG2100 highly versatile for any application and can support .Simple plug and play operation - automatic learning,
multiple fiber connectors (ST, MTRJ, LC, SC) without loss of port negotiation, and crossover detection
density. The RSG2100 is packaged in a rugged galvanized steel .RSTP (802.1w) and Enhanced Rapid Spanning
enclosure with industrial grade DIN, panel, or 19" rack-mount Tree (eRSTP™) network fault recovery (<5ms)
mounting options. .Quality of Service (802.1p) for real-time traffic
.VLAN (802.1q) with double tagging and GVRP support
Features and Benefits .Link aggregation (802.3ad)
.IGMP Snooping for multicast filtering
Ethernet Ports .Port Rate Limiting and Broadcast Storm Limiting
.up to 3-Gigabit Ethernet ports - copper and/or fiber .Port configuration, status, statistics, mirroring, security
.up to 16-Fast Ethernet ports - copper and/or fiber .Loss of link management on fiber ports
.2 port modules for tremendous flexibility .SNTP time synchronization (client and server)
.Non-blocking, store and forward switching .Industrial automation features (eg. Modbus)
.Supports many types of fiber (Multimode, singlemode,
bi-directional single strand) Management Tools
.Long haul optics allow Gigabit distances up to 70km .Web-based, Telnet, CLI management interfaces
.Multiple connector types (ST, MTRJ, LC, SC) .SNMP v1/v2/v3
.Remote Monitoring (RMON)
Cyber Security Features .Rich set of diagnostics with logging and alarms
.Multi-level user passwords
.SSH/SSL encryption Universal Power Supply Options
.Enable/disable ports, MAC based port security .Fully integrated, dual-redundant (optional) power supplies
.Port based network access control (802.1x) .Universal high voltage range: 88-300VDC or 85-264VAC
.VLAN (802.1q ) to segregate and secure network traffic .Popular low voltage ranges: 24VDC(9-36VDC),
.Radius centralized password management 48VDC (36-72VDC)
.SNMPv3 encrypted authentication and access security .Screw or pluggable terminal blocks available
.Terminal blocks for reliable RUGGEDCOM
maintenance free connections
.CSA/UL 60950 safety approved ISO 9001:2000
to +85°C CERTIFIED
www.RuggedCom.com RuggedSwitchTM RSG2100 1
More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

RuggedSwitch™ RSG2100
Modularity:
 10 available slots
 Up to 16 Fast Ethernet
ports & 3 Gigabit ports
 Dual and single port modules

Modularity (8x2)

Mounting Options Fast Ethernet Ports Types: Gigabit Port Types: Modular HMI:
 Panel/Din Rail  up to 16 Fast Ethernet Ports  up to 3 Gigabit Ethernet Ports  Front or Rear Mount
 19” Rack Mount  virtually any mix of fiber or  10/100/1000 TX RJ45
 Front or Rear Mount copper desired  1000SX Multimode
 10/100TX RJ45  1000LX Singlemode
 10FL Multimode  Pluggable Optics (SFP)
 100FX Multimode  SC, ST, LC and MTRJ
 100FX Singlemode

Integrated Power Supply


 Universal high-voltage range:
Critical Alarm Relay
88-300VDC or 85-264VAC Operating Temperature
 Form-C contact ratings:
 Popular low voltage DC ranges: 24VDC  -40oC to +85oC
Max Voltage 250VAC,125VDC
(9-36VDC), 48VDC (36-59VDC)  No Fans
Max Current 2A@250VAC,
 True Dual Redundant Parallel
0.15A@125VDC, 2A@30VDC
Load Sharing (Optional)
 Screw or pluggable terminal
blocks available

www.RuggedCom.com RuggedSwitchTM RSG2100 2


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

ROSTM Features
Cyber Security A configurable "weighted fair queuing" algorithm
Cyber security is an urgent issue in many industries where controls how frames are emptied from the
advanced automation and communications networks play queues.
a crucial role in mission critical applications and where high
reliability is of paramount importance. Key ROS™ features that VLAN (IEEE 802.1q)
address security issues at the local area network level include: Virtual local area networks (VLAN) allow the segregation
of a physical network into separate logical networks with
.Passwords - Multi-level user passwords secures switch independent broadcast domains. A measure of security is
against unauthorized configuration provided since hosts can only access other hosts on the
.SSH / SSL - Extends capability of password protection same VLAN and traffic storms are isolated. ROS™ supports
to add encryption of passwords and data as they cross 802.1q tagged Ethernet frames and VLAN trunks. Port
the network based classification allows legacy devices to be assigned
.Enable / Disable Ports - Capability to disable ports so that to the correct VLAN. GVRP support is also provided to
traffic can not pass simplify the configuration of the switches on the VLAN.
.802.1q VLAN - Provides the ability to logically segregate
traffic between predefined ports on switches Link Aggregation (802.3ad)
.MAC Based Port Security - The ability to secure ports on The link aggregation feature provides the ability to aggregate
a switch so only specific Devices / MAC addresses can several Ethernet ports into one logical link (port trunk) with
communicate via that port higher bandwidth. This provides an inexpensive way to set up
.802.1x Port Based Network Access Control - The ability a high speed backbone to improve network bandwidth. This
to lock down ports on a switch so that only authorized feature is also known as "port trunking", "port bundling", "port
clients can communicate via this port teaming", and "ethernet trunk".
.Radius - Provides centralized password management
.SNMPv3 - encrypted authentication and access security IGMP Snooping
ROS uses IGMP snooping (Internet Group Management
The ROS™ cyber security features are included to help Protocol v1&v2) to intelligently forward or filter multicast traffic
address the various industry specific security standards such streams (e.g. MPEG video) to or from hosts on the network.
as NERC CIP, ISA S99, AGA 12, IEC 62443, ISO 17799:2005 This reduces the load on network trunks and prevents
and PCSRF SPP-ICS. packets from being received on hosts that are not involved.
ROS™ has a very powerful implementation of
Enhanced Rapid Spanning Tree Protocol (eRSTP™) IGMP snooping that:
RuggedCom eRSTP allows the creation of fault-tolerant ring
and mesh Ethernet networks that incorporate redundant links .Can be enabled on a per VLAN basis.
that are 'pruned' to prevent loops. eRSTP yields worst-case .Detects and filters all multicast streams regardless of
fault recovery1 of 5ms times the 'bridge diameter' and allows whether subscribers exist.
rings of up to 80 switches. For example, a ring of ten .Supports "router-less" operation by supporting an
switches will have fault recovery times under 50ms. eRSTP "active" mode.
implements both STP and RSTP to ensure interoperability .Restores traffic streams immediately after an RSTP
with commercial switches unlike other proprietary 'ring' topology change.
solutions.
SNMP (Simple Network Management Protocol)
Quality of Service (IEEE 802.1p) SNMP provides a standardized method for network
Some networking applications such as real-time control management stations the ability to interrogate devices from
or VoIP (voice over IP) require predictable arrival times for different vendors. SNMP versions supported by ROS™ are
Ethernet frames. Switches can introduce latency in times v1, v2c, and v3. SNMPv3 in particular provides security
of heavy network traffic due to the internal queues that buffer features (such as authentication, privacy, and access control)
frames and then transmit on a first come first serve basis. not present in earlier SNMP versions. ROS™ also supports
ROS™ supports 'Class of Service' in accordance with IEEE numerous standard MIBs (Management Information Base)
802.1p that allows time critical traffic to jump ahead to the allowing for easy integration with any network management
front of the queue thus minimizing latency and reducing jitter system (NMS).
to allow such demanding applications to operate correctly. 1 eRSTP fault recovery times may be approximated as follows:
ROS™ allows priority classification by port, tags, MAC For 100 Mbps, fault recovery performance is <5ms/hop
address, and IP type of service (TOS). For 1,000 Mbps, fault recovery performance is <5ms/hop + 20ms

www.RuggedCom.com RuggedSwitchTM RSG2100 3


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

ROSTM Features
SNMP (Simple Network Management Protocol) (cont’d) Port Configuration and Status
A feature of SNMP supported by ROS™ is the ability to ROS™ allows individual ports to be 'hard' configured for
generate "traps" upon system events. A NMS can record speed, duplex, auto-negotiation, flow control and more. This
traps from multiple devices providing a powerful network allows proper connection with devices that do not negotiate or
troubleshooting tool. RuggedVueTM is RuggedCom's NMS have unusual settings. Detailed status of ports with alarm and
that provides graphical visualization of the network and is SNMP trap on link problems aid greatly in system
fully integrated with all RuggedCom products. troubleshooting.

SNTP (Simple Network Time Protocol) Port Statistics and RMON (Remote Monitoring)
SNTP automatically synchronizes the internal clock of all ROS™ provides continuously updating statistics per port
ROS™ devices on the network. This allows for correlation that provide both ingress and egress packet and byte
of time stamped events for troubleshooting. counters as well as detailed error figures. Also provided
is full support for the RMON statistics, history, alarms, and
SCADA and Industrial Automation event groups. RMON allows for very sophisticated data
ROS™ contains features that optimize network performance collection, analysis and detection of traffic patterns.
and simplify switch management based on the unique
requirements found in SCADA and industrial automation Event Logging and Alarms
applications. Features such as Modbus TCP management for ROS™ records all significant events to a non-volatile
retrieval of switch data using the ubiquitous Modbus protocol system log allowing forensic troubleshooting. Events
and DHCP Option 82, a Rockwell Automation ODVA include link failure and recovery, unauthorized access,
requirement for IP address assignment based on the location broadcast storm detection, and self-test diagnostics
of the end device, provide capabilities not found in typical among others. Alarms provide a snapshot of recent
"commercial" or "office grade" Ethernet switches. events that have yet to be acknowledged by the network
administrator. An external hardware relay is de-energized
Port Based Network Access Control (802.1x) during the presence of critical alarms allowing an
ROS™ supports the IEEE 802.1x standard that defines external controller to react if desired.
a mechanism for port-based network access control which
provides a means of authenticating and authorizing HTML Web Browser and Telnet User Interfaces
devices attached to LAN ports. ROS™ provides a simple, intuitive user interface for
configuration and monitoring via a standard graphical
Port Rate Limiting web browser or via Telnet. All system parameters include
ROS™ supports configurable rate limiting per port to limit detailed on-line help to make setup a breeze. ROS™ ,
unicast and multicast traffic. This can be essential to presents a common look and feel and standardized
managing precious network bandwidth for service providers. configuration process allowing easy migration to other
It also provides edge security for denial of service RuggedCom managed products.
(DOS) attacks.
Configuration via ASCII Text File
Broadcast Storm Filtering All configuration parameters are stored in an ASCII
Broadcast storms wreak havoc on a network and can cause formatted text file that can easily be transferred via TFTP
attached devices to malfunction. This could be disastrous on or Xmodem. The configuration file can be saved for
a network with mission critical equipment. ROS™ limits this backup purposes and easily manipulated by a text editor.
by filtering broadcast frames with a user-defined threshold. The same text file can be downloaded to the switch at
a later date in order to re-configure or restore
Loss of Link Management a previous configuration.
Some intelligent electronic devices (IEDs) have dual fiber
optic ports with automatic failover to a backup port should the Command Line Interface (CLI)
primary fail. ROS™ ensures this mechanism works reliably A command line interface can be used in conjunction
under all failure modes by appropriately disabling link signals with remote shell to automate data retrieval, configuration
when required. ROS™ also flushes learned MAC addresses updates, and firmware upgrades. A powerful SQL-like
to ensure the failover occurs quickly. capability allows expert users the ability to selectively
retrieve or manipulate any parameters the device
Port Mirroring has to offer.
ROS™ can be configured to duplicate all traffic on one port
to a designated mirror port. When combined with a network
analyzer, this can be a powerful troubleshooting tool.

www.RuggedCom.com RuggedSwitchTM RSG2100 4


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

EMI and Environmental Type Tests


IEC 61850-3 EMI TYPE TESTS
TEST Description Test Levels Severity Levels
Enclosure Contact +/- 8kV 4
IEC 61000-4-2 ESD
Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
Signal ports +/- 4kV @ 2.5kHz x

D.C. Power ports +/- 4kV 4


IEC 61000-4-4 Burst (Fast Transient)
A.C. Power ports +/- 4kV 4

Earth ground ports 3 +/- 4kV 4


Signal ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
IEC 61000-4-5 Surge D.C. Power ports +/- 2kV line-to-earth, +/- 1kV line-to-line 3
A.C. Power ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
Signal ports 10V 3
D.C Power ports 10V 3
IEC 61000-4-6 Induced (Conducted) RFI
A.C. Power ports 10V 3

Earth ground ports 3 10V 3


IEC 61000-4-8 Magnetic Field Enclosure ports 40 A/m continuous, 1000 A/m for 1 s N/A
D.C. Power ports 30% for 0.1s, 60% for 0.1s, 100% for 0.05s N/A
IEC 61000-4-29
Voltage Dips & Interrupts 30% for 1 period, 60% for 50 periods N/A
A.C. Power ports
IEC 61000-4-11 100% for 5 periods, 100% for 50 periods 2 N/A
Signal ports 2.5kV common, 1kV diff. mode@1MHz 3
IEC 61000-4-12 Damped Oscillatory D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
Signal ports 30V Continuous, 300V for 1s 4
IEC 61000-4-16 Mains Frequency Voltage
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17 Ripple on D.C. Power Supply D.C. Power ports 10% 3
Signal ports 2kVac (Fail-Safe Relay output) N/A
IEC 60255-5 Dielectric Strength D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A
Signal ports 5kV (Fail-Safe Relay output) N/A
IEC 60255-5 H.V. Impulse D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A

IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS


Test Description Test Levels Severity Levels
Enclosure Contact +/- 8kV N/A
IEEE C37.90.3 ESD
Enclosure Air +/- 15kV N/A
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m N/A
Signal ports +/- 4kV @ 2.5kHz N/A
D.C. Power ports +/- 4kV N/A
IEEE C37.90.1 Fast Transient
A.C. Power ports +/- 4kV N/A
Earth ground ports3 +/- 4kV N/A
Signal ports 2.5kV common mode @1MHz N/A
IEEE C37.90.1 Oscillatory D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz N/A
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz N/A
Signal ports 5kV (Fail-Safe Relay output) N/A
IEEE C37.90 H.V. Impulse D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
Signal ports 2kVac N/A
IEEE C37.90 Dielectric Strength D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A

Environmental Type Tests


Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold Temperature Test Ad -40°C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours N/A
95% (non-condensing), 55°C , 6
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db N/A
cycles
IEC 60255-21-1 Vibration Tests Fc 2g @ (10 - 150) Hz Class 2
IEC 60255-21-2 Shock Tests Ea 30g @ 11mS Class 2

Notes: 1. Only applicable to functional earth connections separated from the safety earth connection.
2. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high,
( e.g. shipboard application and for severe transportation conditions")

www.RuggedCom.com RuggedSwitchTM RSG2100 5


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

Technical Specifications
Power Supply EMI Immunity and Environmental Compliance
.Power Consumption: 28W Max .IEC 61000-6-2 Industrial (Generic)
.24VDC: 9-36 VDC, 1.2A .IEC 61800-3 Industrial (Variable Speed Drive Systems)
.48VDC: 36-72 VDC, 0.6A .IEC 61850-3 Electric Utility Substations
.HI Voltage AC/DC: 88-300VDC or 85-264VAC .IEEE 1613 Electric Utility Substations
.NEMA TS 2 Traffic Control Equipment
Critical Alarm Relay
.Form-C contact ratings: IEEE Compliance
Max Voltage 250VAC,125VDC .802.3-10BaseT
Max Current 2A@250VAC, 0.15A @125VDC, .802.3u-100BaseTX, 100BaseFX
2A@30VDC .802.3x-Flow Control
.802.3z-1000BaseLX
Physical .802.3ab-1000BaseTX
.Height: 4.42cm / 1.74" .802.3ad-Link Aggregation
.Width: 46.48cm / 18.3" .802.1d-MAC Bridges
.Depth: 31.5cm / 12.4" .802.1d-Spanning Tree Protocol
.Weight: 5.2kg / 11.5 lbs .802.1p-Class of Service
.Ingress Protection: IP40 (1mm objects) .802.1q-VLAN Tagging
.Enclosure: 18 AWG galvanized steel enclosure .802.1w-Rapid Spanning Tree Protocol
.Mounting: DIN rail or panel mounted .802.1x-Port Based Network Access Control

Switch Properties IETF RFC Compliance


.Switching method: Store & Forward .RFC768-UDP
.Switching latency: 7 us .RFC783-TFTP
.Switching bandwidth: 9.2 Gbps .RFC791-IP
.MAC addresses: 8192 .RFC792-ICMP
.MAC address table size: 64kbytes .RFC793-TCP
.Priority Queues: 4 .RFC826-ARP
.Frame buffer memory: 2 Mbit .RFC854-Telnet
.VLANs: 4094 .RFC894-IP over Ethernet
.IGMP multicast groups: 256 .RFC1112-IGMP v1
.Port rate limiting .RFC1519-CIDR
.No head of line blocking .RFC1541-DHCP (client)
.RFC2030-SNTP
Approvals .RFC2068-HTTP
.ISO: Designed and manufactured using a ISO9001: 2000 .RFC2236-IGMP v2
certified quality program .RFC2284-EAP
.CE Marking .RFC2475-Differentiated Services
.Emissions: FCC Part 15 (Class A), .RFC2865-Radius
EN55022 (CISPR22 Class A) .RFC3414-SNMPv3-USM
.Safety: cCSAus (Compliant with CSA C22.2 No. 60950, UL .RFC3415-SNMPv3-VACM
60950, EN60950)
.Laser Eye Safety (FDA/CDRH): Complies with 21 IETF SNMP MIBS
CFR Chapter1, Subchapter J. .RFC1493-BRIDGE-MIB
.RFC1907-SNMPv2-MIB
Warranty .RFC2012-TCP-MIB
.5 Years - Applicable to design and manufacturing .RFC2013-UDP-MIB
related product defects. .RFC2578-SNMPv2-SMI
.RFC2579-SNMPv2-TC
Network Management .RFC2819-RMON-MIB
.HTTP graphical web-based .RFC2863-IF-MIB
.SNMP v1, v2c, v3 .draft-ietf-bridge-rstpmib-03-BRIDGE-MIB
.Telnet, VT100 .draft-ietf-bridge-bridgemib-smiv2-03-RSTP-MIB
.Command Line Interface (CLI) .IANAifType-MIB

www.RuggedCom.com RuggedSwitchTM RSG2100 6


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

Dimensions

www.RuggedCom.com RuggedSwitchTM RSG2100 7


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

Mounting Options

Slot 1 Slot 3 Slot 5 Slot 7 Slot 9

Slot 2 Slot 4 Slot 6 Slot 8 Slot 10

www.RuggedCom.com RuggedSwitchTM RSG2100 8


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

Order Codes
RSG2100 -______ -______ -____ -____ -____ -____ -____ -____ -____ -____ -____ -____ -____ -_____
Main Mount PS1 PS2 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10

Slot 1 Slot 3 Slot 5 Slot 7 Slot 9 S5: Gigabit Ethernet Modules for slot 5
Slot 2 Slot 4 Slot 6 Slot 8 Slot 10 .XXXX = Empty
.CG01 = 2 x 10/100/1000Tx RJ45
Main: Ethernet and Power Connectors .FG01 = 2 x 1000SX - Multimode, 850nm, LC, 500m
.R = Ethernet on rear; LED panel on front; power connector on rear .FG02 = 2 x 1000LX - Singlemode, 1310nm, SC connectors, 10km
.F = Ethernet on front; LED panel on front; power connector on rear .FG03 = 2 x 1000LX - Singlemode, 1310nm, LC connectors, 10km
. B = Ethernet on rear; LED panel on top; power connector on rear .FG04 = 2 x 1000LX - Singlemode, 1310nm, SC connectors, 25km
. T = Ethernet on front; LED panel on top; power connector on rear .FG05 = 2 x 1000LX - Singlemode, 1310nm, LC connectors, 25km
.FG50 = 2 x 1000LX SFP - Blank (no optical transceiver)
Mount: Mounting Options .FG51 = 2 x 1000SX SFP - Multimode, 850nm, LC, 500m
. RM = 19" Rack Mount Kit .FG52 = 2 x 1000LX SFP - Singlemode, 1310nm, LC, 10km
. DP = DIN and Panel Mount Kit .FG53 = 2 x 1000LX SFP - Singlemode, 1310nm, LC, 25km
. RD = 19" Rack, DIN, and Panel Mount Kit .FG54 = 2 x 1000LX SFP - Singlemode, 1550nm, LC, 70km
. 00 = No Mounting Option .FG70 = 2 x 1000LX GBIC - Blank (no optical transceiver)
.FG71 = 2 x 1000LX GBIC - Singlemode, 1310nm, SC, 10km
PS1 and PS2: Power Supply 1 and 2 .FG72 = 2 x 1000LX GBIC - Singlemode, 1310nm, SC, 25km
. 24 = 24VDC (9-36VDC), screw terminal block .FG73 = 2 x 1000LX GBIC - Singlemode, 1550nm, SC, 70km
. 48 = 48VDC (36-72VDC), screw terminal block
. HI = 88-300VDC or 85-264VAC, screw terminal block S6: Gigabit Ethernet Modules for slot 6
. 24P = 24VDC (9-36VDC), pluggable terminal block .XXXXX = Empty
. 48P = 48VDC (36-72VDC), pluggable terminal block .1CG01 = 1 x 10/100/1000Tx RJ45
. HIP = 88-300VDC or 85-264VAC, pluggable terminal block .1FG01 = 1 x 1000SX - Multimode, 850nm, LC, 500m
. XX = No Power Supply (PS2 Only) .1FG02 = 1 x 1000LX - Singlemode, 1310nm, SC connectors, 10km
.1FG03 = 1 x 1000LX - Singlemode, 1310nm, LC connectors, 10km
.1FG04 = 1 x 1000LX - Singlemode, 1310nm, SC connectors, 25km
S1, S2, S3, S4, S7, S8, S9 and S10:
.1FG05 = 1 x 1000LX - Singlemode, 1310nm, LC connectors, 25km
Ethernet Modules for Slots 1, 2, 3, 4, 7, 8, 9 and 10 .1FG50 = 1 x 1000SX SFP - Blank (no optical transceiver)
. XXXX = Empty .1FG51 = 1 x 1000SX SFP - Multimode, 850nm, LC, 500m
. TX01 = 2 x 10/100Tx RJ45 .1FG52 = 1 x 1000LX SFP - Singlemode, 1310nm, LC,10km
 FL01 = 2 x 10FL - Multimode, 850nm, ST .1FG53 = 1 x 1000LX SFP - Singlemode, 1310nm, LC, 25km
. FX01 = 2 x 100FX - Multimode, 1300nm, ST .1FG54 = 1 x 1000LX SFP - Singlemode, 1550nm, LC, 70km (2)
. FX02 = 2 x 100FX - Multimode, 1300nm, SC .1FG70 = 1 x 1000LX GBIC - Blank (no optical transceiver)
. FX11 = 2 x 100FX – Multimode, 1300nm, LC .1FG71 = 1 x 1000LX GBIC - Singlemode, 1310nm, SC, 10km
. FX03 = 2 x 100FX - Multimode, 1300nm, MTRJ .1FG72 = 1 x 1000LX GBIC - Singlemode, 1310nm, SC, 25km
. FX04 = 2 x 100FX - Singlemode, 1310nm, ST, 20km .1FG73 = 1 x 1000LX GBIC - Singlemode, 1550nm, SC, 70km (2)
. FX05 = 2 x 100FX - Singlemode, 1310nm, SC, 20km
. FX06 = 2 x 100FX - Singlemode, 1310nm, LC, 20km NOTES:

. FX07 = 2 x 100FX - Singlemode, 1310nm, SC, 50km 1 Distance ratings are typical but will depend on type of cabling, number of connectors and splices.
2 These transceivers have an operating temperature range of -20 °C to +85°C.
. FX08 = 2 x 100FX - Singlemode, 1310nm, LC, 50km All other transceivers have an operating temperature range of -40°C to +85°C

. FX09 = 2 x 100FX - Singlemode, 1310nm, SC, 90km


. FX10 = 2 x 100FX - Singlemode, 1310nm, LC, 90km

Example Order Codes:


RSG2100-R-RM-HI-HI-TX01-TX01-FX01-FX01-FG02-
RSG2100-R-RM-24-48-TX01-TX01-XXXX-XXXX-XXXX- XXXXX-FX01-FX01-FX01-FX01
XXXXX-XXXX-XXXX-XXXX-XXXX 19” Rack mounted, HI power supply, HI power supply,
19” Rack mounted, 24VDC power supply, 48VDC power 4 10/100 RJ45 Ethernet Ports, 12 100FX (Multi Mode 1350nm
supply, 4 10/100 RJ45 Ethernet Ports, with Ethernet Fiber) Ethernet ports, 2 1000LX (Gigabit) Ethernet ports,
ports on the rear with Ethernet ports on the front

RSG2100-F-RM-48-48-TX01-TX01-FX01-FX01-XXXX-XXXXX- Accessories/Options
XXXX-XXXX-XXXX-XXXX
19” Rack mounted, 48VDC power supply, 48VDC, 4 10/100 82-01-0002 - Conformal Coating
RJ45 Ethernet Ports, 4 100FX (Multi Mode 1310nm Fiber) 41-11-0011 - Cable support brackets
Ethernet ports, with Ethernet ports on the front 43-10-0007 - Power cable (North America three
prong connector -> beau)

www.RuggedCom.com RuggedSwitchTM RSG2100 9


More user manuals on ManualsBase.com
RuggedSwitchTM RSG2100
19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports

RuggedCom Inc.
30 Whitmore Road
Woodbridge, Ontario, Canada L4L 7Z4
Tel: (905) 856-5288 Fax: (905) 856-1995
Toll Free: (888) 264-0006
Technical Support Center: (866) 922-7975 or (954) 922-7975
© 2007 RuggedCom Inc.
RuggedSwitch is a trademark of RuggedCom Inc.
Ethernet is a trademark of the Xerox Corporation.
Patent Pending For additional information on our products and
All specifications in this document are subject to change without notice. services, please visit our web site at: www.ruggedcom.com
Rev 2-U

www.RuggedCom.com RuggedSwitchTM RSG2100 10

You might also like