KIL2189 - 102 - 0002 - REV05 - Existing & Proposed Fire Escape Strategy 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

This drawing should not be scaled. Dimensions to be verified on site.

Any discrepancies should be referred to the Engineer prior to work being put in
NOTE: hand.

EXISTING ROUTE WILL NOT BE SIGNIFICANTLY ALTERED. This drawing is the property of Kiloh Associates Limited, and the drawing is
issued on the condition that it is not copied reproduced, retained or disclosed to
any unauthorised person, either wholly or in part without the consent in writing of
Kiloh Associates Limited, Unit 6, Pitreavie Court, Pitreavie Business Park,
NOTE; Dunfermline, KY11 8UU t 0131 629 3434

GSK HAVE CONFIRMED THAT THE OCCUPANCY OF


THE DISSO ROOM IS MAXIMUM 2 PERSONS GENERAL NOTES
LEV
27m 26m 1. DO NOT SCALE THIS DRAWING. ANY DISCREPANCY IS TO BE
EXISTING REPORTED TO THE ENGINEER IMMEDIATELY.
WINDOW
2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
NEW WINDOW ENGINEER'S OR OTHER RELEVANT DRAWINGS AND SPECIFICATIONS.

3. ALL DIMENSIONS AND LEVELS ARE TO BE CHECKED ON SITE BY THE


FIRE SAFETY NOTES; CONTRACTOR PRIOR TO PREPARING ANY WORKING DRAWINGS OR
COMMENCING ON SITE.
1. ESCAPE DISTANCES ARE AS FOLLOWS: 18m FOR ONE DIRECTION OF
TRAVEL & 45m FOR MORE THAN ONE DIRECTION OF TRAVEL. THIS IS IN
4. THE CONTRACTOR MUST ENSURE AND WILL BE HELD RESPONSIBLE
EXISTING FIRE ACCORDANCE WITH THE BRITISH STANDARD FOR OFFICES, FACTORIES
FOR THE OVERALL STABILITY OF THE
ESCAPE ROUTE UN & CLASS 2 STORAGE BUILDINGS. 15m FOR ONE DIRECTION OF TRAVEL
EXISTING BUILDING/STRUCTURE/EXCAVATION AT ALL STAGES OF THE WORK.
& 32m FOR MORE THAN ONE DIRECTION OF TRAVEL. THIS IS IN
2 WINDOW ALTERED BY WORKS
ACCORDANCE WITH WITH THE BRITISH STANDARD FOR 5. ALL WORK BY THE CONTRACTOR MUST BE CARRIED OUT IN SUCH A
NEW WINDOW ENTERTAINMENT BUILDINGS, ASSEMBLY BUILDINGS & CLASS 1 WAY THAT ALL REQUIREMENTS UNDER THE HEALTH AND SAFETY AT
STORAGE BUILDINGS. IN THE CASE OF A BUILDING WHICH HAS ONLY 1 WORK ACT ARE SATISFIED.
DIRECTION OF TRAVEL, THE TRAVEL DISTANCE SHOULD BE
MEASURED TO A PROTECTED DOOR GIVING ACCESS TO AN ESCAPE 6. ALL WORK IS TO BE CARRIED OUT IN COMPLIANCE WITH THE
STAIR OR A PLACE OF SAFETY. IN THE CASE OF A BUILDING OR PART REQUIREMENTS OF THE RELEVANT STATUTORY AUTHORITIES AND
OF A BUILDING WHERE THERE ARE AT LEAST TWO AVAILABLE REGULATIONS.
NEW FIRE DOOR DIRECTIONS OF TRAVEL, THE TRAVEL DISTANCE MAY BE MEASURED
TO ANY PROTECTED DOOR. 7. ALL DOORS CONSIDERED AS FIRE EXITS SHOULD HAVE AN
EXISTING FIRE DOOR ILLUMINATED FIRE EXIT SIGN COMPLYING WITH BS ISO 3864-4 ABOVE
2. ALL FIRE ESCAPE ROUTES ARE ASSUMED TO HAVE A MINIMUM HEAD THEM WITH AN EMERGENCY BACKUP.
ROOM OF 2m, IF THIS IS NOT THE CASE GSK TO CONFIRM.
D01 8. ALL PERSONNEL DOORS SHOULD PROVIDE A MINIMUM OPENING
3. ROOM & PLANT LAYOUTS HAVE BEEN PROVIDED BY GSK & ARE WIDTH OF 800mm.
NEW ROLLER SHUTTER ASSUMED TO BE CURRENT, IF THIS IS NOT THE CASE GSK TO CONFIRM
ASSUMED FIRE 18m DOOR CANNOT BE USED SO THAT ALTERATIONS CAN BE ADOPTED WITHIN DRAWINGS.
CORRIDOR 9. CATEGORY L1 FIRE DETECTION & ALARM SYSTEM SHOULD BE
IN THE EVENT OF FIRES
05 4. ALL INFORMATION RELATING TO FIRE ESCAPE ROUTES IN
DESIGNED & INSTALLED IN ACCORDANCE WITH BS5839: PART 1:2017.
ACCORDANCE WITH THE BRITISH STANDARD BS 9999:2017 INDICATED 10. ROOM SECURITY & ACCESS REQUIREMENTS IN ACCORDANCE WITH
WITHIN THIS DRAWING IS FOR INFORMATION ONLY. GSK REQUIREMENTS.

LEGEND; NOTES;
2971.8 2438.4
FIRE ESCAPE ROUTE GSK TO CONFIRM THE FOLLOWING:
9m FIRE ESCAPE DISTANCE xxm 1) ACCEPTANCE OF REVISED FIRE STRATEGY.
EXISTING EMERGENCY LIGHTING
P8343B 2) GSK TO DEVELOP & IMPLEMENT
SEAL POT PROPOSED EMERGENCY TEMPORARY FIRE ESCAPE STRATEGY

2971.8
LIGHTING (NEW LIGHTING TO BE WHEN WORKS IN PROGRESS.
NEW SLIDING DOOR D02 WIRED INTO EXISTING SYSTEM)
CANNOT BE USED IN V8344B P8343B LAYDOWN
THE EVENT OF FIRES (ABOVE) AREA
ROOM OCCUPANCY 2
NEW FIRE DOOR

P8344B
SEAL POT P8344B

18m
V8383D
M8397A/B

LAYDOWN M8397C/D
AREA
P8383D
M8382D
DOOR AMENDED TO SUIT LATEST SPEC. ISSUED FOR
05 15/09/23 JB MM
P8383D SEAL POT ACCESS CONSTRUCTION

STAIRS 04 01/08/23 ISSUED FOR WARRANT JB MM

LIGHTING ADDED, LEGEND AMENDED TO SUIT. DOOR


03 27/06/23 SCHEDULE & DOOR FIXING DETAILS ADDED. FIRE ESCAPE JB MM
DRY RISER ROUTE ADDED. EMERGENCY LIGHTING ADDED

02 29/03/23 EXISTING DOUBLE FIRE DOOR INDICATED BM SF


EXISTING FIRE DOOR EXISTING FIRE DOOR
01 24/03/23 ISSUED FOR CONSTRUCTION JB MM

FIRE ESCAPE STRATEGY 00 03/02/23 ISSUED FOR INFORMATION JB MM


SCALE 1:50 FIRE DOOR SCHEDULE
Rev Date Description Dr'n Ch'd
REFERENCE EXTERIOR/INTERIOR DESCRIPTION TYPE S/O WIDTH (mm) S/O HEIGHT (mm) DOOR LEAF WIDTH/HEIGHT (mm) FIRE RATING SELF CLOSURE COMMENTS
Amendments
D01 INTERIOR DISSO ROOM 1 1000 1980 916 / 1930 FD60(S) YES INTERLOCK REQUESTED BY GSK Project

D02 INTERIOR DISSO ROOM 1 910 1980 826 / 1930 FD60(S) YES INTERLOCK REQUESTED BY GSK
DISSO ROOM
05 Title
215
05 HRD CR8x100mm LONG AT
225mm c/c VERTICALLY
DOOR NOTES EXISTING & PROPOSED
EXISTING BRICKWORK WALL
188mm x 75mm CHANNEL SECTION POST FORMED EXISTING BRICKWORK WALL
600
1. ALL STRUCTURAL OPENINGS MUST BE SITE SIZED BY DOOR CONTRACTOR PRIOR FIRE ESCAPE STRATEGY
TO MANUFACTURE.
FROM 4mm THICK HOT ROLLED STEEL PLATE, GRADE 53x14mm STOP

125
53

250
S275 . IF KINGSPAN PANEL DOES NOT SIT TIGHT 2. KICK PLATE STAINLESS STEEL 316 776x150x1.5mm ON BOTH FACES TO INTERNAL Client
KINGSPAN KS1100 CS
WITHIN CHANNEL STEEL SHIMS MAY BE UTILISED. TIMBER DOORS ONLY.
QUADCORE INSULATED WALL 15mm MORTAR 150
2No. ROBESLEE TYPE C
47
44

POLYEURATHANE PANEL VERTICALLY LAID


500
INFILL LINTELS (100Wx145Dp)
215

SEALANT 3. GENERALLY DOOR IRONMONGERY IS TO CONTRAST WITH ITS BACKGROUND BY A


6.3mm Ø x 80mm Lg 175 188mm x 75mm CHANNEL SECTION LINTEL

715
INTUMESCENT DOOR MINIMUM OF 20%. AND TO MATCH THE EXISTING GSK DOORS IN THE ADJACENT
TEK SCREWS @225mm FORMED FROM 4mm THICK HOT ROLLED STEEL SEALS AS REQUIRED ENGINEERING OFFICES. Kiloh Associates
C/C VERTICAL PLATE, GRADE S275 . IF KINGSPAN PANEL DOES 200 Local Engineering for Local Clients
S/W PACK
175

NOT SIT TIGHT WITHIN CHANNEL STEEL SHIMS POLYEURATHANE 4. ALL DOOR LEAFS TO HAVE 2 PAIR (4 No.) HINGES. Unit 6, Pitreavie Court,
250

53x14mm STOP POLYEURATHANE


53

MAY BE UTILISED. SEALANT S/W PACK


SEALANT Pitreavie Business Park,
5. GLAZED VISION PANELS NOTES. DIMENSIONS ARE CLEAR OPENING SIZE. ALL
POLYEURATHANE SEALANT CUT MASONRY 130 SIZES ARE TO BE CHECKED ON SITE PRIOR TO MANUFACTURE OF THE FRAME. Dunfermline, Fife,
47
44

1250
DOOR LEAF

FACE TIDED UP KY11 8UU


715
2100 CSO

6.3mm Ø x 80mm Lg TEK


1020

44 05 53x14mm STOP 6. INTERNAL GLAZING BY SPECIALIST CONTRACTOR. GLAZING IN INTERNAL WALLS t: 0131 629 3434
DOOR LEAF

SCREWS @225mm C/C


850

INTUMESCENT DOOR
2040

STRUCTURAL OPENING - AND DOORS TO COMPLY WITH BUILDING REGULATIONS PART 4.8.2 COLLISION
2100 CSO

S/W PACK SEALS AS REQUIRED 47 53 6.3mm Ø x 100mm Lg TAPCON e:en [email protected]


SEE SCHEDULE 44 CONCRETE SCREWS WITH GLAZING AND BS 6262: PART 4: 2005, SPECIFICATION FOR IMPACT
www.kiloh.co.uk
400
2040

STRUCTURAL OPENING - KICK PLATE PERFORMANCE REQUIREMENTS FOR FLAT SAFETY GLASS AND FIRE RATED IN
250

53x14mm STOP ACCORDANCE WITH FIRE DOOR RATING. Status


8

SEE SCHEDULE
JAMB DETAIL 47 53 916 CONSTRUCTION
HEAD DETAIL JAMB DETAIL HEAD DETAIL S.0. SEE SCHEDULE Drawn by Date Designed by Checked by

JB FEBRUARY 2023 SF MM
DOOR DETAILS - D01 DOOR DETAILS - D02 DOOR TYPE 1 (VP1) Scales @ A1
SCALE 1:5 SCALE 1:5 SCALE: 1:25 05 work to figured dimensions only 1:50 Project No.
KIL2189
Drawing No.
KIL2189_102_0002 Rev
05