Data Sheet Basket Filter-ATF R1
Data Sheet Basket Filter-ATF R1
MECHANICAL DATA SHEET FOR BASKET FILTER Client Job Number C241112
F-1001 A/B Total Sheets 4
3 SERVICE ATF
5 LIQUID DENSITY kg/m 3 775 - 840
DESIGN CONSIDERATION
28 DESIGN CODE ASME -SEC VIII DIV-1 (LATEST EDITION)
Page 2 of 4
Providing Design, Detailed Engineering Including Residual
Engineering Consultancy, Procurement & Inspection Services For
Piyala Jewar ATF Pipeline (PJPL) Project of BPCL
GENERAL SPECIFICATION
NOZZLE DETAIL
12.04.20
C1 ISSUED FOR CLIENT COMMENTS UOM Size, Pressure Rating & Flange Type/End Details
19
B1 N1 LIQUID INLET Inch 10" NB, 300#, WNRF 30 HC
42 N2 LIQUID OUTLET Inch 10" NB, 300#, WNRF 30 HC
63 PAINTING Required (As per VCS Doc. No. SS-PI-008 for Coastal and Marine environment)
64 INSULATION NA
NOTES :
1 VENDOR TO PROVIDE THE DATA AS MARKED "#".
THIS DATA SHEET TO BE READ IN CONJUNCTION WITH THE MATERIAL REQUISITION (DOC. NO. ) & TECHNICAL
2
SPECIFICATION (DOC. NO. VPC-SS-ME-009) & PROCESS DATA SHEET (DOC. NO. C241112-00-PC-PDS- 10022).
3 FILTER ELEMENT MUST WITHSTAND A DIFFERENTIAL PRESSURE OF 1 KG/CM2 WITHOUT CRACKING AND FAILING.
4 FLANGES AND GASKETS SHALL CONFORM TO ASME B16.5 ≤ 24 " NB & B16.47 SERIES A FOR ≥ 26" NB & ASME B16.20 RESPECTIVELY.
BIDDER TO PROVIDE LOAD CALCULATIONS FOR INLET & OUTLET NOZZLES MENTIONING ALLOWABLE FORCES AND MOMENTS.
5
AS PER PRESSURE VESSEL SPECIFICATION NO.VPC-SS-ME--008.
6 ALL GASKETS USED FOR HYDROSTATIC TESTING SHALL BE SAME AS SERVICE GASKETS.
ALL BUTT WELDED JOINTS SHALL BE FULL PENETRATION WELD & ROOT RUN SHALL BE CARRIED OUT BY TIG, IF ACCESSIBLE FROM OTHER
7
SIDES SHALL BACK CHIPPED TO SOUND METAL & REWELD.
NET OPENING AREA OF FILTER ELEMENT SHALL BE AT LEAST 8 X CROSS SECTIONAL AREA OF INLET NOZZLE..Cartridge filter vessels shall be
9
quick opening type .VENDOR to size Cartridge filter vessel for specified performance
10 EARTHING LUG SHALL NOT BE GALVANISED OR PAINTED.
DPI SHALL NOT EXCEED 0.5 KGF/CM2 THROUGHOUT EST. CLEAN/REPLACE CYCLE TIME WITH SPECIFIED REMOVAL EFFICIENCY
12
13 VENDOR TO ENSURE THAT FILTER SHALL BE SIZED FOR MINIMUM FLOW FOR 10% OF DESIGN FLOW.(TURN DOWN RATIO 10:1)
Page 3 of 4