Filters
Filters
Filters
Radio-interference suppression:
National and international standards specify limits to the harmonics
which equipment can induce in the lines, normally limits in the range
of 0.15 to 30 at the higher frequencies; it is easily possible for standing
–wave phenomena
The harmonic voltage between lines is termed symmetrical voltages,
and those between either line and earth and symmetrical voltage.
Typically, a limit is specified of a 2mv at the supply terminals, and
10mv at the load terminals for the range 5 to 30 mHz, the voltages –
being those measured across 150 Ω connected between lines or line to
earth.
Harmonic Components:
-Harmonic Current Flow
The current drawn by non-linear loads passes through all of the
impedance between the system source and load. This current produces
harmonic voltages for each harmonic as it flows through the system
impedance. These harmonic voltages sum and produce a distorted
voltage when combined with the fundamental. The voltage distortion
magnitude is dependent on the source impedance and the harmonic
voltages produced.
1
be performed if the facility conditions meet one or more of the criteria
below.
The application of capacitor banks in systems where 20% or more of
the load includes other harmonic generating equipment or where
background distortion exceeds 2%.
The facility has a history of harmonic related problems, including
excessive capacitor fuse operation.
Large single non-linear loads are being added greater than about 10%
of the transformer rating.
Many small identical non-linear loads are being added that operate
together.
In facilities where restrictive power company requirements limit the
harmonic injection
back into their system to very small magnitudes.
When coordinating and planning to add an emergency standby
generator as an alternate power source for non-linear load.
Often, the vendor or supplier of non-linear load equipment, such as
variable frequency drives, can evaluate the effects that the equipment
may have on the distribution system.
This usually involves details related to the design of the distribution
system similar to the data required when performing a short circuit
study. Such a study should consider all harmonic sources, including the
utility background distortion.
Reducing Harmonics:
There are many ways to reduce harmonics, ranging from variable
frequency drive designs to the addition of auxiliary equipment.
Following are some of the more common methods used today for
controlling power system harmonics.
Power System Design: Harmonic problems can be kept in check by
limiting the nonlinear load to 30% of the supply transformer rating.
However, with power factor correction capacitors installed, resonant
2
conditions could potentially limit the percentage of non-linear loads.
Use the following equation to determine if a resonant condition is
likely to occur at an undesirable frequency:
3
necessary to determine the capacitor current spectra explicitly. The dc
current spectrum already has been calculated and measured for sine
triangular modulation in and determined by experiment for space vector
modulation as well.
Conclusions:
This work is designed to give the reader a comprehensive understanding
of the harmonic phenomenon. This phenomenon has grown to be a
problem in recent years due to the ever-increasing non
linear loads. It is shown that apart from the traditional effects of
overheating and pulsating torques, harmonics can lead to malfunctions
in control devices due to incorrect or several zero crossings. Poor power
factor is another negative effect. Among the mitigation techniques, the
traditional passive filtering approach is no longer attractive due to its
high kVA rating. Among current injection and Active filtering, the later
is more attractive because of the absence of
power dissipating equipments and fast transient response. The basic
active filtering is illustrated through circuits and actual hardware
generated key waveforms.
With the proliferation of non-linear loads, the issues of power
harmonics are more apparent than ever. Controlling and monitoring
industrial system designs and their effects on utility distribution
systems are a potential problem for the industrial consumer, who is
responsible for complying with the IEEE 519-1992 recommended
practices and procedures. Industrial facilities should include a system
evaluation, including a harmonic distortion analysis, while planning
facility construction or expansion. Vendors of non-linear loads, such as
variable frequency drives, can pro-vide services and recommend
equipment that will reduce harmonics in order to comply with the
revised IEEE 519-1992 guidelines
4
References