As 3814 - 2009
As 3814 - 2009
As 3814 - 2009
Australian Standard®
Standards Australia wishes to acknowledge the participation of the expert individuals that
contributed to the development of this Standard through their representation on the
Committee and through the public comment period.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Standards may also be withdrawn. It is important that readers assure themselves they are
using a current Standard, which should include any amendments that may have been
published since the Standard was published.
Detailed information about Australian Standards, drafts, amendments and new projects can
be found by visiting w ww.standards.org.au
Australian Standard®
Originated as AG 501—1984
Previous edition 2002.
Republished and designated AS 3814—2005.
Second edition 2009.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
COPYRIGHT
© Standards Australia
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher.
Published by Standards Australia GPO Box 476, Sydney, NSW 2001, Australia
ISBN 0 7337 9218 9
AS 3814—2009 2
PREFACE
This Standard was reviewed by the Standards Australia Committee, AG-011, Industrial and
Commercial Gas-Fired Appliances, to supersede AS 3814—2005, Industrial and
commercial gas-fired appliances.
This Standard incorporates Amendment No. 1 (June 2010). The changes required by the
Amendment are indicated in the text by a marginal bar and amendment number against the
clause, note, table, figure or part thereof affected.
The objective of this Standard is to provide uniform minimum requirements for the safe
operation of gas-fired industrial appliances, and other large appliances used for commercial
applications, which are not covered by any other Standard.
This Standard should not be regarded as a design specification or as an instruction manual;
it has been prepared with due regard for gas rules and regulations now in force. In its
preparation, consideration has been given to—
(a) continuity of satisfactory operation of appliances and equipment;
(b) the prevention of fire hazards, and explosions associated with fuel use and processes;
(c) gas rules and regulations now in force;
(d) the prevention of injury to persons or property;
(e) the provision of satisfactory permanent access for service; and
(f) relevant international and overseas Standards.
Explosions are the main hazard on the firing side of the equipment covered by the Standard,
the basic cause being ignition of a combustible mixture in the combustion chamber or
associated ductwork. The magnitude and intensity of the explosion will depend on both the
quantity of combustibles present and the proportion of air with which the combustibles are
mixed.
Explosions may be the result of one or more of the following:
(i) Improper design of equipment or control systems.
(ii) Equipment or control system malfunction, including valve leakage.
(iii) Interruption and restoration of gas or air supply causing loss of flame followed by
delayed ignition of the resultant accumulation of a combustible mixture.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
(iv) Flame failure on a burner and subsequent ignition of the resultant accumulation of a
combustible mixture.
The presence of a well-trained, reliable and competent operator provides a major
contribution to safety.
AS 3814—2005 has been substantially revised with the objective of removing ambiguity
where it may have been experienced in the past. To this end a new section on gas/air ratio
control has been added. Several other sections have been expanded to cater for changing
technology, for example, the use of LEL monitoring or the inclusion of systems that are
commonly found on gas-fired turbines that were not previously covered adequately. The
appendices have been expanded to cover information on maintenance of appliances, the
configuration of gas/air ratio control systems as well as valve train requirements for gas-
fired turbines. The appliance field check sheet has been revised to cover the new clauses
and sections added to the Standard.
3 AS 3814—2009
The user should be aware that in many jurisdictions in Australia, this Standard is deemed as
a ‘prescribed standard’ to which compliance may be mandatory. While Australian and New
Zealand Standards mostly do not do so, all the Australian and New Zealand Technical
Regulators agree that this Standard should include appropriate requirements for particular
components to be certified by a recognized third party assessment body.
The terms ‘normative’ and ‘informative’ have been used in this Standard to define the
application of the appendix to which they apply. A ‘normative’ appendix is an integral part
of a Standard, whereas an ‘informative’ appendix is only for information and guidance.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
AS 3814—2009 4
CONTENTS
Page
SECTION 3 OPERATION
3.1 APPLIANCE OPERATION DETAILS ..................................................................... 52
3.2 IGNITION ................................................................................................................. 52
3.3 MAIN BURNERS ..................................................................................................... 54
3.4 INTERLOCKS AND LIMIT DEVICES.................................................................... 55
3.5 OPERATION SEQUENCES ..................................................................................... 56
3.6 COMBUSTION CONDITIONS ................................................................................ 57
3.7 COMMISSIONING................................................................................................... 58
Page
APPENDICES
A TYPICAL INFORMATION AND TECHNICAL DATA .......................................... 79
B TYPICAL PROCEDURE FOR THE APPROVAL OF INDUSTRIAL AND
COMMERCIAL APPLIANCES................................................................................ 83
C TYPICAL VALVE TRAIN ARRANGEMENTS ...................................................... 84
D FLAME SAFEGUARD SELECTION ....................................................................... 90
E PRO-FORMA LETTER TO THE GAS TECHNICAL REGULATOR FROM A
CONTRACTOR /COMPANY CERTIFYING THE TESTS CONDUCTED ON
THE PES .................................................................................................................. 92
F GAS/AIR RATIO CONTROL PROGRAMMABLE ELECTRONIC SYSTEMS...... 93
G MAINTENANCE AND CHECKS OF SAFETY DEVICES...................................... 96
H TYPICAL OPERATING SEQUENCE FOR AN AUTOMATIC FORCED
OR INDUCED DRAUGHT BURNER WITH INTERRUPTED PILOT.................. 101
I TYPICAL COMMISSIONING PROCEDURE ....................................................... 104
J TYPICAL FIELD CHECK LIST ............................................................................ 107
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
AS 3814—2009 6
STANDARDS AUSTRALIA
Australian Standard
Industrial and commercial gas-fired appliances
1.1 SCOPE
1.1.1 General
This Standard provides minimum requirements for the design, construction and safe
operation of Type B appliances that use town gas, natural gas, simulated natural gas,
liquefied petroleum gas, tempered liquefied petroleum gas or any combination of these
gases either together or with other fuels.
Construction requirements given relate only to matters affecting gas-firing or to any
interconnection between the gas-firing system and the safety requirements of the appliance.
NOTE: Additional information regarding safety principles for industrial appliances is given in
AS 1375.
The Standard does not cover all the requirements for the safety of the process carried out in
the appliance. Other statutory and regulatory requirements may be applicable to the
appliances and/or installations that fall within the scope of this Standard. It is the
installer/manufacturer’s responsibility to ensure that appliances and/or installations comply
with these requirements.
Installation requirements for appliances covered by this Standard are detailed in AS 5601.
1.1.2 Exclusions from Standard
The following appliances are excluded from this Standard:
(a) Manually operated bunsen type burners.
(b) Simple atmospheric burners that are not fitted into a combustion chamber and burn in
an open ventilated space under the control of an operator.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
1.2 APPLICATION
1.2.1 General
The requirements of this Standard shall be used in conjunction with, but do not take
precedence over, the requirements of the technical regulator. The technical regulator may
determine the extent of application of this Standard.
This Standard applies to—
(a) the appliance;
(b) the component parts of the appliance whether supplied with the appliance or
separately; and
(c) Type B appliance approvals commenced after its publication date.
NOTES:
1 ‘Commenced’, for the purpose of this Clause, means the point at which Type B acceptance
has begun.
2 Appliances should comply with requirements of all authorities before being placed into
service (e.g. electrical, water, environmental, occupational health and safety etc.).
1.2.2 Appliance installation
Before an appliance is connected to a gas supply, a submission containing the standard and
technical data specified by the technical regulator may be required by the technical
regulator, in accordance with the administrative procedures of the technical regulator.
NOTE: Typical data and procedural requirements are given in Appendices A and B.
1.2.3 New materials and methods
Materials or methods not prescribed in this Standard shall—
(a) not necessarily be excluded from use if they are not specifically referred to; and
(b) only be used if they are acceptable to the technical regulator.
1.2.4 Unusual installations
Certain gas installations or portions of installations that are unusual due to particular
circumstances or methods may not be covered in detail by this Standard. Details of such gas
installations may be required to be approved by the technical regulator before any work
commences.
1.2.5 Modification or relocation of an appliance
Where an appliance is modified or relocated, it should be upgraded to meet the
requirements of this Standard current at the time of the modification or relocation and may
need to be re-submitted to the technical regulator for approval.
AS
5601 Gas installations
61508 Functional safety of electrical/electronic/programmable electronic safety-
related systems (series)
AS IEC
61511 Functional safety—Safety instrumented systems for the process industry sector
AS/NZS
1425 LP Gas for fuel systems for vehicle engines
1596 The storage and handling of LP Gas
1869 Hose and hose assemblies for liquefied petroleum gases (LP Gas), natural gas
and town gas
3000 Electrical installations (known as the Australian/New Zealand Wiring Rules)
ISO
10380 Pipework—Corrugated metal hoses and hose assemblies
21789 Gas turbine applications—Safety
BS
6501-1 Metal hose assemblies. Guidance on the construction and use of corrugated
hose assemblies
ASTM
F1120 Standard specification for circular metallic bellows type expansion joints for
piping applications
EN
298 Automatic gas burner control systems for gas burners and gas burning
appliances with or without fans
1.4 DEFINITIONS
For the purpose of this Standard, the following definitions apply:
1.4.1 Accessible
Access can be gained without hazard or undue difficulty for inspection, repair, renewal, or
operational purposes.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
mechanical assistance.
1.4.12.2 Automatic burner
A burner system that, on starting, follows a self-acting sequence that has been manually or
automatically initiated, to provide gas and ignition to the burner without any intermediate
manual operation.
1.4.12.3 Forced draught burner
A system where all of the air, oxygen or a mixture of the two used for combustion is
provided under pressure.
1.4.12.4 Induced draught burner
A system where all or part of the air for combustion is introduced by providing suction in
the combustion chamber by mechanical means.
1.4.12.5 Multi-fuel alternative burner
A multi-fuel burner that can use only one fuel at a time.
1.4.58 In service
An appliance connected to the gas supply irrespective of the on or off status of the isolation
valve.
1.4.59 Indoor flueless appliance
An indoor appliance designed to discharge its combustion products into the same room or
space in which it is installed.
1.4.60 Induced draught burner
See ‘Burner’.
1.4.61 Injector
A device that causes air to mix with a stream of gas. In the case of an aerated burner it
incorporates an orifice discharging gas into the mixing tube or throat.
1.4.62 Interlock
A device or function that ensures that the operation of items of equipment is dependent
upon the fulfilment of predetermined conditions by other items of equipment.
1.4.63 Intermittent pilot
A pilot that is automatically ignited each time the burner is started, and which is
automatically extinguished with the main burner.
1.4.64 Interrupted pilot
A pilot that is automatically ignited each time the burner is started, and which is
automatically extinguished at the end of the main flame establishment period.
1.4.65 Leakage detection system
A means of checking that the safety shut off valves and the vent valves, where fitted, of a
safety shut off system are gas tight, also referred to as a valve proving system.
1.4.66 Light back
Transfer of the flame from burner port(s) into the body of the burner or back to the injector.
1.4.67 Limit device
A device that is actuated by the approach to a hazardous situation in an appliance due to
abnormal conditions, and when actuated, causes the gas supply to all burners to shut off
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
with lockout.
1.4.68 Lockout
A safety shutdown condition of the control system that requires a manual reset in order to
restart.
1.4.69 Lower explosive limit (LEL)
The lowest percentage of gas in a mixture of gas and air in which combustion can be self-
sustaining at standard temperature (15°C) and pressure (101.325 kPa absolute) conditions.
1.4.70 Low-gas-pressure detector
A sensing device that is actuated when the gas pressure falls below a pre-set value.
1.4.71 Manual ignition
The lighting of gas at a burner by a manual operation whenever gas flows from the burner.
The appliance gas consumption, in megajoules per hour, stated in specifications, data
plates, instructions and general communications.
1.4.83 Non-return valve
A device designed to operate automatically to prevent reversal of flow in a pipe.
1.4.84 Open flued appliance
An indoor appliance designed to be connected to an open flue system, its combustion air
being drawn from the room or space in which it is installed.
1.4.85 Operating pressure
The gas pressure that the consumer piping or the appliance is or will be subjected to under
normal operating conditions.
1.4.86 Over-pressure protection system
A system preventing the pressure in piping or in an appliance from exceeding a
predetermined value.
A system based on one or more central processing units (CPUs), connected to sensors
and/or actuators, for the purpose of control, protection or monitoring.
1.4.98 Programming flame safeguard
A flame safeguard that automatically sequences at least two burner functions such as
ignition spark, gas valve, etc.
1.4.99 Proof-of-closure switch
A switch fitted to a safety shut off valve that is only activated after the valve is closed and
incorporates over-travel of the valve past the position where the valve is just closed.
1.4.100 Protected pilot
A pilot that is fitted with a flame safeguard.
1.4.101 Purge (or purging)
With respect to an appliance means the removal of combustibles.
2.7 MATERIALS
2.7.1 Materials to be adequate for their intended application
To ensure safe operation, materials used for the construction of an appliance shall be—
(a) strong enough for their intended application;
(b) sufficiently resistant to heat; and
(c) sufficiently resistant to corrosion.
2.7.2 Restriction on use of zinc-base die-castings
Zinc-base die-casting alloys shall not be used where—
(a) failure may result in leakage or ignition of gas;
(b) temperatures may exceed 90°C; or
(c) the alloy is in contact with water.
2.7.3 Materials to be suitable for gas
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Materials in contact with gas shall be suitable for use with the gas for which the equipment
has been designed.
TABLE 2.1
RECOMMENDED MAXIMUM TEMPERATURES OF
SURFACES AND COMPONENTS
Maximum temperature
Surface or component °C
(c) do not contain loose parts that may become detached when the valve handle, dial or
pointer is removed.
2.8.7 Appliance isolating valve
2.8.7.1 Appliance isolating valve to be fitted
A quarter-turn manual shut off valve shall be fitted to isolate all gas to the appliance.
2.8.7.2 Requirements for appliance isolating valve
The appliance isolating valve shall comply with all of the following:
(a) Subject to (b), and be certified to the Type 1 requirements of AS 4617. For valves
requiring excessive physical force to operate, an alternative means to a single-action
type lever may be used provided it has position indication. For valves outside the
scope of AS 4617, the safety requirements detailed in that standard shall be met at
least at an equivalent level and the valve shall be certified. A declaration by the OEM
(original equipment manufacturer) of the valve, which supports the fitness for
purpose of the valves for the application, may be acceptable to the technical
regulator.
NOTE: Guidance on the physical strength for the hand-operation of equipment is given in
EN 614-1.
(b) Be capable of being connected to the inlet piping such that, when the outlet piping is
disconnected from it, the valve will remain securely attached to the inlet piping.
(c) Be suitable for the application.
2.8.7.3 Location of appliance isolating valve
The appliance isolating valve shall be—
(a) located upstream of—
(i) all other controls, and
(ii) the start gas line;
(b) in close proximity to the appliance; and
(c) accessible to enable quick isolation of the gas supply.
2.8.7.4 Identification of appliance isolating valve
Where the location of the appliance isolating valve is such that the valve is not readily
identifiable, a notice shall be provided to clearly indicate—
(a) the function of the valve; and
(b) the appliance that it isolates.
2.8.7.5 Connection of appliance isolating valve
The valve train shall be connected to the appliance isolating valve by means of a flange or
union.
NOTE: This is to enable the valve train to be disconnected from the gas supply.
2.8.8 Main Burner Isolation
2.8.8.1 Main burner isolation valve
Where multiple burners are fitted to an appliance and the appliance can continue to operate
with one or more burners and its associated valve train being serviced, each burner shall be
fitted with suitable means of isolation to allow safe removal of valve train components,
servicing and commissioning of the burner.
Where the appliance burner is located remote from the appliance isolation valve, a separate
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
certified burner isolation valve shall be fitted unless the appliance isolating valve is capable
of being locked in the ‘off’ position.
NOTE: For the purposes of Subclause 2.8.8.1, ‘remote’ is taken to mean it requires access by means
of a ladder over 1.5 m to reach the burner or that it is in excess of 5 metres from the burner at the
same level. The intent of the additional requirement is to facilitate quick location and access to the
appliance isolation valve and, in the case of servicing, allow safe isolation of gas to the burner or
appliance being serviced.
2.8.8.2 Main burner isolation for commissioning
For the purposes of commissioning at the start gas rate, a permanent means shall be
provided to prevent gas from flowing at rates other than the start gas rate specified in
Clause 3.2.3.
NOTE: Suitable means of isolation include the following:
(a) A manual shut off valve (test firing valve) located immediately downstream of the main gas
safety shut off valve(s).
(b) A test firing valve located between the start gas take-off point and the first main gas safety
shut off valve.
(c) A clearly marked removable electrical plug, positive action switch or link in the electrical
supply to the main-gas safety shut off valves (or the main-gas control function within the
safety shut off valves), which cannot be inadvertently or incorrectly reconnected to the
electrical supply. Disconnection of electrical wiring does not satisfy this requirement.
(d) For gas-fired turbines, other means may be used to set the start gas rate to meet the intent of
this Clause.
2.8.9 Restriction on test firing valve
A test firing valve, if fitted, shall not be used to regulate gas input to the main burner under
normal operating conditions.
2.8.10 Pilot burner isolating valve
A manual shut off valve shall—
(a) be fitted to the gas supply line of a pilot burner;
(b) enable the gas supply to a pilot burner to be turned off independently of the main
burner; and
(c) meet the Type 1 requirements of AS 4617 and be certified.
NOTE: The use of a manually-opened pilot take-off port incorporated in a certified thermoelectric
flame safeguard, meeting the requirements of AS 4620 or AS 4624, will satisfy the requirements
of this Clause.
(ii) Where a combination gas control performs the function of both gas pressure
regulator and gas/air ratio control in response to combustion air pressure
changes, the shut off pressure at the system sensing point shall be as low as
possible without causing nuisance shutdowns but shall not exceed 35% above
the pressure at the highest normal firing rate.
NOTE: In order to prevent the production of excessive quantities of carbon monoxide
at less than the maximum burner firing rate, the shut off pressure should be set to the
lowest setting possible without nuisance shutdowns occurring.
2.10.4 Location of over-pressure protection system sensing point
The sensing point for the over-pressure protection system shall be located—
(a) to ensure that the requirements of Clause 2.10.3(a) can be met; and
(b) either—
(i) downstream of a gas pressure regulator; or
(ii) downstream of a combination gas control performing the function of both gas
pressure regulator and gas/air ratio control in response to combustion air
pressure changes.
NOTE: The sensing point should not be located between double block valves.
(b) For a main burner with a total input exceeding 500 MJ/h (140 kW) but not exceeding
5 GJ/h (1.4 MW) (refer to Figure 2.2)—
(i) an additional Class 1 safety shut off valve is fitted in the start gas line; and
(ii) the downstream main gas safety shut off valve is fitted with a closed position
indicator switch.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
FIGURE 2.2 BURNERS OVER 500 MJ/h (140 kW) AND UP TO 5 GJ/h (1.4 MW)
(c) For a main burner with a total input exceeding 5 GJ/h (1.4 MW) but not exceeding
20 GJ/h (5.5 MW) (refer to Figure 2.3), an additional Class 1 safety shut off valve is
fitted in the start gas line and either—
(i) a leakage detection system is fitted; or
(ii) the downstream main gas safety shut off valve is fitted with a proof-of-closure
switch.
FIGURE 2.3 BURNERS OVER 5 GJ/h (1.4 MW) AND UP TO 20 GJ/h (5.5 MW)
(d) For a main burner with a total input exceeding 20 GJ/h (5.5 MW) (refer to
Figure 2.4), an additional Class 1 safety shut off valve is fitted in the start gas line
and either—
(i) a leakage detection system is fitted; or
(ii) all the safety shut off valves are fitted with proof-of-closure switches.
Where a main burner is ignited by a separate pilot and the flow rate through the main burner
safety shut off valve system exceeds 1 GJ/h (275 kW) at start-up, one of the safety shut off
valves in the main burner gas supply, downstream of the pilot gas take off, shall have an
opening time of not less than 5 s.
2.14.6 Requirements for a safety shut off valve and vent valve
2.14.6.1 Rated working pressure
The operating pressure of a safety shut off valve and vent valve shall not exceed the
maximum rated working pressure.
2.14.6.2 Orientation
A safety shut off valve or vent valve shall be fitted in an orientation for which it is
designed.
2.14.6.3 Size of vent valve for a double block and vent safety shut off system
Except as permitted in Clause 2.14.6.4, the minimum size of a vent valve that is part of a
double block and vent safety shut off system shall comply with Table 2.2.
2.14.6.4 Size of vent valve for a leakage detection system
The size of the valve in the vent line of a leakage detection system shall not be less than
8 mm.
2.14.6.5 Arrangement for manual reset vent valve
A manual reset vent valve used in a double block and vent safety shut off system shall be
arranged to prevent gas escaping through the vent line when the upstream safety shut off
valve is open.
2.14.7 Safety shut off system not to be bypassed
A safety shut off system shall not be bypassed unless the bypass is fitted with a safety shut
off system.
2.14.8 Vent line requirement
A vented safety shut off system shall be fitted with a vent line complying with AS 5601.
2.14.9 Requirements for a position-proving system
2.14.9.1 Safety shut off valve
All safety shut off valves used in a position-proving system shall incorporate a proof-of-
closure switch.
2.14.9.2 Vent valve
A vent valve used in a position-proving system shall—
(a) comply with Table 2.2; and
(b) incorporate a position indicator switch.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
TABLE 2.2
MINIMUM SIZE OF VENT VALVE
Minimum size of vent valve
Nominal size of largest mm
safety shut off valve
mm Double block and vent Position proving
systems systems
Less than 20 Same as safety shut off Same as safety shut off
valve valve
20-40 20 15
50 25 15
65 32 20
80 40 20
100 50 25
150 65 32
200 80 50
NOTE: Where a safety shut off valve greater than 200 NB is used, the vent valve may be sized
using an appropriate method such as found in Appendix 6 (for pressures > 100 kPa) of Sizing
of vents of The Institute of Gas Engineers, 2000, IGE/UP/9 The Application of Natural Gas
Fuel Systems to Gas Turbines and Supplementary and Auxiliary Fired Burners, London, UK.
2 A single pressure transmitter is also permissible to perform the above required monitoring
functions.
(c) The pressure settings of switches referred to in (b) shall not overlap.
(d) Where the contents of the space between the safety shut off valves are to be released
into the combustion chamber all of the following shall apply:
(i) The contents of the space are to be released through the burner head.
(ii) A Class 1 safety shut off valve is to be used.
(iii) The average flow rate is to comply with the requirements of Clause 3.2.3.
(iv) The valve used is not to be open for more than 5 s.
(v) The purge air flow is to be—
(A) proved before the valve is opened; or
(B) programmed to start immediately upon completion of a successful
leakage detection cycle.
(vi) The pre-purge requirements of Clause 2.19 are to be met after the valve has
closed as part of the leakage detection cycle.
NOTE: Line pressure shall be no less than the outlet pressure of the next upstream regulator.
2.14.11 Function of interlocks
Where a safety shut off system controls a gas consumption in excess of 20 GJ/h to a
burner(s) which fires into a combustion chamber either connected to a common flue or with
multiple burners firing into it, then the interlocks required by Clauses 2.14.9.3 and
2.14.10.2 shall—
(a) where the appliance is unattended, act on all burners sharing the combustion chamber
or common flue; or
(b) where an operator is in attendance, activate an alarm.
NOTE: The nature and location of an alarm (i.e. audible, visible etc.) should be such that the
operator’s attention is attracted.
2.14.12 Requirements of safety shut off system actuators
2.14.12.1 Individual actuators to be fitted
All valves in a double block and vent safety shut off system shall be individual valves fitted
with their own individual actuators unless the valve fulfils the requirements of either
Clause 2.14.12.2 or 2.14.12.3.
2.14.12.2 Single three-way valve permitted
The combining of a safety shut off valve and a vent valve in a single three-way valve is
permitted provided that all the following conditions are met:
(a) The safety shut off valve is the downstream safety shut off valve.
(b) When energized the valve is open from inlet to outlet and closed to vent.
(c) When de-energized the valve is open from inlet to vent and closed to the outlet.
2.14.12.3 Use of rigidly coupled actuators
Where the valves of a double block and vent safety shut off system are to be rigidly coupled
to a common actuator, all of the following requirements shall be met:
(a) The coupled vent and safety shut off valves are to be downstream of another safety
shut off valve.
(b) The upstream safety shut off valve is to be fitted with an independent actuator.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
(c) The failure of an interlock that serves all burners is to cause all safety shut off valves
to close and all vent valves to open.
(d) Any condition requiring lockout of an individual burner or burner unit is to cause all
safety shut off valves to close and all vent valves to open on the individual burner or
burner unit.
(e) The means of connecting the rigidly coupled valves is to be constructed so that it is
not readily interfered with.
NOTE: A fixed cover is an acceptable means of preventing interference.
(b) adequate for all operating conditions specified by the equipment manufacturer.
2.15.2 Combustion air quality
Combustion air shall be free of contaminants such as suspended particles, flue gases, water
or other gases or fuels that may adversely affect the combustion process.
NOTE: Flue gases, vapours or flammable substances introduced into the combustion air for
emission or process control should not be considered as contaminants.
2.15.3 Air openings to be of adequate size
Air openings shall be adequate to allow satisfactory combustion in compliance with
Clause 3.6.1.
2.15.4 Air openings not to be obstructed
Measures shall be taken to prevent air openings from being obstructed.
(b) flow-sensing, where tapping points of a differential system should be arranged so that
the static pressure difference, in a system with a closed damper, does not result in an
apparent flow signal being given.
NOTE: Proof of adequate air flow is normally obtained by one of the methods in (a) or (b),
however this list is not exhaustive and other methods may be acceptable to the technical
regulator.
2.17.3 Self-check of air flow proving device
2.17.3.1 Self-check to be carried out
The air flow proving device shall be proved in the no-flow state, prior to start-up.
NOTE: Three way vent solenoids may be used to provide the no air flow signal where it is
impractical to shut down or stop the air flow.
2.17.3.2 Failure of air flow proving device during self-check
Failure of the air flow proving device during a self-check shall cause—
(a) start-up to be prevented; or
(b) lockout.
2.17.4 Safety shutdown to occur if air flow fails
Air flow failure at any time during the pre-purge, ignition or operation of the burner, shall
cause the air flow proving device to initiate safety shutdown within 1 s.
NOTES:
1 Following safety shutdown due to incorrect air pressure or air flow, automatic restart is
permitted provided that repetitive recycling could not cause a hazard.
2 The contactors of a combustion air fan and purging air fan (where fitted) should be
interlocked to cause safety shutdown in the event of the contactors opening.
2.17.5 Air-gas mixtures
2.17.5.1 Air-gas mixing machines and mixing blowers
Air-gas mixing machines and mixing blowers shall comply with the requirements of
Clause 5.3.
2.17.5.2 Maximum temperature of mixtures
The temperature of an air-gas mixture to a burner(s) shall not exceed 50% of the auto-
ignition temperature of the gas in degrees Celsius.
NOTE: Typical values for auto-ignition temperatures are given in Table 2.3.
TABLE 2.3
TYPICAL VALUES FOR AUTO-IGNITION
TEMPERATURES (AIT) OF GASES
Auto-ignition temperature
Fuel gas
°C
Natural gas 540
Simulated natural gas 450
Tempered liquefied petroleum gas 450
Liquefied petroleum gas (Butane) 406
Liquefied petroleum gas (Propane) 450
Town gas 560
2.18 DAMPERS
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
that—
(a) complies with AS/NZS 1869;
(b) is of the minimum practicable length for the application but does not exceed 3 m; and
(c) has a certified manual isolating valve, immediately upstream of the hose assembly.
2.21.2.2 Point of ignition to be accessible
The point of ignition of a manually-ignited burner shall be readily accessible while the
appropriate gas controls are being operated.
2.21.2.3 Explosion relief to be provided for a manually-ignited burner
Where a manually-ignited burner fires into an enclosure in which an explosive
accumulation of gas can occur, the enclosure shall have a fixed area for explosion relief in
accordance with the requirements of AS 1375.
TABLE 2.4
FLAME SAFEGUARD CLASSIFICATION
Flame safeguard classification
(b) 15 s, where—
(i) a main atmospheric burner(s) is used, which is either manually-ignited or fitted
with a manually-ignited permanent pilot(s); and
(ii) the total input to the combustion chamber or connected combustion chambers
where the burner(s) are fitted exceeds 500 MJ/h (140 kW), but does not exceed
1 GJ/h (275 kW);
(c) 3 s, where (a) and (b) do not apply.
2.24.6 Requirements for a flame detector
A flame detector shall be accessible and be certified to—
(a) meet the requirements of AS 4625 for the electronic type;
(b) meet the requirements of AS 4620 for the thermoelectric type; or
(c) an approved equivalent Standard.
2.24.7 Flame simulation to be prevented
Flame simulation in a flame detector shall be prevented.
2.24.8 Detector not to detect other flame
A flame detector shall not detect any flame other than the one it is supervising except that
the pilot flame detector required by Clause 2.24.10 may detect the main flame served by
that pilot.
2.24.9 Requirements for a pilot used on atmospheric burner(s) exceeding 1 GJ/h
(275 kW), or forced or induced draught burner(s)
Where an intermittent or permanent pilot is used on atmospheric burner(s) exceeding 1 GJ/h
(275 kW), forced or induced draught burner(s), either two electronic flame safeguard
systems or two electronic flame detectors connected to one flame safeguard system shall be
used.
2.24.10 Detectors to supervise separate flames
Where an intermittent or permanent pilot is used on atmospheric burner(s) exceeding 1 GJ/h
(275 kW), forced or induced draught burner(s), the flame detector(s) required by
Clause 2.24.9 shall be fitted so that one will supervise the pilot and the other will supervise
the main flame.
2.24.11 Requirements for two flame detectors used with one flame safeguard device
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
or system
Where two flame detectors are used in conjunction with one flame safeguard system—
(a) the safe start check shall ensure that both flame detectors are in the no flame position
prior to start-up;
(b) the safe start check on the main burner flame detector shall continue on through the
pilot flame ignition sequence; and
(c) the loss of flame signal from either flame detector shall cause lockout of the
associated pilot and main burner.
NOTE: It is recommended that a proprietary flame safeguard system that performs the required
functions without alteration be used.
2.24.12 Detector to ensure cross lighting is complete
Where cross lighting is necessary to accomplish satisfactory ignition of supervised burners,
the flame detector(s) shall be positioned to ensure cross lighting is completed within the
flame establishment period.
(e) not be used to provide the ignition source for any burner; and
(f) not interfere with the main burner ignition from the pilot.
2.25.2.3 Bleed line termination to be protected against blockage
The termination of a bleed line that may be exposed to falling particles during normal
operation shall be protected against blockage.
(b) where programmable electronic system (PES) control circuitry is used for a burner
management system, then its performance under fault conditions shall at least match
that achieved by conventional technology. Any single failure, or any dormant
condition followed by another single failure, shall be protected against, so that critical
timings and sequence operations remain safe. This applies right through the electronic
system, from the CPU, memory, etc., through to output devices. The safe state is
complete burner shutdown with lockout.
NOTE: Control circuits should be designed to facilitate the detection of fault conditions; e.g. by
means of fault indicating lights.
2.26.2 Gas-actuated controls
Gas-actuated controls shall be of a type where there is no continuous bleed during the off
period.
2.26.3 Requirements for a programmable electronic system (PES)
A Programmable Electronic System (PES) shall not be installed or modified without
notifying the technical regulator. This excludes components certified in accordance with the
requirements of this Standard.
A PES on a Type B appliance shall comply with all the following requirements:
(a) All systems that perform safety-related functions shall be hard-wired directly to the
PES inputs or outputs.
(b) If a PES controller (logic solver and its associated I/O module) is used to perform
safety-related functions—
(i) it shall be a safety-related PES controller and possess a safety certificate from a
certification body e.g. TÜV, to the appropriate safety integrity level (SIL) of
AS 61508; or
(ii) where a customer/contractor insists on using a non-safety-related PES
controller to perform safety-related functions the safety-integrity of the PES
controller shall be independently verified, to the required SIL, by an
appropriate institution.
(c) The following shall be submitted to the technical regulator:
(i) A relevant flow sheet written in plain English containing the description of
events to occur within the PES. (Typically this would be done prior to writing
the PES program).
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Like computer programs, the only true way of assessing a PES user-program to ensure that
it functions the way it was designed, is to test run the program. It is not possible to inspect a
PES program in its entirety by visual examination and conclude that the program does what
it is required to do under all possible operating situations. In order to ensure the integrity of
the PES user software, the person/company who designed the system shall have an
appropriate quality system, and shall have adhered to the principles outlined in AS 61508.
The designer responsible for the development of the program shall test-run the program by
simulating the inputs, and prove that the outputs occur at the right time and duration.
NOTES:
1 A signed written statement to that effect may be required by the technical regulator (see
Appendix E for a sample of the statement).
The term PES extends to and includes all elements in the system such as—
(a) sensors and/or other input devices;
(b) data links and/or other communication paths; and
(c) actuators and/or other output devices.
2 The term PES includes system software, such as executive, users and communication, that is
configured to operate a process.
3 The term PES is used to cover systems incorporating a wide range of programmable
electronic devices and includes systems incorporating—
(a) microprocessors;
(b) programmable controllers (PCs);
(c) programmable logic controllers (PLCs);
(d) programmable state controllers;
(e) other computer based devices.
4 A PES can include a microprocessor-based temperature, pressure, gas/air ratio or level
controller or monitor.
5 Provision of back-up hard-wired hardware safety systems can be used to reduce PES system
SIL requirements as determined by the SIL analysis of the overall safety system.
11
6 10
2 4
1
8 12
3 5
7
9
13
Key
1 Electronic control module 8 Sensor fuel /air
2 Air 9 Scope of the electronic RC
3 Fuel 10 Sensor flame
4 Actuator air 11 Sensor flue gas
5 Actuator fuel 12 Combustion process
6 Sensor air 13 Burner control system
7 Sensor fuel
TABLE 2.5
ACCEPTABLE FEEDBACK TYPES
Valve X — X X
For air
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Fan — X† X X
Valve X — X X
For fuel
Pressure regulator — — X X
— At least 2 feedbacks (1 gas, 1 air) required ‡
* A feedback signal that is directly related to the mechanical part of the actuator.
† If a fan speed signal is used as means to control the air flow, proof of air flow may not rely on fan rotation
alone. A possible additional signal can be derived from an independent air-proving device checked at least
during start up.
‡ Actuator feedbacks can also be the following from the process:
– Ratio of the actual fuel/air mixture.
– Ratio signal from the flame.
– Signal from the flue gas.
NOTE: In cases where more than one means of control is provided for a stream, additional feedbacks are
required for those additional elements. For example, combined speed control and damper control on air
flow will require speed and position feedback to be incorporated.
the limit device(s) shall be fast enough to shut the system down before hazardous
conditions occur. Consideration should be given to sounding an alarm before this point.
Where the limit device(s) are part of a safety PES, the SIL of the gas/air protection loop
will depend on the application and shall be determined in accordance with AS 61508 or
AS IEC 61511.
Appendix F contains a means to comply with the requirements of this Clause. Alternative
configurations may be acceptable to the technical regulator.
NOTE: During system design it is important to consider the effect of sudden reductions of airflow
to firing burners when opening air registers on the burners prior to bringing them into service.
This problem occurs, for example, with multiple burners supplied from common fans and
common windboxes. In such cases, special consideration of the light off and flame failure
conditions needs to be taken into account.
2.27.7 Additional requirements for pneumatically controlled gas/air ratio
All weep lines, bleed holes and vent lines shall be designed and installed to minimize the
likelihood of blockage by dust, dirt and other such contaminants.
3.2 IGNITION
3.2.1 Starting sequence interlocks before starting burner ignition source
Where interlocks are required by this Standard, or are fitted, they shall ensure that burner
ignition is not initiated until—
(a) power supply is available (if required);
(b) any damper fitted for combustion air or flue gas control is in the correct position;
(c) the pre-purge cycle has been completed;
(d) any leakage detection cycle has been satisfactorily completed;
(e) the combustion air sensor is checked and proved; and
(f) all applicable limit devices are in the operational position.
NOTE: Limit devices may include one or more of the following:
(a) Low liquid level.
(b) Excess pressure.
(c) Excess temperature.
(d) High gas pressure.
(e) Low gas pressure.
(f) Essential process limits.
(g) the flame detection system has undergone a safe-start check.
(h) a purge sequence according to the requirements of this standard has been carried out.
3.2.2 Ignition sequence
3.2.2.1 Commencement of ignition
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Where a pre-purge period is required by this Standard, the ignition spark or other means of
ignition shall commence immediately after the pre-purge period is completed, unless an air
flow is maintained up to ignition to ensure a safe level of dilution of any combustibles that
may be present.
3.2.2.2 Completion of ignition
The ignition spark or other means of ignition shall cease at the end of the start gas flame
establishment period.
NOTE: This requirement is not applicable to gas turbines due to the need to ensure the gas
turbine has a stable flame during starting to achieve self sustaining speed.
3.2.2.3 Start gas flame establishment period
The start gas flame establishment period for a burner with an automatic ignition system
shall not exceed 15 s for a pilot on an atmospheric burner where the pilot gas rate does not
exceed the lesser of:
(a) 1% of the main burner gas rate; or
(b) 5 MJ/h.
For all other cases, the flame establishment period shall not exceed—
(i) 5 s; or
(ii) a value shown to be less than 70% of the appliance critical time demonstrated by
detailed calculations of the system critical time in accordance with AS 1375
Appendix D.
3.2.3 Start gas rate
3.2.3.1 Start gas rate not to exceed determined values
Except for a direct-fired air heater, the start gas rate shall not exceed the value determined
by one of the following methods—
(a) throughout the start gas flame establishment period, the gas concentration in relation
to the proven air flow rate for that period is not to exceed the percentages of the lower
explosive limit (% of LEL) as detailed in Table 3.1, provided that—
(i) the gases during the start gas flame establishment period are thoroughly mixed
with the air flow except in the immediate vicinity of the burner; and
(ii) the pre-heated air temperature does not exceed 400°C; or
NOTES:
1 The gas concentration needs to be within the flammability limits at the burner head to
ensure ignition but must be diluted rapidly to the levels specified to ensure that the
mixture elsewhere in the combustion chamber could not be ignited inadvertently.
2 Typical values of LEL for common gases are summarized in Table 3.2.
(b) the energy released during the start gas flame establishment period does not exceed
35 kJ per cubic metre of combustion chamber volume; or
(c) a start gas rate calculation in accordance with AS 1375.
NOTE: For direct-fired air heaters refer to Clause 5.7.6.
TABLE 3.1
PERCENTAGE OF LOWER EXPLOSIVE
LIMIT VALUES (LEL) TO MEET CLAUSE 3.2.3.1(a)
% of % of % % O2 % CO2
Type of gas
LEL stoichiometric excess air in flue in flue
Natural 50 24 310 16.2 2.7
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
TABLE 3.2
LOWER EXPLOSIVE LIMIT VALUES (LEL)
FOR SELECTED GASES
Type of gas LEL % gas in mix Stoichiometric ratio
Natural 5.00 9.55:1
(b) prevent unsafe operation on interruption and restoration of the interlock power
supply;
(c) prevent starting any portion of the process until safe conditions are re-established;
and
(d) not be readily defeated.
NOTES:
1 Where an interlock disables equipment, the disabling action should—
(a) affect the least equipment;
(b) take place in the safest manner possible; and
(c) activate an alarm, either visual and/or audible to attract the attention of the operator.
2 Where an interlock disables equipment, fault detection should be facilitated by means that
will readily indicate the fault; e.g. fault indicating light(s).
(g) Cessation of the source of ignition at the end of the start gas flame establishment
period in accordance with Clause 3.2.2.2.
(h) A start gas flame proving period in accordance with Clause 3.3.1.
(i) A main flame establishment period in accordance with Clause 3.3.2.
(j) Continuous monitoring during operation.
NOTE: A typical operating sequence for a forced or induced draught burner with interrupted pilot
is given in Appendix H.
3.5.3 Appliance to be left in safe condition
Shutdown of an appliance, regardless of the cause of shutdown, shall leave the appliance
and its associated equipment in a safe condition.
3.5.4 Requirement for lockout on flame failure
Flame failure at the point of supervision shall—
(a) result in lockout of the relevant burner system;
(b) result in lockout of all burners, where two or more burners are served by a common
valve train; or
(c) meet the requirements of Clause 3.5.5.
3.5.5 Reignition attempt on flame failure
3.5.5.1 Requirements for forced or induced draught burners
For a forced or induced draught burner, one reignition attempt after flame failure at the
point of supervision may be made provided—
(a) the initial flame failure resulted in a safety shutdown;
(b) a full restart cycle including any pre-purge is carried out;
(c) the total energy released during the period commencing at flame failure and ending at
cessation of the reignition attempt (i.e. main burner shutdown time plus start gas
establishment time) does not exceed the energy release permitted by Clause 3.2.3.1;
and
(d) failure of the burner to reignite shall result in lockout.
3.5.5.2 Requirements for atmospheric burners
For an atmospheric burner, one reignition attempt after flame failure at the point of
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
3.7 COMMISSIONING
3.7.1 Commissioning checks to be carried out
Before an appliance is placed into service, a systematic check shall be carried out to prove
that the following items are installed and function correctly, and operate in the proper
sequence:
(a) Each item of equipment in a gas valve train and burner;
(b) All controls;
(c) All limit devices;
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
4.1 MARKINGS
4.1.1 Markings to be displayed
All appliances shall have clear, permanent markings that are readily accessible and easy to
read when the appliance is installed. These markings are to include—
(a) manufacturer’s name;
(b) model identification;
(c) nominal gas consumption (MJ/h);
(d) gas type;
(e) maximum and minimum gas supply pressures (kPa);
(f) purge times (min);
(g) gas pressure at the burner head, for the nominal gas consumption (kPa);
(h) combustion chamber volume (m3 );
(i) maximum appliance design temperature (°C);
(j) total volume swept by the combustion products in passing from the burner to the flue
connection (m3);
(k) serial number;
(l) date of manufacture (dd/mm/yyyy);
(m) the purge volume for combustible atmospheres (m3) (where applicable);
NOTE: This includes, as a minimum, the combustion chamber volume, the volume of
recirculation ducts and exhaust (flue) ducts, and that portion of the work chamber in which
free circulation occurs, excluding the chimney.
(n) dilution air volume m3/min at 20°C (where applicable); and
(o) design solvent(s) – type and maximum quantity (L/h) (where applicable).
NOTE: Units of measurement should comply with the SI system.
4.1.2 Marking of controls, dials and gauges
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Any controls, dials and gauges fitted shall have clear, permanent markings.
NOTE: Units of measurement should comply with the SI system.
4.1.3 Controls with non-standard operation
Where the method of operation and direction of motion of manual controls does not comply
with accepted practice or any applicable regulations and standards, they shall be clearly
marked to indicate any variations.
4.2 INSTRUCTIONS
4.2.1 Written instructions to be provided
The manufacturer, designer or supplier of the gas-firing equipment or appliance shall
provide written instructions to enable safe and satisfactory installation, operation and
maintenance of the equipment. These should be provided in English as a minimum to the
owner-operator. These instructions are to include detailed procedures for—
(a) start-up;
5.1 GENERAL
The requirements of this Section are additional to all other requirements of this Standard
but shall take precedence in cases of conflict.
All the following requirements shall apply to a high input gas-fired appliance that is
required by Clause 2.24.2 to have a flame safeguard fitted:
(a) Where a manual or automatic start-up of the appliance or burner(s) is not carried out
at least once in any 24 h period, a continuous self-checking flame safeguard (i.e.
Class 1A, in accordance with AS 4625) is to be fitted.
(b) Where a flame safeguard check is carried out by a manual shutdown and start-up,
specific reference to this is to be made in the operator’s instructions.
(c) Where more than one burner is monitored by a single safety shut off system,
individual ignition and flame detection is to be provided for each burner.
(d) Burners with a total gas consumption that exceeds 20 GJ/h shall have a continuous
self-checking flame safeguard (i.e. Class 1A, in accordance with AS 4625) fitted.
A stop or other means shall be provided to effectively prevent air-gas mixing machines that
supply non-combustible mixtures from being adjusted to within or approaching the
combustible range.
5.3.6.3 Air-gas ratio from a mixing blower
The air-gas ratio from a mixing blower shall be automatically maintained within the
required limits over the entire turndown range.
5.3.7 Mixing blower outlets
Pipework connecting a burner(s) to a mixing blower shall—
(a) not exceed 1 m; and
(b) contain no control or safety device.
(b) The supply line from the generator to the point(s) of use is to be closed during the
entire start-up sequence, including the pre-purge period.
5.4.8 Ignition
Where the special atmosphere is combustible and discharges into an appliance that contains
air, both the following shall apply:
(a) A supervised ignition source that is interlocked in accordance with Clause 3.4.1.1 is
to be provided.
(b) Combustion products are to be discharged in a safe place in accordance with the
flueing requirements of AS 5601.
5.4.9 Requirement where the air-gas ratio is variable
Where the air-gas ratio to an atmosphere generator can be varied during operation, flow
indicators shall—
(a) be installed in the air and gas supply lines; and
(b) be well illuminated and easily read from the generator operating station.
NOTE: A differential pressure gauge across a fixed orifice can be an acceptable method of flow
indication.
5.4.10 Requirements where the air-gas ratio is fixed
Where the air-gas ratio to an atmosphere generator is not variable during operation,
provision shall be made for positively locking the ratio adjustment.
5.4.11 Automatic relief device
Where the special atmosphere is to be used at a variable rate, an automatic relief device
shall be fitted to the special atmosphere line.
5.4.12 Flame arrestor
Where the special atmosphere is combustible, or could form a combustible mixture with air
in pipework or equipment prior to the discharge point, a flame arrestor shall—
(a) be installed; and
(b) incorporate a temperature sensitive device that in the event of an increase in
temperature due to the presence of a flame, will activate to cause the closing of a
safety shut off valve(s) controlling—
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
(i) the gas supply to the reaction vessel of the atmosphere generator; or
(ii) the flow of the special atmosphere to equipment in which a combustible
mixture of air and special atmosphere can be formed.
NOTE: The flame arrestor should be as close as practical to all discharge points that are in the
vicinity of an ignition source.
5.4.13 Water-cooled equipment
The outlet for water discharge from water-cooled equipment shall be either—
(a) permanently open; or
(b) provided with an over-pressure relief device or flow-proving device.
5.4.14 Exothermic atmosphere generators
5.4.14.1 Flame safeguard requirement
A flame safeguard system shall be fitted to an exothermic atmosphere generator.
High and low-gas pressure detectors and a low-air pressure detector shall be:
(a) Fitted to the appliance—
(i) gas supply line; and
(ii) air supply line.
(b) Interlocked so as to cause lockout on activation.
The start gas rate for a direct-fired air heater shall not exceed 10% of the maximum main
burner gas rate.
5.7.7 Combustion
5.7.7.1 Limits for combustion products
A direct-fired air heater shall not produce carbon dioxide, carbon monoxide, aldehydes or
nitrogen dioxide in excess of the following values, with the heater handling the
manufacturer’s rated air throughput at nominal gas consumption and at the manufacturer’s
minimum gas consumption—
(a) CO 2 3000 ppm;
(b) CO 10 ppm;
(c) Formaldehyd 1 ppm; and
(d) NO X 0.5 ppm.
NOTES:
1 The ratio of CO to CO2 should not exceed 0.003.
2 In some areas the ambient level of CO may cause the outlet level of CO from the heater to be higher.
However, the level of CO in the heated air stream should not exceed 50 ppm.
For OEM safety shut off valves, a flow control valve shall not be used as a safety shut off
valve. Where a safety shut off valve is used in combination with a control valve, the
assembly shall be considered as equivalent to a single valve only.
5.8.2.3 Emergency isolation and vent valves
A combined emergency manual isolation valve and manual vent valve in compliance with
AS 4617 shall be provided outside of any turbine enclosure or turbine hall. For valves
outside the scope of AS 4617, the safety requirements detailed in that standard shall be met
at least at an equivalent level and the valve shall be certified. A declaration by the OEM of
both the appliance and valves, which supports the fitness for purpose of the valves for the
application, may be acceptable to the technical regulator.
Where the gas rate to the turbine exceeds 5.0 GJ/h, this system shall be automatically
actuated.
Automatic emergency isolation and vent valves shall comply with the requirements of
Clause 5.8.2.2.
NOTE: Automatic actuation of the emergency valve is normally from the operation of the
emergency stop or, if required, from the fire or gas-detection system.
5.8.2.4 Activation of the safety shut off system to shut off gas supply
Safety shutdown shall occur when—
(a) the gas engine or turbine stops;
(b) the gas engine or turbine fails to ignite the gas; or
(c) the inlet gas pressure is reduced to an operating pressure below the normal minimum
operating limit and not cause a hazard for the engine or gas turbine.
5.8.3 Turbine purging
Prior to any start-up, the turbine and the associated equipment shall be purged in
accordance with Clause 2.19.
NOTES:
1 Where heat recovery equipment does not form part of the turbine assembly, three complete
changes in volume to the base of the exhaust stack may be acceptable.
2 Due to the characteristics of gas turbines and their starting systems, a purging flow rate of not
less than eight per cent (8%) of the full load mass air flow may be acceptable for purging the
gas turbine and any associated heat recovery steam generators.
Where a heat recovery system is installed and there is supplementary firing fitted, it is
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
acceptable to purge with turbine exhaust gases provided that under all load conditions, the
temperature of the purge gases does not exceed 450°C for natural gas or 80% of AIT for
other fuels, and the temperature is interlocked.
Where the heat recovery system is initially purged prior to a turbine start up, provided that
a leakage detection system is fitted to the supplementary firing burners, then re-purging is
not required. The integrity of the safety shut off valves must be checked prior to a start up
of the supplementary burners.
Air flow proving devices shall be self checked in accordance with Clause 2.19.5.2.
Turbine rotation speed is an acceptable form of proving air flow and no-flow.
NOTE: This acceptance is based on turbine rotation speed being checked and measured to be
within specified ranges at all critical parts of a gas turbine’s operation.
The energy released during the ignition safety time (critical time) shall comply with the
requirements of Clause 3.2.3 or be limited such that the maximum pressure rise from a
delayed ignition shall not cause unacceptable damage to the plant or injury to personnel.
Over-firing during the ignition sequence shall be prevented.
NOTE: Prevention of over-firing can be achieved by control valve positioning, pressure
monitoring, fuel flow monitoring or a separate start gas supply line.
Where the main gas flow control valve is used for start gas, the flow control valve shall
control the fuel flow to the gas turbine at start-up under all foreseeable operating conditions
and shall not exceed the requirements of Clause 3.2.3. Where failure of the fuel flow
control equipment may lead to excess start gas flow or other dangerous conditions, an
additional independent monitoring device(s) shall be installed to initiate shutdown or if an
‘out of position to demand’ is detected, a start-up shall be prevented.
NOTE: The requirement of Clause 3.2.2.2 for the means of ignition to cease at the end of the start
gas flame establishment period is not applicable to gas turbines due to the need to ensure the gas
turbine has a stable flame during starting to achieve self sustaining speed.
5.8.11 Extinction safety time
On loss of flame, the flame detection and gaseous fuel shutdown system shall have a
combined maximum response time (extinction time) of no more than 3 seconds or shall
limit the release of unburned gaseous fuel to an amount that prevents damage to the plant or
injury to personnel.
Where the shutdown time exceeds 3 seconds, calculation shall be provided to ensure that
the intent of this clause is complied with.
5.8.12 Indirect flame monitoring
Where indirect flame monitoring is used, it shall detect the loss of combustion under all
foreseeable operating conditions. The indirect flame monitoring system shall undergo a safe
start check prior to the ignition sequence commencement.
(b) The combustion air for a primary burner interlocked with a secondary burner is
supplied by means of a high pressure inspirator that is capable of supplying all the
air, as primary air, that is required for the combustion of the gas.
5.9.4 Pre-purge
Where a mechanical means of supplying combustion air is required, the safety system shall
incorporate a pre-purge period to ensure that either—
(a) where only one chamber is fitted with a burner, a volume of air equal to five times the
effective volume of the chamber into which the burner is firing is purged to
atmosphere before ignition is attempted; or
(b) where more than one chamber is fitted with a burner each chamber shall be purged
sequentially, commencing with the primary chamber, with an air volume equal to five
times the effective volume of the chamber into which each burner is firing, before
ignition is attempted in any chamber.
5.9.5 Flues
5.9.5.1 Flues not to be interconnected
The flue shall not be interconnected with the flue from any other type of appliance.
NOTE: Where two or more incinerators or cremators are connected to a common flue, mechanical
assistance may be required to ensure that all flue gases discharge only at the flue terminal.
5.9.5.2 Limiting updraught
Provision shall be made so that updraught in the combustion chamber does not exceed the
design limit.
requirements:
(a) Type of solvents.
(b) Temperature range of operation.
(c) Condensation.
(d) Response times.
Where the solvent LEL monitors are of the self checking type, failure of either shall raise
an alarm and failure of both shall cause cessation of solvent material flow.
A HAZOP shall be conducted to determine if burner shutdown is necessary on high LEL or
device failure.
NOTES:
1 LEL monitor or control devices shall comply with the relevant electrical safety and hazardous
area classification standards.
2 Self checking is taken to mean that the LEL monitoring device is capable of detecting a
sensor fault, and undergoes a calibration check with every start up or at least every 24 hours
for continuously operating systems.
3 Diversion of solvent laden air may be another means of rendering the appliance safe on high
LEL if accepted by the technical regulator.
(b) provide adequate clearance from the burner to avoid flame impingement in the event
of a gas rich flame.
NOTE: See Clauses 2.22.5 and 2.23.5 for the protection of burners.
5.11.6 Flue
5.11.6.1 Minimum requirements for natural draught flue
The cross-sectional area of a natural draught flue shall be at least equivalent to 250 mm2 per
MJ/h of gas consumption, but shall not in any case be less than 8100 mm2 (100 mm
diameter).
5.11.6.2 Flue damper
A damper, where fitted in a natural draught flue, shall not restrict more than one-third of the
total cross-sectional area of the flue.
the water container or the top 20% of the water capacity whichever is the higher.
NOTE: In the case of instantaneous water heaters, fitting the valves in the plumbing immediately
adjacent to the outlet will be deemed to comply with the requirement.
5.12.4.3 Heaters containing 1L of water or less
Unvented water heaters containing 1 L of water or less shall be fitted with a relief device
that will release excess pressure in the waterways to prevent damage to the heater.
5.12.5 Provision for draining
All water heaters and attached water vessels shall be provided with a means to effectively
drain the water in the heater without causing damage to the building or contents.
NOTE: In the case of instantaneous water heaters, a plug or cap on the drain connection will be
deemed to comply with the requirement.
APPENDIX A
TYPICAL INFORMATION AND TECHNICAL DATA
(Informative)
This Appendix contains typical information to be supplied to the technical regulator for
each appliance in accordance with the procedure set out in Appendix B.
1 Name and address of appliance manufacturer.
2 Name and address of the authorized installer or conversion contractor.
3 Name and address of commissioning person.
4 Name and address of organization where appliance is or is to be installed.
5 Customer contact and telephone number.
6 Appliance type, operation and process description.
7 Number of burners and type.
8 Nominal gas consumption for total appliance and for each main burner.
9 Gas consumption at ignition for each burner.
10 Air flow rate at ignition for each burner.
11 Volume of each combustion chamber.
12 Total volume swept by the combustion products from the burner(s) to each flue
connection.
13 Air flow rate during purge periods.
14 Details and method of operation of any combustion air or flue dampers.
15 Details of any explosion reliefs including location, cross-sectional area and weight
together with calculations (refer AS 1375 Appendix E).
16 Appliance marking plate details (refer Clause 4.1 for requirements).
17 Process and instrumentation diagrams for the appliance (see Figure A3).
18 Schematic drawing of the combustion air control system and fuel valve train
specifying all valve train components (i.e. their brand, model number, size and rated
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
working pressure) and the proposed setting of all adjustable devices (refer Figure A1
for a typical example).
19 Schematic electrical wiring diagram showing the safety and control circuits including
details of the brand, model number and method of operation of each major component
and the proposed setting of any adjustable device (refer Figure A2).
20 Purge time calculations.
21 Calculations of start gas rate conditions (refer Clause 3.2.3).
22 Air dilution rate calculations for processes involving solvents or dusts (refer
AS 1375).
23 Ventilation provided or to be provided in the area where the appliance is or is to be
installed (refer AS 5601).
24 Method of flueing and location and type of flue material.
25 Operating instructions.
CIRCUIT COMBUSTION
BREAKER FUSE O/L FAN
1
2
3 M
4
5
6 ISOLATION SWITCH FUSE
7
8 1
9 2
10 3 ALARM LIGHT
ON/OFF
11 4 p BURNER ON/OFF
12 5 SWITCH
APS
13 6 FAN CONTACTOR
1, 3, 5
14 7
15 8
t
16 9
17 10 T EXTENDED PURGE
TIMER
18 11
F
19 12
20 13 IGNITION
p p t
21 14
22 15 GPS 1 GPS 2 OT
23 16 PILOT GAS
24 17
25 18
26 19
27 20 MAIN GAS
28 21
29 22 X
30 23
UV CELL Y
31
APPENDIX B
TYPICAL PROCEDURE FOR THE APPROVAL OF INDUSTRIAL AND
COMMERCIAL APPLIANCES
(Informative)
This Appendix provides guidance on the typical procedure to be adopted by all persons or
bodies wishing to install or commission appliances covered by this Standard.
Whilst the technical regulator may inspect and test the appliance for compliance with the
requirements of this Standard, the person(s) or bodies responsible for the installation or
commissioning of the appliance should ensure—
(a) compliance with these requirements;
(b) adequate instruction of operating personnel; and
(c) the safety of the installed appliance.
The typical procedure for approval is:
1 The details set out in Appendix A should be submitted to the technical regulator for
approval at least 28 days before the appliance is due to be commissioned, together
with any relevant fee that may be required by the technical regulator for inspection
and testing.
2 The technical regulator will examine the details submitted and may give its comments
or preliminary approval within 14 days.
3 No appliance is to have gas turned on until preliminary approval of the technical
regulator has been given.
4 Upon receipt of preliminary approval, the appliance may be commissioned by a
licensed/registered/approved commissioning person.
5 At least 7 days notice should be given to the technical regulator to inspect and test the
commissioned appliance.
6 The technical regulator may carry out an on-site inspection and test of the installed
appliance as soon as possible after the receipt of a request to test and the completion
of commissioning.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
7 When satisfied that the appliance meets these requirements, the technical regulator
may issue a Certificate/Notice of Compliance upon request and may attach an
approval label to the appliance.
8 No appliance should be handed over to the owner/operator for operation until the
requirements of the technical regulator have been met.
APPENDIX C
TYPICAL VALVE TRAIN ARRANGEMENTS
(Informative)
Gas valve trains must comply with the requirements of Clause 2.8. The examples shown
here are a limited selection of arrangements that comply with the requirements of this
Standard. It is not to be construed that these are the only arrangements possible, or that they
will comply or be suitable in every case.
The diagrams of typical valve train arrangements show a double block safety shut off valve
system on both main and start gas supplies. The number and selection of safety shut off
valves must be in accordance with Clause 2.14.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
A symbol shown
Filter in dotted lines means
the item is optional
Pressure test point
Pressure regulator
Automatic safety
Fast-opening fast-closing valve
shut off valves
Vent valve
Burner
Thermoelectric valve
Three-way valve
LG HG
see Note 1
LG HG
LG HG
see Note 1
LG HG
NOTES:
1 An over-pressure protection device is required if downstream components are not rated at the gas inlet
pressure.
2 High gas pressure detectors should preferably be located downstream of safety shut off valves to prevent
nuisance shutdowns. Such shutdowns will occur when either lock-up or positive shock pressure of the
regulator is above the detector setting, or weep past the regulator seat occurs.
Actuator
Actuator
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Actuator
FIGURE C6(a) FUEL GAS SYSTEM FOR TURBINES AND LARGE ENGINES—MINIMUM
ARRANGEMENT
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
FIGURE C6(b) FUEL GAS SYSTEM FOR TURBINES AND LARGE ENGINES—TYPICAL
ALTERNATIVE ARRANGEMENT 1
LEGEND:
Key Type of Equipment
1 Manual isolation valve
2 Optional strainer
3 Shut-off valve
3a Shut-off valve and manual isolation valve
4 Vent valve
5 Vent
6 Optional strainer
7 Shut-off valve*
8 Vent valve**
9 Fast acting shut-off valve*
10 Flow control valve
10a Flow control and shut-off valve*
11 Combustion system
12 Gas turbine enclosure or building limits
*close on every shut down **vent on every shut down
FIGURE C6(c) FUEL GAS SYSTEM FOR TURBINES AND LARGE ENGINES—TYPICAL
ALTERNATIVE ARRANGEMENT 2
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
APPENDIX D
FLAME SAFEGUARD SELECTION
(Informative)
The following information on flame safeguard classification has been provided to assist
users in the selection of a unit appropriate for the application. Table D1 summarises
features for Class 1 and 2 flame safeguards and Table D2 shows the equivalence between
the classification used in this standard and EN 298 classification characters.
The basic flame safeguard is a Class 3D that changes over one or more sets of contacts
whenever a flame is detected. It is primarily intended for use in manual systems or as an
addition to a programming unit to supervise an additional flame. Any safe start checks
required by Appliance Standards or any programming functions are provided by external
circuitry.
The majority of flame safeguard applications will require a Class 2 unit:
Class 2A These units provide timings that are acceptable for most applications.
However, units should still be checked for any other features required for a
particular application and for any duty limits recommended by the
manufacturer.
Class 2B Class 2B units are generally suitable for natural draught burners on small
appliances where the longer flame establishment periods and limited flame
proving periods may be permitted by the gas appliance Standards.
Class 2C These units are provided with a reignition attempt after flame failure. Sub-
type (a) has timings similar to Class 2A units and sub-type (b) has timings
similar to Class 2B units. Class 2C units should only be used under the
strict guidelines laid down in relevant gas appliance Standards.
Class 2D These units are similar to the basic Class 3D units except that a safe start
check is included.
Class 1 Class 1 units are similar to their Class 2 counterparts except that they
automatically check the correct operation of the unit at regular intervals
whilst in use, thus providing additional safety against fault conditions. This
feature is particularly relevant where appliances operate for extended
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
TABLE D1
FEATURES OF CLASS 1 AND 2 FLAME SAFEGUARDS
Class 1A 2A 1Ca 2Ca 1B 2B 1Cb 2Cb 1D 2D 3D
Safe start check Y Y Y Y Y Y Y Y Y Y
Continual self-check Y Y Y Y Y
Rigorous timings Y Y Y Y
Less rigorous timings Y Y Y Y
Reignition – single try Y Y
Reignition – multiple try Y Y
* * *
Forced/induced purge Y Y Y Y Y Y Y Y
Airflow interlock Y* Y Y Y Y* Y* Y* Y*
Waiting time Y* Y* Y Y
Volatile lock out Y Y Y Y
* * *
Non volatile lock out Y Y Y Y Y Y Y Y*
* These are optional features that may be included in the device.
TABLE D2
EQUIVALENCE GUIDE
AS 4625 EN 298 classification characters
classification st nd
1 2 3 rd 4th 5th 6th
1A F,A or B I,T,B,or M L L X,J or B K
2A F,A or B I, T, B or M L L X,J or B N
1B F,A or B I,T,B or M L L X,J or B K
2B F,A or B I, T, B or M L L X,J or B N
1Ca F,A or B I,T,B or M C L X,J or B K
2Ca F,A, or B I, T, B or M C L X,J or B N
2Cb F or A I, T, B or M R R X,J or B N
1D O O O O O K
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
2D O O O O O N
3D O O O O O N
NOTES:
1 Class 1 controls are similar to Class 2 controls except that Class 1 controls incorporate a
continual self check of the flame safeguard and flame detector. EN 298 requires this check for
Class 1 and Class 2 equivalents.
2 EN 298 requires that the flame safeguard checks for presence of flame prior to start up (safe start
check) and the 6th character refers to permanent or non permanent operation only.
APPENDIX E
PRO-FORMA LETTER TO THE GAS TECHNICAL REGULATOR FROM A
CONTRACTOR /COMPANY CERTIFYING THE TESTS CONDUCTED ON THE
PES
(Informative)
CONTRACTOR/COMPANY (letterhead)
......................................................................................................................................
the Programmable Electronic System (PES) has been designed, installed and
tested in accordance with AS 61508 to try to detect any possible systematic
software and systematic/random hardware faults. To the best of our assessment
the PES is error-free and functions according to the logic on the attached flow
sheet.
Yours faithfully
....................................... (Signature)
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Date:...................................................
APPENDIX F
GAS/AIR RATIO CONTROL PROGRAMMABLE ELECTRONIC SYSTEMS
A1
(Informative)
F1 INTRODUCTION
The intent of this Appendix is to provide guidance on a means of complying with the
requirements of Clause 2.27.6 where certified or PES based gas/air ratio systems are used
for combustion control. There may be other configurations that meet the intent of the
standard and may use new and innovative technology. For these alternatives acceptance
from the technical regulator shall be sought prior to implementation.
motors are constantly monitored. Deviations that are outside set limits will cause the burner
to lockout. These types of devices are often referred to as 'parameterisable' air fuel ratio
controls. These systems are covered in more detail under F2 and F3 below.
A non-safety PES shall not be relied upon to initiate any of the safety actions.
(c) The system shall be installed and wired in accordance with the manufacturer’s
installation and wiring instructions and maintained in accordance with the
manufacturer’s recommendations.
(d) Satisfactory combustion shall be maintained at all firing rates. For natural gas, a
minimum excess air level of 23% or 4.2% O2 shall be maintained.
(e) Close attention shall be paid to the connection of the motors to the control dampers
and valves. The preferred option is directly coupled devices. However, linkage
systems may be used provided acceptable steps have been taken to prevent slippage.
Such steps include shafts being connected to linkages by pinning or welding and the
use of keyways or splines.
AS 61508. The configuration of the PES shall meet the requirements of Clause 2.27. Some
of the means of achieving these requirements are as follows:
(a) Duplicate gas and duplicate airflow transmitters that are not SIL-rated feeding a
single safety related PES with SIL 3 certification.
(b) Single gas and single airflow SIL 2 transmitters feeding a single safety related PES
with SIL 3 certification.
(c) Two independent systems that each have a gas transmitter, an air flow transmitter and
non-safety related PES or DCS (Distributed Control System) or a safety related PES
without certification. Both gas and air ratio control systems must be completely
independent of each other and must be continually checking that there is never more
than 2% variation between the measured ratios
(d) Single gas and single airflow transmitters, each with a back-up for the respective flow
measurements such as pressure measurement or control valve position, all feeding a
single safety related PES with certification. It must be ensured that the installation, as
well as the PES, conforms to SIL 2.
(e) Gas/air ratio control systems that are part of a DCS or PES without certification for
safety applications. These shall be fitted with duplicate oxygen probes that will effect
burner shut down or other back up systems that comply with the above. Failure of the
oxygen sensing probe shall cause a safety shut down of the burner. Oxygen probes
that are used for a low oxygen trip function shall be failsafe or trip if high oxygen is
detected.
(a) The probe shall not be activated unless the main burner has been established. Control
by the probe shall be inhibited until the probe is at its correct operating temperature.
Interlocking to ensure the burner is held at low fire will meet this requirement.
(b) On shut down of the burner, the oxygen sensor shall be turned off and allowed to cool
down. If this is in excess of the post-purge time for the appliance, an additional 'cool
down timer' shall be fitted to ensure sufficient time is provided.
(c) On a low oxygen excursion, the burner management system shall immediately, by
hard wired means, shut down the safety shut-off system, and switch off the oxygen
detector’s heated probe.
(d) Manual reset shall not occur until the hard-wired 'cool down timer' for the probe, if
fitted, has timed out.
F6.2 With an oxygen probe that does not act as an ignition source
On start-up with a hot probe, burner light up may commence after the completion of the
purge.
On start-up with a cold probe, the oxygen probe may commence heating itself as soon as
power to the burner management system is provided or continue to operate during the
shutdown period as normal.
On a low oxygen excursion, the burner management system shall immediately, by hard
wired means, shut down the safety shut-off system.
If a supplier states that their oxygen probe is not an ignition source, they shall provide
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
APPENDIX G
MAINTENANCE AND CHECKS OF SAFETY DEVICES
(Informative)
G1 INTRODUCTION
This Appendix is an aid to ensure the continued safe operation of a gas-fired appliance and
plant.
G2 REGULAR TESTING
A regular systematic and thorough inspection, together with programmed maintenance and
testing of safety devices is essential to ensuring safe and efficient operation of gas fired
equipment. Such preventative maintenance and testing should be carried out on an annual
basis. More frequent testing will be determined by the reliability of the device, the
environmental conditions, the back-up protection offered by other devices or procedures,
and the recommendations of the safety device manufacturer, the appliance manufacturer or
installer. Minimum testing and maintenance intervals should be set in consultation with the
appropriate licensed or responsible person.
The following is an aid in ensuring the continued safe operation of the plant.
For appliances that are fitted with a PES base burner management and safety system in
compliance with AS 61508, the testing frequency of critical interlocks and limit devices
will be dictated by the SIL evaluation. In some instances the procedures and tests
requirements will be far more rigorous than indicated by the following generic testing
procedures model. These installations are covered by the requirements of the Technical
Regulator as part of the appliance installation acceptance process.
NOTE: Safety controls are usually activated so rarely that they easily fall into neglect and
become unsafe. If an interlock or valve has not been actuated for months, there is a chance that it
might not work when needed. Thus, an investment in safety equipment should be supported by a
maintenance commitment, i.e. a regular checking of safety circuits, mechanisms and settings, to
make certain that neither deterioration nor tampering has occurred.
Tests should be made by personnel who are competent, accredited and familiar with the
equipment, and the specific functions of the various safety controls. Inspection reports
should go to persons having sufficient authority to act on them. Arrangements should be
made to ensure coordination between operating and inspecting personnel.
In some jurisdictions the service provider carrying out maintenance and servicing may
require to be licensed by the Technical Regulator.
(b) The various safety devices should be operated in turn to check the proper
performance of each one.
(c) Close visual inspection of all mechanical and electrical components of the safety
devices should be made. This includes all timers, relays, contactors and limit
switches. Particular notice should be taken of broken or bent parts, unusual or sticky
action, improper contact appearance or lack of contact pressure, effects of excessive
heating, vibration, the presence of metallic particles and the intrusion of moisture,
dust or chemical attack.
(d) A proper check should be made of the surfaces and engagement of any clutches or
timing gears, and the position of connection levers, wires, cables or pipes to be sure
that mechanical interference cannot occur.
(e) Timing mechanisms and safety devices should be checked several times before
satisfactory performance is assumed to have been proved.
(f) Upon completion of the tests, covers of all safety controls should be properly sealed
in place to minimize tampering, a complete recommissioning procedure including a
dry-run should be carried out.
(g) A comprehensive report of the work and tests carried out must be provided to the
owner operator. The report is to provide the following information:
(i) The combustion readings for the appliance/burner before the tests.
(ii) The combustion readings for the appliance/burner after the completion of
servicing.
(iii) The settings of any safety interlock as found and settings after servicing.
(iv) Record of any modifications or changes to the operation of the appliance.
(v) List of modification additions or replacement of device, components or other
controls associated with the safe use of the appliance.
A Field Check List should be used to record results of the Annual Safety Test. An example
is given in Appendix J.
It is imperative that any test actually simulates the way the equipment would be required to
operate when an unsafe incident occurs.
G5 TESTING SCHEDULES
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Tables G1 to G4 detail the minimum recommended tests for components in the appliance’s
protection system. The tests are based on a typical industrial gas–fired appliance.
However, it is recognized that for other fuel and for specialized processes, departures from
these procedures may be appropriate. Any such departure from the basic principles implied
should only be made on the basis of sound engineering judgement and experience. They
should be applied with the following warnings and provisos in mind:
(a) Do not undertake the following tests unless thoroughly familiar with the operation of
the safety devices and the correct testing procedures.
(b) If in doubt call in the appliance manufacturer, a competent service organization or the
appropriate utility.
(c) Ensure all the original safe settings of the safety devices are recorded before making
adjustments.
(d) Some or all of the tests may be required to be carried out by a person authorized by
the appropriate authority. Check before carrying out any such tests.
(e) All the tests are safety tests, no efficiency tests are included.
(f) The frequency of the tests is a suggested minimum, which may be varied depending
on environment, equipment, manufacturers' instructions, SIL evaluation, operating
procedures, or the requirements of the Technical Regulator. Where the time between
tests is increased, it must only be done on the basis of sound engineering justification.
TABLE G1
SAFETY CHECK—INDUSTRIAL AND COMMERCIAL GAS FIRED APPLIANCES
Minimum Requirements (Annual unless
Component
stated otherwise)
Manual isolating valve Test for gas tightness
Check for ease of movement
Filter/strainers Check, clean or replace filter medium
Test for gas tightness
Pressure regulators Test and record trip settings
Test for gas tightness
Check breather holes and vents are clear
Over pressure or under pressure Test and record trip settings
Gas valve train Safety devices Test for gas tightness
Check breather holes and vents are clear
Safety shut off valves Test between block valves— if faulty:
(including vent valves) Inspect and repair
Test for gas tightness
Test functionality of valves
Gas/air ratio control valves Test for gas tightness if required
Test for smooth operation—lubricate if
required
Repair or replace sloppy or stiff linkages
Non return valves Inspect and repair if required
Test for gas tightness
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
TABLE G2
TYPICAL TEST SCHEDULE FOR COMBUSTION
Minimum requirements (Annual unless
Component
stated otherwise)
Combustion air system Inspect and clean filters
Inspect and clean fans
Check mechanical devices and lubricate if
required
Flueing Check flue for corrosion, obstructions and flue
gas leakage
Explosion relief Check for integrity of explosion relief devices
where fitted
Smoothness of ignition and Clean and adjusted pilot and main burner if
flame stability required
Where a pilot is used, pilot ignition is smooth
not delayed and stable
Where a pilot is used, lighting of main flame
by pilot is smooth and is not delayed
For burners starting at low fire, ignition is not
delayed and is smooth
Check the flame stability of main flame over
its entire range as is practical
Combustion
Flue gas analysis Undertaken in accordance with Clause 3.6.
Record start gas, low, mid and high fire
readings as far as is practical
NOTE: Every endeavour should be made to
confirm satisfactory combustion over the
entire burner range.
Ventilation Check that ventilation openings are clear of
obstruction
Check conditions of mechanical devices and
interlocks
Direct fired heaters or unflued Minimum six monthly check flue gas analysis
appliances (spray booths) to ensure standards for direct fired air heaters
are met. Equipment used to be capable of
measuring how levels of carbon monoxide and
carbon dioxide as well as formaldehyde and
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
NO 2
Electronic gas/air ratio systems Minimum six month check flue gas analysis to
ensure that the equipment is functioning
correctly and maintaining the required gas/air
ratio and trip settings
TABLE G3
TYPICAL TEST SCHEDULE FOR INTERLOCKS AND LIMITS
Components Annual checks
1 Combustion air flow detector Check settings of any related limits and
interlocks
Reset to a safe level and test for shutdown
2 High gas pressure detector Check settings of limits and interlocks
3 Low gas pressure detector Systematically reset one at a time to a safe
level and test for shutdown
4 Gas pressure relief valve Check settings of limits and interlocks
5 Overpressure shut-off device
NOTE: Test must cause limit or interlock to
6 Purge air flow device and timer
operate to be valid. Observe the set out-in and
cut-out position of each device. For low
pressure switches, turn the supervised pressure
medium off and on and observe whether the
load contact opens and closes properly
7 Low or high level limits Check settings of limits and interlocks
8 Excess process temperature or For high temperatures or high pressure
pressure cutout or other process switches, adjust the switch setting down until
9 limit the load contact opens. For low temperature
Positional switches switches, adjust the switch setting upwards
until the load contact opens. Caution: The
switch must be reset to the proper operational
setting.
For positional switches, confirm correct
operation and ‘out of position’ alarm and/or
trip
TABLE G4
TYPICAL TEST SCHEDULE FOR FLAME SUPERVISION SYSTEM
Type of system Annual checks
Thermoelectric Check shutdown time by either removing element from flame; or
disconnecting. Check location of the pilot and thermocouple to
ensure that, if thermocouple is energized, pilot will light main flame.
Inspect thermoelement for deterioration and replace if necessary.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Flame ionization Inspect and clean flame rod and ground fins. Replace where
necessary. Inspect and clean the earth terminal. Check for shutdown
and lockout when rod is not in flame or is disconnected. Check
location of pilot and flame rod to ensure that if pilot energizes the
flame rod, the pilot will light main flame.
Ultraviolet Check for shutdown and lockout by disconnecting or removing and
covering the cell. Clean viewing cell. Replace cell if operation
exceeds 10 000 h or as per manufacturer's instructions. Where a tube
supplying cooling air to the cell is fitted, check if it is clear and
clean.
Infrared Check for shutdown and lockout by disconnecting or removing and
covering the cell. Clean viewing cell. Replace cell as per
manufacturer's instructions. Where a tube supplying cooling air to
the cell is fitted, check if it is clear and clean.
All types Check that at least one complete cycle of operation is performed
immediately following every test and where adjustment has been
made. The checking should include times and functions of each
event in the cycle. Replace components that do not operate in
accordance with their manufacturers' specifications.
APPENDIX H
TYPICAL OPERATING SEQUENCE FOR AN AUTOMATIC FORCED
OR INDUCED DRAUGHT BURNER WITH INTERRUPTED PILOT
(Informative)
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
APPENDIX I
TYPICAL COMMISSIONING PROCEDURE
(Informative)
I1 SCOPE
This Appendix describes a typical commissioning procedure, and is intended as a model on
which the commissioning instructions for an appliance can be based. It is written about a
gas-fired appliance that is automatic in operation as a matter of convenience, but it is
expected that it can be adapted for applications using manual control.
(g) Check availability and correct voltage, phase, etc., of the electricity supply.
(h) Ventilation:
(i) check the plantroom ventilation for compliance with any applicable
requirements, size and location of openings; or
(ii) if mechanical ventilation is provided, check the operation of fans and their
interlocks with ventilation openings.
(i) Carry out a general safety inspection of plantroom area.
(j) Check that the flue complies with applicable requirements.
(c) Check all valves, joints and components for gas leakage.
(d) Set control instruments (e.g. regulators and air pressure switch) to a level at which
they will not cause the burner to lockout.
(e) Switch on power supply.
(f) Check the operation of all fan motors, including the direction of rotation.
(g) Prove that all valves operate in the correct sequence, check and set any valve-proving
provisions.
(h) Check the sequence of the burner management system up to lockout, with no start gas
present.
(i) Check that the purge and/or combustion air pressure switch contacts change over
from the no-flow condition to the start-up flow condition, and that the proving
provisions for both conditions function correctly.
(j) Check the purge time, and that the purge is monitored during the entire purge period.
(k) Check and verify the exhaust rates, dilution air rates, process flow rates etc are as per
specification.
(k) Prove the operation of the flame safeguard system for main flame.
(l) Check the gas flow rate with the appliance specification.
(m) Re-check the start rate.
(n) If high/low firing, check the low fire rate and air setting, and check the flame stability
during transition.
I5 STAGE 4 OPERATION
(a) Carry out combustion checks over the operating range of the burners to ensure that
combustion is appropriate for the appliance and complies with the requirements of
this Standard and the technical regulator.
(b) Check and adjust any air pressure switch.
(c) Check and set all safety and operating controls.
(d) Check the operation of pressure relief devices.
(e) Check the operation of all interlocks (not forgetting any plantroom ventilation
interlocks).
(f) Check and verify the exhaust rates, dilution air rates, process flow rates and any other
process flow rates and conditions are as per specification.
(g) Check that all covers, such as regulator caps, pressure test point screws, hatches, on
controls have been replaced.
(h) Secure all locking devices.
(i) Conduct any required performance verification or efficiency tests.
I6 STAGE 5 COMPLETION
(a) Ensure that the appropriate operative, supervisory or maintenance staff, or the
owner/operator, receive the relevant instructions on the following:
(i) Burner electrical schematic drawings.
(ii) Burner component details.
(iii) Operating sequence.
(iv) Adjustments and settings.
(v) Fault finding.
(vi) Maintenance.
(b) Complete the commissioning data sheet and provide a copy to the owner/operator.
(c) Record and re-submit any variations to the appliance if these constitute a departure
from the original specification.
(d) Record the gas supply details.
(e) Check that safe operating instructions are permanently and prominently displayed
near the appliance operating station.
(f) Check that any necessary post-commissioning approvals, including that of the
technical regulator, have been completed.
(g) Hand over to the owner/operator. Commissioning completed.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
APPENDIX J
TYPICAL FIELD CHECK LIST
(Informative)
This checklist should only be used after the full requirements of the Standard have been
consulted and understood. The checklist is not totally comprehensive and is to be used only
as an aid to thorough field testing of gas appliances.
The installation of gas appliances is covered by AS 5601. Both AS 5601 and this Standard
should be consulted when assessing any gas appliance installation to ensure that, not only
the appliance is safe, but its installation is safe as well.
OWNER/OPERATOR:........................................................................................................
CONTACT: ....................................................................................................................... .
ADDRESS: ....................................................................................................................... .
............................................................................................................................... ..........
CONTRACTOR:.................................................................................................................
ADDRESS: ....................................................................................................................... .
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
............................................................................................................................... ..........
Adjustable devices
Sound construction
Parts secure
No sharp edges
Appliance supports
Provision to sample flue gases
Access to controls, burners & safety devices
Flame visible
Surface and component temperatures
Electrical connection, ease & cross connection
Operator access to controls
Materials suitable
Secure
Interlocked for purge
Interlocked burner ignition
o Automatic
• Appliance purging
Adequate flow
Occurs correctly
Set: Trip:
Interlocked, sealed
Proving fitted, self check, reset
Proof of recirculation zone fans Set: Trip:
Mechanical means conduct
Five changes, >25%, circulation OK
If inert, proved and interlocked
Natural draught requirements
Process controls Set: Trip:
Process limits to cause lockout
Over temperature protection on Recirculation fans
Pilot burners
• Stable (Clause 2.22.1)
• Ignition of main burner (Clause 2.22.1)
• Manual ignition system (Clause 2.21.2)
• Support and location (Clause 2.1.7)
• Ignition systems (Clause 2.21)
Control circuits (Clause 2.26)
Flame safeguards (Section 2.24)
• Required
• Reaction time
• Self check/flame simulation
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Carbon dioxide
Carbon monoxide
Oxygen
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
• Vent lines
• Special atmosphere (combustible)
Safe discharge
Reliable ignition
Flame arrestor
Flame arrestor operation
• Piping for special atmosphere
• Storage of special atmospheres
• Compressed special atmosphere
• Explosion relief
• High temperature limit Set: Trip:
• Access for cleaning
• Processes with solvent and combustible dusts
• Provision of dilution air
• Recirculation fans interlocking
• Monitoring of LEL
AS 3814—2009
CORRECTION
SUMMARY: This Amendment applies to Appendix F.
Published on 21 June 2010.
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
119
NOTES
AS 3814—2009
Accessed by ENERFLEX PROCESS PTY LTD on 28 Sep 2010
AS 3814—2009
120
NOTES
Standards Australia
Standards Australia develops Australian Standards® and other documents of public benefit and national interest.
These Standards are developed through an open process of consultation and consensus, in which all interested
parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth Government,
Standards Australia is recognized as Australia’s peak non-government national standards body. Standards Australia
also supports excellence in design and innovation through the Australian Design Awards.
Australian Standards®
Committees of experts from industry, governments, consumers and other relevant sectors prepare Australian
Standards. The requirements or recommendations contained in published Standards are a consensus of the views
of representative interests and also take account of comments received from other sources. They reflect the latest
scientific and industry experience. Australian Standards are kept under continuous review after publication and are
updated regularly to take account of changing technology.
International Involvement
Standards Australia is responsible for ensuring the Australian viewpoint is considered in the formulation of
International Standards and that the latest international experience is incorporated in national Standards. This role is
vital in assisting local industry to compete in international markets. Standards Australia represents Australia at both
the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC).