BS Iec 60092-501-2013
BS Iec 60092-501-2013
BS Iec 60092-501-2013
Electrical installations
in ships
Part 501: Special features — Electric
propulsion plant
BS IEC 60092-501:2013 BRITISH STANDARD
National foreword
This British Standard is the UK implementation of IEC 60092-501:2013. It
supersedes BS IEC 60092-501:2007 which is withdrawn.
The UK participation in its preparation was entrusted to Technical Com-
mittee JPEL/18, Electrical installations of ships and of mobile and fixed
offshore units.
A list of organizations represented on this committee can be obtained on
request to its secretary.
This publication does not purport to include all the necessary provisions of
a contract. Users are responsible for its correct application.
© The British Standards Institution 2013.
Published by BSI Standards Limited 2013
IEC 60092-501
®
Edition 5.0 2013-10
INTERNATIONAL
STANDARD
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION PRICE CODE
X
ICS 47.020.60 ISBN 978-2-8322-1177-9
Warning! Make sure that you obtained this publication from an authorized distributor.
CONTENTS
FOREWORD ........................................................................................................................... 5
INTRODUCTION ..................................................................................................................... 7
1 Scope .............................................................................................................................. 8
2 Normative references ...................................................................................................... 8
3 Terms and definitions ...................................................................................................... 9
4 System .......................................................................................................................... 11
4.1 System design ................................................................................................. 11
4.1.1 General .......................................................................................... 11
4.1.2 Design requirements ....................................................................... 12
4.1.3 Blocking devices for shafts ............................................................. 12
4.1.4 Special requirements for ships with only one propulsion motor ....... 12
4.1.5 Special requirements for ships with more than one propulsion
motor .............................................................................................. 13
4.2 System responsibility ....................................................................................... 13
4.3 Torsional stress and torsional vibrations .......................................................... 13
4.4 Protection and operational stability .................................................................. 13
4.5 Protection against moisture and condensate .................................................... 14
4.6 Excitation systems ........................................................................................... 14
4.6.1 General requirements ..................................................................... 14
4.6.2 Generators ..................................................................................... 14
4.6.3 Propulsion motors ........................................................................... 15
4.7 Wires, cables, busbars, trunking systems ......................................................... 15
5 Electromagnetic compatibility (EMC) and harmonic distortion ........................................ 15
5.1 General ............................................................................................................ 15
5.2 Total harmonic distortion, THD ......................................................................... 15
5.3 Conducted and radiated RF emissions ............................................................. 15
6 Prime movers ................................................................................................................ 16
6.1 General requirements ...................................................................................... 16
6.2 Speed deviations ............................................................................................. 16
6.3 Parallel operation ............................................................................................. 16
6.4 Regenerated energy from propeller .................................................................. 16
7 Generators .................................................................................................................... 16
7.1 General requirements ...................................................................................... 16
7.2 Bearing and lubrication .................................................................................... 17
7.2.1 General .......................................................................................... 17
7.2.2 Sleeve bearings .............................................................................. 17
7.2.3 Roller bearings ............................................................................... 17
7.3 Cooling ............................................................................................................ 17
7.4 Protection ........................................................................................................ 18
7.5 Test ................................................................................................................. 18
8 Propulsion switchboards ................................................................................................ 18
8.1 General ............................................................................................................ 18
8.2 Test ................................................................................................................. 18
9 Propulsion transformers ................................................................................................. 18
9.1 General requirements ...................................................................................... 18
9.1.1 General .......................................................................................... 18
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) –3–
Figure 1 – Typical equipment (configuration) for ships with one or two propellers ................. 12
Figure 2 – Typical control configuration ................................................................................ 29
Figure A.1 – Propulsion equipment with monitored items ...................................................... 35
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60092-501 has been prepared by IEC technical committee 18:
Electrical installations of ships and of mobile and fixed offshore units.
This fifth edition cancels and replaces the fourth edition published in 2007. It constitutes a
technical revision.
This edition included the following significant technical changes with respect to the previous
edition:
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 60092 series, published under the general title Electrical
installations in ships, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
INTRODUCTION
IEC 60092 forms a series of International Standards for electrical installations in sea-going
ships, incorporating good practice and coordinating, as far as possible, existing rules. These
standards form a code of practical interpretation and amplification of the requirements of the
International Convention on Safety of Life at Sea, a guide for future regulations which may be
prepared and a statement of practice for use by shipowners, shipbuilders and appropriate
organizations.
BS IEC 60092-501:2013
–8– 60092-501 © IEC:2013(E)
1 Scope
This part of IEC 60092 specifies requirements for all electric propulsion plants and gives the
specifications, system design, installation and testing of at least:
Bow and stern thrusters intended as auxiliary steering devices, booster and take-home
devices, all auxiliary generating plants, and accumulator battery powered propulsion
machinery and equipment are excluded.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60092-101, Electrical installations in ships – Part 101: Definitions and general
requirements
IEC 60092-202, Electrical installations in ships – Part 202: System design – Protection
IEC 60092-301, Electrical installations in ships – Part 301: Equipment – Generators and
motors
IEC 60092-302, Electrical installations in ships – Part 302: Low-voltage switchgear and
controlgear assemblies
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) –9–
IEC 60092-303, Electrical installations in ships – Part 303: Equipment - Transformers for
power and lighting
IEC 60092-352, Electrical installations in ships – Part 352: Choice and installation of electrical
cables
IEC 60092-401, Electrical installations in ships – Part 401: Installation and test of completed
installation
IEC 60092-504:2001, Electrical installations in ships – Part 504: Special features – Control
and instrumentation
IEC 61180-1, High-voltage test techniques for low-voltage equipment, Part 1: Definitions, test
and procedure requirements
IEC 61439-1, Low-voltage switchgear and controlgear assemblies Part 1: General rules
IEC 61439-2, Low-voltage switchgear and controlgear assemblies Part 2: Power switchgear
and controlgear assemblies
IEC 61800 (all parts), Adjustable speed electrical power drive systems
International Convention for the Safety of Life at Sea (SOLAS):1974, Consolidated edition
2009
For the purposes of this document, the following terms and definitions apply:
3.1
appropriate authority
governmental body and/or classification society with whose rules the installation is required to
comply
[SOURCE: IEC 60092-101:1995, 1.3, modified — The words “a ship“ has been replaced with
“the installation”.]
BS IEC 60092-501:2013
– 10 – 60092-501 © IEC:2013(E)
3.2
azimuth drive
system which moves the propulsion unit around the vertical axis
3.3
double sensor
two sensor elements in one housing
3.4
motor supply lines
cables and/or busbars used for supply to the propulsion motor(s)
3.5
local control station
place of control where a system is installed which creates a reference value for the convertors
independent from the remote control system and any external limitations
3.6
main control station
place of control of the main propulsion system which is manned under seagoing conditions
3.7
inaccessible spaces
spaces that are not accessible during operation without dry docking.
3.8
nominated body
installer or manufacturer that has been given direct responsibility for the complete propulsion
system
3.9
single failure criterion
criterion applied to a system such that it maintains manoeuvrability in the presence of any
single failure
[SOURCE: IEC 60050-393:2003, 393-18-27, modified — The phrase “it is able to perform its
safety task” has been replaced with “it maintains manoeuvrability”]
3.10
podded drive
propulsion system in which the motor is located in a dedicated, submerged unit (pod housing)
of the ship
3.11
power management system
PMS
control and safety system which provides the load depending starts and stops of the prime
movers, the load sharing, etc.
3.12
propulsion generator
generator mainly used for power supply of the propulsion system
3.13
propulsion motor
electrical motor intended to provide propulsion power
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 11 –
3.14
propulsion switchboard
switchboard mainly used for power distribution to the propulsion systems
3.15
redundant sensor
two single sensors in separate housings
3.16
remote control system
system which comprises all equipment necessary to operate units from a control position
where the operator cannot directly observe the effect of his actions
4 System
4.1.1 General
A typical electrical propulsion system may consist of the following hardware components:
– propulsion generators;
– switchboard;
– transformers to convert the ships voltage to the convertor voltage;
– convertor to supply the electric motor;
– control system;
– propulsion motor.
Key
1 main engine 4 propulsion transformer 7 propeller
2 propulsion generator 5 propulsion convertor
3 switchboard 6 propulsion motor
Figure 1 – Typical equipment (configuration) for ships with one or two propellers
The single failure criterion shall be the basis of the design of the electric propulsion system.
Recognizable failures should not injure the single failure criterion. Undetected failures should
be avoided. However, it may be unavoidable that some undetected failures may injure the
single failure criterion.
It shall be possible for all machinery essential for the safe operation of the ship to be
controlled from a local position, even in the case of failure in any part of the automatic remote
control system, see Clause 14.
Each shaft shall be equipped with a blocking device to prevent shaft rotation, allowing towing
or the operation of the remaining shaft(s). The drive(s) for the remaining shaft(s) may be
limited as long as manoeuvring capability is maintained under all weather conditions.
4.1.4 Special requirements for ships with only one propulsion motor
Synchronous and induction motors shall be equipped with two stator winding systems which
can be disconnected from the respective convertor. Each convertor shall be designed for at
least 50 % nominal power of the propulsion drive.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 13 –
DC motors shall have two separate rectifiers, each for 50 % nominal motor current, with
means for disconnecting each rectifier. The convertors shall be mutually independent. Any
single failure in one convertor shall not result in complete loss of propulsion power.
Motors with permanent excitation shall be equipped with two stator winding systems which
can be disconnected from the respective convertor. Additionally, there shall be a braking or
blocking system which can fix the shaft under all weather and normal towing conditions.
Alternatively, a decoupling system may be used which ensures standstill of motor shaft.
NOTE Winding damages will lead to the total loss of the propulsion motor. In this case the single failure design
criteria cannot be fulfilled.
Auxiliary machinery vital to the propulsion system, such as cooling, lubrication, etc. must be
provided in duplicate in order to provide continued or restored propulsion capability in the
event of a failure or malfunction of any single auxiliary component.
4.1.5 Special requirements for ships with more than one propulsion motor
Any electrical failure in a propulsion convertor or propulsion motor shall not make all shafts
unavailable.
Special consideration in this respect shall be given to shaft lines driven by permanent exited
propulsion motors.
4.2 System responsibility
There shall be one nominated body responsible for the integration of the complete propulsion
system.
This body shall have the necessary expertise and resources enabling a controlled integration
process.
Motors and shaftlines shall be capable of withstanding all loading conditions. Evidence shall
be provided by means of a torsional vibration calculation.
The entire oscillating system may include prime movers, generators, transformers, convertors,
exciters, motors, slip couplings, gears, shafts and propellers.
The manufacturers of the components shall provide all necessary information to the system
responsible body, see 4.2.
The highest oscillating torque may be expected during a two-phase short-circuit of the motor.
The highest steady state torque may be expected during a three-phase short-circuit of the
motor.
The control system shall be able to control the propulsion system under all weather and
manoeuvring conditions.
BS IEC 60092-501:2013
– 14 – 60092-501 © IEC:2013(E)
Other on-board systems shall not influence the propulsion or manoeuvrability of the ship, for
example no common communication links, no common hardware. This shall also apply for
azimuth drives.
All means for normal operation of the propulsion system, including necessary power
generation, shall have interlocks in order to prevent incorrect operation and damages.
Effective means, for example space heaters or air dryers, shall be provided in motors,
generators, convertors, transformers and switchboards to prevent accumulation of moisture
and condensate, even if they are idle for appreciable periods.
The obtainable current and voltage of excitation systems and their supply shall be suitable for
the output required during manoeuvring, overcurrent and short-circuit or stalling conditions.
Excitation power circuits may be protected against short-circuits only, and tripping shall be
alarmed.
If the built-in short-circuit monitoring device of the excitation system trips, the respective
circuit breaker of the generator or motor shall also trip.
If the excitation system is fitted with independent safety devices, for example against under-
frequency and over-voltage or voltage/frequency-functions, they shall be adjusted in such a
way that the system protection reacts first.
Excitation circuits shall be provided with means for suppressing voltage rise when an
excitation switch is opened.
Special consideration shall be given to the total harmonic distortion and power factor.
4.6.2 Generators
The steady and transient regulation conditions of the excitation system including the
automatic voltage regulator shall be in accordance with IEC 60092-301.
Excitation systems shall be supplied from the generator side and the generator shall be self-
excited. In general, the voltage built-up shall be done without the aid of an external electric
power source.
External power supply may be used for exciter control circuits provided that redundancy for
this external source is arranged, even for the voltage built-up. The external source of power
shall be supplied from the corresponding main switchboard section and emergency source of
electrical power with battery backup. At least two external power supplies for all generators
are required. Every generator excitation system shall be supplied by independent power
supply.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 15 –
The exciter circuits shall be supplied from the same energy source supplying the stator
windings.
This means, the switchboard section supplying the stator winding should be the energy
source of the associated exciter system.
Choice and installation of cables shall be in accordance with IEC 60092-352 and
IEC 60092-401.
If the convertor technology requires special properties of the cabling between convertor and
motor, the specification of the convertor manufacturer shall be observed.
Design of cabling, busbars, trunking systems and slip rings shall take into account special
failure conditions including magnitude and duration of failure currents.
5.1 General
Propulsion systems shall comply with performance criterion A of IEC 61000-6-2. This means
no degradation of performance or loss of function is allowed during normal operation.
Equipment producing transient voltage, frequency and current variations is not to cause
malfunction of other equipment on board, neither by conduction, induction or radiation.
The design shall take in account that propulsion convertors create interferences within the
propulsion network.
For the propulsion network the total harmonic distortion (THD) value of the voltage shall not
exceed 10 %. If a THD value of 10 % is exceeded, the person responsible for the propulsion
system, see 4.2, shall ensure interference-free operation of all connected equipment.
If the propulsion network and the ship's network are directly connected, the THD value of
ships network voltage shall not exceed the values stated in IEC 60092-101.
The design of cabling and cables, transformers, protection devices etc. shall take into account
the high level of harmonic currents caused by the convertor system.
The additional heating contribution caused by the harmonic distortion shall be defined by all
parties.
Convertors exceeding the radiated and conducted emission limits of 6.2 of IEC 60533:1999
shall be installed according to the requirements for special power distribution zone as
described in IEC 60533:1999. The immunity requirements of the propulsion convertor shall
comply with at least the requirements for all other equipment on board.
BS IEC 60092-501:2013
– 16 – 60092-501 © IEC:2013(E)
Conducted and radiated emissions leaving the convertor cabinet or room shall be reduced to
a system-compatible level.
6 Prime movers
The engines driving the propulsion generators are auxiliary engines and have to comply with
the specification of the relevant authorities for main engines and of IEC 60092-504.
If the propulsion generators are also used for supplying the ship network, static and dynamic
frequency deviations shall meet the requirements of the ship network.
Where the speed control of the propeller requires speed variation of the prime mover, the
governor shall be provided with means for local control as well as for remote control.
The prime mover rated power in conjunction with its overloading and load build-up capabilities
shall be adequate to supply the power needed during transitional changes in operating
conditions of the electrical equipment due to manoeuvring and sea and weather conditions.
In case of parallel operation of generators, the governing system used shall permit stable
operation to be maintained over the entire operational load range of the prime-movers.
The speed governor characteristics of prime movers shall be such that in parallel operation
the load on individual generators is shared, as far as possible, in proportion to the output of
each generator.
Any vessel speed change or throttle movement shall not cause a ship’s service power
interruption.
When manoeuvring, for example from full propeller speed ahead to full propeller speed
astern, regenerated power may occur.
The amount of regenerated power shall be limited by the control system, so that tripping due
to overspeed or reverse power is avoided.
Means external to the mechanical and electrical rotating machinery may be provided in the
form of for example braking resistors to absorb excess amounts of regenerated energy and to
reduce the speed of the propulsion motor.
7 Generators
Generators shall be designed in accordance with the IEC 60034 series and IEC 60092-301.
Generators shall have a protection degree of at least IP 23. High voltage generators shall
have a protection degree of at least IP 44.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 17 –
Generators operating with semiconductor convertors shall be designed for the expected
harmonics of the system. A sufficient reserve shall be considered for the temperature rise,
compared with sinusoidal load.
Stator windings of generators rated above 500 kVA shall be provided with temperature
sensors.
Generators above 1 500 kVA shall be equipped with differential current protection.
7.2.1 General
All bearings shall be equipped with temperature devices or a thermometer shall be installed.
The measuring point shall be as specified in IEC 60034-1.
Adequate lubrication shall be ensured even in inclined positions. Provision shall be made for
checking the bearing lubrication.
Generators shall be equipped with devices which, in the event of a failure of the normal
lubricating oil supply, provide adequate lubrication until the machine has come to standstill.
No lubricating liquid shall flow out of the bearings and penetrate into the machine.
In case of bearings with forced lubrication, an alarm shall be given for the failure of the oil
supply (loss of oil pump, loss of pressure in the bearing supply pipe) and the attainment of
excessive bearing temperatures. If the temperature rises further, the generator shall be
stopped.
To avoid damage to bearings, it is essential to ensure that no harmful currents can flow
between bearings and shaft. At least one bearing shall be mounted electrically insulated from
the machine.
Two-part bearings shall be fitted with thermometers indicating, wherever possible, the
temperature of the lower bearing shell.
7.3 Cooling
The temperature of the cooling air of machines provided with forced air ventilation, air ducts,
air filters or water coolers shall be continuously monitored by means of thermometers which
are readable from outside the machine. Temperature sensors shall be provided to trigger an
alarm.
For machines with a closed circuit cooling method with a heat exchanger, the flow of primary
and secondary coolants shall be monitored.
For machines with water cooled heat exchangers, leakage monitoring is required.
BS IEC 60092-501:2013
– 18 – 60092-501 © IEC:2013(E)
7.4 Protection
7.5 Test
Propulsion generators shall be individually tested at the manufacturer's works. The scope of
the tests is stated in the IEC 60034 series.
The additional heating caused by total harmonic distortion, see 5.2, shall be taken into
account during the temperature rise test.
8 Propulsion switchboards
8.1 General
The power generation used for the propulsion motors could be used for ship service
distribution.
Special consideration shall be given to the total harmonic distortion, see 5.2, and power
factor.
8.2 Test
A complete test of the protection devices, interlockings etc. shall be carried out in the test
requirements for main switchboards.
9 Propulsion transformers
9.1.1 General
Transformers and reactors shall be in accordance with IEC 60092-303 and power
transformers in accordance with IEC 61378-1 and the IEC 60076 series.
Special consideration shall be given to the total harmonic distortion, see 5.2, and power factor
and in case of PWM type convertors, increased core losses.
Where propulsion transformers are fitted, at least two independent units shall be provided for
a single shaft solution.
Only transformers with separate windings shall be used. Auto-transformers are permitted for
motor starting.
Transformers producing low voltage from high voltage shall be equipped with an earthed
shield winding between the low-voltage and high-voltage coil.
Transformers located in engine rooms shall have a protection degree of at least IP 23. High
voltage transformers, located in engine rooms, shall have a protection degree of at least
IP 44. Other degrees of protection may be chosen in accordance with IEC 60092-503.
9.2 Cooling
Measures shall be taken to ensure that the windings are completely covered by liquid, even
for inclinations up to and including 22,5°.
They shall be provided with a collecting arrangement which permits the proper disposal of the
liquid.
In case of flammable liquids a fire detector and a suitable fire extinguishing system shall be
installed in the vicinity of the transformer. The fire fighting system may be manually operated.
The liquid temperature shall be monitored. A prealarm shall be actuated before the maximum
permissible temperature is attained. When the maximum permissible temperature limit is
reached, the transformer shall be switched off.
The liquid filling level shall be monitored by means of two separate sensors. The monitoring
system shall actuate an alarm at the first stage and shall trigger a shutdown at the second
stage, when the permissible limit is exceeded.
Air flow and temperatures of the cooling air for forced-ventilated transformers shall be
monitored.
For transformers with a closed cooling circuit method with a heat exchanger, the flow of
primary and secondary coolants shall be monitored. Leakage water and condensed moisture
shall be kept away from the windings. Leakage monitoring is required.
9.3 Instrumentation
9.4 Protection
Each propulsion transformer shall be protected against primary and secondary side
short-circuit.
If the primary side of transformers is protected for short-circuit only, overcurrent protection
shall be arranged on the secondary side.
High voltage transformers shall be equipped with differential protection if the primary
protection is not adequate.
BS IEC 60092-501:2013
– 20 – 60092-501 © IEC:2013(E)
9.5 Test
Propulsion transformers shall be individually tested at the manufacturer's works. The scope of
the tests including the vector-group test is stated in IEC 60076.
The additional heating caused by total harmonic distortion, see 5.2, shall be taken into
account during the temperature rise test.
10 Convertors
10.1 General
Convertors shall be designed in accordance with the IEC 60146 series and IEC 61800 series.
The installation of convertors shall be in accordance with requirements of IEC 60533. See
also 5.3 in this document.
Common control of the convertors is not permitted. This means, for example, that two single
sensors or one double sensor shall be installed.
Two galvanically isolated actual speed sensors shall be provided, one for each control
system. Common housing of both sensors is permitted.
If the convertor feeds a permanently excited synchronous motor, a switch with breaking
capacity shall be fitted in the motor-convertor line which opens automatically in case of an
inverter fault.
Propulsion convertors shall be designed for the nominal torque of the drive. Short-term
overload and speed variations resulting from overloads shall not lead to a shutdown of the
system.
The mechanical housing for semiconductor convertors shall be in accordance with the
standards of main switchboards, where applicable.
High voltage convertors shall be treated like high voltage switchgear and controlgear in
accordance with IEC 62271-200 adapted to shipbuilding requirements. The enclosures shall
be manufactured to withstand accidental arcs in accordance with Annex AA of
IEC 62271-200:2011, or shall be located in a way that personnel safety is ensured.
If semiconductor convertors are fitted with forced-cooling, means for monitoring the cooling
system shall be provided.
In case of a failure of the cooling system, measures shall be taken to prevent damage to the
convertor. An alarm shall be given. The alarm signal can be generated by the flow of the
coolant, or by the temperature of the semiconductors.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 21 –
If semiconductors are cooled by liquid, this liquid circuit shall be restricted to one convertor
system. Liquid quality shall be observed.
Single failure criterion in convertor cooling systems shall not lead to the tripping of all
convertors of the ship's propulsion.
10.4 Protection
10.5 Test
Convertors shall be individually tested at the manufacturer's works. The scope of the tests, for
example functional test, adjustments, limitations, failure handling, is stated in IEC 60146-2.
All protection and limiting functions with project related settings shall be tested before
installation. All alarms of the category Alarm, Reduce and Stop shall be tested and
documented with their settings. Proper coordination of convertor and motor protection
functions shall be demonstrated.
11 Harmonic filtering
Line filters can be used to ensure the required harmonic distortion in the mains at any step of
propulsion.
Each individual filter circuit shall be protected against overcurrents and short-circuit currents.
Failure of harmonic filters shall be monitored. Harmonic filter protection circuits shall be fail-
safe.
If filter circuits become faulty an emergency operation shall be possible. Instructions and
limitations for such cases shall be provided and demonstrated during SAT (Sea Acceptance
Test).
The estimated service life of the used harmonic filter shall be taken into account.
Using line filters, the filter layout shall be designed for any conceivable line configuration. In
particular, self-resonance shall be excluded under any load condition and all generator
combinations.
In the case of several parallel filter circuits, the current symmetry shall be monitored. An
asymmetrical current distribution in the individual filter circuits and the failure of one filter
shall be alarmed.
The additional heating caused by total harmonic distortion shall be taken into account during
the temperature rise test.
BS IEC 60092-501:2013
– 22 – 60092-501 © IEC:2013(E)
The cabinets for harmonic filters shall be in accordance with the standards of main
switchboards, where applicable.
12 Propulsion motors
For motors, the requirements of the IEC 60034 series and IEC 60092-301 shall apply.
Motors shall have a protection degree of at least IP 23 according to IEC 60529. High voltage
motors shall have a protection degree of at least IP 44.
Motors operating with semiconductor convertors shall be designed for the expected harmonics
of the system. A sufficient reserve shall be considered for the temperature rise, compared
with sinusoidal load. The motor insulation shall be designed according to the requirements of
the connected convertor.
The requirements of generator bearing and lubrication apply, see 7.2, with the following
additional requirements.
Motor bearings can be shaft bearings. The requirements of the appropriate authority should
be considered.
The requirements of generator cooling apply, see 7.3, with the following additional
requirements.
Sufficient cooling shall be ensured under all load and speed conditions.
If the cooling of the propulsion motors fails, restricted service (manoeuvrability) shall be
possible. Interventions by the operator, for example opening of emergency air flaps are
permitted.
Propulsion motors shall be equipped with an electric heating designed to maintain the
temperature inside the machine at about 3 K above ambient temperature.
12.5 Protection
12.5.1 Overcurrent
Overcurrent protective devices in the main and excitation circuits shall be set sufficiently high
so that there is no possibility of their operating due to the overcurrents caused by
manoeuvring or normal operation in heavy seas or in floating broken ice.
The control system shall ensure that manoeuvring, normal operation in heavy seas or rough
weather or operation in broken ice will not overload any part of the system.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 23 –
Short-circuit and overcurrent protection is required and may be provided by the convertor.
Annex A gives an alarm-matrix of the different motor designs such as permanent excited
motors, synchronous motors, asynchronous motors and DC motors.
In case of overcurrent the system shall be able to switch off the faulty part of the system.
An independent overspeed protection device is required, see SOLAS 1974 Chapter II-1,
Regulation 27, first paragraph.
12.6 Test
Propulsion motors shall be individually tested at the manufacturer's works. The scope of the
tests is stated in the IEC 60034 series.
The additional heating caused by total harmonic distortion, see 5.2, shall be taken into
account during the temperature rise test.
After the first temperature rise test and after each repeated inspection, an insulation
resistance measurement shall be carried out.
If the neutral point is not accessible, the stipulated phase-against-phase insulation test is not
possible. The manufacturer shall offer an equivalent test.
Motors shall be capable of withstanding a sudden short-circuit at their terminals under all
conditions without suffering damage, see 10.1. Both cases, three and two phase
short-circuits, shall be considered.
Steady state short-circuit current of permanent excited motors shall not cause thermal
damages of the motor and the current carrying components (for example cables, feeders, slip
rings).
For purposes of inspection and repair, provision shall be made for access to the stator and
rotor coils, and for the withdrawal and replacement of field coils.
Facilities shall be provided for supporting the shaft to permit inspection and withdrawal
replacement of bearings.
Adequate access shall be provided to permit resurfacing of commutators and slip rings, as
well as the renewal and bedding of brushes, rotating rectifiers and protection equipment, if
any.
Slip couplings shall be designed to permit removal as a unit without axial displacement of the
driving and driven shaft, and without removing the poles.
BS IEC 60092-501:2013
– 24 – 60092-501 © IEC:2013(E)
The manufacturer shall take into account that during operation, inaccessible spaces and
special environmental conditions require sufficient measures, for example highly reliable
materials and components, adequate amount of sensors, special mechanical precautions.
The components, for example controls, sensors, slip rings, cable connections and auxiliary
drives, shall withstand the strength of vibration, of at least 4 g from 3 Hz to 100 Hz.
13.2 Sensors
The manufacturer shall prepare a list of all sensors with type, location of their installation,
task and values (range, set points and action caused).
Important operational values for maintaining the drive and control ability in inaccessible areas
shall be recorded, evaluated and shown redundantly.
The recorded results shall be checked for plausibility. Implausible input signals shall trigger
an alarm. It shall be possible to differentiate extreme measure values from sensor faults.
Sensors which can only be changed during dry docking shall at least be constructed as
double sensors.
13.2.2 Bearings
Oil minimum and maximum levels shall be monitored. Oil temperature shall be monitored as
well (maximum value). This applies also during operation. Oil leakage shall be indicated by an
alarm. Inspection of the oil level shall be possible, independent from the alarm and monitoring
system.
This applies to circulated lubrication systems as well. These systems shall additionally be
equipped with flow monitoring.
Shaft bearings shall be monitored to observe changes during operation, for example by
analysis of temperatures, vibrations and oil quality.
The temperature of the shaft bearings shall be monitored. The alarm shall be carried out in
two steps (action 1: alarm, action 2: stop). The temperature indication for shaft bearings shall
be provided independently from the alarm and monitoring system. Redundant sensors are
required.
The measurement of the motor bearing temperature shall be carried out in accordance with
8.9 of IEC 60034-1:2010.
13.2.3 Bilges
All areas below water line shall be equipped with bilge level sensors. In addition to the
conventional bilge sensors (high level, HL), independent sensors (high high level, HHL) shall
be provided which stop the propulsion automatically and protect it from consequential
damages.
The shaft sealing system shall be monitored in a way that ingress of sea water is detected
before consequential damages appear. An emergency sealing system shall be provided. In
combination with the emergency sealing system there shall be a braking or blocking system
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 25 –
which can fix the shaft under all weather and normal towing conditions. The activation of
sealing and breaking system shall be indicated at each control station.
Sufficient illumination and temporary ventilation shall be provided for accessible areas where
regular maintenance work needs to be carried out. Entries to these areas shall be locked in
such a way that access is only possible, if the personnel cannot be endangered by the drives.
Motors of more than 1 MW and all permanent excited motors shall be provided with protection
against internal faults that also monitors the connections between the convertor and motor. In
the case of a fault, the power supply to the defective equipment shall be interrupted within an
appropriate period of time.
Cables operated at high temperature limits shall be installed separate from other cables. If
required, a protection against contact shall be provided.
Test reports of temperature rise tests of busbars with increased current density or cables
operated at high conductor temperature values shall be submitted to the nominated body,
see 4.2.
During the temperature rise test on the sea trial, it shall be proven that the permitted
maximum temperature values in the area of the terminals are not exceeded.
IP protection for all terminals, cable glands and busbar connections shall be at least IP 44.
13.6.1 General
It shall be taken into account that the mechanical and electrical characteristics of the slip
rings can be degraded by contamination with oil, carbon dust and salt mist air, or by
oxidation.
Enclosures for slip ring assemblies shall ensure at least a degree of protection IP23 according
to IEC 60529.
The suitability of used materials at maximum permitted temperature values shall be proven.
The permitted conductor temperature values of the connected cables shall not be exceeded.
During the temperature rise test at the sea trial, it shall be proven that the permitted
temperature limits are not exceeded.
BS IEC 60092-501:2013
– 26 – 60092-501 © IEC:2013(E)
In case of data transmission carried out via a bus system, two redundant transmission paths
shall be provided. Failure of each single system shall be alarmed.
External or forced cooled slip rings shall be dimensioned sufficiently for restricted operation
without the cooling system. The cooling system failure shall be alarmed.
13.6.2 Tests
• visual inspection;
• insulation resistor measurement;
• high voltage withstand test IEC 61180-1 or IEC 62271-200;
• slip ring contact resistance;
• functional test of auxiliaries (e.g. sensors, data transfer).
A type test shall be performed for each slip ring design on the basis of IEC 62271-200 or
IEC 61439-1 and IEC 61439-2:
For signal and low voltage circuits the suitable test criteria shall apply. Special conditions
regarding EMC shall be taken into account.
During sea trials the maximum allowed temperatures of slip rings, brushes and cabling shall
be demonstrated.
Azimuth drives shall meet the requirements of steering gear in accordance with SOLAS 1974
Chapter II-1, Regulations 29 and 30. Single failure criterion shall be ensured for all electrical
controls and all electronic controls, sensors and hydraulic components. For these purposes, a
failure mode effect analysis (FMEA) shall be provided and practically proven, as far as
possible, by the nominated body, see 4.2. Safe operation of the ship shall be ensured
independently of the angular position of the pod and ship's speed in the event of any failure.
The position of the azimuth drive shall be mechanically indicated on site.
At least two independent azimuth drives shall be provided for each podded drive, whereby
one drive shall be supplied from the emergency switchboard and the other from the main
switchboard.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 27 –
Azimuth drives shall be protected against overcurrent (for example by convertor, if applicable)
and short-circuit. They shall be able to supply 160 % of the torque necessary for the rated
speed of movement in accordance with SOLAS 1974 Chapter II-1, Regulations 29 and 30 for
60 s. Azimuth systems with different design, for example hydraulic systems, shall also be able
to fulfil these requirements.
Generally, the thrust azimuth angle shall be limited to ± 35°, see SOLAS 1974 Chapter II-1,
Regulation 29 and 30. At low propulsion power rating, low ship speed or crash-stop
manoeuvre, these limits may be exceeded.
The thrust azimuth angle shall be limited, related to the propulsion shaft power and/or
selected operation mode so that the safety of the ship is not endangered. The propulsion
power shall be limited, related to the actual azimuth angle so that the safety of the ship is not
endangered.
After triggering the limitation, it shall be possible to move the azimuth drive back to the
allowed range without manual reset.
13.7.3 Control
The operation and indication equipment shall be arranged in a way that the moving direction
or the thrust direction of the ship is clearly discernible. It shall be clearly discernible for the
operator whether the moving direction or the propulsion direction was chosen.
For local control for propulsion, see 14.5. The local control station for azimuth drives shall be
equipped accordingly:
– rudder control;
– ammeter for each supply side current of each load component;
– azimuth angle indicator for each podded drive;
– plant ready for operation for each drive;
– plant disturbed for each drive;
– power limited (from convertor);
– control from engine control room;
– control from the bridge;
– running indication for the associated propulsion drive; and
– alarms according to SOLAS 1974 Chapter II-1, Regulation 29 and 30.
The local control station can be activated locally and shall have the highest priority.
14 Control
14.1 General
Computer based systems shall be designed and tested in accordance with IEC 60092-504.
Any loss of automatic function shall be alarmed.
14.2.1 General
Additional to the requirements described in IEC 60092-504, the following requirements shall
apply.
– For power supply with generators operating in parallel, there shall be a device/computer
program for automatic power management, which will ensure adequate power generation,
even in transit/manoeuvre. Automatic load based disconnection of diesel generators in
manoeuvre mode is forbidden.
– In case of under-frequency of the supplying mains, overcurrent or overload, and reverse
power, the propulsion power has to be limited.
– If generators are running in parallel and one of them is tripping, the power supply system
shall be provided with suitable means of load reductions to protect the remaining
generators against unacceptable load steps. The same requirement applies to bus tie
breakers.
– Tripping of the bus tie breaker may not lead to any malfunction of the system. It is not
necessary that the system remains in the automatic mode if the supply system is split.
14.2.2 Test
Power management systems shall be subjected to a functional test (software FAT) in the
manufacturer’s works. Joint testing with the propulsion switchboard is recommended.
The typical system configuration consists of control stations, one central processing unit, two
convertors, one motor (two winding systems), one local control panel (two independent
reference inputs) and one telegraph receiver.
The wing control and the engine control room (ECR) control are not mandatory for vessels
with restricted operational area.
Local control shall be possible if the remote control system failed. Therefore the local control
panel shall be directly connected to the convertors and shall have the highest priority.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 29 –
Bridge
Bridgedesk
Desk
00 100.0 ON
D1 D2
A2 A3 A4 A5
S1-B
A16 S1 S2 S3 S4 S5
A8 A9 A10 A11
S6-B
A7
A1 S6 S7 S8 S9 S10
S25-B
REDUCE ET
SHUT
DIESEL MODE +1
DOWN
POWER LIMIT
S25
A42 A43 A44 A45 A46 A47
S30-B
DIESEL
REMOTE DIESEL CLUTCH
ELEC-
BRIDGE ON AHEAD
-1
T RIC
REMOTE CLUTCH
DIESEL
ECR AST ERN
EMER- ELEC-
ELEC- CLUTCH
GENCY T RIC
T RIC DIESEL
OPERAT ON
PORT LAMP
LOCAL
MODE T EST
S31-B
ELEC-
ET T O DIESEL ST ART CLUTCH ACOUST .
T RIC
ZERO FAIL FAIL FAIL RESET
FAIL
ENT ER
Wing
Wing Wing
Wing
2
ECR Desk
desk
3
00 100.0 ON
D1 D2
A2 A3 A4 A5
S1 -B
A1 6 S1 S2 S3 S4 S5
A8 A9 A1 0 A1 1
S6 -B
CRIT T RI C EL EC-
RESET SETTING T EST
F AUL T SPEED T RI C
A7
A1 S6 S7 S8 S9 S1 0
S2 5 -B
REDUCE ET
SHUT
DIESEL M ODE
DOWN +1
POWER L IM IT
S2 5
A4 2 A4 3 A4 4 A4 5 A4 6 A4 7
S3 0 -B
A1 2 S1 2 A1 3 S1 3 A1 4 S1 4 A1 5 S1 5
S3 0
DIESEL
ECR ASTERN
A1 7 S1 7 A1 8 S1 8 A1 9 S1 9 A2 0 S2 0
EM ER- EL EC-
EL EC- CL UTCH
GENCY
T RI C
T RI C DIESEL
OPERAT ON
A2 1 S2 1 A2 2 S2 2 A2 3 S2 3 A2 4 S2 4
PORT L AM P
L OCAL
M ODE TEST
A2 6 S2 6 A2 7 S2 7 A2 8 S2 8 A2 9 S2 9 S1 6
Propulsion
Propulsion control
Control System
system
Converter
Converter
A12
A17
A21
A26
SIEMENS
DIESEL
ELEC-
T RIC
S12
DIESEL
S17
ELEC-
T RIC
S21
PORT
MODE
S26
A13
A18
A22
A27
REMOTE
BRIDGE
S13
REMOTE
ECR
S18
EMER-
GENCY
OPERAT
S22
LOCAL
S27
A14
A19
A23
A28
DIESEL
ON
S14
S19
ELEC-
T RIC
ON
S23
S28
A15
A20
A24
A29
CLUTCH
AHEAD
S15
CLUTCH
AST ERN
S20
CLUTCH
DIESEL
S24
S29
M
7 6
IEC 2658/13
Key
1 bridge desk 5 convertors
2 wing 6 local control panel
3 engine control room (ECR) desk 7 telegraph receiver
4 propulsion control system
Whenever control outside the engine room is applied, an arrangement shall be provided
whereby the propulsion plant can also be controlled from the engine room or control room.
BS IEC 60092-501:2013
– 30 – 60092-501 © IEC:2013(E)
The local control station shall be located in the vicinity of the drives or convertors so that
changes in the control of propulsion can be recognized.
Additional to the requirements of 9.5 of IEC 60092-504:2001, the following requirements shall
apply.
At least mutually independent main and local control stations shall be provided. In the case of
breakdown, malfunctioning or loss of power supply of the propulsion control system, the
control of the convertors shall remain possible at the local control panel, see Figure 2.
The bridge shall be fitted with a system which ensures that the steering, the monitoring and
the control of the steering gear can be operated independently of the propulsion system.
Communication to all local control stations in parallel shall be possible.
All alarms shall be acknowledgeable at the local control stations. Alarms which do not require
any further intervention can be acknowledged at the main control station. Restart of the
propulsion plant shall be possible from both control stations, depending on which one has
been preselected. After a blackout, it shall be possible to restart the propulsion plant at the
main control station.
Each control station shall have an emergency stop device which is independent of the drive’s
control and the active control station. The emergency stop device shall ensure the tripping of
the feeder breaker for the propulsion convertor.
If the control station in ECR is not foreseen according to 14.3 an emergency stop device shall
be available at its place.
Failures in measuring, monitoring and indicating equipment shall not cause a failure of the
drives control, for example, failure of the actual value or of the reference value shall not
cause an excessive increase of propeller speed and/or direction.
At least the following measuring and control equipment as well as indicators shall be
provided:
– speed setting;
– local remote switch;
– ammeter for each supply side current of each load component;
– indication excitation on;
– revolution indicator for each shaft;
– pitch indication for plants with variable pitch control;
– indication plant ready for operation;
– indication convertor on/off;
– indication plant disturbed;
– indication power limited;
– indication control from engine control room; and
– indication control from the bridge;
– indication control from local.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 31 –
At the (main) control station on the bridge, at least the following measuring and indication
equipment shall be provided:
– control levers;
– revolution indicator per shaft;
– shaft power meter;
– indication plant ready for switching on;
– indication plant ready for operation;
– indication plant disturbed;
– indication power limitation;
– indication request to reduce the power if not automatically controlled or equipped with
override push button;
– indication control from engine control room;
– indication control from the local control station; and
– indication generators used for propulsion;
– selector switch operation modes ( i.e. sea mode, estuary mode, harbour mode).
When two or more control stations are provided for variable speed and pitch propellers, a
propeller speed and pitch indicator shall be provided at each control station.
At the (main) control station in the engine control room, at least the following measuring and
indication equipment shall be provided:
– control levers;
– revolution indicator for each shaft;
– shaft power meter;
– indication plant ready for switching on;
– indication selected operation mode;
– indication plant ready for operation;
– indication plant disturbed;
– indication power limitation;
– indication request to reduce the power if not automatically controlled or equipped with
override push button;
– indication control from the local control station;
– indication control from the bridge; and
– indication generators used for propulsion.
14.7 Availability
In general, the loss of power of any other control and monitoring system or the malfunctioning
of these systems shall not result in loss of propulsion, steering or azimuth drives.
Propulsion and azimuth drives and controls shall have self-acting routines to detect failure.
BS IEC 60092-501:2013
– 32 – 60092-501 © IEC:2013(E)
Any failures, for example loss of power, wire failure etc., shall result in non-critical new
condition (fail to safety).
The start-up process of the propulsion plant shall be interlocked such that starting is
impossible if existing malfunctions would trigger a shutdown or if the start-up process itself
would cause damage to the propulsion plant.
The pilot light “plant ready to start for switching on” may only be activated when all the
prerequisites for start-up have been met.
The pilot light “plant ready for operation” may only be activated if the propulsion plant would
respond to set point setting.
For the first vessel of a series, the remote control shall be set up with all control stations and
tested.
15 Tests
15.1 General
In addition to the standard tests described in other parts of the IEC 60092 series, the
following special tests shall be carried out.
All tests of components or subsystems or systems carried out during manufacturing, factory
acceptance test and dock and sea trials shall be documented. The test results shall be
documented in such a way that single components can be identified and traced.
The current, voltage and temperature capabilities of cables, busbar systems and slip rings
shall be verified by type tests or routine tests.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 33 –
A plan shall be generated before production which indicates all tests carried out by the
manufacturer and sub-suppliers.
Before the factory acceptance test is carried out, the test procedure shall be documented.
As far as practicable, all normal acceptance tests of equipment shall be carried out at the
manufacturer's works to show that they meet the requirements of this standard and the
ordering specification.
In addition to the standard tests described in other clauses of the IEC 60092 series, all
protective devices shall be tested to show that they are electrically and mechanically
satisfactory.
Before the dock and sea trials, the test procedure shall be documented.
Complete tests shall be carried out including heat run and manoeuvring tests which shall
include a crash stop of the ship from full speed to zero speed.
All tests necessary to demonstrate that each item of the plant and the system as a whole is
satisfactory for duty shall be performed.
The test program shall include tests of the propulsion plant in normal and abnormal
conditions.
The grid quality in the ship’s propulsion network and mains shall be checked according to the
following items:
Start-up and stop sequences shall be tested, both those initiated by manual action and those
initiated by the power management system, when relevant.
Safety functions, alarms and indicators shall be tested. A physical check of all sensors shall
be performed.
Where an FMEA is required, FMEA proving tests shall be performed. Test procedures shall be
provided for each of the failures considered in the FMEA. FMEA proving tests shall be
completed prior to the initial survey of the ship.
Immediately prior to and after trials, the insulation resistance of power circuits shall be
measured and recorded.
BS IEC 60092-501:2013
– 34 – 60092-501 © IEC:2013(E)
16 Documentation
The nominated body, see 4.2, shall be responsible for ensuring that complete documentation
is available for all relevant components and systems.
Each manufacturer shall give documented evidence of conformity that his plant fulfils the
requirements of this standard.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 35 –
Annex A
(normative)
A.1 General
This annex provides protection and alarm matrixes for different motor designs such as
permanent excited motors (Table A.1), synchronous motors (Table A.2), asynchronous motors
(Table A.3) and DC motors (Table A.4).
The set points for warning, alarm, reduction and stop should be separated or time delayed to
allow crew intervention before progression to the next level of protection as far as practicable.
6
7 5
8
~ 5
~ 2
9 5
7 M
~
4 Option
IEC 2659/13
Key
1 transformer 5 coolant 8 power supply, mains
and auxiliaries
2 convertor 6 core
9 bearings
3 motor 7 winding
4 shaft
See Tables A.1, A.2, A.3 and A.4 for requirements to monitoring.
Figure A.1 shows the typical parts of a propulsion unit which shall be monitored as a
minimum.
BS IEC 60092-501:2013
– 36 – 60092-501 © IEC:2013(E)
Figure Monitored value Limiting Local Indication Indication First step Second Last step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action Stop/trip
station station Reduce
if
applicable
3 Motor
9 Bearing oil lubrication
Temperature High X C X - X
Filling level Low Inspection X C X - -
glass
9 Bearing housing Max Thermometer X C X - X
temperature
7 Stator winding temp. Max - X C X X i.a.
5 External cooling
Cooling air temperature Max Thermometer X C X - -
Coolant Leakage - X C X - -
4 Speed Overspeed - X C X - X
4 Locked rotor protection Active - X C X - Xa
3 Earth fault monitoring Min - X C X - -
3 Electrical motor Short-circuit - X X X - Xb
protection
3 Electrical motor Overcurrent - X C X - X
protection
3 Electrical motor Internal - X C X - Xc
protection faults
1 Transformer/reactor, i.a.
7 Transformer, winding Max - X C X X -
temperature
6 Transformer, core Max - X C X X -
temperature i.a.
5 External cooling i.a.
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
1 Electrical protection Overcurrent - X C X - X
1 Electrical protection Short-circuit - X C X - X
1 Differential current (not Max - X C X - X
required for reactors)
2 Convertor
8 Mains (input) Failure - X C X - Xd
8 Auxiliary supplies and Failure - X - X - -
bus systems i.a.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 37 –
Table A.1 (2 of 2)
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
5 External cooling
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
Coolant conductivity in High X X C X - X
case of directly cooled
semiconductors
2 Semiconductor fuses i.a. Blown Indicator X C X - X
device
6 Output overcurrent Max - X C X - X
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
3 Motor
9 Bearing oil lubrication
Temperature High X C X - X
Filling level Low Inspection X C X - -
glass
9 Bearing housing Max Thermometer X C X - X
temperature
7 Stator winding temp. Max - X C X X i.a.
5 External cooling
Cooling air temperature Max Thermometer X C X - -
Coolant Leakage - X C X - -
4 Speed Overspeed - X C X - X
4 Locked rotor protection Active - X C X - Xa
3 Earth fault monitoring Min - X C X - -
3 Electrical motor Short-circuit - X X X - Xb
protection
3 Electrical motor Overcurrent - X C X - X
protection
3 Electrical motor Internal - X C X - Xc
protection faults
3 Exciter system Failure - X C X - X
1 Transformer/reactor, i.a.
7 Transformer, winding Max - X C X X -
temperature
6 Transformer, core Max - X C X X -
temperature i.a.
5 External cooling i.a.
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
1 Electrical protection Overcurrent - X C X - X
1 Electrical protection Short-circuit - X C X - X
1 Differential current (not Max - X C X - X
required for reactors)
2 Convertor
8 Mains (input) Failure - X C X - Xd
8 Auxiliary supplies and Failure - X - X - -
bus systems i.a.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 39 –
Table A.2 (2 of 2)
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
5 External cooling
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
Coolant conductivity High X X C X - X
in case of directly cooled
semiconductors
2 Semiconductor fuses i.a. Blown Indicator X C X - X
device
6 Output overcurrent Max - X C X - X
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
3 Motor
9 Bearing oil lubrication
Temperature High X C X - X
Filling level Low Inspection X C X - -
glass
9 Bearing housing Max Thermometer X C X - X
temperature
7 Stator winding temp. Max - X C X X i.a.
5 External cooling
Cooling air temperature Max Thermometer X C X - -
Coolant Leakage - X C X - -
4 Speed Overspeed - X C X - X
3 Earth fault monitoring Min - X C X - -
3 Electrical motor Short-circuit - X X X - X
protection
3 Electrical motor Overcurrent - X C X - X
protection
3 Electrical motor Internal - X C X - X
protection faults
1 Transformer/reactor, i.a.
7 Transformer, winding Max - X C X X -
temperature
6 Transformer, core Max - X C X X -
temperature i.a.
5 External cooling i.a.
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
1 Electrical protection Overcurrent - X C X - X
1 Electrical protection Short-circuit - X C X - X
1 Differential current (not Max - X C X - X
required for reactors)
2 Convertor
8 Mains (input) Failure - X C X - Xd
8 Auxiliary supplies and Failure - X - X - -
bus systems i.a.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 41 –
Table A.3 (2 of 2)
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
5 External cooling
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
Coolant conductivity High X X C X - X
in case of directly cooled
semiconductors
2 Semiconductor fuses i.a. Blown Indicator X C X - X
device
6 Output overcurrent Max - X C X - X
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
3 Motor
9 Bearing oil lubrication
Temperature High X C X - X
Filling level Low Inspection X C X - -
glass
9 Bearing housing Max Thermometer X C X - X
temperature
7 Exciter and Max - X C X X i. a.
compensation winding
temperature, i. a.
5 External cooling
Cooling air temperature Max Thermometer X C X - -
Coolant Leakage - X C X - -
4 Speed Overspeed - X C X - X
4 Locked rotor protection Active - X C X - Xa
(shunt wound motor
only)
3 Earth fault monitoring Min - X C X - -
3 Electrical motor Short-circuit - X X X - X
protection
3 Electrical motor Overcurrent - X C X - X
protection
3 Electrical motor Internal - X C X - Xc
protection faults
3 Exciter system Failure - X C X - X
1 Transformer/reactor, i.a.
7 Transformer, winding Max - X C X X -
temperature
6 Transformer, core Max - X C X X -
temperature i.a.
5 External cooling i.a.
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
1 Electrical protection Overcurrent - X C X - X
1 Electrical protection Short-circuit - X C X - X
1 Differential current (not Max - X C X - X
required for reactors)
2 Convertor
8 Mains (input) Failure - X C X - Xd
8 Auxiliary supplies and Failure - X - X - -
bus systems, i.a.
BS IEC 60092-501:2013
60092-501 © IEC:2013(E) – 43 –
Table A.4 (2 of 2)
Figure Monitored value Limiting Local Indication Indication First step Second Last Step
A.1 value diagnostic on ECR on bridge action Alarm step action
index tool control control action stop/trip
station station Reduce
if
applicable
5 External cooling
Cooling air temperature Max - X C X - -
Coolant Leakage - X C X - -
Coolant conductivity High X X C X - X
in case of directly cooled
semiconductors
2 Semiconductor fuses i.a. Blown Indicator X C X - X
device
6 Output overcurrent Max - X C X - X
Bibliography
IEC 60092-503, Electrical installations in ships – Part 503: Special features – AC supply
systems with voltages in the range of above 1 kV up to and including 15 kV
_____________
This page deliberately left blank
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW
About us Revisions
We bring together business, industry, government, consumers, innovators Our British Standards and other publications are updated by amendment or revision.
and others to shape their combined experience and expertise into standards We continually improve the quality of our products and services to benefit your
-based solutions. business. If you find an inaccuracy or ambiguity within a British Standard or other
The knowledge embodied in our standards has been carefully assembled in BSI publication please inform the Knowledge Centre.
a dependable format and refined through our open consultation process.
Organizations of all sizes and across all sectors choose standards to help Copyright
them achieve their goals. All the data, software and documentation set out in all British Standards and
other BSI publications are the property of and copyrighted by BSI, or some person
Information on standards or entity that owns copyright in the information used (such as the international
We can provide you with the knowledge that your organization needs standardization bodies) and has formally licensed such information to BSI for
to succeed. Find out more about British Standards by visiting our website at commercial publication and use. Except as permitted under the Copyright, Designs
bsigroup.com/standards or contacting our Customer Services team or and Patents Act 1988 no extract may be reproduced, stored in a retrieval system
Knowledge Centre. or transmitted in any form or by any means – electronic, photocopying, recording
or otherwise – without prior written permission from BSI. Details and advice can
Buying standards be obtained from the Copyright & Licensing Department.
You can buy and download PDF versions of BSI publications, including British
and adopted European and international standards, through our website at Useful Contacts:
bsigroup.com/shop, where hard copies can also be purchased. Customer Services
If you need international and foreign standards from other Standards Development Tel: +44 845 086 9001
Organizations, hard copies can be ordered from our Customer Services team. Email (orders): [email protected]
Email (enquiries): [email protected]
Subscriptions
Subscriptions
Our range of subscription services are designed to make using standards
Tel: +44 845 086 9001
easier for you. For further information on our subscription products go to
Email: [email protected]
bsigroup.com/subscriptions.
With British Standards Online (BSOL) you’ll have instant access to over 55,000 Knowledge Centre
British and adopted European and international standards from your desktop. Tel: +44 20 8996 7004
It’s available 24/7 and is refreshed daily so you’ll always be up to date. Email: [email protected]
You can keep in touch with standards developments and receive substantial
Copyright & Licensing
discounts on the purchase price of standards, both in single copy and subscription
format, by becoming a BSI Subscribing Member. Tel: +44 20 8996 7070
Email: [email protected]
PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
revised or replaced.
To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email [email protected].