ADEMCO VISTA SERIES

VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems

Programming Guide

K5305-1PRV9 3/15 Rev A


RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection
Devices Help Provide Proper Coverage for the Protected Premises.

Recommendations For Smoke And Heat Detectors


With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be installed outside of
each separate sleeping area, and on each additional floor of a multi-floor family living unit, including
basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up
the sleeper if the door is closed.
• Install a smoke detector inside bedrooms
where electrical appliances (such as
KITCHEN
BEDROOM BEDROOM KITCHEN DINING BDRM
portable heaters, air conditioners or
DINING TV ROOM
humidifiers) are used.
LIVING ROOM
BDRM
• Install a smoke detector at both ends of a
BEDROOM hallway if the hallway is more than 40 feet
LIVING ROOM BEDROOM
(12 meters) long.
• Install smoke detectors in any room where
Smoke Detectors for Minimum Protection an alarm control is located, or in any room
Smoke Detectors for Additional Protection where alarm control connections to an AC
Heat-Activated Detectors
BEDROOM source or phone lines are made. If detectors
TO
are not so located, a fire within the room
BEDROOM BR BEDROOM could prevent the control from reporting a
KTCHN
fire or an intrusion.
GARAGE
LVNG RM . CLOSED
DOOR THIS CONTROL COMPLIES WITH NFPA
BASEMENT
REQUIREMENTS FOR TEMPORAL PULSE
floor_plan-001-V1 SOUNDING OF FIRE NOTIFICATION
APPLIANCES.

Recommendations For Proper Intrusion Protection


For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows in a
multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be
sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are
normally sent over the phone lines, if connected to an alarm monitoring station).

NOTE: Copies of the Programming, User, and Installation Guides must be left with the end user.

–2–
TABLE OF CONTENTS
PROGRAMMING MODE COMMANDS .................................................................................................................... 4
DATA FIELD PROGRAMMING FORM ..................................................................................................................... 5
CONFIGURABLE ZONE TYPES WORKSHEET.................................................................................................... 19
56 ZONE PROGRAMMING MENU MODE ............................................................................................................. 20
58 EXPERT ZONE PROGRAM MODE ................................................................................................................... 22
WIRELESS KEY PROGRAMMING TEMPLATES ................................................................................................. 23
57 FUNCTION KEY PROGRAMMING MENU MODE ............................................................................................ 25
OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode) ..................................... 26
79 RELAY/POWERLINE CARRIER DEVICE (X-10) PROGRAMMING MENU MODE ......................................... 26
80 OUTPUT FUNCTION MENU MODE .................................................................................................................. 27
81 ZONE LIST MENU MODE ................................................................................................................................. 29
82 ALPHA DESCRIPTOR MENU MODE ............................................................................................................... 30
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) ......................................................................... 32
SETTING SCHEDULES .......................................................................................................................................... 33
AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS .................................................................. 34
SETTING THE REAL-TIME CLOCK ...................................................................................................................... 34
29 COMMUNICATION DEVICE MENU MODE (Pass-Through Programming) .................................................. 35
UPLOADING/DOWNLOADING VIA the INTERNET .............................................................................................. 37
ZONE TYPE DEFINITIONS..................................................................................................................................... 38
REPORT CODE FORMATS.................................................................................................................................... 39
SYSTEM SECURITY CODES ................................................................................................................................. 40
KEYPAD FUNCTIONS ............................................................................................................................................ 41
VARIOUS SYSTEM TROUBLE DISPLAYS ........................................................................................................... 42
WORKSHEET for ∗56 ZONE PROGRAMMING .................................................................................................... 43
WORKSHEET for ∗57 FUNCTION KEY PROGRAMMING ................................................................................... 45
WORKSHEET for ∗79 OUTPUT RELAY/POWERLINE CARRIER DEVICE PROGRAMMING ............................ 46
WORKSHEET for ∗81 ZONE LIST PROGRAMMING ........................................................................................... 46
WORKSHEET for ∗80 OUTPUT FUNCTION PROGRAMMING ......................................................................... 47
WORKSHEET for SCHEDULES ............................................................................................................................ 49
TABLE OF DEVICE ADDRESSES ......................................................................................................................... 50
COMPATIBLE DEVICES ........................................................................................................................................ 50
UL NOTICES ........................................................................................................................................................... 51
SIA QUICK REFERENCE GUIDE ........................................................................................................................... 51
ULC S304 REQUIREMENTS (for VISTA-15PCN and VISTA-20PCN).................................................................. 51
FCC STATEMENTS ................................................................................................................................................ 52
LIMITATIONS STATEMENT ................................................................................................................................... 53
CONTACTING TECHNICAL SUPPORT ................................................................................................................. 54
5800 SERIES TRANSMITTER INPUT LOOP IDENTIFICATION ........................................................................... 55

–3–
PROGRAMMING MODE COMMANDS
Compatibility: This document applies to systems with microprocessor version 9.1 or higher.
TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control):
A. POWER UP, then press [✱] and [#] at the same time, within 50 seconds of powering up (this method must be used if ✱98
was used to exit program mode). OR
B. Enter Installer Code (4112) then 8 0 0.
PROGRAMMING COMMANDS
Task Command/Explanation
Go to a Data Field Press [∗ ∗] + [Field Number], followed by the required entry.
Entering Data When the desired field number appears, simply make the required entry. When the last entry
for a field is entered, the keypad beeps three times and automatically displays the next data
field in sequence. If the number of digits that you need to enter in a data field is less than the
maximum digits available (for example, the phone number fields *41, *42), enter the desired
data, then press [∗ ] to end the entry. The next data field number is displayed.
Review a Data Field Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Deleting an Entry Press [∗ ∗] + [Field Number] + [∗ ∗]. (Applies only to fields ∗40 thru *46, *94, and pager fields)
Initialize Download ID Press ∗96. Initializes download ID and subscriber account number.
Reset Factory Defaults Press ∗97. Sets all data fields to original factory default values.
Zone Programming Press ∗56. Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
RF transmitters.
Function Key Programming Press ∗57. Unlabeled keypad keys (known as ABCD keys) for special functions
Zone Programming Press ∗58. Same options as *56 mode, but with fewer prompts. Intended for those familiar
(Expert Mode) with this type of programming, otherwise *56 mode is recommended.
Output Device Mapping Press ∗79. Assign module addresses and map individual relays/powerline carrier devices
Output Programming Press ∗80. 4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
Zone List Programming Press ∗81. Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Alpha Programming Press ∗82. Zone alpha descriptors
IP/GSM Programming Press ∗29. For programming the IP/GSM options.
Exit Program Mode with Press ∗98. Exits programming mode and prevents re-entry by: Installer Code + 8 0 0.
installer code lockout To reenter programming mode, the system must be powered down, then powered up. Then
use method A above. See field *88 for other *98 Program mode lockout options.
Exit Program Mode Press ∗99. Exits program mode and allows re-entry by: Installer Code + 8 0 0 or method A
above.
Scheduling Mode Enter code + [#] + 64. Create schedules to automate various system functions.
Site-Initiated Download Installer code + [#] + 1 (perform while system is disarmed and in normal mode)
AVS QUICK PROGRAMMING COMMANDS (for AAV sessions using the AVS system)
For controls with the following firmware revision levels, these commands automatically configure the control for AVS
operation. VISTA-15P = version 6.0 or higher; VISTA-20P = version 7.0 or higher
• installer code + [#] + [0] + 3: enable AVS operation
• installer code + [#] + [0] + 4: enable AVS operation and enable panels sounds on the AVST speaker
• installer code + [#] + [0] + 5: remove all programming options set by [#] + [0] + 3 quick command
• installer code + [#] + [0] + 6: remove all programming options set by [#] + [0] + 4 quick command
Refer to the AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS section for details on the specific options
that are set with each command, depending on the control used.
To select the AAV session communication path (phone line/communication device), see field ∗55 Dynamic Signaling Priority.
To enable AAV operation, use ∗91 Options field (option 4).

USING REMOTE SERVICES SPECIAL PROGRAMMING MESSAGES


This control supports Remote Interactive Services (RIS) • OC = OPEN CIRCUIT (no communication between
such as Total Connect 2.0, Tuxedo/Z-Wave scenes, and Keypad and Control).
Home Automation (Control 4, 4232CBM), if supported by • EE or ENTRY ERROR = ERROR (invalid field number
the communication service in use. entered; re-enter valid field number).
• Remote Interactive Services is automatically enabled in • After powering up, AC, dI (disabled) or “Busy Standby
the control; device address 25 is automatically assigned. vx.x (firmware revision) Dl will be displayed after
• Use programming field ∗189 to enable a remote services approximately 4 seconds. This will revert to a “Ready”
emulated keypad address. message in approximately 1 minute, which allows PIRS,
• Use ∗29 Menu mode to enable the communication etc. to stabilize.
device. You can bypass this delay by pressing [#] + [0].
• If using Total Connect 2.0, use AlarmNet Direct to NOTE for CANADIAN PANELS: Power up time is 2
program the device and enable TC2 services. Be sure to minutes, and Contact ID report code 305 System Reset
“send” the programming data to the Communicator. is sent if the [#] + [0] command is not performed before
the 2 minutes expires.
IMPORTANT: The Real-Time Clock must be set before
• If E4 or E8 appears, more zones than the expansion
the end of the installation. See procedure in the Setting the
units can handle have been programmed. The display
Real-Time Clock section of this manual.
will clear after you correct the programming.
–4–
DATA FIELD PROGRAMMING FORM
Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries
shown in dashed boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the
VISTA-15P/VISTA-15PSIA. In addition, where noted, certain fields have special settings when used with the SIA panels
(indicated by V20PSIA/V15PSIA with heavy borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-20P/VISTA-15P for False Alarm Reduction.
SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications for
False Alarm Reduction. The other controls described in this manual are not certified as SIA compliant, but can be
programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the
applicable programming fields.

∗20 Installer Code


Enter 4 digits, 0000-9999
| | | [4112]
The Installer Code is used to assign the 4-digit Master Security Code.
The Installer Code can perform all system functions except it cannot
disarm the system unless it was used to arm the system. For security
purposes, the factory default installer code should be changed.
∗21 Quick Arm Enable [0,0]
0 = no
Part. 1 Part.2
1 = yes
If enabled, users can press the [#] followed by an arming key to arm
the system instead of using a security code. The security code is
always needed to disarm the system.
∗22 RF Jam Option [0]
0 = no RF Jam detection
1 = send RF Jam report If enabled, a report is sent if the system detects an RF jamming signal.
UL: must be 1 if wireless devices are used

∗23 Quick (Forced) Bypass [0,0]


0 = no quick bypass
Part. 1 Part. 2
1 = allow quick bypass (code + [6] + [#] )
Zones bypassed by this function will be displayed after the bypass is
initiated.
UL: must be 0

∗24 RF House ID Code | | | [00,00,00]


00 = disable all wireless keypad use
P1 P2 Common
01–31 = using 5827, 5827BD or
The House ID identifies receivers and wireless keypads. If a 5827 or
5804BD keypad
5804BD Transmitter is being used, a House ID code must be entered
and the keypad set to the same House ID. You can assign RF house
ID for each partition
∗26 Chime By Zone / [6, 7]
KP Sound Enables
1 2
Entry 1
0 = no “entry 1” keypad trouble Chime by Zone
sounds, AND no chime by zone If Chime by Zone is enabled (entry 1 – option 1), you can define the
(keypad chimes on fault of any specific zones intended to chime when faulted while the system is in
entry/exit or perimeter zone when Chime mode. List chime zones on zone list 3 using *81 Menu mode.
chime mode is on)
1 = Chime by Zone enabled Keypad (KP) Trouble Sounding
2 = Communication Device (LRR) Keypad trouble sounding can be enabled/disabled for the conditions
trouble sounding enabled (for listed for each entry.
communication devices such as
GSMV4G, GSMX4G, IGSMV4G)
4 = System Low Battery sounding For each entry, enter the sum of the desired options. Example Entry 1:
enabled for Chime by Zone and System Low Battery sounding, enter 5. To
7 = select all entry 1 options enable all options, enter 7.
Entry 2
0 = no “entry 2” keypad trouble sounds
1 = RF Supervision sounding enabled
2 = RF Low Battery sounding enabled
4 = RF Jam sounding enabled
7 = select all entry 2 options

∗27 Powerline Carrier Device (X–10) [0]


House Code
0=A 6=G #11 = L Powerline Carrier devices require a House ID, identified in this field.
1=B 7=H #12 = M Program Powerline Carrier devices in interactive modes ∗79, *80 and
2=C 8=I #13 = N *81.
3 =D 9=J #14 = O UL: not for fire or UL installations
4=E #10 = K #15 = P
5 =F
–5–
∗28 Access Code For Phone Module | [00]
00 = disable
(Partition 1 only)
1st digit: enter 1–9
You must assign a 2-digit access code for the 4286 Phone Module, if
2nd digit: enter # + 11 for "∗", or # + 12
used. Example: If desired access code is 7∗, then 7 is the first entry,
for "#".
and [#] + 11 (for ∗) is the second entry.
NOTE: A 0 in either digit disables the phone module.
UL: must be 00 for UL Commercial Burg. installations

∗29 Enable IP/GSM? – Communication Device Menu Mode (pass-through programming)


This is a Menu Mode command, not a data field, for programming IP/GSM communication device options. See ∗29 Menu
Mode section later in this document.

∗31 Single Alarm Sounding Per Zone [0]


0 = unlimited sounding
1 = one alarm sounding per zone If enabled, limits alarm sounding on the bell output to once per zone
per armed period.
V20PSIA/V15PSIA: If “0” selected,
“alarm sounding per zone” will be the
same as the “number of reports in
armed period” set in field *93 (1 if one
report, 2 if 2 reports, unlimited for
zones in zone list 7).

∗32 Fire Alarm Sounder Timeout [0]


0 = sound stops at timeout selected in
field ∗33 This control complies with NFPA requirements for temporal pulse
1 = no timeout; sounds until manually sounding of fire notification appliances. Temporal pulse sounding for a
turned off fire alarm consists of the following: 3 pulses – pause – 3 pulses – pause – 3
pulses.
UL: must be 1 for fire installations

∗33 Alarm Sounder (Bell) Timeout [1]


0 = none 3 =12 min
1 = 4 min 4 = 16 min This field determines whether the external sounder (and keypad
2 = 8 min sounder) will shut off after time allotted, or continue until manually
turned off.
UL: For residential fire alarm installation, must be set for a minimum of 4 min
(option 1); for UL Commercial Burglary installations, must be minimum 16 min
(option 4)

∗34 Exit Delay


| | [60,60]
00 - 96 = 0 - 96 secs
97 = 120 secs Part. 1 Part. 2
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
V20PSIA/V15PSIA: occur. Common zones use same delay as partition 1.
45 - 96 = 45 - 96 secs; 97 = 120 secs SIA Guidelines: minimum exit delay is 45 seconds
NOTE: Entries less than 45 will result Common zones use part. 1 delay.
in a 45-second delay. UL installations: For UL Commercial Burglar Alarm and UL Residential Burglar
Alarm installations with line security, total exit time must not exceed 60
seconds.

∗35 Entry Delay #1 | | [30,30]


00 - 96 = 0 - 96 seconds
Part. 1 Part. 2
97 = 120 secs
Upon entering, the system must be disarmed before the time entered
98 = 180 secs
expires, otherwise it sounds an alarm.
99 = 240 secs
Common zones use same delay as part 1.
V20PSIA/V15PSIA: SIA Guidelines: minimum entry delay is 30 seconds
30-96 = 30 - 96 secs; 97 = 120 secs; For UL Residential Burglary Alarm installations, must be set for a maximum of
30 seconds; entry delay plus dial delay should not exceed 1 min. For UL
98 = 180 secs; 99 = 240 secs
Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
NOTE: Entries less than 30 will result Upon entering, the system must be disarmed before the time entered expires,
in a 30-second delay. otherwise it sounds an alarm.

∗36 Entry Delay #2 | | [30,30]


See *35 Entry Delay 1 for entries.
Part. 1 Part. 2

∗37 Audible Exit Warning [1,1]


0 = no; 1 = yes
Part. 1 Part. 2
V20PSIA/V15PSIA: Feature always Warning sound consists of slow continuous beeps until the last 10
enabled; field does not exist. seconds, and then it changes to fast beeps. Sound ends when exit time
expires.
SIA Guidelines: must be enabled

–6–
∗38 Confirmation Of Arming Ding [0,0]
0 = no
Part. 1 Part. 2
1 = yes (wired keypads and RF)
Confirmation of arming is 1/2-sec external sounder “ding.”
2 = yes, RF only (except 5827,
If 1 selected, ding occurs when closing report is sent if open/close
5827BD)
reporting is enabled, or at the end of Exit Delay. If 2 selected, ding
occurs upon reception of the wireless arming command.
V15P/V15PSIA NOTE: This option applies only to the Telco reporting
path (not for communication device).
UL: must be 1 for UL Commercial Burglar Alarm inst.

∗39 Power Up In Previous State When the system powers up armed, an alarm will occur 1 minute after
0 = no, always power up disarmed; arming if a zone is faulted. Note that if the previous state was armed
1 = yes, power up in previous state Away or Stay, the system ignores sensor changes for 1 minute, which
allows sensors such as PIRs to stabilize.
V20PSIA/V15PSIA: Feature always UL: must be 1
enabled; field does not exist. SIA Guidelines: must be 1

DIALER PROGRAMMING (✱40 – ✱42)


Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum
digits entered, exit the field by pressing [∗]. The next data field number is displayed.

∗40 PABX Access Code or Call | | | | |


Waiting Disable
Enter up to 6 digits.
To clear entries, press ✱40✱. Call Waiting: If the subscriber’s phone service has “call waiting” (and
If call waiting is used, enter call waiting is not using PABX), enter “*70” (“# + 11”) plus “# + 13” (pause) as the
disable digits “∗ (#+11) 70” plus “# + PABX entry to disable “call waiting” during control panel calls. If the
13” (pause). subscriber does not have “call waiting” and is not using PABX, make
no entry in this field.
V20PSIA/V15PSIA: If call waiting is NOTES:
used, enter call waiting disable digits 1. The call waiting disable feature cannot be used on a PABX line.
as described above, and also set Call 2. Using Call Waiting Disable on a non-call waiting line will prevent
Waiting Disable option in field *91. successful communication to the central station.

∗41 Primary Phone No. | | | | | | | | | | | | | | | | | | |


Secondary Phone No.
∗42 | | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱41✱ or ✱42✱ respectively.
Enter the respective phone numbers.
∗43 Partition 1 Primary Acct. No. | | | / | | | | | [FFFFFFFFFF]

∗44 Part. 1 Secondary Acct. No. | | | / | | | | | [FFFFFFFFFF]


Partition 2 Primary Acct. No.
∗45 | | | / | | | | | [FFFFFFFFFF]
Partition 2 Secondary Acct. No.
∗46 Enter 4 or 10 digits, as chosen in *48
| | | / | | | | | [FFFFFFFFFF]

Report Format. Enter digits 0–9; #+11 Enter [∗] as the fourth digit if a 3-digit account number (for 3+1 dialer
for B; #+12 for C; #+13 for D; #+14 for reporting format) is used. Enter 0 as the first digit of a 4-digit account
E; #+15 for F. no. for 0000-0999. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
To clear entries in a given field, press *43*, *44*, *45*, or *46* based
on the field being programmed
∗47 Phone System Select [1]
If Cent. Sta. is not on a WATS line:
0=Pulse Dial; 1=Tone Dial Select the type of phone service for the installation.
If Cent. Sta. is on a WATS line:
2 = Pulse Dial; 3 = Tone Dial
∗48 Report F ormat [77]
0 = 3+1, 4+1 ADEMCO L/S STANDARD
primary secondary
1 = 3+1, 4+1 RADIONICS STANDARD;
Select the format for primary/secondary phone numbers
2 = 4+2 ADEMCO L/S STAND.
3 = 4+2 RADIONICS STANDARD
5 = 10-digit ADEMCO CONTACT ID®
REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4-digit ADEMCO CONTACT ID®
REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXP.;
9 = 3+1, 4+1 RADIONICS EXP

–7–
∗49 Split/Dual Reporting [0]
0 = Standard/backup reporting only (all
to primary) Backup Reporting: All reports are sent only to the primary number
1-5 = see table at right unless unsuccessful after 8 attempts. If unsuccessful, the system will
make up to 8 attempts to send all reports to the secondary number. If
still unsuccessful after the 16 attempts, the system displays the
“COMM. FAILURE” message (FC for fixed-word displays).
Primary Phone No. 2nd Phone No.
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All All
∗50 Burglary Dialer Delay [2,0]
Delay Time:
Delay V20PSIA/V15PSIA
0 = no delay Time Delay Disable
1 = 15 seconds Provides delay of “BURGLARY ALARM” report to the central station,
2 = 30 seconds which allows time for the subscriber to avoid a false alarm transmission.
3 = 45 seconds This delay does not apply to zone type 24 alarms (silent burglary) or to
V20PSIA/V15PSIA: 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary
alarm), which are always sent as soon as they occur.
Delay Time:
UL: Delay Time must be 0
1 = 15 seconds
2 = 30 seconds SIA Guidelines: delay must be minimum of 15 seconds
3 = 45 seconds
Delay Disable:
0 = use delay set in entry 1
1 = dial delay disabled for zones
listed in zone list 6 (use zone list 6
to enter those zones that require
dial delay to be disabled; these
zones ignore the setting in entry 1)
UL: Dial delay plus entry delay must not exceed
one minute; use zone list 6 to disable dial delay
from appropriate zones, if necessary.

∗53 SESCOA/Radionics Select [0


0 = Radionics (0-9, B-F)
1 = SESCOA (0-9 only reporting) Enter 0 for all non-SESCOA formats.

∗54 Dynamic Signaling Delay [0]


0 = no delay (both signals sent)
1 = 15 secs Select delay from 0 to 225 secs, in 15-sec increments.
2 = 30 secs, etc. Intended for reporting via a communication device on the ECP bus
(LRR). This field lets you select the time the panel should wait for
UL: If using line security, must be 0. acknowledgment from the first reporting destination (see ∗55) before it
Reports will be sent to both the dialer and attempts to send a message to the second destination. Delays can be
the communication device. selected from 0 to 225 seconds, in 15-second increments. This delay is
per message. If 0 is entered in this field, the control panel will send
redundant reports to both Primary Dialer and communication device.
∗55 Dynamic Signaling Priority / [0]
AAV Path Select
0 = Primary Dialer first / AAV via phone This field selects the primary communication path for reporting (dialer
line or communication device) of primary phone number events† (see ∗49
1 = Communication Device (LRR) first / Split/Dual Reporting) and selects the communication path used for
AAV via communication device AAV sessions (phone line or communication device path). Use ∗29
path (see AAV Path Select IP/GSM menu mode to enable the communication device being used.
paragraph at right) † Dynamic signaling applies only to the primary phone number. Reports
intended for the secondary phone number are not sent via the
For UL Commercial Burglary installations communication device.
that use a DACT and LRR, this field must
For Dynamic Signaling Priority: Select the initial reporting destination
be 0.
for messages as follows:
Primary Dialer First selected (0):
• If acknowledged before delay expires (see ∗54), then message will
not be sent via LRR.
• If not acknowledged before delay expires, message is sent to both
the Primary Phone No. and via LRR.
Communication Device (LRR) First selected (1):
• If acknowledged before delay expires, then message will not be sent
to the primary dialer.
• If not acknowledged before delay expires, message is sent to both
the Primary Phone No. and via LRR.

–8–
∗55 Dynamic Signaling Priority / For AAV Path Select:
AAV Path Select (continued) • If using the UVS system or AVS system with non-ECP connection,
option 0 must always be used.
• If using the AVS system with ECP connection, either option (0 or 1)
may be used, but note the following:
IMPORTANT: If option “1” is selected, a 2-way voice (AAV) device
compatible with the communication device path must be used (ex.
GSMV4G, GSMX4G communicator). When selected, AAV sessions
always occur via the GSM communicator, even if reporting reverts to
phone line backup due to GSM communicator path reporting failure.
∗56, ∗57, ∗58 Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming, Function Key Programming, and Expert Mode
Zone Programming respectively. See page 3 and respective sections later in this document.

TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (∗ ∗59 thru ∗68, *70 thru ∗76, and ∗89):
For 3+1 or 4+1 Standard Format: Enter a code in the first box:
1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 (not #+10) in the first box disables a report. A 0 (not #+10) in the second box results in advance to the next field.
For Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
A 0 (not #+10) in the second box will eliminate the expanded message for that report. A 0 (not #+10) in both boxes will disable
the report.
For Ademco Contact ID® Reporting: Enter any digit (other than 0) in the first box, to enable zone to report (entries in the
second boxes are ignored).A 0 (not #+10) in the first box disables the report.
UL: Report codes are required in fields *61, *65, *71, *72, for UL Commercial Burglar Alarm installations.
Report codes are required in fields *60, *62, *63, *64, *70, *73, *74, *75, *76, for UL Commercial Burglar Alarm installations and required for
Residential Fire Alarm installations
SYSTEM STATUS REPORT CODES (✱59–✱ 68)
∗59 Exit Error Alarm Report Code [0]
See above for entries.
After arming the system, entry/exit and interior zones remaining open
after exit delay expires cause an alarm sound at the keypad and
V20PSIA/V15PSIA: external sounder (keypad also displays “EXIT ALARM”), and entry
[1] Always enabled. delay begins. Disarming before the end of the entry delay stops the
alarm sounding and no message is sent to the central station. Keypad
displays “CA” (fixed-word) or “ALARM CANCELED” (alpha display).
If the system is not disarmed before entry delay expires, an “EXIT
ALARM” message (V20PSIA/V15PSIA: also zone alarm message) will
be sent to the central station. The keypad will display “EA” (fixed-word )
or “EXIT ALARM” (alpha display), and alarm sounding continues until
the system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay, and an
“EXIT ALARM” message will be sent to the central station (except for
V20PSIA/V15PSIA, see field *69 Recent Closing report). With Contact
ID format, the message will contain the zone number and error code
374 (“ALARM–EXIT ERROR”).
∗60 Trouble Report Code | [10] See UL System Reporting Note above *59.
See above for entries.
Sent if a zone has a trouble condition.

∗61 Bypass Report Code | [00] See UL System Reporting Note above *59.
See above for entries.
Sent when a zone is manually bypassed.

∗62 AC Loss Report Code | [10] See UL System Reporting Note above *59.
See above for entries.
Timing of this report is random with up to a 4-hour delay. If AC restores
before the report goes out, there is no “AC LOSS” report.

∗63 Low Bat Report Code | [10] See UL System Reporting Note above *59
See above for entries.
Sent when the system’s backup battery has a low-battery condition.

∗64 Test Report Code | [00] See System Reporting UL Note above *59.
See above for entries.
Periodic Test Report Schedule Commands: Sent periodically to test the communicator and phone lines.
every 24 hrs = installer code + [#] + [0] + 0 Frequency of report is set in Scheduling mode (event 11) or by the key
once per week = installer code + [#] + [0] + 1 commands listed at left:
every 28 days = installer code + [#] + [0] + 2 Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P)
to the stated repeat option; first test report sent 12 hours after
command.†
† NOTE: Make sure the Real-Time Clock is set to the proper time before
entering the test report schedule command to ensure that test reports are sent
when expected. (see Setting the Real-Time Clock section)

–9–
∗65 Open Report Code [0,0,0] System Reporting Note above *59.
See above for entries.
Part. 1 Part. 2 Common
Sent upon disarming the system in the selected partitions. See UL

∗66 Arm Away/Stay Rpt Code [0,0,0,0,0,0]


See above for entries.
Away Stay Away Stay Away Stay
Part. 1 Part. 2 Common
This option allows for independent programming of Away and Stay
reports for each partition, including the common lobby.
NOTE: “OPEN” reports are not sent if the associated closing report is
not enabled.
∗67 RF Trans. Low Bat Report Code | [00] UL: must be enabled if wireless devices are used
See above for entries.
Sent when a transmitter low-battery condition exists.

∗68 Cancel Report Code | [00]


See above for entries.
Sent upon disarming the system after an alarm condition was reported.
V20PSIA/V15PSIA: [10]
Report enabled.

∗69 Recent Closing Report Code | [11]


Not applicable to V15P/V20P
See above for entries.
V20PSIA/V15PSIA: Field does not apply to other controls.
Similar to the Exit Error condition described in field *59, but occurs if
V20PSIA/V15PSIA: any burglary zone is faulted within two minutes after the initial exit
Always enabled. delay expires. Disarming the system within the two minutes stops the
alarm sound and displays "ALARM CANCELED " or "CA" and faulted
zone number. No message is sent to the Central Monitoring Station.
If the system is not disarmed within two minutes, the alarm sound
continues and a “recent closing” and a “zone alarm” message are
sent to the Central Monitoring Station (after dial delay expires).

RESTORE REPORT CODES (✱70 – ✱76)


∗70 Alarm Restore Rpt Code [0]
See above for entries.
Alarm restore signals indicate that respective alarm zone(s) are no
longer faulted. Alarm restore reports are sent to the central station at
bell timeout (field *33), if the zone(s) in alarm are actually restored to a
non-faulted state at that time. Otherwise, alarm restore report(s) for
respective alarm zones are sent when the system is disarmed.
See UL System Reporting Note above *59.
If Reports Per Armed Period Per Zone (*93) is also programmed, the
system will report alarm and restore codes as described above until the
“Reports Per Armed Period” count is reached. Disarming and rearming
will reset the “Reports Per Armed Period” count.
∗71 Trouble Restore Rpt Code | [00]
See above for entries
Sent when a trouble in a zone is restored and code + OFF performed.
See UL System Reporting Note above *59.

∗72 Bypass Restore Rpt Code | [00]


See above for entries.
Sent when a zone that has been bypassed is unbypassed.
See UL System Reporting Note above *59.

∗73 AC Restore Rpt Code | [00] See UL System Reporting Note above *59.
See above for entries.
Sent after AC power has been restored after an AC power outage.

∗74 Low Bat Restore Rpt Code | [00] See UL System Reporting Note above *59.
See above for entries.
Sent after a system low-battery condition is restored to normal.

∗75 RF Trans. Lo Bat Rst Rpt Code | [00]


See above for entries.
Sent when a transmitter’s low battery condition is restored (i.e., new
battery installed).
UL: must be enabled if wireless devices are used. See UL System Reporting
Note above *59.

∗76 Test Restore Rpt Code | [00] See UL System Reporting Note above *59.
See above for entries.
This is sent when the Test mode is exited or upon timeout (4hrs).

– 10 –
OUTPUT AND SYSTEM SETUP (✱77 – ✱93)
∗77 Daylight Saving Time Start/End | [3][11]
Month
0 = Disabled Enter the start and end month for daylight saving time, if applicable to
1-9 = Jan.-Sept. (1 = Jan, 2 = Feb, etc) the region.
#+10 = October
#+11 = November
#+12 = December
∗78 Daylight Saving Time Start/End | [2][1]
Weekend
0 = disabled 4 = fourth Enter the start and end weekend for daylight saving time, if applicable
1 = first 5 = last to the region.
2 = second 6 = next to last
3 = third 7 = third to last
∗79, *80, *81, *82 Menu Modes
These are Menu Mode commands, not data fields, for Output Device Mapping, Output Programming, Zone List Programming,
and Alpha Programming respectively. See page 3 and their respective sections for procedures.
∗84 Auto Stay Arm [3]
0 = no
1 = partition 1 only If enabled, the system will automatically change AWAY mode to STAY
2 = partition 2 only mode if the entry/exit door is not opened and closed within the exit
3 = both partitions delay time after a user arms in AWAY mode from a wired keypad (non-
RF device). An Opening report followed by an Armed Stay report is
sent to the Central Station.
If the door is opened and closed within the exit delay period, the
system remains in AWAY mode.
Any RF device that arms the system AWAY overrides this feature and
the system remains armed AWAY.
∗85 Cross Zone Timer [0]
0 = 15 secs 6 = 2-1/2 min #+12 = 8 min
1 = 30 secs 7 = 3 min #+13 = 10 min Sets the maximum amount of time in which two cross zones must be
2 = 45 secs 8 = 4 min #+14 = 12 min tripped in an armed system to send an alarm message to the Central
nd
3 = 60 secs 9 = 5 min #+15 = 15 min Station. If only one zone is tripped during this time (and 2 zone is not
4 = 90 secs #+10 = 6 min tripped), a trouble message (CID code 380) for that zone is sent to the
5 = 2 min #+11 = 7 min Central Station. Assign cross zones on zone list 4; see *81 Menu mode.
NOTE: Cross zoning takes effect only after Exit Delay expires.
∗86 Cancel Verify Keypad Display [1]
0 = no “alarm canceled” display
1 = display “Alarm Canceled” when This feature causes an “ALARM CANCELED” display on the LCD
system is disarmed after an alarm has keypad under the following conditions:
occurred. (To clear the “ALARM • After the kissoff of the cancel message to the Central Station,
CANCELED” display, the user must indicating a successful transmission.
enter the security code + OFF again.) • When an alarm is successfully canceled before the Central Station
received the Alarm message. E.g., if an alarm is incorrectly triggered
NOTE: Applies only when the Dialer is and the user presses code + OFF before the dial delay time has
selected as the primary communication expired, the message will never go out to the CS.
path (∗55 = 0). • When the Cancel report is not enabled and the system is disarmed:
a. before dialer delay expires (alarm report not sent) message
“Alarm Canceled” is displayed.
b. after dialer delay expires message “Alarm Canceled” is not
displayed.
∗87 Misc. Fault Delay Time [0]
0 = 15 secs 6 = 2-1/2 min #+12 = 8 min
1 = 30 sec 7 = 3 min #+13 = 10 min (used with Configurable Zone Types “digit 6”)
2 = 45 secs 8 = 4 min #+14 = 12 min Used with zones assigned to a configurable zone type with fault delay
3 = 60 secs 9 = 5 min #+15 = 15 min on (configurable zone type digit “6”), and sets a zone response time of
4 = 90 secs #+10 = 6 min 15 seconds to 15 min. It can be assigned to zones with sensors that
5 = 2 min #+11 = 7 min provide a trouble indication when an oil tank is low, or similar
UL: may only be used on non-burglar applications for critical condition monitoring where a non-alarm
alarm/ non-fire alarm zones when used in response is desired.
fire and/or UL burglar alarm installation

∗88 Program Mode Lockout Options [0] This table summarizes the Program Mode Lockout options:
0 = standard *98 installer code lockout
Exit *88 Reentry By:
(reentry only by [∗] + [#] within 50 secs
Command Entry Installer Power-up† Downloader
after power up)
*99 n/a yes yes yes
1 = lockout [∗] + [#] reentry after *98
*98 0 no yes yes
exit (reenter via installer code or
downloader only) *98 1 yes no yes
2 = lockout local programming after *98 *98 2 no no yes
exit (reenter by downloader only) † pressing [∗] + [#] within 50 seconds of power up

– 11 –
∗89 Event Log Full Report Code | [00]
See box above field *59 for report code
entries. If an Event Logging selection is made in field ∗90, a message can be
sent to the central station receiver when the log is 80% full. If the log
becomes full, new messages overwrite the oldest messages in the log.
∗90 Event Log Enables [3]
0 = None
1 = Alarm/Alarm Restore This system can record various events in a history log (VISTA-20P =
2 = Trouble/Trouble Restore 100 events; VISTA-15P = 50 events). At any time, the downloader
4 = Bypass/Bypass Restore operator can then upload the log and view or print out all or selected
8 = Open/Close. categories of the log, or can clear the log. Event log can also be viewed
at an alpha keypad. The display/printout at the central station will show
Example: To select “Alarm/Alarm the date, time, event, and description of the occurrences.
Restore”, and “Open/Close”, enter 9 (1 Data Entry Example: To select Alarm/Alarm Restore” and
+ 8) “Open/Close”, enter 9 (1+ 8); to select all events, enter #15.
To select all, enter #15. NOTE: System messages are logged when any non-zero entry is made.
∗91 Option Selection [8, 0]
Entry 1: Options
Options V20PSIA/V15PSIA: Call Waiting Disable
0 = None
1 = Bell Supervision Processing IMPORTANT: AAV should not be used when Paging or Alarm Reports
4 = AAV are sent to a secondary number unless the monitoring zone option is
8 = Exit Delay Restart/Reset† used (which pauses calls). Otherwise, the call to the secondary number
#+12 = AAV and Exit Delay by the communicator after the alarm report will prevent the AAV from
Restart/Reset taking control of the telephone line, and the AAV “Listen in” session
cannot take place.
V20PSIA/V15PSIA: UL: for AAV, must use Honeywell AVS system; Exit Delay
Entry 1 Options: Same as above. Restart/Reset must be disabled
Entry 2 Call Waiting Disable:
0 = call waiting not used SIA Guidelines: Exit Delay Restart/Reset should be enabled.
1 = use call waiting disable digits † “Exit Delay Restart/Reset” option allows use of the [∗] key to restart
(∗70) entered in field ∗40; (when the exit delay at any time when the system is armed STAY or
selected, the system dials the INSTANT. This feature also enables automatic exit delay reset, which
entry in ∗40 only on alternate dial resets exit delay if the entry/exit door is re-opened and closed before
attempts; this allows proper exit delay time expires after arming AWAY. Automatic Exit Delay Reset
dialing in case call waiting occurs only once during an armed AWAY period.
service is later canceled by the
user).

∗92 Phone Line Monitor Enable [0,0]


Entry 1::
0 = disabled, 1-15 = 1 min - 15 min 1 2
(#+10 = 10 min; #+11 = 11 min; Entry 1: Sets the length of time a phone line fault must remain after
#+12 = 12 min; #+13 = 13 min; detected before the second digit option is activated.
#+14 = 14 min; #+15 = 15 min) Entry 2: Selects the desired phone line fault response.
Entry 2: Option 2 may be used even if a relay unit or Powerline carrier device is
0 = Keypad display when line is faulted not connected to the control.
1 = Keypad display plus keypad trouble Programmed Output Device must either be programmed to be
sound. Each partition turns off its STOPPED in field ∗80 or STOPPED by entry of [security code] + [#] + 8
own trouble sound. No automatic + device number. Partition in ∗80 should be set to “0,” for STOP.
timeout. UL: Field *92 must be enabled for fire alarm installations, UL commercial
2 = Same as “1”, plus programmed burglar alarm installations and UL residential burglar alarm installations.
output device STARTS. If either If the control unit is used on a UL commercial burglar alarm system which
partition is armed, external sounder requires 2 methods of remote communication, then the control unit’s DACT
activates also. External sounder and the other method of signal transmission must monitor each other against
will be turned off by normal bell communication failure and line fault. The fault must be received and
timeout, or by security code plus annunciated within 200 seconds of its occurrence.
OFF from either partition (it need
not be the one that was armed).

– 12 –
∗93 Reports In Armed Period Per [V20P/V15P = 1,0; V20PSIA/V15PSIA = 2,0]
Zone (Swinger Suppression) Restrict V20PSIA/V15PSIA
Restrict Report Pairs: Report Pairs Unlimited Reports Enable
0 = Unlimited Reports
1 = 1 report pair per zone per armed Selection limits the number of alarm/alarm restore message pairs per
period zone sent to the CS in an armed period.
2 = 2 report pairs per zone per armed Swinger suppression applies to burglary zones only.
period
NOTE: The zone is automatically bypassed after the programmed
V20PSIA/V15PSIA: number of alarms is triggered.
Restrict Report Pairs: SIA Guidelines: Must be set for option 2
1 = 1 report pair; 2 = 2 report pairs
Unlimited Reports Enable:
0 = restrict reports to the setting in
entry 1
1 = unlimited reports for zones listed
in zone list 7; (use zone list 7 to
enter those zones that require
unlimited reporting; these zones
ignore the setting in entry 1)

DOWNLOAD INFORMATION (✱94, ✱95)


∗94 Download Phone No. | | | | | | | | | | | | | | | | | | |
Enter up to 20 digits, 0–9; #+11 for '✱';
#+12 for '#'; #+13 for a 2-second pause. Enter the phone number of the downloading computer.
Do not fill unused spaces. If fewer than UL: downloading may be performed only if a technician is at the site.
20 digits, exit field by pressing ✱. To Up/downloading via the Internet has not been evaluated by UL.
clear entries from field, press ✱94✱.
∗95 Ring Count For Downloading [15]
0 = Disable Station Initiated Download;
1–14 = number of rings (1–9, # +10 =10, Refer to the chart below and program accordingly.
# +11 =11, # +12 =12, # +13 =13, phone answer down-
# +14 =14); module machine loading Set field ∗95 to…
15 = answering machine defeat yes no no 1-14 (not 0)
(# +15 =15). yes yes no greater than rings set on answer machine
(e.g., if ans. machine is 4 rings, set this
NOTE: Do not enter 0 if using 4286 field to 5). This allows access to the
Phone Module. phone module if the answer machine is
off.
yes no yes 1-14 (not 0)
yes yes yes 15 (bypasses answer machine†)
no no no 0
no yes no 0
no no yes 1-14
no yes yes 15
† NOTE: If “15” is entered to bypass an answering machine, and a 4286
Phone Module is included in the system, you should note the following:
When calling in from an off-premises phone, the user should make the initial
call, allow 1 or 2 rings only, then hang up, then call again. The phone module
will now seize the line, and 2 long tones sound, followed by the usual voice
prompt for the access code. If this procedure is not followed, phone module
operation will not be possible.

∗96, ∗97 Initialize/Reset Defaults (These are commands, not data fields. See page 3.)
∗98, ∗99 Exit Commands (These are commands, not data fields. See page 3.)

PAGER OPTIONS (✱160- ✱172)


The system can send various reports to several pagers (VISTA-20P = up to 4; VISTA-15P = up to 2).
To program pager reporting, do the following:
1. Enter the pager phone number(s), preface characters, and pager report options in data fields *160 - *171.
2. Enable Pager Delay, if desired, in field *172 (delays alarm reporting for ALL pagers).
3. Make sure appropriate user open/close pager reports are enabled (see Security Codes section in User Guide). Users that
perform actions in partition 1 will, if enabled, attempt to report to all pagers enabled for open/close reporting in partition 1.
Users that perform actions in partition 2 will, if enabled, attempt to report to all pagers enabled for open/close reporting in
partition 2.
4. If using latchkey pager report, define the latchkey report schedule using Scheduling mode (master code + [#] [6] [4] then
select event type 03). System must be armed for the Latchkey report to be sent.
5. If using a function key to manually send a message to a pager, use *57 Function Key Menu mode to define the key
(function 01).
6. If reporting zone alarms and troubles to a pager, use *81 Zone List menu mode to assign the zones associated with each
pager (zone lists 9-12†).
† VISTA-15P supports zone lists 9 and 10 only.

– 13 –
∗160 Pager 1 Phone No. | | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9
#+11 = '✱' If entering fewer than 20 digits, exit by pressing [∗] + next field number.
#+12 = '#' To clear entries, press ∗160∗.
#+13 = 2-second pause
∗161 Pager 1 Characters | | | | | | | | | | | | | | |
Enter the optional prefix characters, up
to 16 digits. Up to 16 optional characters may be sent as a prefix to the 7-digit
0–9 system status code sent to Pager #1 (if used). Phone number in field
#+11 = '✱' *160 must have been entered. If fewer than 16 characters, exit by
#+12 = '#' pressing [∗] and next field number. To clear entries: press ∗161∗.
#+13 = 2-second pause The 16 characters may be composed of the following:
PIN number, Subscriber account number,
∗ character, # character, 2-second pause,†
Display Example 1. 9 1 1 – 1 0 0 4 special character(s) the user may decide to transmit
Indicates an alarm (911) caused by a † Some paging systems require pause(s) before the prefix.
fault in zone 4 (0004) in part. 1. The Pager format for the 7-digit status code is defined as follows: XXX-
YYYY where:
Display Example 2. 1 0 2 – 2 0 0 5 XXX = 3-digit event code: 911 = Alarm, 811 = Trouble, 101 =
Indicates the system is reporting a Opening (disarm), 102 = Closing (arm AWAY)
closing–system arming (102) by User YYYY = 4-digit user or zone number (depending on type of event).
5 (0005) in partition 2. The first digit indicates partition (0 = system, 1 = part 1, 2 =
part 2, 3 = common), followed by the 3-digit user or zone
number.
∗162 Pager 1 Report Options [0,0,0]
0= no reports sent
P1 P2 comm
1= Opens/closes all users† For each partition, select from the listed options.
4= All alarms and troubles
5= All alarms / troubles, and † For users enabled for paging. Reports to pager only when arming
opens/closes for all users (close)/disarming (open) from a keypad using a security code; auto-
12 = Alarms / troubles for zones arming/disarming, arming with assigned button, and keyswitch arming
entered in zone list 9 do not send pager messages.
13 = Alarms / troubles for zones
entered in zone list 9, and
opens/closes for all users
∗163 Pager 2 Phone No. | | | | | | | | | | | | | | |
See field ∗160 for entries.
If entering fewer than 20 digits, exit by pressing [∗] + next field number.
To clear entries, press ∗163∗.
∗164 Pager 2 Characters | | | | | | | | | | | | | | |
See field ∗161 for entries.
If fewer than 16 characters, exit by pressing [∗] and next field number.
To clear entries, press ∗164∗.
∗165 Pager 2 Report Options [0,0,0]
See field *162 for reporting options.
P1 P2 comm
Select for each partition (use zone list 10 for options 12 or 13)

∗166 Pager 3 Phone No. | | | | | | | | | | | | | | | | | | |


See field ∗160 for entries. If entering fewer than 20 digits, exit by pressing [∗] + next field number.
To clear entries, press ∗166∗
∗167 Pager 3 Characters | | | | | | | | | | | | | | |
See field ∗161 for entries. If fewer than 16 characters, exit by pressing [∗] and next field number.
To clear entries, press ∗167∗.
∗168 Pager 3 Report Options
P1 P2 comm
[0,0,0]
See field *162 for reporting options.
Select for each partition (use zone list 11 for options 12 or 13).
∗169 Pager 4 Phone No. | | | | | | | | | | | | | | | | | | |
See field ∗160 for entries. If entering fewer than 20 digits, exit by pressing [∗] + next field number.
To clear entries, press ∗169∗.
∗170 Pager 4 Characters | | | | | | | | | | | | | | |
See field ∗161 for entries. If fewer than 16 characters, exit by pressing [∗] and next field number.
To clear entries, press ∗170∗.
∗171 Pager 4 Report Options
P1 P2 comm
[0,0,0]
See field *162 for reporting options.
Select for each partition (use zone list 12 for options 12 or 13).

– 14 –
∗172 Pager Delay Option For Alarms [3]
0 = none
1 = 1 minute This field determines the delay of alarm reports to the pager. This gives
2 = 2 minutes the Central Station enough time to verify the alarm report it received
3 = 3 minutes before the dialer attempts to dial the pager.
This delay is for ALL pagers in the system.
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
∗174 Clean Me Reporting Options [0]
0 = disable
1 = Clean Me signal reports For ESL smoke detectors
This is a maintenance feature for ESL 2-wire smoke detectors on Zone
1. If used, this option limits the number of smoke detectors to a
maximum of 10, rather than 16. To enable the “clean me” feature, a
time response setting of “3” (1.2 seconds) must be entered in ∗56 Zone
Programming for zone 1.
NOTE: If Clean Me is enabled, you must enter “3” in field ∗56
programming for zone 1 response time.
∗177 Device Duration 1, 2 [0] [0]
0 = 15 secs 6 = 2-1/2 min #+11 = 7 min
1 = 30 secs 7 = 3 min #+12 = 8 min 1 2
2 = 45 secs 8 = 4 min #+13 = 10 min (used in *80 Menu mode-Device Actions 5/6)
3 = 60 secs 9 = 5 min #+14 = 12 min These entries set the duration for output action options 5 (duration 1)
4 = 90 secs #+10 = 6 min #+15 = 15 min and 6 (duration 2) programmed in ∗80 Output Function Programming.
5 = 2 min

∗181 50/60 Hertz AC Operation [0]


0 = 60 Hz; 1 = 50 Hz
Select the type of AC power applied to the control (option is used for
Real-Time Clock synchronization)
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
(see Configurable Zone Type Worksheet following data field ∗199)
• The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90,
91]) based on the options selected.
• All configurable zone types can be programmed via the downloader. Zone types 90-91 can also be programmed from a
keypad using data fields *182-*185.
• IMPORTANT: Be careful when selecting combinations of options for configurable zone types. Contradictory options can
cause unpredictable results.
Configurable Zone Type Options
Auto Restore (entry 2): Faults on zones set for this option are cleared; restore messages sent upon restoral of faults.
Vent Zone (entry 2): Zones set for this option are ignored if faulted when arming the system, but are protected if the zone is later restored
(e.g., an open window can be ignored when arming, but if the window is later closed, it will be protected; opening the window again causes an
alarm.) NOTE: Vent zones are not for use in UL installations.
Bypass Disarmed (entry 4): Zones set for this option can be bypassed only while the system is disarmed.
Bypass Armed (entry 4): Zones set for this option can be bypassed when the system is armed.
Dial Delay (entry 6): Alarms on zones set for this option participate in dial delay central station reporting, if system dial delay enabled in field
*50.
Fault Delay (entry 6): Faults on zones set for this option are delayed by the time set in field *87. Do not use this option if using entry/exit
delay for this zone type.
Faults Display (entry 7): Selects how faults on zones set for this zone type are displayed.
Power Reset/Verification(entry 7): Selects whether the system resets power (when user enters code + OFF), and whether the system
performs alarm verification (see description for zone type 16 in Zone Type Definitions section) when a fault occurs on these zones.
Use Entry Delay (entry 8): Selects whether to use the system’s entry delay times.
Use Exit Delay (entry 8): Selects whether to use the system’s exit delay time.
Interior Type (entry 8): Zones set for this option are treated same as standard zone type 4 (bypasses when armed STAY, faults displayed).
Alarm Sounds (entry 9): Selects the type of alarms sound for zones set for this zone type.
Bell Timeout (entry 9): Alarm sounding on zones set for this option remain for the duration set in fields *32 / *33.
Fire Zone (entry 9): Zones set for this option respond in the same manner as if programmed for zone type 9. Do not set fire zones to respond
as a “fault” in entries 1-6.
Trouble Sounds (entry 10): Selects the type of trouble sounds for zones set for this zone type (periodic beeps = once every 30 seconds;
trouble beeps = rapid beeping).
Chime Enable (entry 10): Zones set for this option cause a chime when Chime mode is on.

– 15 –
∗182 Configurable Zone Type 90
(0-9, #+10=10, #+11=11, #+12=12,
#+13=13, #+14=14, #+15=15). 1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts
provided in the Configurable Zone Type Worksheet section. Each entry
is the sum of the values of its selected options
To calculate the value for each entry, add the values of the selected
options in each of the entry’s columns shown in the respective chart
(one option per column). For example, to program entry 2 for “alarm
response to short,” “auto restore on,” but not a “vent zone,” enter 5 (“1”
for alarm short + “4” for auto restore-yes + “0” for vent zone-no).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.

∗183 Zone Type 90 Report Codes Enter the desired 3-digit Contact ID® report codes for alarms and
90 ALARM ID: XXX troubles occurring on zones assigned to this zone type. Enter the
TROUBLE ID: XXX codes sequentially (all 6 digits). When entering digits, [#] moves cursor
back, [∗] moves forward.
Press [∗] when done to continue. Important Notice on Report Codes: To avoid confusion at the central
NOTE: Zone alarm report codes and station, it is recommended that existing Contact ID® codes be used
trouble report code (∗60) and relevant with configurable zone types whenever possible. Check with the central
restore codes must be enabled in order station for a complete list of Contact ID® report codes. If none of the
to report configurable zone type codes. codes are suitable, choose a code in the reserved range of 750-789
and make sure to define the code with your central station.
∗184 Configurable Zone Type 91
(0-9, #+10=10, #+11=11, #+12=12,
#+13=13, #+14=14, #+15=15). 1 2 3 4 5 6 7 8 9 10
See ∗182 for entries.
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.

∗185 Zone Type 91 Report Codes See ∗183 for entries.


91 ALARM ID: XXX
TROUBLE ID: XXX
∗188 Keypad Lockout [1]
0 = disable
1 = enable If enabled:
• The system locks out the keypad for 15 minutes if 30 keystrokes are
Alpha keypad display: made without a valid user code being detected.
Line 1 “User Code Error:” (30 keystrokes = 6 attempts of code + command)
Line 2 “Keys 0-9 Locked” • While locked out, the message "User Code Error" is displayed on
Fixed Glass keypad display: alpha keypads in the partition that is locked out.
“CE” (Code Error) • Upon lockout, a message is transmitted to the central station
(Contact ID event 461 Wrong Code Entry), as well as being logged in
the event log.
• When the 15-minute lockout window expires, a Restore message is
sent to the Central Station and entered into the Event Log.
• Lockout perid ends and the display clears when lockout time expires,
or an alarm occurs, or entry delay begins.
If disabled:
• The “Wrong Code Entry” (event 461) message is added to Event Log.
• No report is sent to the central station.
• No message is displayed on the keypad.
• No restore event is entered in the event log.

– 16 –
∗189 AUI Device Enables [1, 1, 0, 0]
(for TouchScreen Style Keypads)
AUI 1 AUI 2 AUI 3 AUI 4
VISTA-20P: System supports touchscreen style keypads (e.g., 6280, Tuxedo
For Touchscreen device usage Touch; V20P = up to 4; V15P = up to 2).
0 = disable NOTE: Use of touchscreen style keypads does not affect the number of
1 = partition 1 standard keypads supported.
2 = partition 2
To enable a touchscreen keypad, enter the option corresponding to
3 = partition 3 (common)
each touchscreen’s home partition.
For Remote Services device usage
5 = part. 1 (auto-stay arm disabled) Note for Remote Services Devices: If using the Remote Services
6 = part. 2 (auto-stay arm disabled) feature of the communication device, select an option 5-7, depending
7 = part. 3 (common; auto-stay arm on the partition the Remote Services device is associated with (these
disabled) options automatically disable auto-stay arming when the system is
armed from the respective Remote Services device). Refer to the
VISTA-15P: communication device’s installation instructions for details on enabling
For Touchscreen device usage the Remote Services feature.
0 = disable
1 = enable Note for Remote Services Device Address: Using an AUI device
For Remote Services device usage address for Remote Services provides enhanced remote services
5 = part. 1 (auto-stay arm disabled) features, but an actual AUI device cannot use the same address. If no
AUI addresses are available (all four AUIs are being used), Total
Device Addresses: Connect 2 cannot be used for remote services. However, Total
Touchscreen device 1: Must set to 1 Connect 1 can be used by choosing an available standard keypad
Touchscreen device 2: Must set to 2 address and using the appropriate keypad address field *190 - *196 to
Touchscreen device 3: Must set to 5 select the Remote Services operating partition (some remote access
Touchscreen device 4: Must set to 6 features will be unavailable).

KEYPAD OPTIONS *190-*196


To enable keypads:
1. Set desired address at keypad (refer to keypad’s instructions for setting the address).
2. Use data fields *190-*196 to enable keypad addresses, assign a partition, and enable sound options.
3. Use fields *197, *198, and *199 to turn on partition number display, exit time interval display, and select fail display mode.
4. Set keypad-related data fields as appropriate: *21 Quick Arm Enable, *23 Forced Bypass, *84 Auto STAY Arm
NOTES: 1. Options for keypad 1, address 16, are set by the factory and cannot be changed.
2. Each keypad must be assigned a unique address. Keypads programmed with the same address will give
unpredictable results.

∗190 Keypad 2 Device Address 17 [1] [0]


Entry 1: Partition/ Enable Partition/ Sound
VISTA-20P: Enter partition in which the Enable
keypad is located where:
Entry 1 - Partition/Enable: Enter the desired option for the keypad’s
For Standard keypad usage home partition.
0 = disable
1 = partition 1
2 = part. 2 Note for Remote Services Devices: If using the Remote Services
3 = part. 3 (common) feature of the communication device, select an option 5-7 (option 5 for
VISTA-15P), depending on the partition the Remote Services device is
For Remote Services device usage associated with (these options automatically disable auto-stay arming
5 = part. 1 (auto-stay arm disabled) when the system is armed from the respective Remote Services
6 = part. 2 (auto-stay arm disabled) device). Refer to the communication device’s installation instructions
7 = part. 3 (common; auto-stay arm for details on enabling the Remote Services feature.
disabled)
VISTA-15P: Entry 2 - Sound: Enter the desired sound option for this keypad.
For Standard keypad usage
0 = disable
1 = enable
For Remote Services device usage
5 = auto-stay arm disabled
Entry 2: Sound
0 = no suppression
1 = suppress arm/disarm and Entry/Exit
beeps
2 = suppress chime beeps only
3 = suppress arm/disarm, Entry/Exit,
and chime beeps
∗191 Keypad 3 Device Address 18 [1] [0]
See field ∗190 for entries. Part./ Enable Sound

∗192 Keypad 4 Device Address 19 [1] [0]


See field ∗190 for entries. Part./ Enable Sound

– 17 –
∗193 Keypad 5 Device Address 20 [1] [0]
See field ∗190 for entries. Part./ Enable Sound

∗194 Keypad 6 Device Address 21 [1] [0]


See field ∗190 for entries. Part./ Enable Sound

∗195 Keypad 7 Device Address 22 [1] [0]


See field ∗190 for entries. Part./ Enable Sound

∗196 Keypad 8 Device Address 23 [1] [0]


See field ∗190 for entries. Part./ Enable Sound

∗197 Exit Time Display Interval [0]


0 = no display
1-5 = seconds between display refresh If enabled, keypads display the exit time remaining after arming the
system, updated at the interval selected (i.e. if the exit delay is 30
TOUCH SCREEN DEVICE NOTE: If seconds and “2” is selected in this field, the keypad display refreshes
using more than one touch screen device every 2 seconds, displaying 30, 28, 26, 24, etc.).
(e.g., 6280, Tuxedo Touch) with the An interval greater than “1” may be necessary for some older keypads
system, leave field *197 Exit Time to allow users time to enter key presses between display updates.
Display Interval set to the default value
“0.” The 6280 automatically displays NOTE: If enabled and using only 2-digit fixed-word keypads (e.g.,
remaining exit time in one-second 6150RF), do not set exit delay time greater than 96 seconds. Using a
increments. longer delay time may cause end-user confusion because 2-digit
display keypads cannot display times greater than “99.” If longer exit
time is required by the installation, it is recommended that the Exit
Time Display option be disabled (“0”).

∗198 Display Partition Number [0] (VISTA-20P; for Alpha Display Keypads)
0 = no If selected, the partition number is displayed in the upper-left corner of
1 = yes (part. no. appears on display) the alpha display. This is useful when using the GOTO partition function.
∗199 ECP Fail Display [0]
0 = 3-digit display
“1” + device address) Select “0” if using Alpha keypads and/or 3-digit Fixed-Word Display
1 = 2-digit fixed-display as “91 keypads. ECP faults will display “1” plus the device address (00-15) of
device causing the fault (e.g., faults on device 07 display as “107”).
Select “1” if using 2-digit Fixed-Word Display keypads (e.g., certain
6128 series keypads). If selected, ECP faults for all devices will display
as “91” on 2-digit displays, and “191” on 3-digit or Alpha keypads.

– 18 –
CONFIGURABLE ZONE TYPES WORKSHEET
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-
*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for
zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields
*183 and *185 to program Contact ID report codes for these zone types.

ENTRY 1 (See note 5 for RF zones) ENTRY 2 (See note 5 for RF zones) Entries for Fields *182 and *184
Response when system disarmed and zone is: Auto Entry Zone Type 90 Zone Type 91
Intact EOL Open Shorted Restore Vent Zone (field *182) (field *184)
RF zone normal RF zone N/A RF zn off-normal 1
0 = normal 0 = normal 0 = normal 0 = no 0 = no 2
1 = alarm 4 = alarm 1 = alarm 4 = yes 8 = yes
2 = trouble 8 = trouble 2 = trouble 3
3 = fault 12 = fault 3 = fault 4
see note 6 5
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone 6
ENTRY 3 (See note 5 for RF zones) ENTRY 4 (See note 5 for RF zones) 7
Response when armed STAY and zone is: Byp. when Byp. when 8
Intact EOL Open Shorted disarmed armed 9
RF zone normal RF zone N/A RF zn off-normal 10
0 = normal 0 = normal 0 = normal 0 = no 0 = no
1 = alarm 4 = alarm 1 = alarm 4 = yes 8 = yes To calculate the value for each entry:
2 = trouble 8 = trouble 2 = trouble Simply add the values of the selected options
3 = fault 12 = fault 3 = fault in each of the entry’s columns (one option per
see note 6 column). For example, to program Entry 2 for
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed “alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
ENTRY 5 (See note 5 for RF zones) ENTRY 6 (See note 5 for RF zones) short + “4” for auto restore yes + “0” for vent
Response when armed AWAY and zone is: Dial Delay Fault Delay zone no).
Intact EOL Open Shorted (see field *50) (see field *87)
RF zone normal RF zone N/A RF zn off-normal
0 = normal 0 = normal 0 = normal 0 = no 0 = no
1 = alarm 4 = alarm 1 = alarm 4 = use delay 8 = use delay
2 = trouble 8 = trouble 2 = trouble
3 = fault 12 = fault 3 = fault see note 1
see note 6 INTACT OPEN SHORTED
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay EOL
ZONE-003-V0

ENTRY 7 ENTRY 8 Zone Conditions Represented


in Entries 1-6
Display Faults Power Reset/ Use Entry Use Exit Respond as
Verification Delay 1/2 Delay Interior Type NOTES:
0 = show alarms 0 = no 0 = no 0 = no 0 = no 1. Fault Delay: Do not use the “Fault Delay”
when armed 4 = power reset 1 = delay 1 4 = use exit 8 = yes option with a configurable zone type if it is
& disarmed after fault 2 = delay 2 delay set for an entry or exit delay, otherwise
1 = don’t show (by code + OFF) see note 2 unpredictable results may occur.
alarms when 12 = verification Fault Delay applies only to alarms and
armed (show (see zone troubles.
alarms, trbles, type 16)
faults when
2. To create an interior type zone, select
disarmed) “respond as interior zone type” (entry 8,
3 = never show interior type = yes), and set zone
any alarms, response to “fault” in entries 3-4 to ensure
trbles, faults fault displays; do not set as “normal,”
Entry 7 = fault display + power Entry 8 = entry delay 1/entry delay 2 + exit delay + “alarm,” or “trouble.”
reset/verification interior zone type 3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
ENTRY 9 ENTRY 10 not display unless the [∗] key is pressed.
Alarm Sounds Use Bell Respond as Trouble Chime when 4. 4219/4229 modules must use EOLRs or
Timeout Fire Zone Sounds Chime Mode On unpredictable results may occur.
0 = none 0 = no 0 = no 0 = none 0 = no 5. RF Zones: The “open” option in entries 1,
1 = steady 4 = yes 8 = yes 1 = periodic 4 = yes 3, and 5 is not applicable for RF zones.
keypad beep Use the “intact EOL” option for normal RF
2 = steady bell see fields *32, see zone type 2 = trouble zone conditions and “shorted” for off-
and keypad *33 09; see note 4 beeps normal RF zone conditions.
3 = pulsing bell 6. a. Zone-Doubling/Double-Balanced: A
and keypad short on either zone of a zone-doubled
Entry 9 = alarm sounds + bell timeout + fire zone Entry 10 = trouble sounds + chime pair or on a double-balanced zone
causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones, both zones
of the doubled pair must be assigned
the same response to a short.

– 19 –
∗56 ZONE PROGRAMMING MENU MODE
(press *56 while in Program mode) The Zone Programming Worksheet is on page 43.
Zones and Partitions
Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or ✱58 Expert
Programming Mode. Using this mode, enter the zone number to be programmed and make appropriate entries at the
prompts. Finally, Confirm the serial number of wireless transmitter zones.
The VISTA-20P system can control two independent areas of protection (known as partitions) for use by independent users, if
desired, by simply assigning zones to one or the other partition during zone programming. The VISTA-20P, by default,
automatically distributes users between the two partitions. The master user can change the user number distributions.
Zones can also be assigned to a common partition, which is an area shared by users of both partitions (such as a lobby in a
building). This allows either partition to arm, while leaving the common partition disarmed for access into the other partition.
The following describes the functioning of the VISTA-20P common partition:
• The common zone sounds and reports alarms only when both partitions are armed. If only one partition is armed, the
system ignores faults on the common zone.
• Either partition may arm its system if the common zone is faulted, but once armed, the other partition will not be able to arm
unless the common zone is first bypassed or the fault is corrected.
• Faults on the common zone are displayed on common zone keypads, and will also appear on another partition’s keypad
when that partition is armed.
• Either partition can clear and restore the common zone after an alarm.
∗56 Menu Mode
PROMPT VALID ENTRIES EXPLANATION
Confirm? This display appears upon entry into this mode.
SET TO CONFIRM?
0 = no The default is 0 (No).
0 = NO 1 = YES 0
1 = yes If 1 (Yes) is entered, you will be prompted to confirm each
[∗] to continue transmitter after entering the serial and loop numbers (at the
“XMIT TO CONFIRM” prompt later).
Enter Zn Num. Zone Number Enter the zone number that you wish to program. Zone 10 has
(00 = Quit) 10 VISTA-20P: been entered in the example display at left.
wired 01-08 (and 09-48†); Enter a report code for zone 91 to enable addressable device
wireless 09-48; RF button reporting.
zones 49-64 Enter a report code for zone 92 to enable duress reporting.
VISTA-15P: 95, 96, 99 are emergency (panic) key zones.
wired 01-06 (and 09-24†);
wireless 09-34; RF button † if zone expanders are used.
zones 49-56
Both Controls:
91 = addr. device report enable
92 = duress report enable
95, 96, 99 =emerg. zones
[∗] to continue
00 to quit

Zn ZT P RC In: L Summary Screen “IN: L” appears for wireless zones and indicates input type and
[∗] to continue loop.
10 00 1 10 RF: 1 “IN: AD” appears for hardwire expansion zones (AW) and
indicates the module’s address (AD), which is based on the
zone number.
“HW: RT” appears for hardwire zones and indicates
configuration (EOL, NO, NC, zone doubling, double-balanced)
and response time selection.
10 Zone Type Zone Type (ZT) Each zone must be assigned to azone type, which defines the
Perimeter 03 See table at right. way in which the system responds to faults in that zone. Enter the
Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used 07 = 24-Hr Audible 20 = Arm–STAY*
01 = Entry/exit #1 08 = 24-Hr Aux 21 = Arm–AWAY*
02 = Entry/exit #2 09 = Fire 22 = Disarm*
03 = Perimeter 10 = Interior w/Delay 23 = No Alarm Resp
04 = Interior Follower 12 = Monitor Zone 24 = Silent Burglary
05 = Day/Night 14 = Carbon Monoxide 77 = Keyswitch
06 = 24-Hr Silent 16 = Fire w/Verify 81 = AAV Mon. Zone
*5800 button-type transmitters only

Partition No. (P) Enter the Partition number for this zone. Partition 1 is shown
10 Partition
(VISTA-20P) entered.
1 1-3 = partition
(3 = common)
[∗] to continue

– 20 –
Report Code (RC) Enter the report code for this zone, which consists of 2
10 Report Code
First Digit: 1-9, 10 for 0, 11 for hexadecimal digits, each in turn consisting of 2 numerical digits.
1st 01 2nd 00 10 B, 12 for C, 13 for D, 14 for E, For example, for a report code of “10,” enter 01 and 00.
15 for F For Contact ID®, entering any non-zero entry as the first digit
00 to disable enables the report code for this zone.
Second Digit: same as above
[∗] to continue
02 HARDWIRE TYPE Hardwire Type This prompt appears only for zone numbers 02-08.
0 = EOL Zone 1 is automatically set for EOL operation.
EOL 0
1 = NC
2 = NO † VISTA-20P
3 = zone doubling (ZD) †;
4 = double-balanced (DB)†
[∗] to continue
Response Time (RT) Appears only for hardwire zones 01-08 (zone 02 is the display
02 Response Time
0 = 10mSec; shown).
1 1 = 350mSec Option 3: used for “clean me” option on zone 1 (see field ∗174).
2 = 700mSec NOTE: If zone doubling is being used, the response time
3 = 1.2 seconds selected for zones 02-08 automatically applies to each zone’s
[∗] to continue associated doubled zone.

Input Device type (In) This prompt is skipped for zones 2-8, or 2-16 if zone-doubling
10 INPUT TYPE
2 = AW (Aux wired zone) was enabled at “Hardwire Type” prompt.
RF TRANS 3 3 = RF (supervised RF All of the RF transmitters have one or more unique factory-
transmitter assigned input (loop) ID codes. Each of the inputs requires its
4 = UR (unsupervised RF own programming zone (e.g., a 5804's four inputs require four
transmitter) programming zones).
5 = Button type RF RF Transmitters can be enrolled as one of the following types:
transmitter Type Description
(unsupervised). RF Sends periodic check-in signals, as well as
(Supervised RF) fault, restore, and low-battery signals. The
[∗] to continue
trans. must stay within receiver's range.
UR Sends all the signals that the “RF” type
(Unsupervised RF) does, but the control does not supervise
the check-in signals. The transmitter may
therefore be carried off-premises.
BR Sends only fault signals. It will not send a
(Unsupervised low-battery signal until it is activated. The
Button RF) transmitter may be carried off-premises.
NOTE:
• For the built-in hardwired zones, the Input Device type is
automatically displayed as HW and cannot be edited.
• To change the input type of a previously programmed wireless
device (type RF, UR, BR) to a wired zone (type AW), you must
first delete transmitter’s serial number (see To Delete A Serial
Number prompt)

10 INPUT S/N: L Input Serial number and Enroll the transmitter’s serial number and loop number as
Loop Number follows:
A022-4064 1 1. a. Transmit two open/close sequences (for button-type trans,
[∗] to continue
Used only when enrolling press and release the button twice, waiting about 4 secs
wireless transmitters. before pressing the button the second time).
OR
b. Manually enter the 7-digit serial number printed on the label
of the transmitter. Press the [∗] key to move to the “L”
position, then enter the loop number.
Use the [A] (Advance) and [B] (Back) keys to move the
cursor forward and back within the screen. Pressing the [C]
(Copy) key will insert the previously enrolled serial number,
if desired (used when programming a transmitter with
several input loops).
To delete an existing serial number, enter 0 in the loop
number field. The serial number will change to 0's. If 0
was entered in error, simply re-enter the loop number or
press [#], and the serial number will return to the display.
2. Press [∗] to continue. The system now checks for a duplicate
serial/loop number.
If no duplicate is found, the display shows the serial number
and loop number.
3. Press [∗] to continue to confirmation screen.

– 21 –
Loop Number Change NOTE: If the [C] key is used to copy the previously enrolled
10 INPUT S/N L
[∗] to continue serial number, the cursor will move to the Loop column (L) with
A022-4064 ? the previous serial number displayed, and display a highlighted
question mark for the loop number.
Enter the loop number and press [✱]. The system will now
check for a duplicate serial/loop number combination.
Confirmation Option This prompt will only appear if you answered “Yes” at the first
XMIT TO CONFIRM
[∗] to continue prompt in this section.
PRESS ✱ TO SKIP The system will enter a confirmation mode so that the operation
of the actual programmed input can be confirmed.
Activate the loop input or button that corresponds to this zone.
Entd A022-4063 1 If Serial or Loop If the serial number transmitted does not match the serial
Numbers do not match number entered, a display similar to the one shown appears. If
Rcvd A022-4064 1 the loop number does not match, it will also be displayed.
after activating the
If so, activate the loop input or button on the transmitter once
transmitter again. If a match is not obtained (i.e., summary display does not
[∗] to continue appear), press the [#] key twice and then enter (or transmit) the
correct serial number.
To Delete a Serial No. To delete an existing serial number, enter 0 in the loop number
10 INPUT S/N: L
0 = delete serial number field. The serial number will change to 0's.
A000-0000 0 # = undo deletion If 0 was entered in error, simply re-enter the loop number or
[∗] to continue press [#], and the serial number will return to the display.

Summary Screen If the serial number transmitted matches the serial


Zn ZT RC In: L
[∗] to continue number entered, the keypad will beep 3 times and a
10 03 10 RF: 1s summary display will appear, showing that zone's
programming. Note that an “s” indicates that a
transmitter’s serial number has been enrolled.
Press [∗] to accept the zone information and continue.
Alpha Descriptors If you want to program descriptors for zones now, enter 1 (Yes)
PROGRAM ALPHA?
0 = no and refer to the ∗82 Descriptor Programming section for
0 = NO 1 = YES 0 1 = yes available descriptors.
[∗] to continue

Next Zone Number If 0 (No) was entered above, the system will return you to the
E N TE R Z N N U M.
[∗] to continue; ENTER ZN NUM. prompt for the next zone.
( 0 0 = Q U I T) 1 1 00 = quit When all zones have been programmed, enter 00 to quit

Completing Zone Programming


• When you have finished programming all zones, test each zone using the system’s TEST mode.
• Do not use the Transmitter ID Sniffer Mode for checking wireless transmitting devices, as it will only check for
transmission of one zone on a particular transmitter, NOT the zones assigned to each additional loop.

∗58 EXPERT ZONE PROGRAM MODE


(press ∗58 while in Data Programming mode)
This method is designed for use by installers with previous experience in programming HONEYWELL control panels. This
mode is also used to program wireless keys using pre-defined templates.

Confirm? Select whether you want confirmation of wireless device


SET TO CONFIRM?
0 = no; 1 = yes; [∗] to enrollment. (See “XMIT TO CONFIRM” prompt later in this
0 = NO 1 = YES 0 continue section.) We recommend that you confirm the programming
of every transmitter.
If 1 (Yes) is entered, you will be prompted to confirm each
transmitter after entering the serial and loop numbers (at the
“XMIT TO CONFIRM” prompt later).
Zn ZT P RC HW: Summary Screen A summary screen appears, showing zone 1’s currently
RT 01-64 = zone number; programmed values.
01 09 1 10 EL 1 [∗] to continue; Enter the zone number being programmed, then press [∗], which
00 = quit displays a summary screen for that zone and the cursor moves
[D] to go to prompts for to the Zone Type location. The cursor then automatically moves
wireless key programming to the next locations after each entry is made.
templates If programming a wireless key, press the [D] key then skip to
the Wireless Key Programming Templates section following this
section. When [D] is pressed, you can choose from a series of
preset templates for easy programming of wireless key zones.
When all zones have been programmed, press 00 at this prompt
to quit this menu mode.

– 22 –
Zone Programming A summary screen with the selected zone’s current
Zn ZT P RC IN: L
ZT = see Zone Type chart programming appears.
10 00 1 10 RF 1 shown in *56 Menu Begin programming zone information as follows:
Mode “Zone Type” • Enter Zone Type (ZT), Partition (P), Report Code (RC; 0-9
prompt only; use *56 mode to enter hex codes), and Input Device
P = partition 1, 2, 3 Type (IN)* sequentially, but not the Loop No. (L).
(common); • Use the [A] (Advance) and [B] (Back) keys on the keypad to
RC = 1 (send CID report); 0 move the cursor within the screen.
(no report) • Use the [C] key to copy the previous zone’s attributes.
IN = input type;
L = loop number Press [✱] to save the programming and continue to the serial
number/loop number prompt. If needed, you can press the [#]
[∗] to continue
key to back up without saving.
* If HW (hardwired) or AW (Auxiliary) is entered for Input Device
Type, the next screen will be similar to the prompt shown, except
that HW or AW will be displayed under “IN”.
If RF, BR, or UR is entered, a prompt for Serial and Loop
number will be displayed, as described in ∗56 Menu mode
section.
When done, the display returns to the initial summary screen
prompt to let you program the next zone.
To exit this mode, enter 00 at the Summary Screen prompt.

WIRELESS KEY PROGRAMMING TEMPLATES


(press the [D] key from *58 Menu mode Summary Screen)
This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user
number (see System Operation section, Assigning Attributes Command in the User Guide).

TEMPLATE ? Template Number • Enter Template number 1–6 (see chart on next page).
1–6 = templates See the defaults provided for each template in the chart that
1–6 1 follows these procedures.
• Select from templates. Press [∗] to display template (1
shown selected).
NOTE: If necessary, press [#] to back up and re-enter
template number.
• Press [#] if you want to return to *58 Menu mode summary
screen.

L 01 02 03 04 Template Display • When [∗] is pressed, the selected template will be displayed.
Top line of display represents loop numbers; bottom line
T 23 22 21 23 represents zone type assigned for each loop.
• Press [∗] to accept template.

PARTITION Partition • Enter the partition in which the key is to be active, then press
VISTA-20P. 1 = partition 1; [∗] to continue.
1 2 = partition 2

ENTER START ZONE Start Zone Number • The system will search for the highest available consecutive
4-zone group (the four zones in the case of the 5804BD), and
00 = QUIT 36 display the lowest zone number of the group.
If you want to start at a different zone, enter the zone desired,
and press [✱]. If that zone number is displayed, the system
has the required number of consecutive zones available,
beginning with the zone you entered. If not, the system will
again display a suggested zone that can be used.
If the required number of consecutive zones is not available
at all, the system will display “00”.
To quit this mode and return to *58 Menu mode, enter 00 at
this prompt.
• Press [∗] to accept.

INPUT S/N L Serial Number • Manually enter the serial number printed on the label for the
wireless key or press and release the button to transmit its
AXXX-XXXX – serial number.
• Press [∗] to accept the serial number. The system will check
for a duplicate.
• If necessary, press the [#] key to back up without saving, and
re-enter the serial number.
• Use the [A] key to move forward within the screen, and the
[B] key to move backward.

– 23 –
XMIT TO CONFIRM Confirm • If “Yes” was entered at the SET TO CONFIRM? prompt
[∗] to continue previously (see first prompt following entry into the ∗58
PRESS ✱ TO SKIP Expert Programming Mode), the display on the left will
appear. Confirm serial and loop numbers by activating the
wireless key.
IMPORTANT:
When confirmed, the key is not active for arming/disarming until
it is assigned to a user number (using the assigning attributes
command, attribute “4”). See System Operation section for
procedure.
Not Confirmed If the serial number transmitted does not match the serial
Entd A022-4063
[∗] to continue number entered, a display similar to the one shown will appear.
Rcvd A022-4064 If the loop number does not match, it will also be displayed.
If so, activate the button on the wireless key once again. If a
match is not obtained (i.e., summary display does not appear),
press the [#] key and then enter the correct serial number.
If the serial number transmitted matches the serial number
entered, the keypad will beep 3 times and will return you to the
Zone Number prompt to enter the starting zone for the next
wireless key.
Or you can return to *58 Menu mode by pressing 00 at the Zone
Number prompt.

Wireless Key Predefined Default Templates


SERIAL #2 GREEN/YELLOW
LOOP 1 LED LOOP 2
SERIAL #1 SERIAL #1
LOOP 3 LOOP 2

RED/YELLOW
LED
SERIAL #2 SERIAL #2 LOOP 4
LOOP 3 LOOP 4

LOOP 3

SERIAL #1 SERIAL #1
LOOP 4 LOOP 1 LOOP 1
••
••
• • • ••
•• • •• • ••
••
ENROLL AS "BR" 5804BD-007-V1
SERIAL #2
LOOP 2 5834-013-V0

5804BD 2-Way Wireless Key


5834-4 Wireless Key Transmitter
Transmitter

NOTE: Some transmitters are not intended for use in UL installations.


For Button-Type Devices For Button-Type Devices
TEMPLATE 1 Loop Function Zone Type TEMPLATE 4 Loop Function Zone Type
1 No Response 23 1 No Response 23
2 Disarm 22 2 No Response 23
3 Arm Away 21 3 Arm Away 21
4 No Response 23 4 Disarm 22
TEMPLATE 2 Loop Function Zone Type TEMPLATE 5 Loop Function Zone Type
1 No Response 23 1 No Response 23
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
TEMPLATE 3 Loop Function Zone Type TEMPLATE 6 Loop Function Zone Type
1 24-hour audible 7 1 24-hour audible 7
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22

Deactivating & Removing a Wireless Key from the System


Deactivate a wireless key by deleting the associated user code:
Delete the User Code: Master code + [8] + 2-digit user no. + [#] [0]
Remove a wireless key from the system by deleting one of the wireless key zones using Zone Programming mode:
1. Press *56 while in Program mode then enter a zone number assigned to the wireless key.
2. Scroll through each prompt by pressing [∗] until the Input S/N prompt appears.
3. Enter 0 for the loop number and press [∗].
4. Exit program mode.
– 24 –
∗57 FUNCTION KEY PROGRAMMING MENU MODE
(press ∗57 while in Data Programming mode) The Function Key Worksheet is on page 45.
The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The
end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions
(listed below) include single-button arming, turning lights on/off, or single-button paging.
To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for
“A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using ∗56 (or ∗58) Zone Programming mode, then use ∗57
Function Key menu mode to assign the desired key.
To use a function key to activate a relay action (∗57 Menu mode key function 07), use ∗79 Menu mode to map the output, and
use ∗80 Menu mode to define the output’s action; select system operation type “66.”
To use a function key for a user macro, use ∗57 menu mode to activate the desired key, then define the actual macro
functions using the user code + [#] + [6] [6] command.

Function Key Press the desired function key (A-D) you want to program.
Press Key to Pgm
Press the desired function NOTE: A key programmed as a function key is no longer
0 = Quit 0 key, A-D. available to be used as an end-user macro key or panic key.
[∗] to continue A 1 OFF 2 AWAY 3 STAY

0 = Exit this mode


B 4 MAX 5 TEST 6 BYPASS

keypad_keys-00-001-V0
C 7 INSTANT 8 CODE 9 CHECK

D 0 #
* READY

Partition Number Enter the partition in which the function key is active.
Partition
(VISTA-20P)
1
1 = partition 1
2 = partition 2
3 = common partition
[∗] to continue

Define Key Function Enter the desired function for this key, 00 to 12, from the options
Key "A" Func
00-12 = see list at right listed. (00 selected for example display shown at left). Press [∗]
Zone 95 00 [∗] to continue; returns to to returns to key number prompt with the next function key letter
key number prompt with the displayed.
next function key letter 00† = For the Function key selected, the functions are predefined as
displayed follows:
If A selected = Zone 95 (emergency key, same as [1] [∗] pair)
If B selected = Zone 99 (emergency key, same as [∗] [#] pair)
If C selected = Zone 96 (emergency key, same as [3] [#] pair)
If D selected = Single-button paging
01 = Single-button paging (sends a 999-9999 message to pager)
02 = Display time
03 = Arm AWAY (reports as User 00 if closing reports are enabled)
04 = Arm STAY (reports as User 00 if closing reports are enabled)
05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled)
06 = Step Arming (arms STAY, then NIGHT-STAY†††, then AWAY)
07 = Output Device Command (for device programmed as system
operation type 66–function key in *80 Menu Mode)
08 = Communication Test (sends Contact ID code 601)
09 = Macro Key 1 (define macro by user code + [#] [6] [6] command)
10 = Macro Key 2 (define macro by user code + [#] [6] [6] command)
11†† = Macro Key 3 (define macro by user code + [#] [6] [6] command)
12†† = Macro Key 4 (define macro by user code + [#] [6] [6] command)
† System defaults to these function key settings.
†† Macros 11-12 apply to VISTA-20P only.
††† If Night-Stay zones are listed in zone list 5

– 25 –
OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode)
Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices)
plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide
output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device
addresses.
The VISTA-15P supports 8 relays and 2 built-in trigger outputs (total 10 outputs).
Output Functions: The system also provides installer-defined output functions, which can be assigned to any of the
physical outputs. Therefore, the action of any one of the outputs can be based on as many of these
defined functions as desired. This lets a single relay or X-10 device perform many functions.
The control supports: V20P = up to 48 defined functions; V15P = up to 24 functions
Use *80 Menu Mode to define output functions.
WARNING: Relays and output devices are not recommended for life safety applications.
NOTE: When navigating the *79 and *80 menus: The [✱] key is used to accept an entry and advance to the
next prompt. The [#] key is used to revert back to the last question to check or change an entry. Press [✱] to
go forward again.
Programming Output Devices
1. Use *79 Menu Mode to assign module and output numbers and map them to device addresses.
NOTE: You must map output devices using *79 Menu Mode before you can use *80 menu Mode.
2. Use *80 Menu Mode to create output definitions, which control the output devices, if desired.
3. Use *81 Zone List Menu mode to define zone lists for use with output devices if the device action is based on more than
one zone.
• To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for scheduled automatic
activation, simply map the device using *79 Menu mode.
• To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map the device,
then use *80 Menu mode to define the automated device action.

∗79 RELAY/POWERLINE CARRIER DEVICE (X-10) PROGRAMMING MENU MODE


(press ∗79 while in Programming mode) The *79 Device Mapping Worksheet is on page 46.
Use this menu to assign Relay Module device addresses and specific relay numbers, and Powerline Carrier unit numbers. The
system is based on predefined module addresses for 4204 and 4229 modules. Refer to the table shown at the “Module
Address” prompt on the next page and set the modules’ addresses (via module DIP switches) accordingly.
The following table shows how these outputs are identified.
Output Identification
This output… is identified by…
Relays the Relay Module’s device address and the relay position on that module (i.e. the physical relay
number, 1-4, on that module).
X-10 Device a house ID (entered in data field *27) and the unit number of the device.
Built-in Outputs the output number assigned, 17 for Trigger 1 and/or 18 for Trigger 2.

ENTER OUTPUT NO. Device Output Number This is the logical (or reference) relay number as used in the
VISTA-20P: system. Relays and X-10 devices are numbered 01-16; the on-
00 = QUIT xx board triggers are numbered 17 and 18 and can be programmed
01-16 = relays/X-10
17, 18 = on-board triggers for inverted output, if required.
VISTA-15P:
01-08 = relays/X-10
17, 18 = on-board triggers
[∗] to continue
00 to quit
17 OUT NORM LOW Output Normally Low (prompt appears only if trigger 17 or 18 was selected above)
0 = no (standard default) Selecting 0 (no) sets the output level normally high (default
0 = NO 1 = YES 0 setting).
1 = yes
[∗] to continue Selecting 1 (yes) sets the output normally low.
Output Trigger 17 can be used for resetting 4-wire smoke
detectors† by connecting it to the negative power terminal of the
smoke detector, selecting 1 at this prompt, and setting as zone
type 54, fire zone reset, in *80 Menu mode.
After entry, display returns to Output Number prompt. Use *80
Menu mode to program the function of the trigger.
† Power Reset: This control does not automatically reset power
to 4-wire smoke detector zones, so you must use a relay (e.g.,
4204, 4229) or on-board trigger to reset power (also required
for fire verification).

– 26 –
XX OUTPUT TYPE Output Type Select whether this is a relay or a Powerline Carrier (X-10)
0 = delete device.
DELETE 0 If Powerline Carrier Device (X-10) is selected, go to “A” prompt.
1 = relay on 4204/4229
2 = Powerline Carrier Device If relay is selected, skip to “B” prompt.
[∗] to continue
“A” Unit Number (prompt appears if X-10 is selected)
01-16 = predefined address Enter the unit code (set at the device) and press [∗].
XX UNIT No.
[∗] to continue The system returns to the Output Number prompt.
yy

“B” Module Address (prompt appears if relay is selected)


07-15 = predefined address Enter the predefined address for this module as listed below.
XX MODULE ADDR Make sure the module’s DIP switches are set to the selected
[∗] to continue
07-15 yy address.
REMOTE SERVICES NOTE: If
using the communication device’s
Multi-Mode 4204 or 2-4204
Module Addresses
options, select one of the 4204 Address Module
addresses, though a physical 07 1st 4229 (with zones 09-16)
4204 module is not installed. If 08 2nd 4229 (with zones 17-24)
using 2-4204 multi-mode option, 09† 3rd 4229 (with zones 25-32)
the second 4204 address is 10† 4th 4229 (with zones 33-40)
automatically one number higher 11† 5th 4229 (with zones 41-48)
than the first address. Make sure 12 1st 4204
these addresses are not used by
13 2nd 4204
physical 4204 modules that may
be installed. See the 14† 3rd 4204
communication device’s 15† 4th 4204
instructions to enable Multi-Mode. † These addresses apply to VISTA-20P only.

XX REL POSITION Relay Position This is the actual (or physical) relay number with respect to the
1-4 = relay position Relay Module upon which it is located. For 4204 modules, relay
1-4 zz numbers are 1-4. For 4229 modules, relay numbers are 1-2.
[∗] to continue
The system returns to the Output Number prompt for
programming the next device.
REMOTE SERVICES NOTE: If using the communication device’s
multi-mode, program virtual 4204 relays to trigger on those
system events intended to be sent to the user’s email address.
(4204 option = up to 4 events; 2-4204 option = up to 8 events)

∗80 OUTPUT FUNCTION MENU MODE


(press ∗80 while in Programming mode) The Output Definition Worksheet is on page 47.
Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output
devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified
by an output function number, and includes the following components:
Output Definition Components
Component Description
Output Function No. A reference number that defines an output’s characteristics.
Activated By Determines whether the initiating event occurs on a zone, a zone list, or a zone type.
Event Event that triggers the output action. Can be an event occurring on a specific zone number or a zone list, or a
specific zone type.
Partition If the output is activated by zone type, this defines the partition in which the programmed event is to cause the
device action.
Output Action Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2 seconds, stay
closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle the device state, or
activate for a defined duration (set in data field *177).
Output No. Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output number that will
perform this function upon the triggering event. Note that each defined function is associated with only one
output number. This means that if more than one output device needs to perform this particular function, you
need to define another output function number with the same attributes, but assign the appropriate output
number. (i.e. output devices can be assigned more than one function number, but each function number can
only be assigned a single output number.
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as
programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt Entry
Output Funct. # = 01 (assuming this is the first output function)
Activated By: = 3 (zone number)
Enter Zn No. = 04 (requires 2-digit zone numbers)
Output Action = 3 (continuous pulse)
Output Number = 02 (device mapped in *79 Menu Mode)

– 27 –
80 Menu Mode
Output Function No. Enter the output function number to be defined (or 00 to exit)
Output Funct. #
(VISTA-20P: 01-48
(00 = Quit) 01 (VISTA-15P: 01-24)
[∗] to continue; 00 to quit
Summary Screen This screen displays a summary of the current output
01 A E P Trig
[∗] to continue programming (for this example, Zone List has been selected-this is
?00 0 0 – ZL=00 the default screen).
A = Output Action; E = Triggering event; P = Partition;
Trig = Trigger type
NOTE: A question mark in the summary screen indicates that the
device number shown has not been mapped. Use *79 Menu mode
to map the device.
Activated By Select where the initiating event for this output definition is to occur
01 Activated By:
0 = delete as follows:
Zone List 1 = zone list (go to “A”) If you enter “0,” the following prompt appears:
2 = zone type (go to “B”) Delete?
3 = zone number (go to “C”) 0 = NO, 1 = YES
[∗] to continue Press 1 to delete this output definition. The system deletes the
output function and any previous programming.
A” Zone List (prompt appears if zone list was selected)
01-08 = zone list Enter the desired zone list number associated with this output
01 Zn List
[∗] to continue number. At the ENTER EVENT prompt, enter the zone list event
1 that will activate this output
NOTE: Do not use pager zone lists 09-12 in output definitions.
Enter Event 0 = restore; 1 = alarm;
Alarm 1 2 = fault; 3= trouble
NOTE: For alarm, fault, and trouble, an event on ANY zone in the
list activates the output, but ALL zones in the list must be restored
before the output is restored.
Press [✱] to continue and skip to the “Output Action” prompt.
“B” Zone Type (prompt appears if zone type was selected)
See list at right for available Enter the desired zone type associated with this output number. At
01 Enter Zn type the PARTITION prompt, enter the partition in which this zone type
zone types.
Perimeter 03 will occur.
CHOICES FOR ZONE TYPES:
00 = Not Used 05 = Day/Night 12 = Monitor Zone
01 = Ent/Exit #1 06 = 24 Hr Silent 14 = Carbon Monoxide††
02 = Ent/Exit #2 07 = 24 Hr Audible 16 = Fire w/verification
03 = Perimeter 08 = 24 Hr Aux 23 = No Alarm Response
04 = Interior Follower 09 = Fire 24 = Silent Burglary
10 = Interior w/Delay 77 = Keyswitch Zone
81 = AAV Monitor Zone
90-91 = Configurable
CHOICES FOR SYSTEM OPERATION:
20 = Arming–Stay 36 = **At Bell Timeout*** 58 = Duress
21 = Arming–Away 38 = Chime 60 = AAV
22 = Disarming 39 = Any Fire Alarm 61 = AVS/GSMV4G session begin §
31 = End of Exit Time 40 = Bypassing 62 = AVS/GSMV4G session end §
32 = Start of Entry Time 41 = **AC Power Failure 66 = Function Key†
33 = Any Burglary Alarm 42 = **System Battery Low 67 = Bell Fail
43 = Comm. Failure 68 = Telco Line Cut
52 = Kissoff 78 = Keyswitch Red LED
54 = Fire Zone Reset 79 = Keyswitch Green LED
** Use 0 (Any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu Mode to assign the function key (function “07”).
†† when used with an output function, the carbon monoxide zone type
activates upon CO alarms only. Does not activate for trouble conditions.
§ automatically set when appropriate AVS Quick Command performed.
Note: In normal operation mode:
Code + # + 7 + NN Key Entry starts Device NN.
Code + # + 8 + NN Key Entry stops Device NN.
Enter the partition in which this zone type will occur.
01 Partition 0 = any partition; 1 = partition 1;
Any partition 0 2 = partition 2; 3 = common

Press [ ] to continue and skip to the “Output Action” prompt.

– 28 –
“C” Zone Number (prompt appears if zone number was selected)
Press [✱] to continue. Enter the desired zone number associated with this output
01 Enter Zn No. number. At the ENTER EVENT prompt, enter the zone event
12 that will activate this output.
01 Enter Event 0 = restore; 1 = alarm/fault/trouble
Restore 0
Press [✱] to continue to the “Output Action” prompt
Output Action Enter the desired device action.
01 Output Action
0 = off
Close for 2 sec 1 1 = Close for 2 seconds
2 = Stay Closed
3 = Pulse on & off (1 sec
ON, 1 sec OFF)
4 = Change Device State
5 = Duration 1 (see data
field *177)
6 = Duration 2 (see data
field *177)
Press [✱] to continue.
Output Number Enter the device output number (programmed in *79 Menu
Enter Output No.
01-16 = VISTA-20P outputs Mode) you want associated with this output.
R02 02 01-08 = VISTA-15P outputs
17-18 = on-board triggers
Press [✱] to continue.
Summary Screen A summary screen appears showing the programmed settings.
02 A E P TRIG
Press [✱] to continue. Press [∗] to return to OUTPUT FUNCTION NUMBER prompt
R02 1 1 3 ZL=00

∗81 ZONE LIST MENU MODE


(press *81 while in Programming mode) The Zone List Worksheet is on page 46.
Zone lists let you group individual zones for use with certain system actions. Using this mode, simply select an appropriate
zone list number, then add the desired zone numbers to be included in that list.
The following table shows the available zone lists and their purposes:
List No. Used for… Notes
1, 2 general purpose (GP) • Any list may include any or all of the system's zone numbers.
3 chime-by-zone (see field *26 to enable option) • A zone list can be assigned to more than one output relay.
4 cross zones (see note at right) • Zone List 4: When creating zone list 4 for cross zoning,
5 night stay zones include only zones assigned to zone types 3, 4, or 5. Do not
6 general purpose include zones that have delays (entry/exit zones, interior
V20PSIA/V15PSIA: dial delay disable w/delay) or 24-hour zones, as these zone types may produce
7 general purpose unpredictable operation and may not function as intended.
V20PSIA/V15PSIA: unlimited reports See field *85 for Cross Zone Timer option.
8 general purpose • Zone List 6: V20PSIA/V15PSIA: See field *50 for Dial Delay
9 zones that activate Pager 1 Disable option.
10 zones that activate Pager 2 • Zone List 7: V20PSIA/V15PSIA: See field *93 for Unlimited
11 zones that activate Pager 3 (VISTA-20P) Reports option.
12 zones that activate Pager 4 (VISTA-20P)
*81 Menu Mode
Zone List Number Enter the Zone List Number to program (or 00 to quit). Press [✱]
Zone List No.
01-12 = zone list number to advance.
(00 = Quit) 01 [∗] to continue In the following displays, zone list 01 has been selected.

Zone Number Enter each zone number to add to the zone list, followed by
01 Enter Zn Num.
01-64† = zone numbers pressing [✱] (example, 01✱, 02✱, 03✱). After all zones are
(00 = Quit) 00 entered, press 00 to continue.
followed by [∗] to
accept each zone IMPORTANT: Do not include fire zones in zone lists that are
00 to continue used to STOP device actions.
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
Deleting Zone Lists To delete the zone list, enter 1. All zones in the zone list will be
01 Del Zn List?
0 = don’t delete list deleted automatically and the system returns to the Zone List
0 = No 1 = Yes 0 1 = delete this zone list No. prompt.
[∗] to continue To save the zone list, enter 0.

– 29 –
Deleting a Zone To save the zone list, enter 0 and the system returns to the Zone
01 Delete Zone?
0 = don’t delete zones List No. prompt.
0 = No 1 = Yes 0 1 = go to next prompt to To delete a zone or zones in a zone list, enter 1 to continue.
delete zones
[∗] to continue
Delete the Zone Enter each zone to be deleted from the list, followed by [✱]. After
01 Zn to Delete?
01-64† = zones to be all zones to be deleted are entered, enter 00 to return to the
(00 = Quit) 00 Zone List No. prompt so that another list can be programmed, if
deleted from list
desired.
followed by [∗] to
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
accept each zone
00 to continue

∗82 ALPHA DESCRIPTOR MENU MODE


The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each
description can be composed of a combination of up to 3 words selected from a vocabulary of words stored in memory (see
Alpha Vocabulary List page). In addition, up to 10 installer-defined words can be added to those already in memory, plus 3
additional words can be assigned as partition descriptors. Thus, when an alarm or trouble occurs in a zone, an appropriate
description for that zone's location can be displayed at the keypad. Zone descriptors are recommended for systems using Alpha
display keypads, and are necessary if a 4286VIP Phone Module is used.
NOTE: You can also enter zone descriptors when the zone is being defined in ✱56 Menu mode.

4286 NOTE: If using a 4286VIP Phone Module, select from those words in the Alpha Vocabulary List shown in boldface
type. The phone module will not provide annunciation of the other words.
If a Phone Module is added to an existing system, the Alpha descriptors presently in the system should be reprogrammed,
selecting from those words shown in boldface type in the Alpha Vocabulary List. The phone module will not provide
annunciation of any other words.

∗82 Menu Mode


Program Alpha The “Program Alpha ?” prompt will appear. Press 1 to continue.
Program Alpha ?
0 = no (quit Alpha mode)
0 = N o , 1 = Ye s 0 0 1 = yes
[∗] to continue
Custom Words The “Custom Words” prompt will appear.
Custom W ords ?
0 = no Press 0 to program standard alpha descriptors from the fixed
0 = N o , 1 = Ye s 0 0 1 = yes vocabulary. The system then automatically displays the descriptor
for zone 1.
Press 1 to define custom words (see “Adding Custom Words”).
✱ ZN 01 Summary Screen Note that this is a “Summary mode,” and that no entries can be
[∗] to continue to edit mode made. Entries can be made only when the display contains a
[#] = return to Program flashing cursor, which signifies Edit mode.”
Alpha prompt (to quit) To exit the Alpha Descriptor mode, press ∗ + 0 + 0 at the
summary display.
Edit Mode – Flashing Descriptor screen for zone 1 appears. To program a descriptor
✱ ZN 01 (up to 3 words) for a zone, do the following:
Cursor
1. Enter the desired zone number (existing descriptor, if any, is
to edit = zone number then displayed) and press [∗], then enter the zone number again to
[∗], then zone start edit mode (flashing cursor appears).
number again 2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary
6 = save word and go to List for the first word.
next word in a b. Press [6] to accept the word and move the cursor for the next
descriptor word in the descriptor.
3. Repeat steps 2a and 2b for the second and third words (if used).
8 = save descriptor and go 4. When all words for that descriptor have been entered, press [8]
to next zone to save the descriptor for that zone. The summary screen
[#] = return to Program displays for that zone and the flashing cursor disappears.
Alpha prompt (to quit) 5. Press [∗] at the summary screen and repeat steps 1-4 to
assign a descriptor for the next zone.
6. When all descriptors have been entered, press [#]) at the last
descriptor summary screen to return to the PROGRAM
ALPHA? prompt. Enter 0 (no) at the prompt to exit this mode
and return to Data Field mode.

– 30 –
Descriptor Example EXAMPLE: “BACK DOOR”
EXAMPLE:
a. From the list, BACK = 013, so, after entering the zone number
(a)
to be edited (step 1), enter #013. If you accidentally enter the
✱ ZN 01 B ACK wrong word, simply press [#] plus the correct 3-digit number for
the word you want.
b. Press [6] to accept the selected word and continue to the next
(b) word. (if this is the only word you are using for the descriptor
✱ ZN 01 BACK press [8] to save it).
c. Enter the 3-digit number for the next word, “DOOR,” whose
number is “057.” Enter # 0 5 7.
(c) d. Because this is the last word in the example descriptor, press
✱ ZN 01 BACK [8] to save it. (If there was a third word in the descriptor, press
[6] to accept the selected word and continue to the third word.)
D OOR The summary screen displays with the selected descriptor.

(d)
✱ ZN 01 BACK
DOOR

Summary Screen The flashing cursor disappears, indicating that the word(s) are
✱ ZN 01 BACK
[∗] = to enter another zone saved for that zone, as shown in the summary display at the left.
DOOR number To enter a descriptor for the next zone, press [✱] plus the
[#] = return to Program desired zone number. The summary display appears. Repeat
Alpha prompt (to quit) the previous steps to enter the descriptor for the zone.
Adding Custom Words (will not be annunciated by 4286 Phone Module)
You can addup to 10 installer-defined words to the built-in vocabulary, which can then be used when programming zone
descriptors. Each of the 10 words can actually consist of a word string of one or more words, but no more than ten
characters can be used for each word or word string.
When adding custom words, the keypad keys perform the following functions:
[4] Moves cursor one space to the left.
[6] Moves cursor one space to the right.
[8] Saves the new word in the system's memory.
1. Select Custom Word mode (enter 1) when the prompt “CUSTOM WORD ?” is displayed.
2. Enter the number (01–10†) of the custom word or word string to be created, corresponding to index numbers 245 - 254
respectively (for example, if you are creating the first custom word or word-string, enter 01, for the second, enter 02, etc.).
A cursor will now appear at the beginning of the second line.
† or 11, 12, 13 for partition 1, partition 2 and common lobby descriptors respectively. See Assigning Partition
Descriptors paragraph below.
NOTE: Custom words 8, 9, and 10 are “reminder words” that are programmed using Scheduling Mode.
3. Refer to the Character List of letters, numbers, and symbols on a following page.
Press [#], followed by the two-digit entry for the first letter you would like to display (e.g., # 65 for “A”).
Press [6] to advance the cursor to the right, in position for the next character.
To delete a character, simply enter the SPACE character (#32) at the unwanted character’s location..
4. Repeat Step 3 to create the desired word(s). Note that the “4” key can be used to move the cursor to the left, if necessary.
Remember, no word or word-string can exceed 10 characters (except custom message/partition descriptor word numbers
11, 12, and 13, which can be a maximum of 16 characters).
5. When the word is complete, press the [8] key to save the custom word(s) and return to the “CUSTOM WORD ?” display.
Repeat Steps 2–5 for other custom words to be entered. To change a custom word, just overwrite it. When all words have
been programmed, press [0] to return to the Descriptor entry. The custom word(s) will be automatically added to the built-
in vocabulary.
Assigning Partition/Custom Message Descriptors
VISTA-15P: You can create a custom message display that appears on alpha keypads instead of “System Ready.” To assign
a custom message, use word number 11 as described below.
VISTA-20P: You can assign a partition descriptor (up to 16 characters) for each partition plus the common lobby. The system
displays the appropriate partition’s word instead of “DISARMED READY TO ARM.”
Use the same procedure as for adding custom words (described above), but use these word numbers in step 2:
11 = partition 1 ___________________________________________
12 = partition 2 ___________________________________________ (VISTA-20P only)
13 = common lobby ________________________________________ (VISTA-20P only)

Once a custom word is entered in any of these word locations (11-13), the system displays the appropriate partition’s word
instead of the default “DISARMED READY TO ARM” message.

– 31 –
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000 (Word Space) • 057 DOOR ∗ –L– –R– –V–
–A– • 059 DOWN • 106 LAUNDRY ∗ 155 RADIO 209 VALVE
• 001 AIR • 060 DOWNSTAIRS • 107 LEFT • 156 REAR 210 VAULT
• 002 ALARM ∗ 061 DRAWER 108 LEVEL 157 RECREATION 212 VOLTAGE
004 ALLEY • 062 DRIVEWAY • 109 LIBRARY ∗ 159 REFRIGERATION –W–
005 AMBUSH • 064 DUCT • 110 LIGHT 160 RF 213 WALL
• 006 AREA –E– 111 LINE • 161 RIGHT 214 WAREHOUSE
• 007 APARTMENT • 065 EAST • 113 LIVING ∗ • 162 ROOM ∗ • 216 WEST
• 009 ATTIC ∗ 066 ELECTRIC • 114 LOADING 163 ROOF • 217 WINDOW ∗
010 AUDIO 067 EMERGENCY ∗ 115 LOCK –S– • 219 WING
–B– 068 ENTRY 116 LOOP 164 SAFE 220 WIRELESS
• 012 BABY ∗ • 069 EQUIPMENT 117 LOW 165 SCREEN –X–
• 013 BACK ∗ • 071 EXIT ∗ • 118 LOWER 166 SENSOR 222 XMITTER
• 014 BAR 072 EXTERIOR –M– • 167 SERVICE –Y–
• 016 BASEMENT ∗ –F– • 119 MACHINE • 168 SHED ∗ 223 YARD
• 073 FACTORY 121 MAIDS 169 SHOCK –Z–
• 017 BATHROOM ∗
• 018 BED 075 FAMILY 122 MAIN ∗ • 170 SHOP ∗ 224 ZONE (No.)
• 076 FATHERS • 123 MASTER ∗ 171 SHORT • 225 ZONE ∗
• 019 BEDROOM ∗
020 BELL • 077 FENCE • 125 MEDICAL ∗ • 173 SIDE ∗ • 226 0
• 021 BLOWER • 079 FIRE ∗ 126 MEDICINE 174 SKYLIGHT • 227 1
• 022 BOILER • 080 FLOOR ∗ 128 MONEY 175 SLIDING ∗ • 228 1ST ∗
023 BOTTOM 081 FLOW 129 MONITOR • 176 SMOKE ∗ • 229 2
025 BREAK 082 FOIL • 130 MOTHERS • 178 SONS • 230 2ND ∗
• 026 BUILDING • 083 FOYER • 131 MOTION ∗ • 179 SOUTH • 231 3
–C– 084 FREEZER 132 MOTOR 180 SPRINKLER • 232 3RD ∗
028 CABINET • 085 FRONT ∗ –N– • 182 STATION • 233 4
• 029 CALL –G– • 134 NORTH 184 STORE • 234 4TH
030 CAMERA • 089 GARAGE ∗ 135 NURSERY • 185 STORAGE ∗ • 235 5
031 CAR • 090 GAS –O– 186 STORY • 236 5TH
033 CASH 091 GATE • 136 OFFICE ∗ 190 SUPERVISED ∗ • 237 6
034 CCTV • 092 GLASS • 138 OPEN ∗ 191 SUPERVISION • 238 6TH
035 CEILING 093 GUEST 139 OPENING 192 SWIMMING • 239 7
036 CELLAR 094 GUN • 140 OUTSIDE 193 SWITCH • 240 7TH
• 037 CENTRAL –H– 142 OVERHEAD –T– • 241 8
038 CIRCUIT • 095 HALL ∗ –P– 194 TAMPER • 242 8TH
• 040 CLOSED ∗ • 096 HEAT 143 PAINTING 196 TELCO • 243 9
• 046 COMPUTER 098 HOLDUP • 144 PANIC ∗ 197 TELEPHONE • 244 9TH
047 CONTACT 099 HOUSE ∗ 145 PASSIVE • 199 TEMPERATURE
–D– 100 INFRARED • 146 PATIO ∗ 200 THERMOSTAT 245 Custom Word #1
• 048 DAUGHTERS • 101 INSIDE ∗ 147 PERIMETER • 201 TOOL 246 Custom Word #2
049 DELAYED 102 INTERIOR • 148 PHONE 202 TRANSMITTER 247 Custom Word #3
• 050 DEN ∗ 103 INTRUSION 150 POINT –U– 248 Custom Word #4
051 DESK –J– 151 POLICE ∗ • 205 UP 249 Custom Word #5
• 052 DETECTOR ∗ • 206 UPPER 250 Custom Word #6
104 JEWELRY 152 POOL ∗
• 053 DINING ∗ –K– • 153 POWER • 207 UPSTAIRS ∗ 251 Custom Word #7
054 DISCRIMINATOR • 105 KITCHEN ∗ • 208 UTILITY ∗ 252 Custom Word #8
055 DISPLAY 253 Custom Word #9
254 Custom Word #10

Note: Bulleted (•) words in boldface type are those that are also available for use by the 4286 Phone Module. If using a
Phone module, and words other than these are selected for Alpha descriptors, the module will not provide
annunciation of those words.
Italicized words followed by an asterisk indicate those words supported by the 6160V/6150V Voice Keypads

CHARACTER (ASCII) CHART (For Adding Custom Words)


32 (space) 41 ) 50 2 59 ; 68 D 77 M 86 V
33 ! 42 * 51 3 60 < 69 E 78 N 87 W
34 " 43 + 52 4 61 = 70 F 79 O 88 X
35 # 44 , 53 5 62 > 71 G 80 P 89 Y
36 $ 45 – 54 6 63 ? 72 H 81 Q 90 Z
37 % 46 . 55 7 64 @ 73 I 82 R
38 & 47 / 56 8 65 A 74 J 83 S
39 ' 48 0 57 9 66 B 75 K 84 T
40 ( 49 1 58 : 67 C 76 L 85 U

– 32 –
SETTING SCHEDULES
(Installer Code + [#] + [6] [4])
The system provides schedules, which can be used to automatically control 11 types of system events at pre-defined times.
Some events are reserved for the installer only.
VISTA-20P: Provides up to 32 schedules: 16 schedules for use by the end-user, 16 for use by the installer.
VISTA-15P: Provides up to 8 schedules: 4 schedules for use by the end user, 4 for use by the installer.
NOTES:
• The master code can only access schedules 01-16 (VISTA-15P = 01-04) and events 00-07.
• System clock must be set before schedules can take effect.
• Programmed schedules do not take effect until the next scheduled “start” time. (e.g., if programming a schedule time window
for 8AM to 5PM, the schedule does not take effect until 8AM after the schedule has been programmed.)
Schedule Mode
ENTER SCHED NO. Schedule Number Enter the desired schedule number.
VISTA-20P To Quit, enter 00.
00=QUIT 00
01-16 = end-user schedules
17-32 = installer-only
VISTA-15P
01-04 = end-user schedules
05-08- = installer-only
[∗] to continue
ENTER EVENT Enter Event Enter the desired event number for event you want to occur at a
00 = clear event specified time.
01 = Relay On/Off Events 10-11 are reserved for the installer only.
02 = User Access Latch key report (option 03) is sent to all pagers in the user’s
03 = Latch Key Report to partition and is active only when the system is armed (message
Pager sent is 777-7777). User must be enabled for paging (see User
04 = Forced Stay Arming† Attributes in System Operation section).
05 = Forced Away Arming†
06 = Auto Disarm † Forced bypass is automatically enabled regardless of setting
07 = Display “Reminder” in field *23.
10 = Display custom words †† †† If selected, system displays custom words 8, 9, and 10 at
11 = Periodic Test Report††† defined time. Can be used as installer’s reminder message to
the end user.
Press [∗] to continue. ††† See key commands in Test Report Code data field *64
section to quickly set periodic test reporting intervals.
NOTE: Events 07 and 10 cause the keypad to beep every 30 seconds
when messages are displayed. Stop the beeps by pressing any key.

DEVICE NUMBER Device Number (For event 01-relay on/off)


V20P: Enter the physical device number as programmed in ∗79 Menu
XX
01-18 = device number Mode, then press [*] to continue to the “Start” prompt.
V15P: 01-08, 17, 18 Device numbers 17 and 18 designate built-in triggers 1 and 2
Press [∗] to continue. respectively.

GROUP NUMBER Group Number (For event 02-user access)


1-8 = group number
X
Press [∗] to continue to the
“Start” prompt.
PARTITION Partition (V20P only; for events 03-07, 10)
0 = all partitions
X
1 = partition 1
2 = partition 2
3 = common
Press [*] to continue to the
“Start” prompt.
START SMTW TFS Start Time Enter the event’s start time and days of the week to occur.
01-12 = hour To select days, position the cursor under the desired days using
HH MMAM 0 0 1 0 0 0 0
00-59 = minute the [∗] key to move forward, then press “1” to select the day.
0 = AM; 1 = PM
Days = place “1” under days
Press [∗] to continue.
STOP SMTW TFS Stop Time (For events 01-relay on/off; 02-user access; 03-latch key report)
01-12 = hour Enter the event’s stop time and days of the week to occur.
HH MMAM 0 0 1 0 0 0 0
00-59 = minute To select days, position the cursor under the desired days using
0 = AM; 1 = PM the [∗] key to move forward, then press “1” to select the day.
Days = place “1” under days
Press [∗] to continue.

– 33 –
REPEAT OPTION Repeat Option Enter the desired repeat option for this schedule.
0 = do not repeat e.g., To make a schedule that happens everyday you would
0-4 X
1 = repeat weekly select all days with a repeat count of 1. To make a schedule that
2 = repeat biweekly (every runs for one week then stops, select everyday with a repeat
other week) count of 0.
3 = repeat every third week
4 = repeat every fourth week
Press [∗] to continue.
RANDOMIZE Randomize (For events 01 and 11)
0 = no If selected, the scheduled start and stop times will vary within 60
0=NO 1=YES X
1 = yes minutes of the “hour” time. For example, if a schedule is set to
Press [∗] to continue and start at 6:15pm, it will do so the first time 6:15pm arrives, but on
return to ENTER SCHED subsequent days it will start anytime between 6:00 and 6:59 p.m.
NO. prompt to program the NOTE: Do not use the random option if the start and stop times
next schedule. are within the same “hour” setting, otherwise unpredictable
results may occur (e.g., the randomized stop time may occur
before the start time).

AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS


Applies to an AVS system using an ECP connection to the control.
1. Install the AVS module according to its instructions.
2. Use one of the control’s AVS Quick Program commands as follows (see Quick Program Command Results below for
results of each command):
• installer code + [#] + [0] + 3: enable AVS operation without panel sounds on the AVST speaker
• installer code + [#] + [0] + 4: enable AVS operation and enable panel sounds on the AVST speaker
3. Use data field ∗55 Dynamic Signaling Priority to select the desired reporting paths (phone line and/or GSMV4G, GSMX4G)
and path for AAV communication.
4. To undo the Quick Command programming, use the following commands:
• installer code + [#] + [0] + 5: remove all options set by [#] + [0] + 3 quick command
• installer code + [#] + [0] + 6: remove all options set by [#] + [0] + 4 quick command

Quick Program Command Results


When either the #03 or #04 Quick Program command is used, the following are automatically programmed and no longer
available for other control panel purposes.
Pre-Programmed #03 Command #04 Command
Output Function No. VISTA-15P series VISTA-20P series VISTA-15P series VISTA-20P series
(∗80 mode) 22 (zone type 60, relay 07) 46 (zone type 60, relay 15) Same as #03 plus: Same as #03 plus:
23 (zone type 61, relay 08) 47 (zone type 61, relay 16) 17 (zone type 14, relay 05) 41 (zone type 14, relay 13)
24 (zone type 62, relay 08) 48 (zone type 62, relay 16) 18 (zone type 22, relay 05) 42 (zone type 22, relay 13)
19 (zone type 39, relay 06) 43 (zone type 39, relay 14)
20 (zone type 33, relay 06) 44 (zone type 33, relay 14)
21 (zone type 36, relay 06) 45 (zone type 36, relay 14)
Output Relay No. 07 (addr 08, relay pos 2) 15 (addr 11, relay pos 2) Same as #03 plus: Same as #03 plus:
(∗79 mode) 08 (addr 08, relay pos 1) 16 (addr 11, relay pos 1) 05 (addr 08, relay pos 4) 13 (addr 11, relay pos 4)
06 (addr 08, relay pos 3) 14 (addr 11, relay pos 3)
Protection Zone 4229 zn 24 (zt 81, addr 08) 4229 zn 48 (zt 81, addr 11) Same as #03 command Same as #03 command
(∗56/∗58 mode)
Device Address address 08 (AVS module) address 11 (AVS module) Same as #03 command Same as #03 command
Data Field ∗91 AAV enabled AAV enabled AAV enabled AAV enabled

SETTING THE REAL-TIME CLOCK


IMPORTANT: The Real-Time Clock must be set before the end of the installation.
NOTE: All partitions must be disarmed before the date/time can be set.
1. Master Code + [#] + [6] [3]
2. Press [∗] when the time/date is displayed.
A cursor appears under the first digit of the hour.
To move cursor ahead, press [∗]. To go back, press [#].
• Enter the 2-digit hour setting.
• Enter the 2-digit minute setting.
• Press [1] for PM or [2] for AM.
• Enter the last two digits of the current year.
• Enter the 2-digit month setting.
• Enter the 2-digit day setting.
3. To exit, press [∗] when cursor is at the last digit, or wait 30 seconds.

– 34 –
∗29 COMMUNICATION DEVICE MENU MODE (Pass-Through Programming)
This mode is for programming an IP, GSM, or IP/GSM Communicator Module using an alpha keypad. Alternatively, these
options can be programmed via the AlarmNet Direct website. After programming is complete, the module must be registered
with AlarmNet before reporting via the communication device can occur. Refer to the device’s instructions for registration
procedures.
NOTE: The module must be set to device address 3.
IMPORTANT: The use of an IP/GSM Communicator Module
requires an AlarmNet–I account. Please obtain the account
information from the central station prior to programming this
module.
Using an Alpha Keypad as a 7720P Programming Tool
When programming with ∗29 menu mode, the alpha
keypad mimics the functions of the 7720P Programming A B C

Tool. See figure to right and table below for 7720P key
ARMED (A) BS/ESC 1 OFF 2 AWAY 3 STAY

D E F
functions. Each key has two possible functions: a normal READY (B) / 4 MAX 5 TEST 6 BYPASS

function and a SHIFT function. S T X

Normal functions: The numeric values labeled directly SHIFT


(C) N/Y 7 INSTANT 8 CODE 9 CHIME

SPACE ENTER
on the keys and the left-hand functions shown in FUNCTION

diagram on the ABC keys. To perform a normal key


WHEN LIT (D) SHIFT READY 0 #
function, simply press the desired key.
SHIFT functions: Those functions shown in diagram 6160-7720P-001-V0
above the numerical keys and the right-hand functions
shown on the ABC keys. To perform a SHIFT key 7720P Emulation Template for Alpha Keypads
function, press SHIFT key (D key), then press the
desired function key (shift function is indicated by the lit
READY LED).
∗29 IP/GSM Program Mode
Press ∗29 while in Data Field Programming mode. The following prompts appear.
ENABLE IP/GSM? Enable IP/GSM? If using a communication device, enter 1 at this prompt and
0 = no, not using IP or GSM; enter 1-Prog at the next prompt to program the device. Use the
0=No, 1=Yes communication device’s Installation Guide for details of the
1 = yes using IP and/or
GSM module device’s programming prompts and instructions for registration.
[∗] to continue Fixed-Word Keypad Note: Although programming IP/GSM
[Default = 0 (no IP and/or GSM)] options cannot be done via a fixed-word keypad, IP/GSM can be
enabled by doing the following:
Enter ∗29 (to enter IP/GSM menu mode), then press 1 + [∗ ∗] + [∗
∗]
1=PROG 2=DIAG Programming / Select whether you want to program the communication device
Diagnostics Select or enter the device’s diagnostic mode.
0=QUIT
1= Prog (program the Diagnostic Mode Note: Diagnostic mode option available only
IP/GSM options) for communicators with firmware version 2.4.16 or higher.
2 = Diag (diagnostic mode)
0 = Quit; returns to data field
programming mode
Normal and SHIFT key Functions While in ∗29 Menu Mode
Key Normal Key Function SHIFT Key Function
(A) = BS/ESC [BS]: Press to delete entry [ESC]: Press to quit Program Mode
Also, can reset EEPROM defaults †
(B) = ↓/↑ [↓]: Scroll down programming [↑]: Scroll up programming
(C) = N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer
(D) = SHIFT Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a
key is pressed. Press again for each SHIFT function desired.
1/A [1]: For entering the number 1 [A]: Used for entering C.S. ID number
2/B [2]: For entering the number 2 [B]: Used for entering C.S. ID number
3/C [3]: For entering the number 3 [C]: Used for entering C.S. ID number
4/D [4]: For entering the number 4 [D]: Used for entering C.S. ID number
5/E [5]: For entering the number 5 [E]: Used for entering C.S. ID number
6/F [6]: For entering the number 6 [F]: Used for entering C.S. ID number
7/S [7]: For entering the number 7 [S]: Press to display diagnostic status
8/T [8]: For entering the number 8 [T]: Press to send TEST messages
9/X [9]: For entering the number 9 [X]: Press to reset the IP/GSM
[∗] / SPACE [∗]: Used to select programming options [SPACE]: Not used
0 [0]: For entering the number 0
[#] / ENTER [#] / ENTER: Press to accept entries No SHIFT function
† Active only when the "REVIEW?" prompt is displayed

– 35 –
Registering the Communication Device with AlarmNet
The communication device must be registered with AlarmNet before internet communication (via IP or GSM) can occur.
Register Using the Alpha Keypad and ∗29 Menu Mode
1. Enter *29 Menu mode, select Diagnostic mode, then press Shift then [↑] key (D key followed by the B key). The
registration message is sent (“Registering” displayed) and the control waits for the acknowledgment.
2. “Registration SUCCESS” displayed, indicating successful registration.
Or Register with AlarmNet Direct Website or by Phone
To register via AlarmNet Direct Website, please go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
To register by phone, call 1-800-222-6525. You will need the MAC ID and MAC CRC number and Subscriber information.
Communication Device Status Report Codes
The Communication Device sends status messages to the control panel for network connectivity failures. Trouble messages
are displayed on the keypad as “Check 103,” with status displayed as “LngRng Radio” followed by a 4-digit keypad display
status code, defined below.
Keypad Display Status Codes
CODE DESCRIPTION
0000 Control panel lost communication with internal device
0005 Communication device has lost contact with AlarmNet-G network
000F Communication device is not registered; account not activated
0019 GSM module shut down
0400 Communication device Power-on reset

– 36 –
UPLOADING/DOWNLOADING VIA the INTERNET
UL: Up/downloading via the Internet has not been evaluated by UL.
This control, when used with a compatible Internet/Intranet Communication Device, supports upload/download programming
capability via the Internet using the AlarmNet network or, depending on the communication module used, a Private local area
network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally
via the Internet. Depending on the module used, Internet connection from the protected premises is either via high speed
(broadband) cable or phone service, or via the GSM/GPRS digital cellular network (GSM modules).
Refer to the instructions provided with the communication module for information regarding its installation, programming, and
registration. The System Requirements table below lists two sets of system requirements, depending upon whether you
intend to communicate over the Internet or whether you are communicating over a Private LAN (Intranet).
Compatible Communication Modules: The following modules support Internet uploading/downloading, but future modules
may also provide Internet upload/download support; refer to the module’s instructions for compatibility. Compatible Modules:
7845i-ent (supports LAN), GSMV4G, GSMX4G, IGSMV4G
System Requirements
Internet Communication Intranet (Private LAN) Communication, if applicable*
At the Installation Site: At the Installation Site:
• Appropriate Internet Communication Module • Internet/Intranet Communication Module
• 7720P Programmer • 7720P Programmer
• Broadband Internet Access (for wired modules) • Ethernet Network Connection
• Broadband (Cable/DSL) Modem (for wired modules) • IP compatible Control Panel
• Broadband (Cable/DSL) Router (for wired modules if At the Downloading Office:
connecting more than one device to the Internet) • 7810iR-ent IP Receiver and Internal Router
• IP compatible Control Panel • Computer(s) running the following software:
At the Downloading Office: - Compass Downloading Software version that supports IP
• Broadband Internet Access upload/download for this control.
• Broadband (Cable/DSL) Modem - Compass Connect Data Server Application
- Compass Connect Control Server Application
• Broadband (Cable/DSL) Router (optional, if connecting
more than one device to the Internet) * see module’s instructions for applicability for LAN usage
• Computer running Compass Downloading Software NOTE: Compass, the Compass Connect Data Server, and the
version that supports Internet upload/download for this Compass Connect Control Server applications may all be installed
control. on the same computer if desired. If they are installed on one
computer, the computer must have a fixed IP Address.
To set up the control panel, do the following:
1. Connect the communication device to the control panel’s ECP (keypad) terminals.
2. Internet Users: Connect the communication device to the Internet via a cable/DSL modem and router.
Intranet Users: Connect the communication device to the Intranet (LAN) via the appropriate Ethernet connection.
3. Enable the communication device (using ∗29 Menu mode) to enable alarm reporting and module supervision.
4. Using the communication device’s programming menus (via ∗29 Menu mode or 7720P programmer), program the
communication device for address 3 and program the device’s other options as required.
5. Register the communication device with AlarmNet. The communication device must be registered before downloading or
alarm reporting can take place.
To perform upload/download functions:
1. Connect the computer to the Internet and start the Compass downloading software.
2. Open the control’s account, then select the Communications function and click the Connect button.
3. At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is checked.
4. Click Connect. The Internet connection to the control is made automatically via AlarmNet.
5. Once connected, use the Compass downloading software as normal to perform upload/download functions.

– 37 –
ZONE TYPE DEFINITIONS
Zone types define the way in which the system responds to faults in each zone.
Type 00 Zone Not Used Type 12 Monitor Zone
Program a zone with this zone type if the zone is not used. • Works as a dynamic monitor of a zone fault/trouble (not alarm). In
Type 01 Entry/Exit Burglary #1 the case of a short/open, the message, "*ALARM*-24 Hr. Non-Burg.
• Assign to zones that are used for primary entry and exit. -#XXX " (where XXX is the zone number) will be sent to the Central
• Provides entry delay when zone is faulted if control is armed in Station. The system keypad will display a “check” message
the Away, Stay, or Night-Stay modes. indicating the appropriate zone (but keypad beeping does not
• No entry delay provided when the panel is armed in the occur). Upon restoral of the zone, the message, "*RESTORE*-24
Instant/Maximum mode. Hr. Non-Burg. -#XXX " will be sent to the Central Station.
• Entry delay #1 is programmable for each partition (field *35). • The “check” message will automatically disappear from the keypad
dynamically, when the zone restores; a user code + off sequence is
• Exit delay begins whenever the control is armed, regardless of
not needed to reset the zone.
the arming mode selected, and is programmable (field ✱34).
• Faults of this zone type are independent of the system, and can
Type 02 Entry/Exit Burglary #2 exist at the time of arming without interference.
• Assign to zones that are used for entry and exit and require • Since this is a “trouble” zone type, do not use this zone type with
more time than the primary entry/exit point. relays set to activate upon “alarm.”
• Provides a secondary entry delay, similar to entry delay #1.
Type 14 24 Hour Carbon Monoxide Monitor
• Entry delay #2 is programmable for each partition (field *36).
• Assigned to any zone with a carbon monoxide detector.
• Exit delay is same as described for Type 01.
• A carbon monoxide alarm produces keypad and detector sounding
Type 03 Perimeter Burglary (does not affect bell output).
• Assign to all sensors or contacts on exterior doors and windows. • Always active and cannot be bypassed.
• Provides an instant alarm if the zone is faulted when the panel is Type 16 Fire w/Verification
armed in the Away, Stay, Night-Stay, Instant or Maximum modes.
• Provides a fire alarm when zone is shorted, but only after the alarm
Type 04 Interior Follower is verified to help eliminate false alarms due to electrical or physical
• Assign to a zone covering an area such as a foyer, lobby, or transients.
hallway through which one must pass upon entry (to and from • Verifies alarm by resetting smoke detectors after short is detected
the keypad). (removes power 7 seconds for zone 1, 3 seconds for trigger output).
• Provides a delayed alarm (using the programmed entry 1 time) Another short circuit within 90 seconds triggers fire alarm, otherwise
if the entry/exit zone is faulted first. Otherwise this zone type first alarm is ignored.
gives an instant alarm. • Provides a trouble response when zone is open.
• Active when the panel is armed in the Away mode. Type 20 Arm-Stay (BR only)
• Bypassed automatically when the panel is armed in the Stay or • Arms the system in Stay mode when the zone is activated.
Instant modes; if armed in Night-Stay mode, zones assigned to
• Pushbutton units send the user number to the central station when
zone list 05 (night-stay zone list) are not bypassed when
arming or disarming.
system armed in Night-Stay mode.
• User number for button must be assigned.
Type 05 Trouble by Day/Alarm by Night
Type 21 Arm-Away (BR only)
• Assign to a zone that contains a foil-protected door or window
(such as in a store), or to a zone covering a sensitive area such • Arms the system in Away mode when the zone is activated.
as a stock room, drug supply room, etc. • Pushbutton units send the user number to the central station when
• Can also be used on a sensor or contact in an area where arming or disarming.
immediate notification of an entry is desired. • User number for button must be assigned.
• Provides an instant alarm if faulted when armed in the Away, Type 22 Disarm (BR only)
Stay, Night-Stay, Instant or Maximum (night) modes. • Disarms the system when the zone is activated.
• During the disarmed state (day), the system will provide a • User number for button must be assigned.
latched trouble sounding from the keypad (and a central station Type 23 * No Alarm Response
report, if desired). • Can be used on a zone when an output relay action is desired, but
Type 06 24-hr Silent Alarm with no accompanying alarm (e.g., lobby door access).
• Usually assigned to a zone containing an emergency button. Type 24 Silent Burglary
• Sends a report to the central station but provides no keypad • Usually assigned to all sensors or contacts on exterior doors and
display or sounding. windows where bells and/or sirens are NOT desired.
Type 07 24-hour Audible Alarm • Provides an instant alarm, with NO audible indication at any keypad
• Assign to a zone that has an emergency button. or external sounder, if the zone is faulted when the system is armed
• Sends a report to the central station, and provides an alarm in the Away, Stay, Instant, or Maximum modes.
sound at the keypad, and an audible external alarm. • A report is sent to the central station.
Type 08 24-hour Auxiliary Alarm Type 77 Keyswitch
• Assign to a zone containing an emergency button, or to a zone • Assign to zone wired to a keyswitch.
containing monitoring devices such as water or temperature • Do not use input type “BR” devices with this zone type.
sensors. Type 81 AAV Monitor Zone (for AVS)
• Sends a report to the central station and provides an alarm • Assign to zone connected to AVS module.
sound at the keypad. (No bell output.) • Monitors 2-way voice sessions as follows:
Type 09 Supervised Fire - When the zone is faulted, all alarm sounding and dialer reporting
• Provides a fire alarm on short circuit and a trouble condition on stops, except for fire alarms, which immediately terminate the
open circuit. A fire alarm produces a pulsing bell output. voice session and cause a fire report to be sent.
• This zone type is always active and cannot be bypassed. - When the zone is restored (session ended), sounding resumes (if
Type 10 Interior w/Delay bell timeout has not expired) and reports that were stopped are sent.
• Provides entry delay (using the programmed entry time), if Types 90-93 Configurable
tripped when the panel is armed in the Away mode. Allows for various custom responses. Options include response to
• Entry Delay 1 begins whenever sensors in this zone are entry/exit delays, response opens/shorts, types of alarm/trouble
violated, regardless of whether or not an entry/exit delay zone sounding, dial delay, and unique Contact ID report codes. Types 92
was tripped first. and 93 can only be programmed via downloader. UL installations:
• Bypassed when the panel is armed in the Stay or Instant Zone Types 90 -93 may not be used as fire or burglar alarm zones on
modes; if armed in Night-Stay mode, zones assigned to zone fire or UL burglar alarm installations.
list 05 (night-stay zone list) are not bypassed when system * The system can still be armed when these zone types are in a
armed in Night-Stay mode. faulted condition.

– 38 –
REPORT CODE FORMATS
The following table describes the communication formats.
FORMAT TYPE DESCRIPTION
3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a single-digit report code (e.g., Alarm,
Standard Formats Trouble, Restore, Open, Close, etc).
Ex. SSS(S) A Ex. S = Subscriber ID; A = Report Code
3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a two-digit report code. The first digit
Expanded Formats is displayed on the first line. The first digit is repeated on the second line 3 (or 4) times
Ex. SSS(S) A followed by the second, “expanded” digit.
AAA(A) Z Ex. S = Subscriber ID; A = Report Code–1st digit; Z = Typically Zone Number–2nd digit
4+2 Format Comprises a 4-digit subscriber number and 2-digit report code.
Ex. SSSS AZ Ex. S = Subscriber ID; A = Report Code; Z = Typically Zone Number)
ADEMCO Contact ID Comprises a 4- or 10-digit subscriber number (depending on format selected), 1-digit
Reporting Format event qualifier (“new” or “restore”), 3-digit event code, and 3-digit zone number, user
Ex. CCCC Q EEE GG ZZZ number, or system status number (see below for example explanation).

ADEMCO Contact ID®


The ADEMCO Contact ID® Reporting Format comprises the following:
4-digit or 10-digit subscriber number (depending on format selected).
1-digit event qualifier (“new” or “restore”).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see table below).

ADEMCO Contact ID® Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where: CCCC(CCCCCC) =Customer (subscriber) ID
Q = Event qualifier, where: E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
GG = Partition Number (system messages show “00”)
ZZZ = Zone/contact ID number reporting the alarm, or user number for open/close reports.
System status messages contain zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
(Some event codes may not apply to certain control panels;
for a complete list of event codes, refer to the central office receiver manual)
Code Definition Code Definition
110 Fire Alarm 383 RF Sensor Tamper
121 Duress 384 RF Sensor Low-battery
122 Alarm, 24-hour Silent 393 Clean Me
123 Alarm, 24-hour Audible 401 Disarmed, Armed AWAY, Armed MAXIMUM
131 Alarm, Perimeter 403 Schedule Arm/Disarm AWAY
132 Alarm, Interior 406 Cancel by User
134 Alarm, Entry/Exit 407 Remote Arm/Disarm (Downloading)
135 Alarm, Day/Night 408 Quick Arm AWAY
143 Alarm, Expansion Module 409 Keyswitch Arm/Disarm AWAY
145 ECP Module cover tamper 441 Disarmed/Armed STAY/INSTANT,
146 Silent Burglary Quick-Arm STAY/INSTANT
150 Alarm, 24-Hour Auxiliary/Monitor zone 442 Keyswitch Arm/Disarm STAY
162 Carbon Monoxide 455 Scheduled Arm Fail
301 AC Power 459 Recent Closing (SIA panels only)
302 Low System Battery/Battery Test Fail 570 Bypass
305 System Reset (Log only) 601 Manually Triggered Dialer Test
321 Bell/Siren Trouble 602 Periodic Test
333 Trouble, Expansion Mod. Supervision 606 AAV to Follow
341 Trouble, ECP Cover Tamper 607 Walk Test Entered/Exited
344 RF Receiver Jam 623 Event Log 80% Full
351 Telco Line Fault 625 Real-Time Clock was Changed (log only)
353 Long Range Radio Trouble 627 Program Mode Entry (log only)
354 Failure to Communicate (log only) 628 Program Mode Exit (log only)
373 Fire Loop Trouble 642 Latch Key (log only)
374 Exit Error Alarm 750 - Reserved for Configurable Zone Type report
380 Global Trouble, Trouble Day/Night 789 codes (check with central station when using
381 RF Sensor Supervision these codes)
382 Supervision Auxiliary Wire Zone

– 39 –
SYSTEM SECURITY CODES
The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of
the system. These codes can each be assigned one of 5 authority levels, which determine the functions each code can
perform as listed in the table below.
VISTA-20P: Provides 48 security codes (plus Installer code), including one System Master code, two Partition Master
codes, and 45 general user codes.
VISTA-15P: Provides 32 security codes (plus Installer code), including one System Master code and 31 general user codes.
Authority Levels (can be assigned to users 03-49 only; users 1 and 2 cannot be changed)
Level User No. Functions
Installer 01 (default=4112) perform all security functions except can disarm only if used to arm; can
enter program mode; can change System Master code; cannot assign any other user codes
NOTE: For security purposes, the factory default installer code should be changed.
System Master 02 (default 1234) only one system master code per system; can perform all security functions,
add/delete users in either partition, change system master code, view event log, set system
clock, program keypad macro, program scheduled events, activate output devices
(triggers/relays)
Partition Master P1 = 03 VISTA-20P. Same as Master, except add/delete users limited to assigned partition only,
(default) P2 = 33 (these users can be assigned different authority levels, if desired; any user can be
assigned the partition master authority level)
0-User 03-49 (V20P) perform security functions (arm, disarm, etc.) only; cannot add/delete users, view event log,
03-33 (V15P) set system clock or program scheduled events
1-Arm Only see “user” arm system only
2-Guest see “user” can disarm the system only if it was used to arm the system
3-Duress see “user” performs security functions, but also silently sends a duress message to the central station;
reports as duress code user number.
4-Partition Master see “user” VISTA-20P. See Partition Master paragraph above; used to assign other user numbers as
partition masters

Refer to the user guide for detailed procedures on adding/deleting security codes and changing user attributes.
The following is a brief description of how to add user codes.
Changing the System Master code:
Using Installer code: Installer code + [8] + 02 + new code
Using current System Master code: System Master code + [8] + 02 + new code + new code again
Adding a User Code: Master code + [8] + 2-digit user no. + user’s code
Deleting a User Code: Master code + [8] + 2-digit user no. + [#] [0]
Assigning Attributes: Master code + [8] + 2-digit user no. + [#] [attribute no.] + value
Attributes: Values
1 = Authority Level 0-4 (see Authority Level table above)
2 = Access Group 0-8 (0 = not assigned to a group)
3 = Active Partition(s) 1, 2, 3 (common)
for this user; Enter partitions consecutively if more than one and press [#] to end the entries.
4 = RF Zone No. Assigns user number to button type zone for arm/disarm (keyfob must be
enrolled in system first; see Wireless Key Templates section).
Deactivating a key fob: You can deactivate the arming/disarming functions for a
key fob (ex. if lost or stolen) by deleting the associated key fob user. See “Delete
a User” above. Other key fob functions such as panic or device activation (if
programmed) remain active. To fully remove the programming for a key fob,
delete the zone(s) associated with the key fob functions.
IMPORTANT SECURITY NOTICE
Please inform the User about the security importance of their key fob, and what to
do if it is lost.
Explain that the key fob is similar to their keys or access card. If lost or stolen,
another person can compromise their security system. They should immediately
notify the Dealer/Installer of a lost or stolen key fob. The Dealer/Installer will then
remove the key fob programming from the security system.
5= Open/Close Paging 1 for yes, 0 for no

– 40 –
KEYPAD FUNCTIONS
The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's
Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI) User’s Guide.
Keypad Commands
Function Description
Silence Burglary Alarms Pressing any key will silence the keypad sounder for 10 seconds. Disarming the system
(security code + OFF) silences both keypad and external sounders.
Silence Fire or Carbon Press the OFF [1] key to silence the keypad sounder and, for fire alarms, the external sounder.
Monoxide Alarms
Quick Arm If enabled (field ∗21), you can press [#] in place of the system's security code, plus the desired
arming key (Away, Stay, Instant, Maximum)
Single-Button arming If programmed (*57 Function Key menu mode), lettered keys A-D can be used for arming,
using options 3-AWAY, 4-STAY, 5-NIGHT-STAY, or 6-Step-Arming
Alarm Memory When the system is disarmed, any zones that were in an alarm condition during the armed
period will be displayed. To clear this display, simply repeat the disarm sequence (enter the
security code and press the OFF key) again.
Arming Away Enter code + AWAY [2] or simply press appropriate lettered key on the keypads. If the “Auto-
Stay Arm” feature is enabled (field *84) and the entry/exit door is not opened and closed within
the programmed exit delay time, the system will automatically arm in STAY mode if armed from
a wired keypad (non-RF device). If the door is opened and closed within the exit delay period,
the system arms in AWAY mode.
Arming Stay Enter code + STAY [3] or simply press appropriate key on the keypads (see “Single-Button
Arming” above). See “Arming Away” above for Auto-Stay arming feature.
Arming Night-Stay Enter code + STAY [3] + STAY [3] or simply press appropriate key on the keypads (see
“Single-Button Arming” above).
Arming Instant Enter code + INSTANT [7].
Arming Maximum Enter code + MAXIMUM [4] or simply press appropriate lettered key on the keypads (see
“Single-Button Arming” above).
Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF.
Bypassing Zones Enter code + BYPASS [6] + zone number(s).
Forced (Quick) Bypass To automatically bypass all faulted zones, use the “Quick Bypass” method. Enter code +
BYPASS + [#], then wait for all open zones to be displayed. Arm when display indicates “ZONE
BYPASSED” and “READY TO ARM”.
Chime Mode Enter code + CHIME [9]. To turn chime off, enter code + CHIME again.
Activate Output Devices [Security Code] + # + 7 + [2-digit Device #] activates (starts) that device.
[Security Code] + # + 8 + [2-digit Device #] deactivates (stops) that device.

– 41 –
VARIOUS SYSTEM TROUBLE DISPLAYS
Alpha Display Fixed Disp. Meaning
ALARM CANCELED CA Will appear if an exit or interior zone contained a fault during closing at the time
the Exit Delay ended (e.g., exit door left open), but the system was disarmed
during the Entry Delay time. The alarm sounder and keypad sound continuously,
but stop when the system is disarmed. No message will be transmitted to the
central station.
EXIT ALARM EA Appears when Exit Delay ends if an exit or interior zone contained a fault during
closing. The alarm sounder and keypad sound continuously until the system is
disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central
station. Also results if an alarm from an exit or interior zone occurs within 2
minutes after the end of an Exit Delay.
CHECK CHECK Indicates that a problem exists with the displayed zone(s) and requires attention.
ALARM 1xx 1xx Indicates that communication between control and a zone expander or wireless
FAULT 1xx 1xx receiver is interrupted, where “xx” is the device address. Check the wiring and DIP
CHECK 1xx 1xx switch settings on the units.
91 If field *199 is set to “1,” all ECP module problems are displayed as “91.”
If there are wireless sensors in the system, the Check condition may also be
caused by some change in the environment that prevents the receiver from
receiving signals from a particular sensor.
SYSTEM LO BAT BAT With no zone number indicates that the system's standby battery is weak.
LO BAT BAT With a zone number and about twice-per-minute beeping at the keypad indicates
that a low-battery condition exists in the wireless sensor displayed (zone “00”
indicates a wireless keypad). If the battery is not replaced within 30 days, a
“CHECK” display may occur.
NOTE: Some wireless sensors contain a non-replaceable long-life battery which
requires replacement of the entire unit at the end of battery life (e.g., Nos. 5802,
5802CP).
TELCO FAULT 94 Telephone Line Failure, indicates that a monitored telephone line (if programmed
in field *92) has been cut or disconnected. Depending on how the system was
programmed, the keypad may also produce a trouble sound, and the external
sounder may be activated. Silence by entering installer code + OFF.
Busy-Standby dl If this remains displayed for more than 1 minute, the system is disabled.
NOTE for CANADIAN PANELS: Power up time is 2 minutes, and CID code 305
System Reset is sent if the [#] + [0] command is not performed before the 2
minutes expires.
Modem Comm CC The system is in communication with the central station for change of function or
status verification.
no display no display Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power (AC
and battery) for the system has stopped and the system is inoperative.
If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word
display keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage,
the control's power will shut down to minimize deep discharge of the battery.
Comm. Failure FC A communication failure has occurred.
Open Circuit 0C The keypad is not receiving signals from the control; sees an open circuit.
Long Rng Trbl bF Backup communication device (LRR) had communication failure.
Bell Failure 70 Bell supervision failure.
RCVR Jam 90 RF jam detected.
KEYPAD LOW BAT 00 BAT Wireless keypad low battery.
Phone Okay Cd The dialer test has been successful (CID code 601).
Dialer Off d0 The dialer is disabled.
Test in Progress dd Walk test mode is active (CID code 607).
Upload Completed dC The upload or download session was completed.
Upload Failed dF The upload or download session failed before completion.

– 42 –
WORKSHEET for ∗56 ZONE PROGRAMMING
(VISTA-15P supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets]
Zone Zn Type Part. Report Hardwire Rsp. Time Location
Type

1 [09] [1] [EOL] [1]

2 [01] [1] [EOL] [1]

3 [03] [1] [EOL] [1]

4 [03] [1] [EOL] [1]

5 [03] [1] [EOL] [1]

6 [03] [1] [EOL] [1]

7 [03] [1] [EOL] [1]

8 [03] [1] [EOL] [1]


Zone Zn Type Part. Report Input Type Loop Serial No. Location

10

11

12

13

14

NOTES: 15
Zone Type: see chart ∗56
Zone Programming Menu
mode section. 16
Report Code: enabled if
first digit is a non-zero 17
number.
Hardwire Type (zns 2-8):
0 = EOL 3 = ZD
18
1 = NC 4 = DB
2 = NO 19
Input Type:
2 = AW (zones 9-48)
3 = RF (zones 9-48)
20
4 = UR (zones 9-48)
5 = BR (zones 49-64) 21
NOTE: Zones 9-16 not
available if zone
doubling enabled. 22
Response Time:
0 = 10msec 23
1 = 350msec
2 = 700msec
3 = 1.2 sec 24

Reserved Zones
25
91 = addressable device
report enable/disable
default zone type = 26
[05].
92 = Duress report 27
enable/disable
28

29

30

31

– 43 –
Zone Zn Type Part. Report Input Type Loop Serial No. Location

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49 [1] [BR]

50 [1] [BR]

51 [1] [BR]

52 [1] [BR]

53 [1] [BR]

54 [1] [BR]

55 [1] [BR]

56 [1] [BR]

57 [1] [BR]

58 [1] [BR]

59 [1] [BR]

60 [1] [BR]

61 [1] [BR]

62 [1] [BR]

63 [1] [BR]

– 44 –
Zone Zn Type Part. Report Input Type Loop Serial No. Location

64 [1] [BR]

95 [00] N/A** N/A N/A N/A keypad [1] / [∗]

96 [00] N/A** N/A N/A N/A keypad [3] / [#]

99 [06] † N/A** N/A N/A N/A keypad [∗] / [#]


** Emergency key zones 95, 96, and 99 report the partition of the keypad used to activate the emergency zones.
† “06 = non-SIA controls; “00” = SIA controls

WORKSHEET for ∗57 FUNCTION KEY PROGRAMMING


A B C D Comments
Option Function P1 P2 com P1 P2 com P1 P2 com P1 P2 com

01 Paging

02 Time Display

03 Arm AWAY

04 Arm STAY

05 Arm NIGHT-STAY

06 Step Arming

Device:
07 Device Activation

08 Comm. Test

09 Macro Key 1 Assign each macro key to only a single partition. †

10 Macro Key 2 Assign each macro key to only a single partition. †

11 Macro Key 3 Assign each macro key to only a single partition. †

12 Macro Key 4 Assign each macro key to only a single partition. †

00 Emergency Keys: zone 95 zone 99 zone 96 paging

Personal Emergency n/a

Silent Alarm n/a

Audible Alarm n/a

Fire n/a

Emergency Keys: A = paired keys [1] / [∗] (zone 95); B = paired keys [∗] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
† There are only four macros system-wide.

– 45 –
WORKSHEET for ∗79 OUTPUT RELAY/POWERLINE CARRIER DEVICE PROGRAMMING
Applicable only if Relays and/or Powerline Carrier (X-10) Devices are to be used.
∗79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE OUTPUT TYPE (09-16 apply to VISTA-20P only)
Relay X10 Relay X10
Output Module Pos Unit Output Module Pos Unit
No. Addr. (1-4) No. Description No. Addr. (1-4) No. Description

01 09

02 10

03 11

04 12

05 13

06 14

07 15

08 16

17 On-Board Trigger 1 norm output =

18 On-Board Trigger 2 norm output =

WORKSHEET for ∗81 ZONE LIST PROGRAMMING


Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
NOTE: Record desired zone numbers below, noting that a list may include any or all of system's zone numbers.

List No. Used For… Contains These Zones…


01 General Purpose (GP)

02 General Purpose

03 Chime-by-Zone or GP (see field *26 for Chime-by-Zone option)

04 Cross Zones or GP (see field *85 for Cross Zone Timer option)

05 Night-Stay Zones or GP

06 Dial Delay Disable or GP V20PSIA/V15PSIA: see field *50 for Dial Delay Disable option

07 Unlimited Reports or GP V20PSIA/V15PSIA: see field *93 for Unlimited Reports option

08 General Purpose

09 Zones activating pager 1

10 Zones activating pager 2

11 Zones activating pager 3 (VISTA-20P)

12 Zones activating pager 4 (VISTA-20P)

– 46 –
WORKSHEET for ∗80 OUTPUT FUNCTION PROGRAMMING
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
Notes: 1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
2. For Powerline Carrier devices (plcd), field ✱27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Output Activation Type and Detail Partition Event (for zone list/activated by) Action Output Device
Function Activated by Zone List Zone Type Zone No. Number By Zone List By Zone No. 0 = off Number Type
Number 0=delete (ZL) (ZT) (ZN) (P) 1 = close 2 secs
(V20P=1-48) 1=zn list 1-8 = list (see table 00=none (if using ZT trig) 0 = restore 0 = restore 2 = stay closed V20P=1-18 R = relay
(V15P=1-24) 2=zn type below) V20P: 01-64 0 = any 1 = alarm 1 = alrm/flt/trbl 3 = pulse T = trigger
3=zn no. 1 = partition 1 2 = fault 4 = toggle V15P=1-8, X = X10
V15P: 01-06,
09-34, 49-56
2 = partition 2 3 = trouble 5 = duration 1†† 17, 18
3 = common 6 = duration 2††

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

– 47 –
Output Activation Type and Detail Partition Event (for zone list/activated by) Action Output Device
Function Activated by Zone List Zone Type Zone No. Number By Zone List By Zone No. 0 = off Number Type
Number 0=delete (ZL) (ZT) (ZN) (P) 1 = close 2 secs
(V20P=1-48) 1=zn list 1-8 = list (see table 00=none (if using ZT trig) 0 = restore 0 = restore 2 = stay closed V20P=1-18 R = relay
(V15P=1-24) 2=zn type below) V20P: 01-64 0 = any 1 = alarm 1 = alrm/flt/trbl 3 = pulse T = trigger
3=zn no. 1 = partition 1 2 = fault 4 = toggle V15P=1-8, X = X10
V15P: 01-06,
09-34, 49-56
2 = partition 2 3 = trouble 5 = duration 1†† 17, 18
3 = common 6 = duration 2††

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:


00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary §§ when used with an output function,
01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch the carbon monoxide zone type
02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide§§ 81 = AAV Monitor Zone activates only upon CO alarms. Does
03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 90-91 = Configurable not activate for trouble conditions.
04 = Interior Follower 09 = Fire 23 = No Alarm Response
Choices for System Operation are: Note: In normal operation mode:
20 = Arming–Stay 38 = Chime 58 = Duress
21 = Arming–Away 39 = Any Fire Alarm 60 = AAV Trigger Code + # + 7 + NN Key Entry starts Device
22 = Disarming (Code + OFF) 40 = Bypassing 61 = AVS/GSMV4G session begin § Code + # + 8 + NN Key Entry stops Device
31 = End of Exit Time 41 = **AC Power Failure 62 = AVS/GSMV4G session end §
32 = Start of Entry Time 42 = **System Battery Low 66 = Function key† ** Use 0 (any) for Partition No. (P) entry.
33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure *** Or at Disarming, whichever occurs earlier.
36 = **At Bell Timeout*** 52 = Kissoff 68 = TELCO Line Fault † Use *57 Menu mode to assign the function key.
54 = Fire Zone Reset 78 = Keyswitch red LED††† †† Duration is set in program field *177.
79 = Keyswitch green LED††† ††† Device action not used for these choices.
§ automatically set when appropriate AVS Quick
Command performed.

– 48 –
WORKSHEET for SCHEDULES
(installer code + [#] + [6] [4]; master code can only access schedules 01-16 for VISTA-20P, 01-04 for VISTA-15P, and events 00-07 for both
controls; VISTA-15P supports up to 8 schedules, VISTA-20P supports up to 32 schedules )
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events: Days Days (1-4) (yes/no)
enter 01-18 enter 1-8 enter 1, 2, or 3
(VISTA-20P)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Events: Master/Installer Installer Only
00 = clear event 03 = latch key report 06 = auto disarm 10 = display custom words 8-10
01 = device on/off 04 = forced STAY arm 07 = display “reminder” 11 = periodic test report
02 = user access 05 = forced AWAY arm
Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week

– 49 –
TABLE OF DEVICE ADDRESSES
This Device Uses Address Reports as †† Enabled By…
RF Receiver 00 100 ∗56 zone programming: input device type entry
AUI 1 (touchscreen) 01 n/a automatic if AUI enable field ∗189 enabled for AUI 1
AUI 2 (touchscreen) 02 n/a automatic if AUI enable field ∗189 enabled for AUI 2
AUI 3 (touchscreen) (V20P) 05 n/a automatic if AUI enable field ∗189 enabled for AUI 3
AUI 4 (touchscreen) (V20P) 06 n/a automatic if AUI enable field ∗189 enabled for AUI 4
Communications Device (LRR) 03 103 automatic if communications device enabled in menu mode ∗29
4286 Voice Module 04 104 automatic if phone module access code field ∗28 enabled
Zone Expanders (4219/4229): ∗56 zone programming: input device type entry, then:
module 1 (for zones 09 - 16) 07 107 automatic if zone no. 9-16 entered as AW type or relay assigned
module 2 (for zones 17 - 24) 08 108 automatic if zone no. 17-24 entered as AW type or relay assigned
module 3 (for zones 25 - 32) 09 (V20P) 109 automatic if zone no. 25-32 entered as AW type or relay assigned
module 4 (for zones 33 - 40) 10 (V20P) 110 automatic if zone no. 33-40 entered as AW type or relay assigned
module 5 (for zones 41 - 48) 11 (V20P) 111 automatic if zone no. 41-48 entered as AW type or relay assigned
Relay Modules (4204): ∗79 output device programming: device address prompt:
module 1 12 112 entered at device address prompt
module 2 13 113 entered at device address prompt
module 3 14 (V20P) 114 entered at device address prompt
module 4 15 (V20P) 115 entered at device address prompt
Keypads: data field programming as listed below:
keypad 1 16 n/a always enabled, all sounds enabled.
keypad 2 17 n/a data field ∗190 †† Addressable devices are identified by “1” plus the
keypad 3 18 n/a data field ∗191 device address when reporting. Enter report code for
19 n/a zone 91 to enable device reporting (default = enabled).
keypad 4 data field ∗192
20 n/a See field ∗199 for addressable device (ECP) 3-digit/2-
keypad 5 data field ∗193
21 n/a digit identification keypad display options.
keypad 6 data field ∗194 AUI devices are not supervised and therefore do not
keypad 7 22 n/a
data field ∗195 report.
keypad 8 23 n/a
data field ∗196
RIS Communication 25 n/a automatic

COMPATIBLE DEVICES
2-Wire Smoke Detectors Sounders
Detector Type Model No. AB12M 10” Motorized Bell & Box
Photoelectric w/heat sensor System Sensor 2WT-B
Photoelectric System Sensor 2W-B 702 Outdoor Siren
Photoelectric System Sensor 2151 w/B110LP base 719 2-Channel Siren
713 High Power Speaker
Keypads 746 Indoor Speaker
Fixed-Word Keypad 6150 747 Indoor Siren
Alpha Keypad 6160 747PD Two-Tone Piezo Dynamic Indoor Siren
Voice Keypads 6150V, 6160V 747UL Indoor Siren
Touch Screen Keypad 6272, 6280, TUXEDO 748 Dual Tone Siren
Wireless Receivers 749 Speaker/Horn
Up to 8 transmitters 5881ENL 745VSD3 Voice Siren Driver
Up to 16 transmitters 5881ENM
Up to system max transmitters 5881ENH
Up to system max transmitters 5883H 713 Speaker
WAVE Speaker
Keypad/Receivers WAVE2 Two-Tone Siren
Up to 16 trans, fixed-word 6150RF WAVE2PD Two-Tone Piezo Dynamic Siren
Up to system max trans, alpha 6160RF 5800WAVE Wireless Siren
Modules System Sensor MHW (beige)/; MHW (red) Indoor
Wired Expander Module 4219 Piezo Sounder
Wired Expander/Relay Module 4229
Relay Module 4204
Communication Device GSMV4G, GSMX4G, IGSMV4G etc.
Transformers
25VA, 16.5VAC Plug-In Trans. 1321 (1321CN in Canada)

– 50 –
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and
entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not
exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay time must not
exceed 60 seconds.
3. The maximum number of reports per armed period (field ∗93) must be set to “0” (unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The tamper switch
installed to protect the control unit enclosure door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications, the following
UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring location, or to
delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm the
system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
14. Vent zones are not for use in UL installations.

SIA QUICK REFERENCE GUIDE


1. ∗31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports in armed
period” set in field ∗93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
2. ∗34 Exit Delay: Minimum exit delay is 45 seconds.
3. ∗35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4. ∗37 Audible Exit Warning: Feature always enabled; field does not exist.
5. ∗39 Power Up in Previous State: Must be “1,” power up in previous state.
6. ∗40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91 must be set.
7. ∗50 Burglary Dial Delay: Delay must be minimum of 30 seconds.
8. ∗59 Exit Error Alarm Report Code: Always enabled.
9 ∗68 Cancel Report Code: Default is “code enabled.”
10. ∗69 Recent Closing Report Code: Always enabled.
11. ∗91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be set to “1” (enabled).
12. ∗93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13. Cross zone timer programming is set in field ∗85; cross zone pairs are assigned in zone list 4 using ∗81 Zone List mode.
14. Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code reporting by
programming zone 92 using ∗56 Zone Programming mode.
15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.

ULC S304 REQUIREMENTS (for VISTA-15PCN and VISTA-20PCN)


Refer to the following notes for systems intended for Low Risk Level (low extent of protection) and Medium Risk Level (medium extent of
protection) installations.
Low Risk Level
If the panel is used for Low Risk Level installations, the system must include the following:
• Subscriber control unit may use one telephone number, but it must be programmed that
a) it transmits over the single channel to the receiver once every 24 hour;
b) it detects a loss of communication and initiates the local trouble signal within 180 seconds;
c) in event of failure in the communication channel, all alarm and trouble signals must be annunciated locally.
• Protection circuit conductors shall form one fully supervised circuit so arranged that an alarm signal will be initiated at the central
station from the effect of loss data, an open circuit or other change in normal status.
• Trouble response time must be in compliance with CAN/ULC-S301, Central and Monitoring Station Burglar Alarm Systems
Medium Risk Level
If the panel is used for Medium Risk Level installations, the system must include the following:
• Subscriber control unit may use at least two communication levels, one being the telephone number and the other being a radio
frequency communication channel – the GSM communicator may be used. The Subscriber control unit must be programmed that
a) it transmits over the both channels to the receiver once every 24 hours;
b) failure of communication of either channel is reported to the Central Station on the other channel within 240 sec;
c) the first attempt to send a status change signal shall utilize the Telephone line. Where it is known to have failed, transmission
attempts over the alternate communication channel shall occur.
• Protection circuit conductors shall form double fully supervised circuits so arranged that an alarm signal will be initiated at the central
station from the effect of loss data, an open circuit or other change in normal status.
• Trouble response time must be in compliance with CAN/ULC-S301, Central and Monitoring Station Burglar Alarm Systems
Perimeter, Space, Safe, and Vaults Protection
Protection for perimeter, space, safe, and vaults need to be provided during the installation.
• For the Low Risk Security Level – Accessible openings should be contacted whether fixed or moveable;
• For the Medium Risk Security Level – All moveable and fixed accessible openings should be contacted.

– 51 –
FCC STATEMENTS
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for
your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the
manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the
limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC/IC STATEMENT
This device complies with Part 15 of the FCC rules and RSS 210 of Industry Canada. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may
cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux
conditions suivantes: (1) Cet appareil ne doit pas causer d' interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y
compris les interférences causant une réception indésirable.

TELEPHONE/MODEM INTERFACE
FCC Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration
number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This
equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications
network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements
document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications
company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance
with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the
user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the
equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or
electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals
allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to
the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
Industrie Canada
AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de
protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences
techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de
télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier
qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations.
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de
télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par
l’utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes
téléphoniques et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante
dans les régions rurales.
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des
installations électriques, ou à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui
peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques
dispositifs, à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.

– 52 –
LIMITATIONS STATEMENT

WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other
emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without
power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly.
Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal
path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or
provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal
Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are
as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start
where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not
sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of
fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in
bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing
with matches, or arson. Depending on the nature of the fire and/or location of the smoke detectors, the detector, even if it operates
as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual.
Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion
can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place
behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or
spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive
Infrared Detectors sense changes in temperature; however, as the ambient temperature of the protected area approaches the
temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other
side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then
they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the
alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning
devices, however loud, may not warn hearing-impaired people.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves
from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as
long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm
system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote
keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity
of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used.
External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery
life in a given installation. This wireless system, however, can identify a true low-battery situation, thus allowing time to arrange a
change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to
insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to
learn about these developments.

– 53 –
CONTACTING TECHNICAL SUPPORT
PLEASE, before you call Technical Support, be sure you:
• READ THE INSTRUCTIONS!
• Check all wiring connections.
• Determine that the power supply and/or backup battery are supplying proper voltages.
• Verify your programming information where applicable.
• Note the proper model number of this product, and the version level (if known) along with any documentation
that came with the product.
• Note your Honeywell customer number and/or company name.
Having this information handy will make it easier for us to serve you quickly and effectively.

Technical Support: ............................................................................................... 1-800-645-7492 (8 a.m.-10 p.m. ET.)


MyWebTech: .............................................................. http:// www.honeywell.com/security/hsc/resources/MyWebTech

– 54 –
5800 SERIES TRANSMITTER INPUT LOOP IDENTIFICATION
All of the transmitters illustrated have one or more unique factory assigned input (loop) ID numbers. Each of the inputs
requires its own programming zone (e.g., a 5804's four inputs require four programming zones). For information on any
transmitter not shown, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.
UL NOTE: The following transmitters are not intended for use in UL installations: 5804BD, 5814, 5816TEMP, 5819,
5819WHS and 5819BRS.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
LOOP 1 LOOP 1
(LOW (LOW
SENSITIVITY SENSITIVITY
LOOP
1 LOOP 2 LOOP 2
LOOP 1 (HIGH (HIGH
SENSITIVITY) SENSITIVITY)
LOOP
1 LOOP 3 (TEMP) LOOP 3 (TEMP)
LOOP 4 (TAMPER) LOOP 4 (TAMPER)
5800CO 5800Micra 5800PIR-RES 5800PIR/ 5800PIR-OD
ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" 5800PIR-COM ENROLL AS "RF"
ENROLL AS "RF"

LOOP 2 LOOP 3
ON

LOOP 4 LOOP 4 OF
F LOOP 2
LOOP 1
LOOP 1 LOOP 1
LOOP
1 LOOP LOOP
1 3 ••

LOOP 1
•• •

••• ••••
••
• ••

5800SS1 5 8 0 0 WAV E 5 8 0 4 B D / 5 8 0 4 B DV 5804E 5806/5806W3/5807 5809


E N RO L L A S " R F " P RO G R A M ENROLL AS "BR" ENROLL AS "BR" 5808/5808LST/5808W3 ENROLL AS "RF"
HOUSE ID PROGRAM HOUSE ID ENROLL AS "RF"

LOOP 1
(PRIMARY) LOOP 2 LOOP 2
LOOP 2 (REED) (REED)
LOOP 1 (REED) LOOP 2
(AUX. LOOP 3
CENTER) (TERMINALS)
LOOP 1 LOOP 1 LOOP 3
(TERMINALS) LOOP 3 (TERMINALS) LOOP 1
(AUX. (INTERNAL
LOOP 1 RIGHT) LOOP 1 SHOCK
(TERMINALS) SENSOR
5811 5814 5816 5817 5818MNL 5819 5819S (WHS & BRS)
ENROLL AS "RF" ENROLL ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF"
AS "RF"

SERIAL #2 SERIAL #2
LOOP 1 SERIAL #1 LOOP 1
SERIAL #1
LOOP 1 LOOPS LOOP 3 LOOP 3 LOOP 3 SERIAL #1
SERIAL #1
1-3 (TILT LOOP 2 LOOP 2
SENSOR)
AR
ME
D
SERIAL #2
RE
LOOP 3
SERIAL #2
AD
Y

MIC

ME
SSAG
E LOOP 4
LOOP 1
(TERMINALS) SERIAL #1
LOOP 4
SERIAL #1
SERIAL #2 LOOP 1
LOOP 2
5820L 5821 5822T 5828/5828V 5834-2 5834-4
ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" P RO G R A M ENROLL AS "BR" ENROLL AS "BR"
HOUSE ID

LOOP 1 SERIAL #1
(HIGH LOOP 3 LOOP 1
SECURITY) AW
AY SERIAL #1 (LOW SENSITIVITY)
SERIAL #1 ST
AY LOOP 2
LOOP 1 LOOP 2 LOOP 4 1
LOOP 2
LOOP 1 2
(HIGH SENSITIVITY)
(STANDARD SERIAL #1
SERIAL #2 3

LOOP 1
SECURITY) LOOP 3
4

LOOP 3 (TILT MODE) SERIAL #2 5800-006-V2


LOOP 2
5853 LOOP 4 (TAMPER) 5878
5869 5870API 5898
ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "RF" ENROLL AS "BR" ENROLL AS "RF"