Energy Standard For Buildings Except Low-Rise Residential Buildings
Energy Standard For Buildings Except Low-Rise Residential Buildings
Energy Standard For Buildings Except Low-Rise Residential Buildings
Energy Standard
for Buildings
Except Low-Rise
Residential Buildings
See Informative Appendix H for ASHRAE, IES, and ANSI approval dates.
This addendum was approved by a Standing Standard Project Committee (SSPC) for which the Standards Committee has
established a documented program for regular publication of addenda or revisions, including procedures for timely, docu-
mented, consensus action on requests for change to any part of the standard. Instructions for how to submit a change can
be found on the ASHRAE® website (https://www.ashrae.org/continuous-maintenance).
The latest edition of an ASHRAE Standard may be purchased on the ASHRAE website (www.ashrae.org) or from
ASHRAE Customer Service, 180 Technology Parkway NW, Peachtree Corners, GA 30092. E-mail: [email protected]. Fax:
678-539-2129. Telephone: 404-636-8400 (worldwide), or toll free 1-800-527-4723 (for orders in US and Canada). For
reprint permission, go to www.ashrae.org/permissions.
* Denotes members of voting status when the document was approved for publication
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
ASHRAE STANDARDS COMMITTEE 2020–2021
SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus Standard developed under the auspices of ASHRAE. Consensus is defined
by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this Standard as an ANS, as
“substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority,
but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.”
Compliance with this Standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project
Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all
must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees.
The Senior Manager of Standards of ASHRAE should be contacted for
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.
DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and accepted
industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components, or systems
tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its Standards or Guidelines
will be nonhazardous or free from risk.
ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ANSI is a registered trademark of the American National Standards Institute.
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
The track changes in this document show the changes made in addenda ap, aq, ar, q, s,
and z.
4.2 Compliance
4.2.1 Compliance Paths
4.2.1.1 New Buildings
New buildings shall comply with Sections 4.2.2 through 4.2.5 and either the provisions of
a. Section 5, “Building Envelope”; Section 6, “Heating,
Ventilating, and Air Conditioning”; Section 7, “Service Water Heating”; Section 8,
“Power”; Section 9, “Lighting”; and Section 10, “Other Equipment,” or
b. Section 11, “Energy Cost Budget Method,” or
c. Normative Appendix G, “Performance Rating Method.”
When using Appendix G, the Performance Cost Index (PCI) of new buildings, additions
to existing buildings and/or alterations to existing buildings shall be less than or equal to
the Performance Cost Index Target (PCI t ) when calculated in accordance with the
following:
PCI t = [BBUEC + (BPF × BBREC) - PNA]/BBP
where
PCI = Performance Cost Index calculated in accordance with Section G1.2.
BBUEC = Baseline Building Unregulated Energy Cost, the portion of the annual
energy cost of a baseline building design that is due to unregulated energy
use.
BBREC = Baseline Building Regulated Energy Cost, the portion of the annual energy
cost of a baseline building design that is due to regulated energy use.
BPF = Building Performance Factor from Table 4.2.1.1. For building area types
not listed in Table 4.2.1.1 use “All others.” Where a building has multiple
building area types, the required BPF shall be equal to the area-weighted
average of the building area types.
BBP = Baseline Building Performance.
PBP = Proposed Building Performance including the reduced, annual purchased
energy cost associated with on-site renewable energy generation systems
PBP nre = Proposed Building Performance without any credit for reduced annual
energy costs from on-site renewable energy generation systems.
PNA = Proposed renewable energy contribution not allowed for compliance
Regulated energy cost shall be calculated by multiplying the total energy cost by the
ratio of regulated energy use to total energy use for each fuel type. Unregulated energy cost
shall be calculated by subtracting regulated energy cost from total energy cost.
…
5.4 Mandatory Provisions
5.4.1 Insulation
ANSI/ASHRAE/IES Addenda ap, aq, ar, q, s, z to ANSI/ASHRAE/IES Standard 90.1-2016
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
Where insulation is required in Section 5.5 or Section 5.6, it shall comply with the
requirements found in Section 5.8.1.
5.4.2 Fenestration and Doors
Procedures for determining fenestration and door performance are described in
Section 5.8.2. Product samples used for determining fenestration performance shall be
production line units or representative of units purchased by the consumer or contractor.
5.4.3 Air Leakage
Air leakage control for the building envelope shall comply with this section. Materials and
assemblies that are part of the continuous air barrier and fenestration and doors shall
comply with Section 5.8.3.
5.4.3.1 Continuous Air Barrier
The entire exterior building envelope and the semiexterior building envelope shall be
designed and constructed withhave a continuous air barrier complying with Sections
5.4.3.1.1 and 5.4.3.1.2.
Exceptions to 5.4.3.1
1. Semiheated spaces in Climate Zones 0 through 6, except as
required to complete the continuous air barrier of an adjacent conditioned space.
2. Single wythe concrete masonry buildings in Climate Zone
2B.
5.4.3.1.1 Whole Building Air Leakage
Whole-building pressurization testing shall be conducted in accordance with ASTM E779
or ASTM E1827 by an independent third party. The measured air leakage rate of the
building envelope shall not exceed 0.40 cfm/ft2 under a pressure differential of 0.3 in. of
water, with this air leakage rate normalized by the sum of the above-grade and below-grade
building envelope areas of the conditioned and semiheated space.
Where a building contains both conditioned space and semiheated space compliance shall
be shown:
a. separately for the conditioned space and for the semiheated space, with the air
leakage rate for the conditioned space normalized by the exterior building envelope
area of the conditioned space and the air leakage rate for the semiheated space
normalized by the semiexterior building envelope area of the semiheated space; or
b. for the conditioned space and for the semiheated space together, with the air
leakage rate for the overall space normalized by the sum of the exterior building
envelope area and the semiexterior building envelope area minus the semiexterior
building envelope area that separates the conditioned space from the semiheated
space.
Reporting shall be in compliance with Section 4.2.5.1.2.
Exceptions to 5.4.3.1.1
1. For buildings having over 50,000 ft2 of gross conditioned
floor area, air leakage testing shall be permitted to be conducted on less than the whole
building, provided the following portions of the building are tested and their measured air
leakage is area-weighted by the surface areas of the building envelope:
a. The entire floor area of all stories that have any
spaces directly under a roof.
b. The entire floor area of all stories that have a building
entrance or loading dock.
c. Representative above-grade wall sections of the
building totaling at least 25% of the wall area enclosing the remaining conditioned space;
floor area tested per (a) and (b) shall not be included in the 25%.
2. Where the measured air leakage rate exceeds 0.40 cfm/ft2
but does not exceed 0.60 cfm/ft2, a diagnostic evaluation, such as a smoke tracer or
infrared imaging shall be conducted while the building is pressurized, and any leaks noted
shall be sealed if such sealing can be made without destruction of existing building
components. In addition, a visual inspection of the air barrier shall be conducted, and any
leaks noted shall be sealed if such sealing can be made without destruction of existing
building components. An additional report identifying the corrective actions taken to seal
leaks shall be submitted to the code official and the building owner and shall be deemed
to satisfy the requirements of this section.
3. Continuous air barrier design and installation verification program in accordance with
Section 5.9.2.21.
following portions of the building are tested and their measured air leakage is area-weighted
by the surface areas of the building envelope:
a. The entire floor areafloor area of all stories that have any spaces directly under a
roof.
b. The entire floor areafloor area of all stories that have a building entrance or loading
dock.
c. Representative above-grade wall sections of the building totaling at least 25% of the
wall area enclosing the remaining conditioned space; floor areafloor area tested per (a) and (b)
shall not be included in the 25%.
2. Where the measured air leakage rate exceeds 0.40 cfm/ft2 but does not exceed 0.60
2
cfm/ft , a diagnostic evaluation, such as a smoke tracer or infrared imaging shall be conducted
while the building is pressurized, and any leaks noted shall be sealed if such sealing can be
made without destruction of existing building components. In addition, a visual inspection of
the air barrier shall be conducted, and any leaks noted shall be sealed if such sealing can be
made without destruction of existing building components. An additional report identifying the
corrective actions taken to seal leaks shall be submitted to the code official and the building
owner and shall be deemed to satisfy the requirements of this section.
b. Materials that have an air permeance not exceeding 0.004 cfm/ft2 under a pressure
differential of 0.3 in. of water (1.57 psf) when tested in accordance with ASTM E2178. The
following materials meet these requirements:
1. Plywood—minimum 3/8 in.
2. Oriented strand board—minimum 3/8 in.
3. Extruded polystyrene insulation board—minimum 1/2 in.
4. Foil-faced urethane insulation board—minimum 1/2 in.
5. Exterior gypsum sheathing or interior gypsum board—minimum 1/2 in.
6. Cement board—minimum 1/2 in.
7. Built-up roofing membrane
8. Modified bituminous roof membrane
9. Single-ply roof membrane
10. A Portland cement/sand parge, stucco, or gypsum plaster—minimum 1/2 in. thick
11. Cast-in-place and precast concrete
12. Sheet metal
13. Closed-cell 2 lb/ft3 nominal density spray polyurethane foam—minimum 1 in.
c. Assemblies of materials and components (sealants, tapes, etc.) that have an
average air leakage not to exceed 0.04 cfm/ft2 under a pressure differential of 0.3 in. of water
(1.57 psf) when tested in accordance with ASTM E2357, ASTM E1677, ASTM E1680, or
ASTM E283. The following assemblies meet these requirements:
1. Concrete masonry walls that are
(a) fully grouted, or
(b) painted to fill the pores.
5.4.3.2 Fenestration and Doors
Air leakage for fenestration and doors shall be determined in accordance with
AAMA/WDMA/CSA 101/I.S.2/A440, NFRC 400, or ASTM E283 as specified below. Air
leakage shall be determined by a laboratory accredited by a nationally recognized
c. Assemblies of materials and components (sealants, tapes, etc.)that used as a component of the
continuous air barrier shall have an average air leakage not to exceed 0.04 cfm/ft2 under a pressure
differential of 0.3 in. of water (1.57 psf) when tested in accordance with ASTM E2357, ASTM
E1677, ASTM E1680, or ASTM E283. The following assemblies meet these requirements:
b. The following assemblies meet these comply with the requirements in Table 5.8.3.1:
a) fully grouted, or
2. Shale or clay masonry units that are assembled as a solid wall: without weeps, with nominal width of 4-in. (100
mm) or more, and with Type S mortar.
Air leakage vVerification of the design and installation of the continuous air barrier shall be
determined in accordance with one of the following methods by an independent third party
when using Exception 3 of Section 5.4.3.1.1:
a. An air barrier design and installation verification program
shall be implemented and shall include the following elements:
1. A design review shall be conducted to assess verify
and document compliance with the requirements in Sections 5.4.3.1.1, 5.4.3.1.2,
and the applicable portions of Section 5.4.3.1.3. 5.4.3 and 5.8.3.2.
2. Periodic field inspection of the continuous air barrier
components materials and assemblies shall be conducted during construction
while the continuous air barrier is still accessible for inspection and repair to
verify and document compliance with the requirements of Sections 5.4.3.1.1,
5.4.3.1.2, and 5.8.3. the applicable portions of Section 5.4.3.1.3.
3. Reporting shall be in compliance comply with Section
4.2.5.1.2.
b. A whole-building air leakage verification program shall be
implemented and shall include the following elements:
1. Whole-building pressurization testing shall be performed
in accordance with Section 5.4.3.1.3(a) and the use of any exceptions shall be
documented.
Reporting shall be in compliance comply with Section 4.2.5.1.2.
…
6.5.3.5 Supply Air Temperature Reset Controls
Multiple zone HVAC systems shallmust include controls that are capable of and configured
to automatically reset the supply air temperature in response to representative building
loads, or to outdoor air temperature. The controls shall reset the supply air temperature at
least 25% of the difference between the design supply air temperature and the design room
air temperature. Controls that adjust the reset based on zone humidity are allowed in
Climate Zones 0B, 1B, 2B, 3B, 3C and 4 through 8. HVAC Zzones that are expected to
experience relatively constant loads, such as electronic equipment rooms, shall be have
maximum airflow designed for to accommodate the fully reset supply air temperature.
Informative Note:
HVAC zones that are expected to experience relatively constant loads typically include
electronic equipment rooms and interior zones.
Exceptions to 6.5.3.5
1. Systems in Climate Zones 0A, 1A, 2A, and 3A with less than
3000 cfm (1500 L/s) of design outdoor air.
2. Systems in Climate Zone 2A with less than 10,000 cfm
(5000 L/s) of design outside air.
3. Systems in Climate Zones 0A, 1A, 2A, and 3A with at least 80% outside air and
employing exhaust air energy recovery complying with Section 6.5.6.1.
4. Systems that prevent reheating, recooling, or mixing of heated and cooled supply air.
5. Systems in which at least 75% of the energy for reheating (on an annual basis) is from site
recovered energy or site-solar energy.
6.5.3.5.1 Dehumidification Control Interaction
In climate zones 0A, 1A, 2A, and 3A, the system design shall allow supply air
temperature reset while dehumidification is provided. When dehumidification
control is active, air economizers shall be locked out.
Informative Note:
Examples of HVAC systems that can allow supply air temperature reset while
dehumidifying include cooling of outside air with a separate cooling coil, bypassing return
air around the cooling coil, a dedicated outside air system, and series energy recovery.
…
9.1 General
9.1.1 Scope
This section shall apply to the following:
a. Interior spaces of buildings.
b. Exterior lighting that is powered through the building's or
building site’s electrical service.
Exception to 9.1.1
1. Emergency lighting that is automatically off during normal
building operation.
2. Lighting, including exit signs, that is specifically designated
as required by a health or life safety statute, ordinance, or regulation.
3. Decorative gas lighting systems.
…
9.2.2.3
The following lighting equipment and applications listed in Table 9.2.2.3 shall not
be considered when determining the interior lighting power allowance developed in
accordance with Section 9.5 or 9.6, nor shall the wattage for such lighting be
included in the installed interior lighting power identified in accordance with
Section 9.1.3. However, any suchThis exemption shall only apply when the lighting
and controls shall not be exempt unless it is are in compliance with the
requirements of Table 9.2.2.3.an addition to general lighting and is controlled by
an independent control device. Lighting controls noted in this table are the only
required controls for this equipment and these applications.
1. Display or accent lighting that is an essential element for the
function performed in galleries, museums, and monuments.
2. Lighting that is integral to equipment or instrumentation and
is installed by its manufacturer.
3. Lighting specifically designed for use only during medical
or dental procedures and lighting integral to medical equipment.
4. Lighting integral to both open and glass-enclosed
refrigerator and freezer cases.
5. Lighting integral to food warming and food preparation
equipment.
6. Lighting specifically designed for the life support of
nonhuman life forms.
7. Lighting in retail display windows, provided the display area
is enclosed by ceiling-height partitions.
8. Lighting in interior spaces that have been specifically
designated as a registered interior historic landmark.
9. Lighting that is an integral part of advertising or directional
signage.
10. Exit signs.
Table 9.2.2.3 Exceptions to Interior Lighting Power and Minimum Control Requirements
Item # Equipment/Application In Addition to and Required Controls
controlled
Separately from
General Lighting
Lighting that is integral to equipment, YES No control
1 medical equipment or instrumentation and requirements
is installed by its manufacturer.
Lighting specifically designed for use YES 9.4.1.1(a) – Local
2
only during medical or dental procedures. control
Lighting specifically designed for the life
3
support of non-human life forms.
Lighting for theatrical purposes, including
4 performance, stage, broadcast studio, and
film and video production.
Lighting in sporting activity areas for
5
television broadcasting.
6 Lighting for photographic processes.
Lighting that is an integral part of YES 9.4.1.1(i) – Scheduled
7
advertising or directional signage. shutoff
Lighting integral to both open and glass- YES 9.4.1.1(h) – Automatic
8
enclosed refrigerator and freezer cases. full OFF or 9.4.1.1(i) –
9 Casino gaming areas. NO Scheduled shutoff
Lighting in retail display windows, YES 9.4.1.1(a) – Local
10 provided the display area is enclosed by control and 9.4.1.1(i) –
ceiling-height partitions. Scheduled shutoff
Display or accent lighting that is an YES 9.4.1.1(a) – Local
essential element for the function control and either
11
performed in galleries, museums, and 9.4.1.1(h) – Automatic
monuments. full OFF or 9.4.1.1(i) –
Lighting integral to food warming and Scheduled shutoff
12
food preparation equipment.
Lighting that is for sale or lighting
13
educational demonstration systems.
14 Mirror lighting in dressing rooms.
Accent lighting in religious pulpit and
15
choir areas.
16 Lighting in interior spaces that have been NO
…
Exception to9.4.1.1(i)
The following lighting is not required to be on scheduled shutoff:
1. Lighting in spaces where lighting is required for 24/7
continuous operation.
2. Lighting in spaces where patient care is rendered.
3. Lighting in spaces where automatic shutoff would endanger
the safety or security of the room or building occupants.
4. Lighting load not exceeding 0.02 W/ft2 multiplied by the
gross lighted floor area of the building.
Lighting controls noted in this section are the only required controls for this equipment and
these applications. Lighting exempt from interior lighting power shall be controlled in
accordance with Table 9.2.2.3. Lighting using additional interior lighting power
applications shall be controlled in accordance with Section 9.6.2.
a. The following lighting shall be separately controlled from
Lighting used for the following applications shall be equipped with a local control
independent of the control of the general lighting in all spaces: in accordance with
Section 9.4.1.1(a). In addition, such lighting shall be controlled in accordance with
Section 9.4.1.1(h) or Section 9.4.1.1(i).
1. Display or accent lighting.
2. Lighting in display cases.
3. Nonvisual lighting, such as for plant growth or food
warming.
4. Lighting equipment that is for sale or used for demonstrations
in lighting education.
b. Guestrooms
1. All lighting and all switched receptacles in guestrooms
and suites in hotels, motels, boarding houses, or similar buildings shall be
automatically controlled such that the power to the lighting and switched
receptacles in each enclosed space will be turned off within 20 minutes after all
occupants leave that space.
Exception to 9.4.1.3(b)(1)
Enclosed spaces where the lighting and switched receptacles are controlled by card key controls
and bathrooms are exempt.
2. Bathrooms shall have a separate control device
installed to automatically turn off the bathroom lighting within 30 minutes after
all occupants have left the bathroom.
Exception to 9.4.1.3(b)(2)
Night lighting of up to 5 W per bathroom is exempt.
c. All sSupplemental task lighting, including permanently
installed undershelf or undercabinet lighting, shall be controlled from either (1) a
control device integral to the luminaires or (2) by a wall-mounted control device that
is readily accessible and located so that the occupant can see the controlled lighting a
local control independent of the control of the general lighting in accordance with
Section 9.4.1.1(a). In addition, such lighting shall be controlled in accordance with
Section 9.4.1.1(h) or Section 9.4.1.1(i).
…
minimum efficiency levels, both part load and full load, in accordance with Sections
6.4 and 7.4. Chillers shall use Path A efficiencies as shown in Table 6.8.1-3.
c. Supply Fan Energy in Certain Package Equipment. Where
efficiency ratings include supply fan energy, the efficiency rating shall be adjusted to
remove the supply fan energy. For Budget System Types 3, 4, 6, 9, and 11, calculate
the minimum COPnfcooling and COPnfheating using the equation for the applicable
performance rating as indicated in Tables 6.8.1-1 through 6.8.1-4. Where a full- and
part-load efficiency rating is provided in Tables 6.8.1-1 through 6.8.1-4, the full-load
equation below shall be used:
COP nfcooling = 7.84E-8 × EER × Q + 0.338 × EER
COP nfcooling = –0.0076 × SEER2 + 0.3796 × SEER
COP nfheating = 1.48E-7 × COP 47 × Q + 1.062 × COP 47
(applies to heat pump heating efficiency only)
COP nfheating = –0.0296 × HSPF2 + 0.7134 × HSPF
where COP nfcooling and COP nfheating are the packaged HVAC equipment cooling and
heating energy efficiency, respectively, to be used in the budget building design, which
excludes supply fan power, and Q is the AHRI-rated cooling capacity in Btu/h. If Q is greater
than 760,000 Btu/h, use 760,000 Btu/h in the calculation.
EER, SEER, COP, and HSPF shall be at AHRI test conditions. Fan energy shall
be modeled separately according to Section 11.5.2(h). Supply and return/relief
system fans shall be modeled as operating at least whenever the spaces served are
occupied, except as specifically noted in Table 11.5.2-1.
d. Minimum Outdoor Air Ventilation Rate. Minimum outdoor
air ventilation rates shall be the same for both the budget building design and
proposed design. Exhaust air heat recovery shall be modeled for the budget building
design in accordance with Section 6.5.6.1.
e. Economizers. Budget building systems as listed in Table
11.5.2-1 shall have air economizers or fluid economizers, the same as in the proposed
design, in accordance with Section 6.5.1. The high-limit shutoff shall be in
accordance with Table 11.5.2-4.
f. Preheat Coils. If the proposed design system has a preheat
coil, the budget building design’s system shall be modeled with a preheat coil
controlled in the same manner.
g. Supply Airflow Rates. System design supply air rates for the
budget building design shall be based on a supply-air-to-room-air temperature
difference of 20°F. If return or relief fans are specified in the proposed design, the
budget building design shall also be modeled with the same fan type sized for the
budget system supply fan air quantity less the minimum outdoor air, or 90% of the
supply fan air quantity, whichever is larger.
h. Fan System Efficiency. Fan system efficiency (bhp per cfm of
supply air, including the effect of belt losses but excluding motor and motor drive
losses) shall be the same as the proposed design or up to the limit prescribed in
Section 6.5.3.1, whichever is smaller. If this limit is reached, each fan shall be
proportionally reduced in brake horsepower until the limit is met. Fan electrical
power shall then be determined by adjusting the calculated fan hp by the minimum
motor efficiency prescribed by Section 10.4.1 for the appropriate motor size for each
fan.
i. Equipment Capacities. The equipment capacities for the
budget building design shall be sized proportionally to the capacities in the proposed
design based on sizing runs, i.e., the ratio between the capacities used in the annual
simulations and the capacities determined by the sizing runs shall be the same for
both the proposed design and budget building design. Unmet load hours for the
proposed design or baseline building designs shall not exceed 300 hours. The unmet
load hours for the proposed design shall not exceed the unmet load hours for the
budget building design. Alternatively, unmet load hours exceeding these limits may
be approved by the building official, provided that sufficient justification is given
indicating that the accuracy of the simulation is not significantly compromised by
these unmet loads.
j. Determining the HVAC System. Each HVAC system in a
proposed design is mapped on a one-to-one correspondence with one of eleven
HVAC systems in the budget building design. To determine the budget building
system, do the following:
1. Enter Figure 11.5.2 at “Water” if the proposed design
system condenser is water or evaporatively cooled; enter Figure 11.5.2 at
“Air/None” if the condenser is air cooled. Closed-circuit dry coolers shall be
considered air cooled. Systems utilizing district cooling shall be treated as if the
condenser water type were “water.” If no mechanical cooling is specified or the
mechanical cooling system in the proposed design does not require heat rejection,
the system shall be treated as if the condenser water type were “Air.” For proposed
designs with ground-source or groundwater-source heat pumps, the budget system
shall be water-source heat pump (System 6).
2. Select the path that corresponds to the proposed design
heat source: electric resistance, heat pump (including air source and water source),
or fuel-fired. Systems utilizing district heating (steam or hot water) shall be treated
as if the heating system type were “Fossil Fuel.” Systems with no heating capability
shall be treated as if the heating system type were “Fossil Fuel.” For systems with
mixed fuel heating sources, the system or systems that use the secondary heating
source type (the one with the smallest total installed output capacity for the spaces
served by the system) shall be modeled identically in the budget building design,
and the primary heating source type shall be used in Figure 11.5.2 to determine
budget system type.
3. Select the budget building design system category. The
system under “Single-Zone Residential System” shall be selected if the HVAC
system in the proposed design is a single-zone system and serves a residential
space. The system under “Single-Zone Nonresidential System” shall be selected if
the HVAC system in the proposed design is a single-zone system and serves other
than residential spaces. The system under “All Other” shall be selected for all
other cases.
k. Kitchen Exhaust. For kitchens with a total exhaust hood
airflow rate greater than 5000 cfm, use a demand ventilation system on 75% of the
exhaust air. The system shall reduce exhaust and replacement air system airflow rates
by 50% for one half of the kitchen occupied hours in the baseline building design. If
the proposed design uses demand ventilation, the same airflow rate schedule shall be
used. The maximum exhaust flow rate allowed for the hood or hood section shall meet
the requirements of Section 6.5.7.2.2 for the numbers and types of hoods and
appliances provided in the proposed design.
Chillers shall use Path A efficiencies as shown in Table 6.8.1-3. Where efficiency
ratings include supply fan energy, the efficiency rating shall be adjusted to remove the
supply fan energy. For Baseline HVAC Systems 1, 2, 3, 4, 5, and 6, calculate the
minimum COP nfcooling and COP nfheating using the equation for the applicable
performance rating as indicated in Tables 6.8.1-1 through 6.8.1-4. Where a full- and
part-load efficiency rating is provided in Tables 6.8.1-1 through 6.8.1-4, the full-load
equation below shall be used:Fan energy shall be modeled separately according to
Section G3.1.2.9.
COP nfcooling = 7.84E-8 × EER × Q + 0.338 × EER
COP nfcooling = –0.0076 × SEER2 + 0.3796 × SEER
COP nfheating = 1.48E-7 × COP 47 × Q + 1.062 × COP 47
(applies to heat pump heating efficiency only)
COP nfheating = –0.0296 × HSPF2 + 0.7134 × HSPF
where COP nfcooling and COP nfheating are the packaged HVAC equipment cooling and
heating energy efficiency, respectively, to be used in the baseline building design,
which excludes supply fan power., and Q is the AHRI-rated cooling capacity in Btu.
EER, SEER, COP, and HSPF shall be at AHRI test conditions. Fan energy shall be
modeled separately according to Section G3.1.2.9.
…
Table G3.5.2 Performance Rating Method Electrically Operated Unitary and Applied Heat Pumps—
Minimum Efficiency Requirements
Heating Section Subcategory or Test
Equipment Type Size Category Type Rating Condition Minimum Efficiency Procedure
Air-cooled <65,000 Btu/h All Single package 9.7 SEER3.0 AHRI
(cooling mode) COP nfcooling 210/240
≥65,000 Btu/h and Split-system and 9.9 EER3.4 COP nfcooling AHRI
<135,000 Btu/h single-package 340/360
≥135,000 Btu/h and 9.1 EER3.2 COP nfcooling
<240,000 Btu/h
≥240,000 Btu/h 8.8 EER
8.9 IEER3.1
COP nfcooling
Air-cooled <65,000 Btu/h Single-package 6.6 HSPF3.4 AHRI
(heating mode) (cooling capacity) COP nfheating 210/240
≥65,000 Btu/h and 47°F db/43°F wb 3.2 COP H 3.4 AHRI
<135,000 Btu/h outdoor air COP nfheating 340/360
(cooling capacity)
17°F db/15°F wb 2.2 COP H 2.3
outdoor air COP nfheating
Table G3.5.3 Performance Rating Method Water Chilling Packages—Minimum Efficiency Requirements
Subcategory or
Equipment Type Size Category Rating Condition Minimum Efficiency Test Procedure
Water-cooled, electrically <150 tons kW/ton 0.790 FL ARI 550/590
operated, positive 0.676 IPLV.IP
displacement ≥150 tons and 0.718 FL
(rotary screw and scroll) <300 tons 0.629 IPLV.IP
≥300 tons 0.639 FL
0.572 IPLV.IP
Water-cooled, electrically <150 tons kW/ton 0.703 FL ARI 550/590
operated, centrifugal 0.670 IPLV.IP
≥150 tons and 0.634 FL
<300 tons 0.596 IPLV.IP
≥300 tons 0.576 FL
0.549 IPLV.IP
Table G3.5.4 Performance Rating Method Electrically Operated Packaged Terminal Air Conditioners,
Packaged Terminal Heat Pumps
Subcategory or
Equipment Type Size Category Rating Condition Minimum Efficiencya Test Procedure
PTAC (cooling mode) All capacities 95°F db outdoor air 12.5 – (0.213 × Cap/1000) AHRI 310/380
EER3.2 COP nfcooling
PTHP (cooling mode) All capacities 95°F db outdoor air 12.3 – (0.213 × Cap/1000) AHRI 310/380
EER3.1 COP nfcooling
PTHP (heating mode) All capacities 3.2 – (0.026 × Cap/1000) COP3.1 AHRI 310/380
COP nfheating
a. “Cap” means the rated cooling capacity of the product in Btu/h. If the unit's capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the unit's
capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.
Table G3.5.5 Performance Rating Method Warm-Air Furnaces and Unit Heaters
Subcategory or
Equipment Type Size Category Rating Condition Minimum Efficiency Test Procedure
Warm-air furnace, gas-fired <225,000 Btu/h 78% AFUE or 80% E t DOE 10 CFR Part 430
or ANSI Z21.47
≥225,000 Btu/h Maximum capacity 80% E c ANSI Z21.47
Warm-air unit heaters, gas-fired All capacities Maximum capacity 80% E c ANSI Z83.8
Table G3.6 Performance Rating Method Lighting Power Densities for Building Exteriors
Uncovered Parking Areas
Parking lots and drives 0.15 W/ft2
Building Grounds
Walkways less than 10 ft wide 1.0 W/linear foot
Walkways 10 ft wide or greater 0.2 W/ft2
Plaza areas
Special feature areas
200.0 95.0
This appendix is not part of this standard. It is merely informative and does not contain requirements necessary
for conformance to the standard. It has not been processed according to the ANSI requirements for a
standard and may contain material that has not been subject to public review or a consensus process. Unresolved
objectors on informative material are not offered the right to appeal. at ASHRAE or ANSI.
Informative Appendix H
bg (formerly 9.2, 9.3, Table Adds a simplified building method for interior lighting in offices, schools, and 1/12/2019 10/3/2019 12/14/2018 2/13/2019
addendum bg to 9.3 retail buildings, and exterior lighting. This includes the addition of table 9.3.
90.1-2013)
dn (formerly A9.4 Allows the use of the R-value of an airspace in enclosed cavities with or 1/12/2019 1/16/2019 12/14/2018 1/17/2019
addendum dn without insulation (Appendix A). Expands the R-value table in Appendix A
to 90.1-2013) (based on 2009 ASHRAE Handbook—Fundamentals, Chapter 26).
a 6.4.3.3.3, Changes term "ventilation air" to "outdoor air" in multiple locations. Revises 1/20/2018 1/24/2018 1/8/2018 1/25/2018
6.3.3.4.2, tables and footnotes. Clarifies requirements for economizer return dampers.
6.5.1.1.4
b 5.5.3.1.1, 12 Updates reference to ANSI/CRRC S100 "Standard Test Methods for 6/24/2017 6/24/2017 6/13/2017 6/29/2017
Determining Radiative Properties of Materials".
c 3.2 Adds rooftop monitors to definition of fixed and operable vertical fenestration. 6/24/2017 6/24/2017 6/13/2017 6/29/2017
d Tables G3.1.1 \ Modifies text to make it consistent with other portions of Appendix G for 6/24/2017 6/24/2017 6/13/2017 6/29/2017
projects undergoing phased permitting.
e Table G3.1.11 Adds direction that SWH piping losses shall not be modeled. 6/24/2017 6/24/2017 6/13/2017 6/29/2017
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
f G3.1.2.1 Modifies text to require that the capacity used for selecting the system 6/24/2017 6/24/2017 6/13/2017 6/29/2017
efficiency represents that for the size of the actual zone instead of the size of
the zones as combined into a single thermal block.
g 3.2, 6.3.2, Provides definition of "occupied-standby mode" and adds new ventilation air 1/20/2018 1/24/2018 1/8/2018 1/25/2018
6.5.3.8 requirements for zones served rooms in occupied-standby mode.
h 6.5.6.1 Clarifies that exhaust air energy recovery systems should be sized to meet 1/20/2018 1/24/2018 1/8/2018 1/25/2018
both heating and cooling design conditions unless one mode is not exempted
by existing exceptions.
j 6.4.3.8 Changes an exception related to demand control ventilation. 6/24/2017 6/24/2017 6/13/2017 6/29/2017
k 3.2, 6.4.3.3.5 Revises definition of "networked guest room control system" and aligns 6/23/2018 6/27/2018 5/30/2018 7/25/2018
HVAC and lighting time-out periods for guest rooms.
l Table G3.1.2.9 Adds requirements for fan break horsepower for two systems. 1/20/2018 1/24/2018 1/8/2018 1/25/2018
m Table G3.1.5 Lowers baseline building performance air leakage and sets an air leakage 1/12/2019 1/16/19 12/14/2018 2/13/2019
value to be used in conjunction with the air-barrier verification path.
n 3.2 Removes ten unused definitions and changes definition of "unitary cooling 1/20/2018 1/24/2018 1/8/2018 1/25/2018
equipment" to "unitary air conditioners".
o 3.2, 4.2.2.3, 5.5, Revises the submittals section of the envelope and power chapters for 6/23/2018 6/27/2018 5/30/2018 6/28/2018
5.7 through consistency across the standard.
11.7, G 1.3
p Table 6.1.8 -14 Revises the rating conditions for indoor pool dehumidifiers. 1/20/2018 1/24/2018 1/8/2018 1/25/2018
q 5.4.3, 5.5, 5.8.3, Clarifies and restructures air leakage requirements for the building envelope. 9/14/2018 10/10/2018 10/23/2018 12/7/2018
5.9.1
r G3.1.2.6 Specifies air economizer control types for Appendix G. 1/20/2018 1/24/2018 1/8/2018 1/25/2018
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
s 4.2.1.1, Modifies the Performance Cost Index (PCI) equation to implement a 5% 9/14/2018 10/10/2018 10/23/2018 12/7/2018
11.4.3.1, G2.4 limitation on renewable energy usage and clarifies what types of renewable
energy systems are eligible.
t 9.4.2, Table Expands the exterior LPD application table to cover additional exterior 6/22/2019 6/26/2019 6/10/2019 7/24/2019
9.4.2-2 spaces that are not currently in the exterior LPD table
v 6.5.6.3 Adds section 6.5.6.3 containing heat recovery requirements for space 6/22/2019 6/26/2019 6/10/2019 7/24/2019
conditioning in acute inpatient hospitals.
x 4.1.1.2, 4.2.1.1, Clarifies compliance paths for new construction, additions, and alterations. 6/23/2018 6/27/2018 5/30/2018 6/28/2018
4.2.1.2, 4.2.1.3
y G3.1.2.2 Fixes duct sizing run parameters within the Appendix G. 6/22/2019 6/26/2019 6/10/2019 7/1/2019
z G3.1.2.1, Table Modifies the formulas in Section 11 and G3.1.2.1 for removing fan energy 9/14/2018 9/28/2018 10/23/2018 10/1/2018
G3.5.1, Table from baseline packaged heating and cooling efficiency ratings to cap the
G3.5.2 system capacity equations in Section 11 to levels allowed in Section 6 and
provide a fixed baseline efficiency rating for Appendix G.
ab 3.2 Modifies definition of "door", "entrance door", "fenestration", and "sectional 6/23/2018 6/27/2018 5/30/2018 6/28/2018
garage door".
ac 3.1, 3.2 Clarifies use of defined terms to include the term with different tense or 6/23/2018 6/27/2018 5/30/2018 6/28/2018
plurality.
ad 5.2 through This addendum clarifies the requirements for showing compliance using the 6/23/2018 6/27/2018 5/30/2018 6/28/2018
11.2 methods in Sections 5‐10, or Section 11, or Appendix G.
ae 3.2, 6.4.3.6, Clarify humidification and dehumidification control requirements. 6/23/2018 6/27/2018 5/30/2018 6/28/2018
G3.1.3.18
ag Table G3.1.12 Provides accounts for the inclusion of automatic receptacle controls in a 6/23/2018 6/27/2018 5/30/2018 6/28/2018
proposed building design for spaces that are not required to have them.
ah 9.1.4 Updates the language and terminology of the lighting wattage section. Also 6/23/2018 6/27/2018 5/30/2018 6/28/2018
adds a section specifically to address using DC power over Cat6 structured
cable for connection of LED lighting to a remote power supply.
ai 3.2., 4.2.5, Restructures commissioning and functional testing requirements in all 1/12/2019 1/16/2019 12/14/2018 2/13/2019
5.2.9, 6.7.2.4, sections of Standard 90.1 to require verification for smaller and simpler
9.4.3, 5.9 buildings and commissioning for larger and more complex buildings.
through 10.9,
11.2
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
aj 3.2, 6.5.1, Adds a new definition "process application" and uses it throughout Standard 1/12/2019 1/16/2019 12/14/2018 2/13/2019
6.5.2.3, 6.5.4.4 in place of "process load".
ak Table G3.1.5, Defines SHGC baseline for buildings in zones where there is no prescriptive 6/23/2018 6/27/2018 5/30/2018 6/28/2018
Tables G3.4-1 maximum SHGC.
through G3.4-8
al Table G3.1.3, Clarifies the modeling rules within section G3.1. 6/22/2019 6/26/2019 6/10/19 7/1/2019
Table G3.1.7
am 6.5.6.4 Adds an indoor pool dehumidifier energy recovery requirement in new 6/23/2018 6/27/2018 5/30/2018 6/28/2018
section 6.5.6.4.
an 3.2; 10.4.7; Provides a new table (Table 10.8.6) of information about the new efficiency 6/22/2019 6/26/2019 6/10/2019 7/24/2019
Table 10.8-6; requirements for commercial and industrial clean water pumps to users of
12; Appendix E ASHRAE 90.1. It also provides new definitions that are needed to
accompany the table. New section 10.4.7 was also added.
ao 3.2; 6.5.3.1.3; Introduces the revised fan product efficiency requirement FEI and 6/22/2019 6/26/2019 6/10/2019 7/24/2019
12 complements the fan power limitation in section 6.5.3.1.1.
ap 6.5.3.5 Revises supply air temperature reset controls. 9/14/2018 9/28/19 10/23/2018 10/1/2018
aq 9.1.1, 9.2.2.3, Clarifies lighting control requirements for applications not covered in Section 9/14/2018 9/28/19 10/23/2018 10/1/2018
9.4.1.1, 9.4.1.3, 9.6.2.
9.4.4, 9.6.2
ar Table G3.1.12, Cleanup of motor requirements in Appendix G related to Addend di in 9/14/2018 9/28/19 10/23/2018 10/1/2018
G3.1.2.9, Table Standard 90.1-2016.
G 3.5.5, Table
G.3.5.6, Table
G3.6, Table
G3.9.1
at 11.5.1; G1.2.2 Revises language for energy accounting at buildings that provide fuel or 6/22/2019 6/26/2019 6/10/2019 7/24/2019
electricity to vehicles.
au 6.5.2.1 Eliminates the requirement that zones with DDC have air flow rates that are 1/12/2019 1/16/2019 12/14/2018 1/17/2019
no more than 20% of the zone design peak flow rate.
aw 3.2; Tables 5.5- Revises the fenestration prescriptive criteria in Tables 5.5-0 through 5.5-8. 6/22/2019 6/26/2019 6/10/2019 7/24/2019
0 through 5.5-8,
5.8.2.5, 12
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
ay 3.2, 6.5.6 Provides separate requirements for nontransient dwelling unit exhaust air 6/22/2019 6/26/2019 6/10/2019 7/24/2019
energy recovery.
az Table G3.1.17 Revises the modeling methodology language to clarify the baseline and 1/12/2019 1/16/2019 12/14/2018 1/17/2019
proposed designs for refrigeration equipment.
ba Table G3.1.1 Establishes a methodology for determining the baseline flow rates on 6/22/2019 6/26/2019 6/10/2019 7/1/2019
Table G3.1.11 projects where service water-heating is demonstrated to be reduced by water
conservation measures that reduce the physical volume of service water
required.
bb Table 9.6.1 Revises the lighting power densities for the Space-by-Space method 6/22/2019 6/26/2019 6/10/2019 7/24/2019
bd Table 6.8.1-16 Adds the minimum efficiency requirements of Heat Pump and Heat Reclaim 6/22/2019 6/26/2019 6/10/2019 7/1/2019
Chiller Packages. and
be 6.4.1.1; Table Revises the efficiency requirements for Computer Room air conditioners. 7/22/2019 8/15/2019 7/19/2019 8/19/2019
6.8.1-10 &
6.8.1-17
bf 5.4.3.4; 10.4.5 Establishes an alternative to the requirement for vestibules by use of an air 6/22/2019 6/26/2019 6/10/2019 7/24/2019
curtain that meets specific requirements prescribed in the proposed
language. Adds new section 10.4.5.
bh Table 5.8.3.2 Corrects an omission related to nonswinging doors in Table 5.8.3.2 6/22/2019 6/26/2019 6/10/2019 7/1/2019
bi 11.4.2; 12; Updates the reference year for Standard 140 in Sections 11 and 12 as well 6/22/2019 6/26/2019 6/10/2019 7/1/2019
Appendix C; as Appendix C and G.
Appendix G
bj 6.5.5.1 Adds tables to the list of products that are exempt from meeting the 6/22/2019 6/26/2019 6/10/2019 7/1/2019
requirements of section 6.5.6 - Heat Rejection Equipment.
bk 3.2, 11.4.3.2, Clarifies that such projects must model the same electricity generation 6/22/2019 6/26/2019 6/10/2019 7/1/2019
G2.4.2 system in the baseline and proposed design and is aligned with the
interpretation IC 90.1- 2013-16 OF ANSI/ASHRAE/IES STANDARD 90.1-
2013 form January 21, 2018.
bl Table 6.8.1-1 Revises Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and 6/22/2019 6/26/2019 6/10/2019 7/1/2019
Condensing Units—Minimum Efficiency
Requirements.
bm Table 6.8.1-2, Revises Table 6.8.1-2 Electrically Operated Air Cooled Unitary Heat 7/22/2019 8/15/2019 7/19/2019 8/19/2019
6.8.1-15 Pumps—Minimum Efficiency Requirements. Adds Table 6.8.1-15.
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
bn 3.2, Table Revises Table 6.8.1-4 Electrically Operated Packaged Terminal Air 7/22/2019 8/15/2019 7/19/2019 8/19/2019
6.8.1-4, Table Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air
F3 Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners,
and Room Air Conditioner Heat Pumps—Minimum Efficiency Requirements.
Adds Table F-3.
bo 3; Table 6.8.1- Revises Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air 6/26/2019 8/1/2019 7/19/2019 8/26/2019
5; Table F-4 Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit
Heaters—Minimum Efficiency Requirements and adds Table F-4 Residential
Warm Air Furnaces – Minimum Efficiency Requirements for sale in the US
(see 10 CFR Part 430).
bp Table 6.8.1-6; Revises Table 6.8.1.6 – Gas and Oil-Fired Boilers – Minimum Efficiency 7/22/2019 8/15/2019 7/19/2019 8/19/2019
Table F-5 Requirements and adds table F-5 - Residential Boiler Minimum Efficiency
Requirements for applications in the US (Refer to 10 CFR 430).
bq Table 6.8.1-7; Revises Table 6.8.1-7 Performance Requirements for Heat Rejection 6/22/2019 6/26/2019 6/10/2019 7/1/2019
12 Equipment—Minimum Efficiency Requirements.
br Table 6.8.1-11 Revises the previous Tables 6.8.1-12 & 13 and combines them into one table 7/22/2019 8/15/2019 7/19/2019 8/19/2019
- Table 6.8.1-131 Commercial Refrigerators, Commercial Freezers and
Refrigeration—Minimum Efficiency Requirements.
bs Table 7.8; F2; Revises Table 7.8 Performance Requirements for Water-Heating 7/22/2019 8/15/2019 7/19/2019 8/19/2019
Table F-2 Equipment—Minimum Efficiency Requirements and Table F-2 Minimum
Energy Efficiency Requirements for Water Heaters.
bt Table 4.2.1.1 Revises Table 4.2.1.1 Building Performance Factor (BPF). 6/22/2019 6/26/2019 6/10/2019 7/1/2019
bu Table G3.1.1-1, Clarifies requirements in the Appendix G as they related to HVAC zones and 7/22/2019 8/15/2019 7/19/2019 8/19/2019
G3.1.1, G3.1.3, baseline heating.
Table G3.4-1
through Table
G3.4-8
bv 6.2.1, 6.6.2, Clarifies that designers have the option to use ASHRAE Standard 90.4 7/22/2019 8/15/2019 7/19/2019 8/19/2019
8.2.1, 8.6.1 requirements instead of ASHRAE 90.1 requirements in computer rooms that
have an IT equipment load larger than 10 kW. Adds section 8.6.1.
bx 3.2, A6.1, A6.3 Adds heated slab F-factors for multiple combinations of under-slab and 6/22/2019 6/26/2019 6/10/2019 6/27/2019
perimeter insulation in Appendix A. Adds Table A6.3.1-1&2.
bz 3.2; Appendix Clarifies requirements of Appendix C as they pertain to informative outputs, 6/22/2019 6/26/2019 6/10/2019 7/1/2019
C1.4, C2, the schedule of shades, energy costs, and updated references to Section 6.
C3.1.2, C3.3,
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
C3.5.5.1,
C3.5.8
ca Table A3.2.3 Adds U-factors to Table A3.2.3 for use of continuous insulation on metal 6/22/2019 6/26/2019 6/10/2019 7/1/2019
building walls with double layer cavity insulation.
cc A9.4.6 Clarifies the limitations of the calculation procedures in A9.4.6. 6/22/2019 6/26/2019 6/10/2019 7/1/2019
ce 6.5.3.1.2 Makes revisions to provide energy savings potential by removing one of three 6/22/2019 6/26/2019 6/10/2019 7/1/2019
criteria for fan motor selections, increasing the design options for load-
matching variable-speed fan applications, accommodating new motor and
drive technologies, and simplifying the motor selection criteria for fans.
cf 6.4.5 Adds vacuum insulating glazing to the list of options for reach-in doors in 7/22/2019 8/15/2019 7/19/2019 8/19/2019
walk-in coolers and freezers.
cg Table 9.5.1 Revises Table 9.5.1 Lighting Power Density Allowances Using the Building 6/22/2019 6/26/2019 6/10/2019 7/1/2019
Area Method.
ch 3.2; 9.4.1.1 (e) Clarifies daylighted area requirements as they relate to skylights and clarifies 6/22/2019 6/26/2019 6/10/2019 6/27/2019
primary sidelighting requirements.
ci Table 4.2.1.1 Further revises Table 4.2.1.1 Building Performance Factor (BPF). 6/22/2019 6/26/2019 6/10/2019 7/1/2019
cj Table 11.5.1.6; Revises the energy cost budget method in reference to lighting. 6/22/2019 6/26/2019 6/10/2019 7/1/2019
Table G3.1.6;
Table G3.7
cl 3.2; 11; Clarifies requirements throughout Section 11 to better align with Appendix G 6/26/2019 8/1/2019 7/19/2019 8/26/2019
Appendix G providing greater consistency between the two sections.
cm 6.5.2.1 Revises exceptions related to DDC enabled zones. 7/22/2019 8/15/2019 7/19/2019 8/19/2019
cn 6.4, 6.4.1.1, Cleans up outdated language regarding walk-in cooler and walk-in freezer 6/22/2019 6/26/2019 6/10/2019 7/1/2019
6.4.5m; Tables requirements, and make the requirements consistent with current federal
6.8.1-18,19, & regulations that either already came into effect June 5, 2017 or will come into
20. effect July 10, 2020. Adds new section 6.4.5m and Tables 6.8.1-18, 19, & 20.
co 12 Revises the normative references in Standard 90.1. 6/22/2019 6/26/2019 6/10/2019 7/1/2019
cq 3.2; 6.4.1.2, Makes clarifications ensure that the maximum fan power input is properly 7/22/2019 8/15/2019 7/19/2019 8/19/2019
6.5.3.1.3 reported for installations both inside and outside the United States. Adds
sections 6.4.1.3 and 6.5.3.1.3.
ct 12 Updates the CTI normative reference in Standard 90.1. 7/22/2019 8/15/2019 7/19/2019 8/19/2019
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
cu 6.4.1.1, 6.4.1.5, Revises requirements for liquid-to-liquid heat exchangers. 7/22/2019 8/15/2019 7/19/2019 8/19/2019
Table 6.8.1-8
cv 9.4.1.2 Updates lighting control requirements for parking garages in section 9.4.1.2. 6/26/2019 8/1/2019 7/19/2019 8/26/2019
cw 9.4.1.1(e), Revises the daylight responsiveness requirements to continuous dimming. 6/26/2019 8/1/2019 7/19/2019 8/26/2019
9.4.1.1(f)
cy 9.4.1(e) Revises the sidelighting requirement exceptions. 7/22/2019 8/15/2019 7/19/2019 8/19/2019
NOTE
Approved errata or interpretations for this standard can be downloaded free of charge from the ASHRAE Web site at www.ashrae.org/technology.
a. *These descriptions may not be complete and are provided for information only.
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment.
ASHRAE’s members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of
the systems and components in their responsibility while maximizing the beneficial effects these systems provide,
consistent with accepted Standards and the practical state of the art.
ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the
indoor and outdoor environment to a greater extent than specified by the Standards and Guidelines as established by
itself and other responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive Technical Committee structure,
continue to generate up-to-date Standards and Guidelines where appropriate and adopt, recommend, and promote
those new and revised Standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date Standards and design considerations as the
material is systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and
will seek out and disseminate information from other responsible organizations that is pertinent, as guides to updating
Standards and Guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the
system’s intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope
operates. However, energy source selection and the possible environmental impact due to the energy source and
energy transportation will be considered where possible. Recommendations concerning energy source selection
should be made by its members.
© ASHRAE. Per international copyright law, additional reproduction, distribution, or transmission in either
print or digital form is not permitted without ASHRAE's prior written permission.
About ASHRAE
Founded in 1894, ASHRAE is a global professional society committed to serve humanity by advancing the arts and
sciences of heating, ventilation, air conditioning, refrigeration, and their allied fields.
As an industry leader in research, standards writing, publishing, certification, and continuing education, ASHRAE
and its members are dedicated to promoting a healthy and sustainable built environment for all, through strategic
partnerships with organizations in the HVAC&R community and across related industries.
To stay current with this and other ASHRAE Standards and Guidelines, visit www.ashrae.org/standards, and
connect on LinkedIn, Facebook, Twitter, and YouTube.
To ensure that you have all of the approved addenda, errata, and interpretations for this
Standard, visit www.ashrae.org/standards to download them free of charge.
Addenda, errata, and interpretations for ASHRAE Standards and Guidelines are no longer
distributed with copies of the Standards and Guidelines. ASHRAE provides these addenda,
errata, and interpretations only in electronic form to promote more sustainable use of
resources.
3/21