ICC Fiber Acceptance Criteria
ICC Fiber Acceptance Criteria
ICC Fiber Acceptance Criteria
AC32
PREFACE
Evaluation reports issued by ICC Evaluation Service, Inc. (ICC-ES), are based upon performance features of the International family
of codes and other widely adopted code families, including the Uniform Codes, the BOCA National Codes, and the SBCCI Standard Codes.
Section 104.11 of the International Building Code® reads as follows:
The provisions of this code are not intended to prevent the installation of any materials or to prohibit any design or method
of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative
material, design or method of construction shall be approved where the building official finds that the proposed design is
satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for
the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance,
durability and safety.
Similar provisions are contained in the Uniform Codes, the National Codes, and the Standard Codes.
This acceptance criteria has been issued to provide all interested parties with guidelines for demonstrating compliance with performance
features of the applicable code(s) referenced in the acceptance criteria. The criteria was developed and adopted following public hearings
conducted by the ICC-ES Evaluation Committee, and is effective on the date shown above. All reports issued or reissued on or after the effective
date must comply with this criteria, while reports issued prior to this date may be in compliance with this criteria or with the previous edition. If the
criteria is an updated version from the previous edition, a solid vertical line (›) in the margin within the criteria indicates a technical change, addition,
or deletion from the previous edition. A deletion indicator (º) is provided in the margin where a paragraph has been deleted if the deletion involved
a technical change. This criteria may be further revised as the need dictates.
ICC-ES may consider alternate criteria, provided the report applicant submits valid data demonstrating that the alternate criteria are
at least equivalent to the criteria set forth in this document, and otherwise demonstrate compliance with the performance features of the codes.
Notwithstanding that a product, material, or type or method of construction meets the requirements of the criteria set forth in this document, or
that it can be demonstrated that valid alternate criteria are equivalent to the criteria in this document and otherwise demonstrate compliance with
the performance features of the codes, ICC-ES retains the right to refuse to issue or renew an evaluation report, if the product, material, or type
or method of construction is such that either unusual care with its installation or use must be exercised for satisfactory performance, or if
malfunctioning is apt to cause unreasonable property damage or personal injury or sickness relative to the benefits to be achieved by the use of
the product, material, or type or method of construction.
Copyright © 2007
Business/Regional Office P 5360 Workman Mill Road, Whittier, California 90601 P (562) 699-0543
www.icc-es.org Regional Office P 900 Montclair Road, Suite A, Birmingham, Alabama 35213 P (205) 599-9800
Regional Office P 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 P (708) 799-2305
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
1.0 INTRODUCTION 1.3.2.3 ASTM C 78-02, Test Method for Flexural
Strength of Concrete (Using Simple Beam with Third-Point
1.1 Purpose: The purpose of this acceptance criteria is Loading).
to establish requirements for concrete with synthetic fibers
to be recognized in an ICC Evaluation Service, Inc. (ICC- 1.3.2.4 ASTM C 94, Standard Specification for Ready-
ES), evaluation report under the 2006 International Building Mixed Concrete.
Code® (IBC), the 2006 International Residential Code® 1.3.2.5 ASTM C 192, Standard Practice for Making
(IRC), the BOCA® National Building Code/1999 (BNBC), the
and Curing Concrete Test Specimens in the Laboratory.
1999 Standard Building Code© (SBC) and the 1997 Uniform
Building Code™ (UBC). The bases of recognition are IBC 1.3.2.6 ASTM C 234-91a, Test Method for Bond
Section 104.11, IRC Section R104.11, BNBC Section 106.4, Strength1.
SBC Section 103.7 and UBC Section 104.2.8. Applicable 1.3.2.7 ASTM C 403-99, Standard Test Method for
code sections in the IBC are Sections 1909 (Structural Plain Time of Setting of Concrete Mixtures by Penetration
Concrete) and 1910 (Minimum Slab Provisions); in the IRC Resistance.
are Table R402.2 (Minimum Specified Compressive
Strength of Concrete) and Section R506 [Concrete Floors 1.3.2.8 ASTM C 494-99ae1, Standard Specification for
(On Ground)]; in the BNBC are Sections 1901.0, 1902.0, Chemical Admixtures for Concrete.
and 1905; in the SBC are Sections 1901 and 1909; and in 1.3.2.9 ASTM C 470-02a, Standard Specification for
the UBC are Sections 1907.12, 1922 and 1922.3. Molds for Forming Concrete Test Cylinders Vertically.
1.2 Scope: Synthetic fibers are added to concrete to 1.3.2.10 ASTM C 666-97, Test Method for Resistance
reduce plastic shrinkage cracking of reinforced concrete and of Concrete to Rapid Freezing and Thawing.
structural plain concrete and/or to reduce shrinkage and
temperature cracking in structural plain concrete slabs on 1.3.2.11 ASTM C 823-00, Standard Practice for
grade. Examination and Sampling of Hardened Concrete in
Construction
1.2.1 Consideration shall be given to the volume, size
and type of fibers used. Extrapolation to other volumes, 1.3.2.12 ASTM C 1018-97, Test Method for Flexural
sizes and types of fibers shall be documented in accordance Toughness and First-Crack Strength of Fiber-Reinforced
with this acceptance criteria, or by an engineering evaluation Concrete (Using Beam with Third-Point Loading)1.
signed, sealed and dated by a registered design 1.3.2.13 ASTM C 1116-02 Specification for Fiber-
professional. Reinforced Concrete and Shotcrete.
1.2.2 The fibers are regarded as an admixture and are 1.3.2.14 ASTM D 698-00a, Test Method for Laboratory
used in addition to any structural reinforcement, shrinkage Compaction Characteristics of Soil Using Standard Effort.
and temperature reinforcement and joints required in the
applicable code. 1.3.2.15 ASTM D 1557, Test Method for Laboratory
Compaction Characteristics of Soil Using Modified Effort.
1.2.3 The fibers may be used in concrete over steel
deck construction. 1.3.2.16 ASTM D 2256-02, Standard Test Method for
Tensile Properties of Yarns by the Single-Strand Method.
1.2.4 The fibers may be used in fire-resistive
construction on steel decks. 1.3.2.17 ASTM E 119, Standard Test Methods for Fire
Test of Building Construction and Materials.
1.3 Reference Standards: Where standards are
referenced in this criteria, these standards shall be applied 1.3.3 American Concrete Institute (ACI) Committee
consistently with the code upon which compliance is based. Reports:
Standards editions applicable to each code are summarized 1.3.3.1 ACI 305R-99, Specification on Hot Weather
in Table 1. Concreting.
1.3.1 Codes: 1.3.3.2 ACI 318 (-05 for the IBC and IRC, -95 for the
1.3.1.1 2006 International Building Code ®
(IBC), BNBC, SBC and UBC), Building Code Requirements for
International Code Council. Structural Concrete.
1.3.3.3 ACI 544.2R-89(1999), Measurement of
1.3.1.2 2006 International Residential Code® (IRC),
Properties of Fiber-reinforced Concrete.
International Code Council.
1.3.3.4 ACI 544.1R-96(2002), State-of-the-Art Report
1.3.1.3 BOCA® National Building Code/1999 (BNBC).
on Fiber Reinforced Concrete.
1.3.1.4 1999 Standard Building Code© (SBC). 1.4 Definitions:
1.3.1.5 1997 Uniform Building Code™ (UBC). 1.4.1 Admixture: Admixture is material other than
1.3.2 ASTM International Standards: water, aggregate, or hydraulic cement used as an ingredient
of concrete and added to concrete before or during its
1.3.2.1 ASTM C 31, Standard Practice for Method of mixing to modify its properties.
Making and Curing Concrete Test Specimens in the Field.
1.4.2 Plastic Shrinkage Cracking: Plastic shrinkage
1.3.2.2 ASTM C 39, Test Method for Compressive cracking is cracking that occurs in the surface of fresh
Strength of Cylindrical Concrete Specimens. concrete soon after it is placed and while it is still plastic.
1
Discontinued by ASTM International. Available from Global Engineering Documents [telephone (800) 854-7179; web site
http://www.global.ihs.com.
2
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
3
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
without fibers (control). Air content of each mixture shall be Results of tests conducted in accordance with Sections
as specified in Section 12.2.2 of ASTM C 494. 4.6.1 and 4.6.2, above, shall be submitted within two years
of the date of application for an evaluation report.
4.3.3 Condition of Acceptance: The average durability
factor of the three specimens containing the fibers shall be 4.7 Post-crack Integrity:
at least equal to the average durability factor of the control
specimens. The number of cycles shall be 300 or until the 4.7.1 General: One of the following tests shall be used
average relative MOE of the fiber specimens or the control to evaluate the integrity of concrete with synthetic fibers,
specimens reaches 60 percent of the respective initial after cracking:
modulus, whichever occurs first.
4.7.1.1 Post-peak Flexural Strength: This test
4.3.4 In lieu of providing test information in accordance evaluates the ability of fibers to hold concrete together after
with ASTM C 666, a proven record of freeze-thaw cracking. Tests shall be conducted in accordance with the
performance in accordance with Section 21.4 of ASTM C procedure outlined in Annex D.
1116 may be provided. The field test report shall be
prepared by a recognized independent agency, and include Conditions of Acceptance: The average post-peak
the size, quantity, trade name and type of fiber along with flexural strength of the test specimens shall be at
the concrete mix design. Test reports from at least three least 50 psi (345 kPa) or 20 percent of the peak
separate locations are required. stress, whichever is less.
4.4 Effect on Reinforcement Bond Strength: (May be 4.7.1.2 Impact Resistance: This test compares the
omitted if use of fibers is limited to plain concrete slabs on impact resistance of concrete with and without synthetic
grade.) The purpose of the test is to determine whether the fibers. The test shall be conducted in accordance with the
addition of fibers to a concrete mix adversely affects the procedure outlined in Annex E.
bond strength between the reinforcement and concrete.
Conditions of Acceptance: The number of blows to
4.4.1 Comparative tests shall be conducted in ultimate failure for fiber concrete specimens shall
accordance with ASTM C 234. Steel reinforcement shall be exceed the blows to plain concrete specimens by 100
evaluated horizontally in accordance with Section 4.3 of percent at 7 days and 50 percent at 28 days.
ASTM C 234. Concrete shall be cured a minimum of 26
days. 4.8 Concrete over Steel Deck Composite Construction
Test:
4.4.2 Tests shall be conducted on three concrete
specimens with synthetic fibers, and three specimens 4.8.1 General: The purpose of the test is to evaluate
without fibers (control). whether the addition of fibers to a concrete mix placed over
steel deck adversely affects the shear bond between the
4.4.3 Conditions of Acceptance: The average bond concrete and steel deck construction.
strength for the steel reinforcement embedded in the
concrete with the fibers shall be equal to or exceed the Results of full-scale superimposed load tests (see
average bond strength for the steel reinforcement Figure 1) providing comparative load capacity and deflection
embedded in the control specimen. Slight deviations, due to information, shall be submitted. A minimum of two decks for
variations in testing, may be considered. each reinforcement method shall be tested. Consideration
shall be given to the volume, type and size of fibers used.
4.5 Plastic Shrinkage Cracking: The purpose of the test
Extrapolation to other volumes, types and sizes shall be
is to show that fibers decrease the plastic shrinkage justified.
cracking of concrete. Testing shall be conducted in
accordance with Annex A. 4.8.2 Procedure (see Figure 1):
Conditions of Acceptance: Noted in Annex A. 4.8.2.1 A No. 20 gage [0.0359 inch (0.91 mm)] steel
4.6 Compatibility with Concrete: The purpose of the test deck (ASTM A 653 Structural Steel Grade 33), 3 inches (76
is to evaluate the long-term resistance of the fiber to mm) deep with 12-inch (304.8 mm) rib spacing, designed for
deterioration when in contact with moisture and alkalis composite use, shall be used.
present in cement paste or the substances present in air- 4.8.2.2 Two and one-half inches (63.5 mm) of
entraining and chemical admixtures. concrete fill having a specified compressive strength of
4.6.1 Procedure: 3,000 psi (20.7 MPa), shall be used. Specimens shall
include:
4.6.1.1 The test begins with two cylinders filled with
concrete having the correct proportion of fibers. Cylinders 1. One set of specimens containing concrete fill
shall be placed in a moist environment at 73/F ± 3/F (23.7/C with 6 x 6—W1.4 x W1.4 (WWF), 1 inch (25.4 mm) below
± 1.7/C) for two years. A moist environment exists when test the top of the slab.
specimens have free water on the entire surface area at all
2. One set of specimens containing concrete fill
times.
with fibers.
4.6.1.2 At the end of two years, the cylinders shall be
broken and the fibers examined under 1500× magnification 4.8.2.3 The composite deck shall be loaded at the
to see if there is any deterioration. quarter points in approximately eight equal increments until
failure. Increments can be determined from the theoretical
4.6.1.3 Conditions of Acceptance: There shall be no load capacity of the composite construction.
deterioration of fibers.
4.8.2.4 Ultimate flexural load capacity shall be
4.6.2 Alternative Test (Optional): On an interim basis, determined for each set. At least three dial gauges equally
tests conducted in accordance with one of the procedures spaced at midspan shall be used for deflection readings.
outlined in Annex B or Annex C are acceptable. Deflection readings shall be reported.
4
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
4.8.2.5 Conditions of Acceptance: 6.1 If the report applicant purchases the fibers from a fiber
manufacturer, evidence is needed of an agreement between
1. Average ultimate flexural capacity of the decks the fiber manufacturer and the applicant indicating that the
with fibers shall equal or exceed the average ultimate manufacturer will inform the applicant of any changes to the
flexural capacity of the decks with WWF. fiber. The applicant shall then notify ICC-ES.
2. The average mean shear transfer coefficient 6.2 The evaluation report shall include the condition that
(VT) for the decks with the fibers shall equal or exceed the use of the fibers is approved by the project engineer or
average mean transfer coefficient for the deck with the architect.
WWF.
6.3 For structural plain concrete, the evaluation report
4.9 Fire-resistance Test: The purpose of the test is to shall indicate that control joints, as required by Section
evaluate whether the addition of fibers in a concrete mix will 1909.3 of the IBC, are to be provided.
adversely affect the fire resistance of steel deck assemblies. 6.4 For reinforced concrete, the evaluation report shall
indicate that structural reinforcement and shrinkage and
Consideration shall be given to the volume, type and size
temperature reinforcement in accordance with Section
of fiber used. Extrapolation to other volumes, types and
1907.12 of the IBC are to be provided.
sizes, shall be justified.
6.5 A batch ticket, signed by a ready-mix representative,
Tests shall be conducted in accordance with ASTM E 119 shall be available to the code official upon request. The
(UBC Standard 7-1). delivery ticket shall include, in addition to the items noted in
ASTM C 94, the type and amount of fibers added to the
5.0 QUALITY CONTROL
concrete mix.
5.1 A quality control manual complying with the ICC-ES 6.6 If recognition for other types of concrete, such as
Acceptance Criteria for Quality Control Manuals (AC10) lightweight, is desired, results of tests conducted in
shall be submitted. accordance with this criteria shall be submitted for each
type.#
5.2 Third-party follow-up inspections are not required
under this acceptance criteria.
6.0 EVALUATION REPORT RECOGNITION
5
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
ANNEX A
TEST METHOD FOR EVALUATING PLASTIC SHRINKAGE CRACKING
OF RESTRAINED CONCRETE WITH SYNTHETIC FIBERS
A1.0 INTRODUCTION
This test method compares the surface cracking of a concrete panel containing synthetic fibers with the surface cracking of a
control concrete panel without fibers. Both concretes are subjected to prescribed conditions of moisture loss severe enough to
produce cracking. Both concretes shall also be subjected to anticipated job conditions of temperature and humidity to obtain the
difference between the cracking potentials of plain concrete and concrete with synthetic fibers in the field.
Shrinkage cracking is quantified by computing the area of surface cracks in each panel specimen to obtain a value in square
inches, which represents the assumed total area of crack opening on the surface of the concrete panels.
The effect of fibers on the development of shrinkage cracking is determined by expressing the cracking value for the concrete
with synthetic fibers as a percentage of the value for the control concrete (without fibers) when subjected to the identical and
simultaneous drying conditions.
Values of shrinkage cracking stated in square inches (mm2) are regarded as the standard. This method attempts to control or
duplicate atmospheric variables to quantify the performance of the fiber variable in a given concrete mixture. Since many other
variables, such as cement fineness, aggregate gradation and surface finishes, also influence cracking potential and cannot be
precisely duplicated, this method may not be suitable for interlaboratory evaluations.
A2.0 SUMMARY OF METHOD
Following casting and screeding, the surfaces of concrete test panels with and without fibers are subjected to airflow produced
by a fan or fans. The use of a fan box is a method for producing a uniform airflow over the panel surface (see Figure A1). A clear
cover over the specimen in conjunction with the fan box will aid in obtaining uniform airflow and allow for specimen observation.
The test is conducted using a method shown in Figure A1, by exposing the panels to an evaporation rate of 0.2 pound of water
per square foot of surface per hour (0.975 kg/m2/h) or more. (See ACI 305.)
Referring to the evaporation graph in ACI 305R, evaporative variables are set in the laboratory for the comparison test to obtain
a minimum of the critical rate, i.e., 0.2 pound of water per square foot of surface per hour (0.975 kg/m2/h). The evaporation rate
is monitored by a one-square-foot (0.0929 m2) pan of water that is weighed initially and thereafter periodically until the termination
of the test, to determine the evaporation rate (Annex Note 1).
Annex Note 1: A principal determinant in this method is evaporative water loss that is controlled by the atmospheric environment
of the test specimens. Since the concrete specimens will not always provide the same rate of free water evaporation as is
available from the pan of water, the rate of evaporation from the pan of water is the standard for this test.
The drying conditions are intended to induce shrinkage in cracking which will occur due to internal or external restraints on
volume reduction. End of test shall be determined when final set of the concrete is reached. Final set will be determined according
to ASTM C 403.
The specimens shall be uncovered and exposed to the same conditions. The total area of crack opening at the end of the test
is computed for each test panel. The shrinkage of the concrete is expressed as the total area of crack opening for the panel in
square inches.
During the setting stage, from initial through final set, “plastic” shrinkage cracks occur. Because it is difficult to measure cracks
in the plastic state, all cracks are measured after the termination of the test period.
The test specimens and monitoring pan are inserted into an environmental chamber designed for this purpose. (See Figures A1
and A2.) The atmospheric variables set to achieve the minimum prescribed evaporation rate are not critical in the comparison
test, because the average evaporative rate is the determining factor of the test.
Before casting of the concrete panels, it is expeditious to check the atmospheric variables in the laboratory test facility to
determine that the necessary conditions can be achieved.
Cracking values are determined by counting the number of cracks in each panel and recording the approximate length and width
of each crack. The accumulated crack area is computed based on these measurements, to determine the cracking value for each
test panel. The ratio of the cracking values for fiber-reinforced versus control panels is the fiber effectiveness ratio expressed as
a percentage. Refer to Section A6.0 for quantification of cracking.
A3.0 APPARATUS
Molds: As shown in Figure A2, a mold with a depth of 4 inches (102 mm), a minimum surface area of 1.75 square feet (0.16 m2),
and rectangular dimensions of 14 inches by 22 inches (356 mm by 559 mm), with internal restraint and stress risers. The mold
shall be fabricated from metal, plastic or plyform (Annex Note 2). Fabricate the internal restraints and stress riser for a separate
sheet metal piece. This sheet metal piece shall seat snugly at the bottom of the mold. (See Figure A2.)
Annex Note 2: The use of plyform, with very little absorption, is an appropriate choice for constructing lightweight, stiff molds.
Restraint: Two 1.25-inch (31.7 mm) risers, placed 4 inches (102 mm) inward from each end of the mold, provide restraint to the
concrete. The center 2.5-inch (63.5 mm) stress riser serves as an initiation point for plastic shrinkage cracking.
The sheet metal stress riser insert is lightly oiled to provide appropriate debonding of the concrete from the bottom of the sheet.
The insert is considered to be properly oiled when the entire surface is coated and all excess oil has been removed. The sides
of the mold are oiled in the same manner as the insert.
6
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
Fan(s): Adjustable-speed fan(s) capable of achieving a minimum 10 mph (16.1 km/h) airflow over the entire test specimen
surface area.
Sensors: Sensors shall provide means of recording ambient air and concrete temperatures to the nearest 1°F (0.5°C), and
relative humidity to the nearest 1 percent, near the test specimen surface during testing. An anemometer capable of measuring
air velocity to the nearest 1 mph (1.61 km/h) shall be used.
Vibrating Platform: Any device that can fully consolidate the test panels within 12 seconds and that meets minimum frequency
requirements for an external vibrator, is suitable.
Monitoring Pan: A pan suitable for holding water in the air stream between the concrete test panels. The sides of the pan shall
be vertical and shall expose precisely 1 square foot (0.0929 m2) of water ±1 percent to the atmosphere. This size of pan will
expedite the calculation of evaporation rate. The exposed lip of the pan shall not extend more than 1/8 inch (3.2 mm) above the
water level at the start of the test. A 12-inch-by-12-inch-by-1-inch (305 mm by 305 mm by 25 mm) or 8-inch-by-18-inch-by-1-inch
(203 mm by 457 mm by 25 mm) configuration is appropriate.
Scale: A balance or scale for weighing the monitoring pan shall have a capacity of at least 5 pounds (2.2 kg) and shall be
accurate to within 0.1 percent of its capacity.
Optional: A scale for weighing the test panels shall have a capacity of at least 200 pounds (90.7 kg) and shall be accurate to
within 1 percent of the test load.
A4.0 SAMPLING, TEST SPECIMENS AND TEST UNITS
General Requirements: The preferred specimen depth for concrete is 4 inches (102 mm). Maximum coarse aggregate size when
using stress risers is 3/4 inch (19 mm).
Test Specimens: The specimens are cast in the laboratory in accordance with the applicable provisions of ASTM C 192.
Test Units: A test unit is at least six test specimens. Three are control specimens without fibers. The other specimens are
identical except they contain specified amounts and types of fiber. Control concrete specimens may be compared to more than
one series of fiber-reinforced concrete specimens.
A5.0 PROCEDURE
The molds are filled with concrete and subjected to a source of external vibration until the concrete is consolidated and
approximately level with the top of the mold. Each specimen is then screeded three times with an angle iron screed. The total
vibration time is limited to 12 seconds, to avoid material segregation.
Optional: The molds are weighed prior to filling the concrete. Following removal of any waste concrete adhering to the outside
of the mold, each specimen while in the mold is weighed prior to testing, to allow evaporation in the form of water loss during
testing to be determined at the end of the test by subsequent weighing.
After vibration and screeding, the surface of the concrete shall be floated with a magnesium float to embed the aggregate and
compact the surface. The number of passes shall be determined for each mixture and material source used during testing. Float
specimens of the same mixture and material using equal number of passes.
The fiber-reinforced and control specimens are placed in the selected exposure area downstream from the fan(s). (See
arrangement in Figure A1.)
The fan(s), preset to achieve a minimum airflow velocity of 10 mph (16.1 km/h), are turned on, and the time of day is recorded.
Simultaneously, the specimens are exposed to identical drying conditions. The evaluation of cracking commences at this time.
Air and concrete temperatures, relative humidity and airflow velocity, at a location 4 inches (102 mm) above the specimen, shall
be recorded at the start and at 30-minute intervals. The time at which cracking is first observed shall be recorded for each
specimen.
Observations are continued at 30-minute intervals until final set, or for a minimum of three hours. Measurement of cracking
commences only at the completion of the drying period.
The evaporation rate is determined by initially weighing the full monitoring pan at the start of the test and at 30-minute intervals
thereafter. The weight loss in pounds is recorded to the nearest 0.01 pound (4.53 g) at each weighing in the air stream to prevent
an interruption in evaporation losses.
Annex Note 3: Adjustments shall be made if necessary to maintain the standard evaporation rate at the prescribed level. It is
suggested that the monitoring pan be placed on a scale in the air stream for continuous monitoring without periodic removal during
testing.
After final set, or a minimum of three hours under the test conditions, atmospheric variables are recorded, and the fans are
stopped and the total water loss from the monitoring pan is determined. The test is not valid if the total standard evaporation rate
was less than 0.2 pound of water per square foot of surface per hour (0.975 kg/m2/h).
Optional: If mass loss of test panels is desired, test panels are weighed at this time.
7
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
8
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
FIGURE A1—SCHEMATIC OF FAN BOX USED WITH PLASTIC SHRINKAGE SLAB TO TEST FIBERS
9
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
10
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
ANNEX B
TEST METHOD FOR DETERMINING ALKALINE RESISTANCE OF FIBERS
B1.0 INTRODUCTION
This test method covers the laboratory procedure for determining the alkaline resistance over time of fibers used for reinforcing
concrete.
B2.0 MATERIALS
Materials shall include:
• Continuous filament.
• Three solutions of calcium hydroxide at pH’s 11 to 13.
B3.0 METHOD
B3.1 Prepare 24 skeins of fiber, each several feet long.
B3.2 Prepare three solutions of calcium hydroxide ranging in pH from 11 to 13.
B3.3 Submerge six skeins of fiber in each solution. Make sure all solutions are well covered and monitored to control pH. The
solutions shall be maintained at room temperature [70° F ± 2° F (21° C ± 1° C)].
B3.4 Remove one skein from each solution following 3, 7, 11, 20, 28 and 35 days. Wash, dry and condition each skein for 24
hours at 70/F ± 2/F (21/C ± 1/C) and 65 ± 2 percent relative humidity.
B3.5 Tensile test each skein according to ASTM D 2256. One control skein with each pH series shall be tested. A total of 10
specimens from each skein shall be tested. Record the breaking strength for each specimen and calculate the average breaking
strength for each skein. Calculate the breaking strength retained as follows:
Skein Breaking Strength (Avg.)/ Control Breaking Strength (Avg.) X 100% =
% Breaking Strength Retained
B3.6 Examine each skein under the microscope and note surface defects.
B4.0 CONDITIONS OF ACCEPTANCE
The breaking strength retained shall be at least 90 percent of the control skein.
11
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
ANNEX C
TEST METHOD FOR DETERMINING LONG-TERM DURABILITY OF FIBERS
USED IN FIBER-REINFORCED CONCRETE
C1.0 INTRODUCTION
This test method evaluates the long-term durability of fibers in concrete in accordance with an accelerated aging procedure. The
accelerated test method was adopted from “Toughness of Glass Reinforced Concrete Panels Subjected to Accelerated Aging,”
by S. P. Shah, J. I. Daniel, and D. Ludirdja, which appeared on pages 82-99 of the September-October, 1987, PCI Journal.
C2.0 MATERIALS
Materials shall include:
• Cut fiber.
• Concrete mix: 3,000 psi (20.7 MPa).
C3.0 PROCEDURE
C3.1 The accelerated aging test for durability is adopted from the test used for glass-fiber-reinforced concrete. In this test, the
fiber-reinforced specimens are stored in lime-saturated water at 50/C (122/F) for various time intervals. This elevated temperature
was found to accelerate the fiber degradation process. The presence and effectiveness of the fibers could be evaluated using
either tension or flexure testing. For the purpose of this evaluation, flexure testing is used. The flexural test is conducted prior to
accelerated aging and following 4, 8, 16, 32 and 52 weeks of accelerated aging.
C3.2 The fibers are added to the concrete at a rate of 8 pounds per cubic yard (4.7 kg/m3) of concrete (approximately 0.5 percent
by volume). The primary contribution of fibers in concrete is ductility. This high volume loading allows for well-defined load
deflection curves under flexural loading, and thus consistently measurable toughness index values. Minute changes in fiber
effectiveness will be easily seen and measured because of the high fiber volume.
C3.3 Prepare the primary test specimens, 4-inch-by-4-inch-by-14-inch (102 mm by 102 mm by 356 mm) beams.
Three test specimens, plus several extras, shall be made for each time interval. Moist cure for 28 days. After curing, place the
specimens in a lime-saturated water bath maintained at 122/F (50/C) [Compressive cylinders, measuring 6 inches (152 mm) in
diameter by 12 inches (305 mm) in height, shall also be cast and cured. Test at 28 days to obtain the compressive strength for
quality control purposes.]
C3.4 Remove appropriate specimens just prior to testing. Conduct flexural testing according to ASTM C 1018. Calculate the
toughness index values (I5, I10, I30, I10/I5 I30/I10) using the load deflection curves.
C4.0 CONDITIONS OF ACCEPTANCE
The I30/I10 ratio for fiber-reinforced specimens following accelerated aging shall be at least 85 percent of the unaged specimen
value.
12
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
ANNEX D
TEST METHOD FOR DETERMINING POST-PEAK FLEXURAL STRENGTH
OF SYNTHETIC FIBER-REINFORCED CONCRETE
D1.0 INTRODUCTION
This test method evaluates the flexural post-peak strength of synthetic fiber-reinforced concrete in terms of the stress sustained
by fibers consequent to concrete matrix cracking. Flexural post-peak strength of synthetic fiber-reinforced concrete is indicative
of crack widening or post-cracking resistance provided by fibers.
D2.0 DESCRIPTION OF TERMS SPECIFIC TO THIS STANDARD
D2.1 Flexural Stress: Maximum stress in a cross section under the effect of bending moment and based on elastic section
analysis.
D2.2 Peak Deflection: Loading point deflection attained by a specimen tested under one-third point bending at the maximum
(peak) load.
D3.0 SUMMARY OF METHOD
Beams (molded or sawn) of synthetic fiber-reinforced concrete are tested in flexure using the third-point loading arrangements
as described in ASTM C 78. Loads and deflections at loading points (one-third points) are monitored either continuously using
an X-Y plotter or incrementally via displacement transducers or dial gauges at sufficient frequency. The data collected is used
to draw the flexural stress vs. load point deflection of beam specimens. Post-peak range starts approximately at the point where
the flexural load (or stress) levels off consequent to the maximum (peak) load or peak stress. The flexural stress sustained by the
material in the post-peak range is termed the post-peak flexural strength.
D4.0 SIGNIFICANCE AND USE
The post-peak flexural strength of synthetic fiber-reinforced concrete can be used to describe material crack widening and/or
cracking resistance in the range beyond the ultimate flexural stress. Furthermore, it can be used to characterize or specify
synthetic fiber reinforced concrete.
D5.0 APPARATUS
D5.1 Testing Machine: Testing machine is according to ASTM C 78 and, additionally, shall be operated at a constant deflection
rate.
D5.2 Deflection Measurements: Dial gages or displacement transducers shall be used for deflection measurement.
D5.3 X-Y Plotter: X-Y plotter can be used to draw load deflection curve for this test method.
D6.0 SAMPLING, TEST SPECIMENS, AND TEST UNITS
D6.1 Length of test specimens shall be at least 2 inches (51 mm).
D6.2 This test method is used for synthetic fiber-reinforced concrete specimens, assuming that proper concrete practice is
followed and uniform fiber distribution, without balling or tangling, is achieved.
D7.0 PROCEDURE
D7.1 At least three specimens for each concrete mixture are needed to obtain the post-peak flexural strength.
D7.2 A typical experimental setup is shown in Figure D1. For each specimen, the stress-deflection curve is constructed.
D7.3 The average post-peak stress for each specimen is determined.
D7.4 The range over which post-peak strength is averaged starts from Point A (the point at which flexural resistance starts to
increase after it has decreased from the peak value) and proceeds to a specified deflection value. Point A is defined as the point
at which the deflection equals 1.50 times the deflection at peak load. The point at which the deflection equals five times the peak
deflection, marks the conclusion of the post-peak range for the purpose of the test method described herein.
D7.5 The average post-peak flexural resistance of three specimens is considered representative for a synthetic fiber concrete
mixture. No specimen can deviate from the average by more than 10 percent for validation of this test procedure.
D7.6 Figure D2 can facilitate comprehension of the concept of post-peak flexural resistance of synthetic fiber reinforced concrete.
13
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
14
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
ANNEX E
TEST METHOD FOR EVALUATING IMPACT RESISTANCE
OF CONCRETE WITH SYNTHETIC FIBERS
E1.0 SCOPE
The test method compares the impact resistance of concrete with and without synthetic fibers. Impact resistance is characterized
by the measure of:
1. The energy consumed to fracture a specimen.
2. The number of blows in a “repeated impact” test to achieve a prescribed level of distress.
3. The extent of damage.
E2.0 APPARATUS
The equipment for the drop weight impact test consists of:
E2.1 A standard, manually or mechanically operated 10-pound (4.54 kg) compaction hammer with an 18-inch (457 mm) drop
as specified in ASTM D 698 or ASTM D 1557.
E2.2 A 21/2-inch-diameter (63.5 mm) hardened steel ball.
E2.3 A flat base plate with four lugs welded to it. (Refer to Figures E1 and E2.)
E2.4 Molds to cast 6-inch-diameter (152 mm) by 21/2-inch (63.5 mm) ±1/8-inch (±3 mm) concrete specimens. This is accomplished
with molds complying with ASTM C 31 or C 470.
E3.0 TEST PROCEDURE
The 21/2-inch-thick-by-6-inch-diameter (63.5 mm by 152 mm) concrete samples are prepared using external vibration.
The method, frequency, amplitude and time of vibration shall be recorded. Test specimens of 21/2-inch (63.5mm) thickness shall
be cast in a single layer to avoid fiber orientation and fiber-free planes. The molds are filled partially to the 21/2-inch (63.5 mm)
depth and float-finished.
The specimens are tested at 7 and 28 days of age. Specimen thickness shall be recorded to the nearest 1/16 inch (1.6 mm). The
reported thickness is determined by averaging the measured thickness at the center and each edge of the specimen along any
diameter across the top surface. The samples shall be coated on the bottom with a thin layer of petroleum jelly or a heavy grease,
and placed on the base plate within the positioning lugs with the finished face up. The base plate shall be bolted to a rigid base
such as a concrete floor or cast concrete block. The hardened steel ball is placed on top of the specimen within the bracket.
Foamed elastomer pieces shall be placed between the specimen and positioning lugs to restrict movement of the specimen during
testing to first visible crack.
The drop hammer shall be placed with its base upon the steel ball and held there with enough down pressure to keep it from
bouncing off the ball during the test. The hammer shall be repeatedly dropped 18 inches (457 mm), and the number of blows
required to cause the first visible crack on the top and to cause ultimate failure are both recorded. The foam elastomer is removed
after the first visible crack is observed. Ultimate failure occurs when the test specimen comes in contact with three of the four lugs
welded to the base plate. Illustrative details are in Figures E1 and E2.
E4.0 SAMPLING, TEST SPECIMENS AND TEST UNITS
E4.1 Sampling: Five specimens are molded for each test age and test condition. Specimens involving a given variable can be
made on any given day. When it is possible to make at least one specimen for each variable on a given day, the mixing of the
entire series of specimens shall be completed in as few days as possible, and one of the mixtures shall be repeated each day
as a standard comparison.
E4.2 Test Specimens: The test specimens are cast in accordance with ASTM C 192, the Standard Method for Making and
Curing Concrete Test Specimens in the Laboratory.
E4.3 Test Units: A test unit is at least five test specimens of each variation. One unit is the control concrete without fibers. The
other units are the same concrete mixture with specified amounts and types of fiber.
E5.0 CONDITIONS OF ACCEPTANCE
The results shall be evaluated on the basis of averaging the test results. Any individual peculiarities among test results shall be
noted. The minimum acceptance for the final results shall be that the synthetic fibers increased the impact of concrete by 100
percent at 7 days and 50 percent at 28 days.
E6.0 REPORT
In addition to the requirements of AC85, the report shall include the following:
• The concrete design mix for all variations.
• Fiber dosage for each set of specimens, by weight.
• Fiber length for each of set specimens.
• Thickness and dimension of specimen.
15
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
16
ACCEPTANCE CRITERIA FOR CONCRETE WITH SYNTHETIC FIBERS
17