PBRS RE-R1 Prescriptive Methodology
PBRS RE-R1 Prescriptive Methodology
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
Summarry
This guidaance docume ent outlines details relatiing to the Peearl Building Rating Systeem (PBRS), RE‐R1:
R
Minimum m Energy Perfformance, Prrescriptive Methodology,
M in order to facilitate com
mpliance with the
quirements. The Prescriptive Method is based upo
credit req on selected requirements
r s in the Abu Dhabi
onal Energy Conservation Code
Internatio C (AD‐IECCC), version 1..0 as issued by
b DMA Januaary 2011.
This Presccriptive Methodology is appplicable to buildings with a gross interrnal floor areaa (GIFA) of 50
000m²
or less. Building
B projects that exceed 5000m² an nd wish to unndertake the prescriptive compliance
c o
option
should appproach the Estidama team m at the UPC prior to comm mencing the design
d submission.
ument provid
This docu des a summaary of the requirements relating
r to envelope, systtems, lightingg and
renewables within the Prescriptive approach forr buildings.
Requirements
The Presccriptive requirements are based upon an alignmen nt with the AD‐IECC
A wherre applicable.. It is
intended to set a higher standard of o performan nce than the Performance
P Approach in order to enssure a
suitably stringent targget for energyy usage and to enable an n appropriatee level of impprovement beeyond
the Baseliine requirements. Thereffore the majo ority of the taarget values within
w this guidance are su
ubject
to a 10% improvement
i t over the values given in the
t AD‐IECC.
1
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
Building Envelope
E
The followwing target performance
p values are the
t mandateed upper limits for each building envvelope
element type.
t For en
nvelope elemeents not coveered by the following
f tables please ref
efer to AD‐IEC
CC for
further deetails.
Opaque Fabric
F U‐valuees (W/m2.K) (C Climate Zonee 1):
General "R
Residential"
Rooof:
Inssulation entirrely above deck 0
0.20 0.20
Me etal buildingss 0
0.33 0.33
Attic and other 0
0.17 0.14
Wall, Above Grrade:
Maass 0
0.30 0.30
1
Me etal buildingss 0
0.48 0.48
Me etal framed 0
0.19 0.19
Wood framed and a other 0
0.18 0.18
Wall, Below Grrade C‐factor,, W/m².K:
Beelow grade waall 5
5.83 5.83
Flo
oors U‐value,, W/m².K:
Maass 1
1.65 1.65
Joiist/Framing 1
1.44 1.44
Slaab‐on‐Grade Floors F‐factor, W/m.K:
Unnheated slabss (F) 3
3.73 3.73
Heeated slabs (FF) 5
5.21 5.21
Building Air
A Leakage: building shaall be tested as per ASTM
M E779 and should not exceed
e 3.64l/s/m2
e area of exposed façade.
@75Pa baased upon the
2
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
on Factor2 (P
Solar Heaat Gain Coeffficient (SHGC), accountingg for Projectio PF) of externaal shading deevices
(see IECC section 502.3
3):
SHGC all frame
f types
PF < 0.25 0
0.23
0.25 ≤ PF < 0.50 0
0.30
PF ≥ 0.50 0
0.36
PF = A/B
A
A = Distance measured
m horizontally fromm the furthestt continuous extremity of any overhangg,
eaave, or permaanently attached shading device to thee vertical surfaace of the glaazing
B = Distance measured
m verttically from th
he bottom of the glazing too the undersiide of the
ovverhang, eave, or permanently attacheed shading deevice
Skylight performance:
p
Skylight (M
Max 3% roof area)
a
U‐value (W
W/m².K) 3.80
SHGC 0.30
2 See Intern
national Energy Conservation
C Co
ode, Section 502.3.2
3
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
4
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
Condensin
ng Units:
Subcateegory or Test
Equipment Type Size Categgory Minimum
m Efficiency³
Rating Condition Procedure
Split system 13.0 SEER 3.81 SCoP
< 19kW
Single package
p 13.0 SEER 3.81 SCoP AHRI
> 19kW Split system and 210/240
11.0 EER 3.22 CoP
Air cooled,(Cooling and < 40kW
W single package
p
mode) > 40kW Split system and
10.6 EER 3.11 CoP
and < 70kW
W single package
p AHRI
Split system and 9.5 EER 2.78 CoP 340/360
> 70kW
single package
p 9.2 IPLV 9.2 IPLV
Throuugh‐the‐Wall Split system 12.0 SEER 3.52 SCoP
AHRI
(Air co
ooled, cooling < 9kW
Single package
p 12.0 SEER 3.52 SCoP 210/240
mode)
Air cooled
d chillers:
Minimmum Efficiencyy Test
Equipm
ment Type Size Category
Full Lo
oad, EER Fuull Load, CoP IPLV Procedurre
< 150 tonss > 9.562
9 > 2.803 > 12.500
Air‐coo
oled chillers
> 150 tonss > 9.562
9 > 2.803 > 12.750
AHRI
Air coo
oled without Air‐coooled chillers without
w condensers must be
550/590
0
condenser, electrical All capacitties rated with
w matching condensers an nd comply withh
operatted the air‐cooled chiller efficiency requirements
r
4 Cap mean ns the rated cooling capacity of thet product in Bttu/h. If the unit’’s capacity is lesss than 7,000 Btu
u/h, use 7,000 Bttu/h in
the calculation. If the unit’s capacity is greaater than 15,000
0 Btu/h, use 15,0
000 Btu/h in the calculation
5
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
Energy reecovery systeems are required for all systems wherre the design n supply flow
w rate exceed
ds the
specified value at the given
g percenttage of outdo
oor air as detaailed in the fo
ollowing tablee:
>30% >40
0% & >50% & >60% & >70% &
Percentagge Outdoor Airr at Full Design
n Flow Rate >8
80%
&<40% <5
50% <60%
% <70% <80%
Design Su
upply Fan Airflo
ow Rate m³/s n/a n
n/a 11.04
4 5.10 2.12 1.70
Demand Control
C Ventilation (DCV) must be inco
orporated in the mechanical ventilation
n system desiggn for
all zones larger
l than 50
0m² with an average
a occupant density exceeding 2.3
3m²/person.
The follow
wing requiremments must also be satisfieed where app plicable:
• All CHW pump p motors shall be fitted witth variable sp
peed drives
• All ducts locate ed in unconditioned spacees shall be inssulated with a minimum off R‐5 insulatio
on
• All ducts locate ed in external spaces shalll be insulated
d with a minim
mum of R‐8 innsulation
• All piping serving as part off a cooling sysstem shall be thermally inssulated with a minimum 38mm
3
in
nsulation (bassed on insulattion thermal conductivity
c o less than 0.039W/m.K)
of 0
6
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
Su
ubcategory or
Size Category (Input) Minimum
m Efficiency Test Procedure
Raating Condition
n
< 12 kW Reesistance 0.97 ‐ 0.00
00349V, EF DOE 10 CFR Paart 430
> 12 kW Reesistance 0.134V + 45.4 SL, W ANSI Z21.10.3
< 24 amps
Heeat pump 0.97 ‐ 0.00
00349V, EF DOE 10 CFR Paart 430
and < 250 vo
olts
on to the gen
In additio neration system performaance the follo owing requirrements must also be sattisfied
where applicable:
• Teemperature controls
c mustt be providedd to allow a set
s point of 43°C
4 for dwellings and 32°°C for
otther occupan ncies
• Outlet
O temperrature in public rest roomss must not exceed 43°C
• Sw wimming poo ol, spa or hoot tub heatin
ng or coolingg systems shaall be equipp
ped with a reeadily
acccessible on‐‐off switch too allow shuttting off the system with hout adjustin
ng the therm mostat
seetting
• All pools shall be equipped with a vapou ur retardant pool
p cover on or at the watter surface
• Po ools, spas orr hot tubs which are heated to more than 32°C shall s have a pool cover with
w a
m
minimum insulation value of
o R‐12
Internal Lighting:
L
All internal lighting syystems are to
o have a ligh
hting power density less than the tarrget value fo
or the
relevant zone
z type in the
t following table:
LIGHTING
G POWER DENSITY
Whole Space by Whole Spacce by
Building Space Building S
Space
Building Area
A Type (W/m2) (W/m2)
( Building Area Typee (W
W/m2) (W//m2)
Active Sto
orage 7.8 Cardd File & Cataloguing 10.7
Atrium – First Three Flo
oors 5.8 Reading Area 11.6
MAN NUFACTURING G
Atrium – Each Additional Floor 1.9 12.6
FAC
CILITY
AUTOMO OTIVE FACILITY 8.7 MOTTEL 9.7
Classroomm/lecture/train
ning 12.6 Dining Area 11.6
Conferennce/Meeting/M Multipurpose 10.7 Gueest quarters 10.7
Corridor//Transition 4.8 Receeption/Waitingg 20.3
MOTTION PICTURE
Electrical/Mechanical 10.7 11.6
THEEATER
Food Preparation 11.6 Auddience/Seating Area 11.6
Inactive Storage
S 1.9 Lobby 9.7
7
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
8
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
The follow
wing sensors and controls are required to be provideed as noted:
• Liight reductio on controls: occupant controls to reduce r the connected
c liighting load in a
reeasonably uniform illumination pattern n by at least 50
5 percent
• Daylight zone control: provvide individuaal sensor/con ntrol that con
ntrols the ligh
hts independeent of
geeneral area lighting. Each daylight conttrol zone shall not exceed 232m²
• Occupancy
O sen
nsors: installeed in all classrooms, confeerence/meeting rooms, em mployee lunch and
break rooms, private officees, restroomss, storage roo oms, janitorial closets and other zones 28m²
or less enclose ed by ceiling height
h partitioons. Devices must be proggrammed to automaticallyy turn
offf lights within 15 minutess of all occupaants leaving the space
• Tiime clock co ontrols: in zoones not con ntrolled by occupancy
o seensors, autom matic time switch
s
coontrol devices shall be useed, incorporatting override devices
• Sp pecific application controls: dedicated controls
c for the following applications
o Displayy/accent lightting
o Hotel guest
g room liighting
o Task lighting
o Non‐visual lighting
o Demonstration ligh hting
9
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
External Lighting:
L
The total exterior lighhting power for
f the buildiing is to be less than thee sum of the individual ligghting
power deensities permiitted for the relevant appplications considered. Trade‐offs are permitted
p bettween
the appliccations listed under the Trradable Surfaaces section. All external lighting applications undeer the
Non‐tradaable Surfaces must complyy with the ligh hting power density
d speciffied.
Applicationns Lighting Po
ower Densitiess
Uncovere ed Parking Areeas
Parkking Lots and drives
d 1.45
5 W/m2
Building Grounds
Walkways
W less than 3 metres wide 2.95
5 W/linear metre
Walkways
W 3 mettres wide or grreater 1.94
4 W/m2
Stairrways 9.69
9 W/m2
Tradable Surfaces
deposittories 81.0
0 W per addittional ATM perr location
W/m2 of un ncovered area (covered
Enttrances and gaatehouse inspeection areas are in
ncluded in the "Canopies
12.1
1
stations at
a guarded faccilities and Overhaangs" section of
o
"Tradable Surfaces")
S
W/m2 of un ncovered area (covered
Loading areas for law
w enforcementt, fire,
areas are in
ncluded in the "Canopies
ambulaance and otherr emergency seervice 4.84
4
and Overhaangs" section of
o
vehhicles
"Tradable Surfaces")
S
Drive‐up windows at faast food restauurants 360.0
0 W per drivee‐through
Parkking near 24‐ho
our retail entraances 720.0
0 W per main n entry
The follow
wing sensors and controls shall be provvided for all exxterior lightin
ng application
ns:
• Automatic con ntrols capablee of turning off exterior ligghting when sufficient
s dayllight is available or
w
when the lightting is not req
quired during night time ho ours
10
PBRS – RE-R
R1 Energy
y Prescrip
ptive Pathway
Da
ate: July 2011
2
11