S3-Logger Datalogger

User Manual

Ginlong Technologies Co., Ltd.


Contents
S3-Logger Datalogger User Manual ………………………………………………………………………………………………………………………
1
1. About this document ……………………………………………………………………………………………………………………………………………………………………
1
1.1 Target ………………………………………………………………………………………………………………………………………………………………………………………………
1
1.2 Note ……………………………………………………………………………………………………………………………………………………………………………………………………
1
1.3 Symbol Description ……………………………………………………………………………………………………………………………………………………………… 1
2. Safety Notice ……………………………………………………………………………………………………………………………………………………………………………………… 2
3. Product Description ………………………………………………………………………………………………………………………………………………………………………
3
3.1 Product Introduction ……………………………………………………………………………………………………………………………………………………………
3
3.2 Application Scenarios Introduction …………………………………………………………………………………………………………………………
3
3.3 Appearance ………………………………………………………………………………………………………………………………………………………………………………
4
3.4 Power Wiring Diagram ……………………………………………………………………………………………………………………………………………………… 4
3.5 Communication Terminal Description …………………………………………………………………………………………………………………
5
3.6 Indicator Light Description ……………………………………………………………………………………………………………………………………………… 6

4. Installation Process ……………………………………………………………………………………………………………………………………………………………………


7
5. Mechanical Installation ……………………………………………………………………………………………………………………………………………………………
8
5.1 Equipment Disassembly ……………………………………………………………………………………………………………………………………………………
8
5.2 Device Installation …………………………………………………………………………………………………………………………………………………………………
8
6. Electrical Connections …………………………………………………………………………………………………………………………………………………………… 10
7. Configuration ……………………………………………………………………………………………………………………………………………………………………………………… 12
7.1 Network Configuration ……………………………………………………………………………………………………………………………………………………… 12
7.2 Software Configuration ………………………………………………………………………………………………………………………………………………… 12

8. Routine Maintenance ………………………………………………………………………………………………………………………………………………………………… 23


9. Common Problems ……………………………………………………………………………………………………………………………………………………………………… 24

10.Appendix …………………………………………………………………………………………………………………………………………………………………………………………………… 25

Product Datasheet ………………………………………………………………………………………………………………………………………………………………………


25
1. About this document
This manual is applicable to the following data logger of Ginlong Technology Co., Ltd.
S3-Logger, G3-Gateway.

1.1 Target
Provide users with detailed product information and installation, operation and maintenance
instructions of S3-Logger.

1.2 Note
This manual is applicable to the on-site installation and configuration of S3-Logger data logger,
and requires professional technicians to operate.

1.3 Symbol Description


In order to ensure the safety of users, power grid, and equipment when using this product, the
manual provides relevant warning symbols. Please read it carefully to better use the equipment
and avoid personal and property damage.

Danger:
Indicates a high potential danger, which may cause personal injury or property damage if it
cannot be avoided.
WARNING:
Indicates a moderate potential danger, which may result in personal injury or property
damage if it cannot be avoided.
CAUTION:
Indicates a low potential hazard which, if not avoided, may result in personal injury or
property damage.
Note:
Indicates that there is a low potential danger, if it cannot be avoided, it may cause personal
injury and property damage.

.1.
2. Safety Notice
S3-Logger is designed in accordance with international safety regulations in order to ensure
the safety of people, power grid and equipment. As a power electronic product, relevant safety
regulations must be followed in the stages of installation, commissioning, operation, and
maintenance. Improper operation may result in casualties and equipment damage.
Special attention: Only professionals with relevant qualifications can perform installation,
wiring and other operations on this product.

Danger:
Please install and connect this product by professionals with relevant knowledge.

.2.
3. Product Description
3.1 Product Introduction
S3-Logger is mainly used in industrial and commercial, distributed photovoltaic projects,
safe and reliable, easy to install, flexible networking, multi-device access, intelligent operation
and maintenance.
Easy to install: Desktop installation, rail installation
Flexible networking: Support 4 channels of RS485, 1 channel of Ethernet communication
Multi-device access: Support inverter, electricity meter, weather station equipment access
(standard modbus)
Support Protocol: RS485: support modbus-RTU / Ethernet: support modbus-TCP, 104
Intelligent operation and maintenance: support EPM, breakpoint resume and other functions

3.2 Application Scenarios Introduction


Application scenarios of data logger
PV Plant Digitial
Solis Cloud Management System

Solis inverter

Router

PV

Solis Cloud

PV

Solis inverter S3-Logger Meteorograph

.3.
Power Meter
PV

Grid

PV
DC AC Internet Ethernet RS485 Communication Cable Communication

.3.
3. Product Description
3.3 Appearance

3.4 Power Wiring Diagram

+ - PE

.4.
3. Product Description
24V power supply

COM Logger

AC:85-264V
DC:120-370V

Danger:
Please strictly follow the above example for wiring.

3.5 Communication Terminal Description

1 10

5.08mm 1*10P Terminals

.5.
3. Product Description

NO. definition NO. definition

1 Port 1 RS-485_A 6 Port 3 RS-485_A

2 Port 1 RS-485_B 7 Port 3 RS-485_B

3 Port 2 RS-485_A 8 Port 4 RS-485_A

4 Port 2 RS-485_B 9 Port 4 RS-485_B

5 GND 10 GND

WARNING:
Follow the wire markings for wiring.

3.6 Indicator Light Description

Model S3-Logger

Light Color Status Function

ON Always on after power on,the power supply is normal


PWR Green
OFF Power OFF

RUN Green ON/Blink System running indicator,on/flashing is normal

F1 Green OFF Unused

F2 Green Blink Module communication status,flashing irregularly

.6.
4. Installation Process
Equipment
disassembly and
1
inspection

Mechanical
2 installation

Electrical
3
Installation

Software
4 configuration

Data check
5

NO. Process Reference Chapter

Equipment disassembly
1 5.1
and inspection

2 Mechanical installation 5.2

3 Electrical Installation 6

4 Software configuration 7

5 Data check 7

.7.
5. Mechanical Installation
5.1 Equipment Disassembly
Check that the delivery is complete and undamaged according to the packing list inside the package.

NO. Name Num Comment

1 S3-Logger Datalogger 1

2 Power terminal 1

Serial communication With 2*120 ohm


3 1 terminating resistors
terminal

4 Power Supply 1

5 DIN-Rail 1

5.2 Device Installation


It can be installed on the wall, desktop or rail according to the actual situation of the site

DIN-Rail Wall Mount

COM Logger

10cm

Wall and desktop installation

.8.
5. Mechanical Installation
1. Choose a suitable place (wall, metal surface, desktop);
2. Use a marker to mark the drilling position;
3. Use an electric drill/impact drill to make holes at the marked locations;
4. Fastening with expansion screws (wall) or with nuts (metal surface)

Danger:
Please avoid other wires in the wall when drilling to avoid casualties.

Rail installation
1. Fix the guide rail in a suitable position
2. S3-Logger is tilted at a certain angle, so that the upper clip fits into the guide rail
3. Push the lower part of S3-Logger and snap it into the guide rail

Warning:
Please observe the surrounding environment during installation to avoid hand scratches.

Power supply installation


The power supply only supports rail installation. For installation steps, please refer to the
S3-Logger rail installation steps.

.9.
6. Electrical Connections
24V power supply

COM Logger

AC:85-264V
DC:120-370V
Power supply installation steps

1. Use a 2.5mm² wire, strip the insulation for 8-10mm.


2. The +V and -V terminals of the power supply are respectively connected to the V+ and
V- terminals of the S3-Logger device.

Danger:
Please be sure to check the corresponding terminal carefully when wiring, so as to avoid
injury to personnel and equipment.

RS485 connection

1 10

5.08mm 1*10P Terminals

.10.
6. Electrical Connections
NO. definition NO. definition

1 Port 1 RS-485_A 6 Port 3 RS-485_A

2 Port 1 RS-485_B 7 Port 3 RS-485_B

3 Port 2 RS-485_A 8 Port 4 RS-485_A

4 Port2 RS-485_A 9 Port 4 RS-485_B

5 GND 10 GND

1. Use 1~1.5mm² twisted pair with shielding layer ;


2. Strip the protective layer of the communication cable by about 20mm, and strip the insulation
layer of the wires by about 10mm ;
3. Connect the stripped wires to the RS485 port of the S3-Logger device ;
4. If multiple inverters need to be monitored on site, daisy-chain cables can be used for the
inverters. Each serial port of S3-Logger can connect 15 inverters.

Note:
When wiring, RS485A is connected to the A port of the S3-Logger device, and RS485B is
connected to the B port of the S3-Logger device.

.11.
7. Configuration
7.1 Network Configuration
The product adopts WEB configuration, it is recommended to use browser chrome version 100
or above, and the resolution of computer is recommended to be 1920*1080. If there is a firewall
on site, please let the firewall allow the following IP and port, so that the data collected can be
effectively uploaded.
IP: Allocation according to firewall policy, Logger for adaptation.
Solis cloud platform: port 1883.
IEC104 protocol: 2404-2405 ports.
Remote maintenance ports: 47, 1723, 1777 ports.

7.2 Software Configuration


1.Modify the computer IP, and keep the computer and Logger datalogger IP in the same network
segment, and use the network cable to connect the computer and Logger device.

.12.
7. Configuration
2. Enter 192.168.1.254:1323 in the URL bar of the browser.
Account: admin; Password: 123456

.13.
7. Configuration
3. Func on introduc on

Interface config Used to configure device access

Device data For device view

Forwarding service Used to select forwarding channels

Used to configure
App Config Zero Injection (datalogger + meter)
parameters and select me zone

Account password Used for password change

Plug-in Configura on CN/EN


Device restart Full screen switch IP configura on
update update switch

For configura on
For so ware file update, Device so
driver update, follow the restart
follow the opera on
prompts
prompts

.14.
7. Configuration
4.Interface config
The configuration function of S3 logger, you can add inverters, EPM (Solis EPM Device),
meteorological meters, meters and other devices through the Add Device. Com1 and Com2
support inverters and EPM devices, Com3 supports meteorological meters, and com4 supports
meters (two-way electric meters can be used to meet the zero injection function).

5.Add EPM and inverter to Com1 and com2.


(1) Click Add Device to select a device type. You can select EPM or inverter
(2) The default device address of the EPM is 1, and the default device address of the inverter is
1-15. If the default value is used, you do not need to consider the second row. The third line
is the rated power of the inverter, which must be filled in.
(3) If the inverter address is not in the default setting, click the number from 1 to 15 based on
the number of connected devices, and manually enter the inverter address in the second row.
Note: The device address entered manually cannot be the same as the default address.
(4) If an error occurs, the configuration content will be confused. You can delete all the
configurations (YES or NO) and restart the datalogger to restore the data.

.15.
7. Configuration
After the configuration is completed, as shown in Figure:

6. Configure the weather meter and electricity meter in COM3 and COM4.
The default device addresses are 1-3. If other addresses are required,
configure them like above inverters

.16.
7. Configuration
7. If you want to view Zero Injection (datalogger + meter) data, you need to add the
corresponding meter information to COM4; otherwise, the corresponding device
information cannot be added to the Zero Injection list. This page is used to display
Zero Injection data. If YES is selected, you can view the corresponding Zero Injection
function data.

Note that after adding the device, it is necessary to restart the device

.17.
7. Configuration
8. "Device data" can view the real-time data of the connected device. At the same time,
the inverter can be remotely adjusted and controlled by "Control and Telecontrol".

Because the meter involves PT/CT ratio and other issues, after adding the meter
information in Interface config, you must set the strain ratio parameters in the Device data
according to the sequence in below figure. For example, if the PT ratio is 10kv to 100v,
100 needs to be delivered.

.18.
7. Configuration
9. “Forwarding service” allows you to set forwarding information.
Supports IEC104, Modbus-TCP, and Soliscloud forwarding, the backflow power and
Zero Injection function can be changed remotely via IEC 104 or Modbus-TCP with
Zero Injection function (datalogger + meter).

Protocol Communication parameter

IP address, subnet mask, and gateway Same as the device network port
IEC104
Port 2404
IP address, subnet mask, and gateway Same as the device network port

Port 502

Tele Function code 02


signaling Register start address

Function code 03
Register start address
Telemetering
Data type 32-bit short floating point

Byte order HH HL LH LL

Function code 04
Register start address
Tele pulse
Data type 32-bit short floating point

Byte order HH HL LH LL

Function code 05
Control
Register start address

Function code 06 or 10
Tele
Data type 16 bit signed integer
control
Byte order HL

ON Upload to Solis Cloud


Soliscloud
OFF Do not upload to Solis Cloud

.19.
7. Configuration

10. Zero Injection function (datalogger + meter)


Note: This function only supports the function judgment based on the total power of the
grid point.
Configuration:
(1) Select the Zero Injection list in the sequence shown in the following figure,
and select System Configuration Table to set Zero Injection system parameters

.20.
7. Configuration

Name Meaning

Backflow power(KW) Backflow power setting value

Judgment interval Logic judgment time, the default is 3 seconds,


(seconds) Calculate based on the number of inverters * 1.5 seconds

Three-phase average power mode (default)


Working mode
Three-phase minimum power mode

Active power value Calculated according to three-phase voltage and current (default)
sampling Take sampling value

Grid-side meter Select from a list

Note that after the configuration is completed, the device needs to be restarted

.21.
7. Configuration
11. Time zone selection, this time zone involves the timing of the inverter and other functions,
please select your own time zone according to the sequence shown in the diagram,
and select no for the rest. After the configuration is complete, click Save and restart
datalogger

12. Datalogger login password change

.22.
8. Routine Maintenance
Check Method

Check whether there is electrical interference near S3-Logger

Check for corrosive substances near S3-Logger


Working environment
Check if the S3-Logger ambient temperature is out of range
Check if S3-Logger is clean
Check whether the S3-Logger power supply is stable and reliable

Circuit maintenance Check whether the S3-Logger power supply and communication
cables are fastened

Check if S3-Logger is well grounded

Equipment installation
Check S3-Logger for dropping risk
and maintenance

.23.
9. Common Problems
No Problems Explanation

Observe the indicator light of the equipment


How to deal with the
1 and check item by item according to the instruction
device offline?
manual;

1. Debug software to check whether the inverter is


normal (excluding inverter hardware problems);
2. Measure whether the 485 cable has any abnormal
How to deal with the conditions such as interruption and grounding and
2
inverter without data? check whether the shielding layer of the 485
communication cable is effectively grounded;
3. Replacement test with other normal equipment
(excluding data acquisition hardware problems);

1. Recommended weather station manufacturers:


Jinzhou Sunshine (http://www.jz322.net/).Jinzhou
Licheng (http://www.zn17.com.cn/);
Are there any
2. Recommended meter manufacturer: Acrel
recommended
(https:llwww.acrel.cn/);
3 manufacturers for
3. Other brands: The equipment communication
weather stations and
protocol is required to be standard Modbus. and the
electricity meters?
customer provides the communication protocol for
advanced development. It is recommended to be a
relatively reliable and well-known local brand.

.24.
10.Appendix
Model Name S3-Logger

Communication

Supported device type Solis inverter


Number of connected
Each RS485 PORT≤ 15
inverter
Data collection intervals 5 minutes

Status indicator LED x 2,Power,Run

RS485 COM x 4,1200-19200 bps,communication distance ≤ 1000m

Ethernet communication LAN x 1,10 / 100Mbps adaptive,communication distance ≤ 100m

Communication Protocol

RS485 Modbus-RTU,IEC60870-5-103,DLT645

Ethernet Modbus-TCP,IEC60870-5-104

Electrical

AC power supply 100~240V,50Hz/ 60Hz

DC power supply 9~36V


Operating power
consumption
5W@12VDC

Environment

Operating temperature -40℃ ~+80℃

Storage temperature -40℃ ~+80℃

Operating humidity ≤ 85%,Relative humidity,no condensa

Operating altitude ≤ 4000m

Protection degree IP20

Mechanical

Dimensions(L*W*H) 89*121*27mm

Installation method Rail Mounting,Desktop installation

Others

Certification CE、RoHS