Kontaktor Trifazen Bobina 24vdc 3pst - 3no 12a lp1k1201bd NC 0
Kontaktor Trifazen Bobina 24vdc 3pst - 3no 12a lp1k1201bd NC 0
Kontaktor Trifazen Bobina 24vdc 3pst - 3no 12a lp1k1201bd NC 0
Main
Range of product TeSys K
Product or component type Contactor
Device short name LP1K
Contactor application Motor control
Resistive load
Utilisation category AC-1
AC-3
AC-4
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage 690 V AC 50/60 Hz for power circuit
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
<= 690 V AC 50/60 Hz for signalling circuit
[Ie] rated operational current 20 A (<= 50 °C) at <= 440 V AC AC-1 for power
circuit
16 A (<= 70 °C) at 690 V AC AC-1 for power circuit
12 A at <= 440 V AC AC-3 for power circuit
Motor power kW 3 kW at 220...230 V AC 50/60 Hz
4 kW at 480 V AC 50/60 Hz
4 kW at 500...600 V AC 50/60 Hz
4 kW at 660...690 V AC 50/60 Hz
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
5.5 kW at 380...415 V AC 50/60 Hz
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
5.5 kW at 440 V AC 50/60 Hz
Control circuit type DC standard
Control circuit voltage 24 V DC
Auxiliary contact composition 1 NC
[Uimp] rated impulse withstand 8 kV
voltage
Overvoltage category III
[Ith] conventional free air thermal 20 A at <= 50 °C for power circuit
current 10 A at <= 50 °C for signalling circuit
Irms rated making capacity 110 A AC for signalling circuit conforming to IEC
60947
144 A AC for power circuit conforming to NF C 63-
110
144 A AC for power circuit conforming to IEC
60947
Rated breaking capacity 110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand 80 A 1 s signalling circuit
current 90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
115 A <= 50 °C 1 s power circuit
105 A <= 50 °C 5 s power circuit
100 A <= 50 °C 10 s power circuit
75 A <= 50 °C 30 s power circuit
55 A <= 50 °C 1 min power circuit
50 A <= 50 °C 3 min power circuit
25 A <= 50 °C >= 15 s power circuit
Associated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC
60947
10 A gG for signalling circuit conforming to VDE
0660
Average impedance 3 mOhm at 50 Hz - Ith 20 A for power circuit
[Ui] rated insulation voltage 690 V for power circuit conforming to IEC 60947-4-
1/3
1
600 V for power circuit conforming to UL 508
690 V for signalling circuit conforming to IEC
60947-4-1
690 V for signalling circuit conforming to IEC
60947-5-1
600 V for signalling circuit conforming to UL 508
600 V for power circuit conforming to CSA C22.2
No 14
600 V for signalling circuit conforming to CSA
C22.2 No 14
Electrical durability 0.3 Mcycles 20 A AC-1 at Ue <= 440 V
1.3 Mcycles 12 A AC-3 at Ue <= 440 V
Mounting support Plate
Rail
Standards BS 5424
IEC 60947
NF C 63-110
VDE 0660
Product certifications CSA
UL
Connections - terminals Screw clamp terminals 1 cable(s) 1.5...4 mm² -
cable stiffness: solid
Screw clamp terminals 1 cable(s) 0.75...4 mm² -
cable stiffness: flexible - without cable end
Screw clamp terminals 1 cable(s) 0.34...2.5 mm² -
cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 1.5...4 mm² -
cable stiffness: solid
Screw clamp terminals 2 cable(s) 0.75...4 mm² -
cable stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 0.34...1.5 mm² -
cable stiffness: flexible - with cable end
Tightening torque 1.3 N.m - on screw clamp terminals - with
screwdriver Philips No 2
1.3 N.m - on screw clamp terminals - with
screwdriver flat Ø 6 mm
Operating time 10 ms coil de-energisation and NO opening
30...40 ms coil energisation and NO closing
Safety reliability level B10d = 1369863 cycles contactor with nominal
load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with
mechanical load conforming to EN/ISO 13849-1
Mechanical durability 10 Mcycles
Operating rate 3600 cyc/h
Complementary
Control circuit voltage limits 0.8...1.15 Uc at <= 50 °C operational
0.1...0.75 Uc at <= 50 °C drop-out
Inrush power in W 3 W at 20 °C
Hold-in power consumption in W 3 W at 20 °C
Heat dissipation 3W
Auxiliary contacts type Type instantaneous (1 NC)
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non overlap distance 0.5 mm
Insulation resistance > 10 MOhm for signalling circuit
Environment
IP degree of protection IP2x conforming to VDE 0106
Protective treatment TC conforming to IEC 60068
TC conforming to DIN 50016
Ambient air temperature for operation -25...50 °C
Ambient air temperature for storage -50...80 °C
Operating altitude 2000 m without derating in temperature
2/3
Flame retardance V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Mechanical robustness Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Shocks contactor opened, on X axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on X axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Height 58 mm
Width 45 mm
Depth 57 mm
Product weight 0.225 kg
Offer Sustainability
Sustainable offer status Green Premium product
RoHS Compliant - since 0633 - Schneider Electric declaration of conformity
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
3/3