Technical Specifications
Technical Specifications
PROPOSED RENOVATION OF
TWO (2) STOREY RESIDENCE
AT
BLK 15 LOT 11 PHASE 1,
HONGKONG VILLAGE, BRGY.
BANAY-BANAY, CITY OF
CABUYAO, LAGUNA, 4025
The project will involve the PROPOSED RENOVATION OF TWO (2) STOREY
RESIDENCE located at BLK 15 LOT 11 PHASE 1, HONGKONG VILLAGE, BRGY. BANAY-
BANAY, CITY OF CABUYAO, LAGUNA, 4025 pursuant to the technical specifications.
The project will have an Approved Budget for the Contract (ABC) of TWO MILLION
ONE HUNDRED NINETY-FOUR THOUSAND NINETY-THREE AND FIFTY-FIVE CENTAVOS
(₱ 2,194, 093.55) excluding all taxes and applicable permits, licenses and clearances, for
the projects mentioned above.
The RENOVATION OF TWO (2) STOREY RESIDENCE in which the Approved Budget
Contract shall be allocated for the Architectural, Civil, Electrical, and Plumbing works.
Structural works
D. Slab on fill must not be placed unless fill has been properly compacted
clean coarse sand bed except driveways where it shall be 50mm. Backfill
1
of all excavated areas and the preparation of sub-base shall be well
compacted at least 95% of the standard proctor density before well
compacted clean coarse sand are laid.
E. The contractor shall coordinate with the AR, ME, SE, and EE plans as to
the exact sizes and location of the holes thru floors slab and walls.
G. Concrete Slabs
o For two-way slabs, bars along the shorter span shall be placed
below the longer span bars at center and above of the longer span
bars at the supports. The spacing of bars at the column strip shall
be 1.5 times the spacing in the middle strip but in any case, greater
than 2.5 the slab thickness or 450mm.
o When Beam crosses a girder, rest beam bars on top of the girder
bars. Reinforcing bars shall be symmetrical about the centerline
whenever possible. Upper bars shall be placed directly above those
bars in the bottom layers.
o No splices shall be permitted on beams where critical bending
occurs. Length of lap splice where permitted shall be shown in the
approved drawings, not more than 50% of the bars at any one
section shall be allowed to splice therein. A typical welded splice
detail is shown in the approved drawing.
o For all beams, always fit the reinforcement in one layer whenever
possible. Whenever beams are supporting a planted column, bottom
bar at midspan of the beam shall continue up to the supports.
o For girders, hoops shall be used within the distance twice of the
girder depth. Beyond it, stirrups with seismic hooks may be used
within the spliced length, 10mmǿ hoops shall be provided at 0.10M
3
O.C.
o Individuals bars within a bundle shall terminate at different points
with at least 40 times the bar diameter stagger.
10mmǿ 300 450 250 375 250 350 450 650 400 575 350 500 200 200 200 250 200 200
12mmǿ 350 550 300 450 300 400 550 800 475 700 425 625 200 200 200 300 250 250
16mmǿ 475 750 425 600 375 550 750 1050 650 925 575 825 250 250 250 350 350 300
20mmǿ 600 900 525 750 475 700 900 1300 800 1150 700 1025 300 300 250 450 400 350
25mmǿ 900 1375 800 1200 700 1050 1375 2050 1200 1800 1050 1600 400 350 300 550 500 450
28mmǿ 1025 1650 900 1325 800 1200 1550 2300 1325 2000 1200 1800 450 400 350 650 550 500
32mmǿ 1175 1750 1000 1525 900 1350 1750 2625 1525 2275 1350 2050 500 450 400 750 650 550
NOTES: 1. For reinforcing bars in tension with stand hook at its end. Development length may be divided by 2.50
2. Case 1 is for bars with the clear spacing not less than the bar diameter or either less than 25mm otherwise Case 2 shall be used
I. Concrete Column
0.450MM
Bigger Column Dimension
(Clear Column Height)/16
J. Structural Steel
4
o All welds shall be E70XX electrode and shall develop at least
100% of the strength of the connected members.
o The contractors shall submit to the structural engineer the
shop/fabrication drawings for approval before any works shall
commence.
o All double angle structural members must be provided with filler
plates at 0.30M 0.C. maximum spacing.
o All exposed structural steel members shall have at least two
coats of red lead o zinc chromate primer paint.
o All trusses, beams, and Girders, must be provided with a camber
at the rate of 3mm for every 3.0m of clear span in a parabolic
layout.
K. Foundations
L. CHB Walls
o All CHB Walls have a minimum compressive strength of 450PSI
and shall be reinforced as presented in Table 3.
o Minimum lap length of splice shall be 250mm.
5
Electrical Works
Plumbing Works
7
o Proposed sanitary utilities shall conform to the actual
location, depth and invert elevation of all existing
pipes and structure as verified by the contractor.
o Refer to architectural plans for area drain, catch
basin, floor drains and clean out location.
o All slopes for horizontal drainage shall maintain 2%
unless otherwise specified.
o Size of water supply pipes to fixtures shall be in
accordance with the manufacturer’s instructions.
o The contractor shall verify all existing utilities at site,
coordinate the woks with the line service connecting
point unless otherwise specified.
o All pipe sizes and dimensions are in millimeters unless
otherwise specified.
o All hangers shall not be anchored at purlins, unless
otherwise approved by the structural engineer.
MATERIAL SPECIFICATIONS
o Water lines- riser, down feed, main distribution and taping water lines shall be
galvanized iron pipe (G.I.) schedule 40, similar to “supreme” pipe.
o Roughing-ins of water lines shall be polypropylene random copolymer (PPRC) pipe,
PN-20, standard conforming to DIN-8077-8078, “BUGATTI” brand or approved equal
fittings shall be fusion type.
o Sewer pipes- shall be polyvinyl chloride (PVC) pipe, series 1000, “NELTEX” brand or
approved equal.
o Waste pipes- shall be polyvinyl chloride (PVC) pipe, series 1000, “NELTEX” brand or
approved equal.
o ACU/AHU/FCU Waste pipe- shall be polyvinyl chloride (PVC) pipes, series 1000,
“NELTEX” brand or approved equal and shall be provided with thick close cell
elastometric thermal insulation “AEROFLEX” brand or approved equal and installed
as per manufacturers recommendation.
o Vent pipes- shall be polyvinyl chloride (PVC) pipes, series 1000, “NELTEX” brand or
approved equal.
o Downspouts- shall be polyvinyl chloride (PVC) pipe, series 1000, “NELTEX” brand or
approved equal.
o Storm drainage lines- for inside building, shall be polyvinyl chloride (PVC) pipes,
series 1000, “NELTEX” brand or approved equal and reinforced concrete drain pipe
for outside building.
o Underdrains/ perimeter drain pipes- shall be polyvinyl chloride (PVC) pipes, series
1000,”NELTEX” brand or approved equal.
o Gate valves- 50 mmФ and smaller, rising stem, all bronze, female threaded,
minimum of 125 PSIG working pressure, similar to “ BERMAD” brand or approved
equal 65 mmФ and larger, shall be rising outside screw and yoke
POTABLE WATER LINES SANITARY DRAINAGE AND VENT LINES
Nominal Pipe Polypropylene Random (PPR) Nominal Pipe Soil and Vent Piping Polyvinyl Chloride
Diameter (mm) Pipe PN20 (mm) Diameter (mm) (PVC) Pipe -Series 1000 (mm)
8
15 25 50 63
20 32 75 90
25 40 100 110
32 50 150 160
40 63 200 200
50 75 250 250
65 90 300
75 110 375
Pipe Diameter (mm) Polypropylene Random (PPR) Pipe Diameter (mm) Polyvinyl Chloride (PVC) Pipe (m)
Pipe (mm)
25 .75 63 .75
32 .75 90 1
40 .75 110 1
50 1 160 1.25
63 1 200 1.25
75 1 250 1.5
Nominal Pipe Polyvinyl Chloride (PVC) Pipe-Series 1000 (mm) High Density Polyethylene (HDPE) Pipe-PE 80/PN
Diameter (mm) 6 (mm)
50 63
75 90
100 110
150 160
200 200
250 250
300 315
350 400
400 450
450 500
Pipe Diameter (mm) Polyvinyl Chloride (PVC) Pipe (m) High Density Polyethylene (HDPE) (mm)
63 .75
90 1
110 1
150 1.25
200 1.25
9
III. SCOPE OF WORKS AND PROJECT IMPLEMENTATION
A. Construction Phase
The CONTRACTOR shall propose the most reasonable time schedule for the
completion of the project. It is expected that this period will not exceed One Hundred
Fifty (150) working days for the Construction Phase.
a) The CONTRACTOR shall certify that he has, at his own expense, inspected and
examined the proposed project site, its surroundings and existing
infrastructure and facilities related to the execution of the work and has
obtained all the pieces of information that are considered necessary for the
proper execution of the work covered under these Terms of Reference.
c) 10
The CONTRACTOR will be held accountable for accidents that might occur
during the execution of the project. The CONTRACTOR is required to install
warning signs and barriers for the safety of the general public and the
avoidance of any accidents and provide appropriate and approved type
personal protective equipment for their construction personnel.
VI. INSTALLATION AND WORKMANSHIP
Tapping for utilities such as power supply, water supply and sewage drainage
shall be coordinated with their respective utilities/ service provider/ companies, and all
works involved, including access to utilities tapping point, excavation, removal of
obstructions, concrete breaking, backfilling and restoration of affected areas, shall be
coordinated and included in the scope of work and cost of the project.
11