Tem 3038450 0104
Tem 3038450 0104
Tem 3038450 0104
Technical Manual
Temperature Controller KS 50-1
90600-6032
TechPub_2614345_0109 - TeM_3038450_0104_fro.fm
WARNING
Read and follow all safety precaution instructions throughout this
manual and on safety signs attached to this equipment.
Failure to follow all safety precaution instructions could result in death or
serious injury.
The rebuilding must only be performed by personnel mandated by Tetra Pak.
and all Tetra Pak products are trademarks belonging to the Tetra Pak Group.
The content of this manual is in accordance with the design and construction of the machine or
equipment at the time of publishing. Tetra Pak reserves the right to introduce design modifications
without prior notice.
The English language version of this document contains the original instructions. All other language
versions are translations of the original instructions.
This document was produced by:
Tetra Pak Packaging Solutions AB
Ruben Rausings gata
221 86 Lund
Sweden
Additional copies can be ordered from Tetra Pak. When ordering additional copies, always provide the
document number.
Doc. No. TeM-3038450-0104
Issue 2011-09
This manual is valid for: i Introduction
1 Installation Instructions
TeM
Technical Manual
2 Enclosed
Documentation
UP Updates of Manuals
Issue 2011-09
TechPub_2614345_0109 - TeM_3038450_0104_fro.fm
i Introduction
TechPub_2614345_0105 - 04_3031797_01.fm
TechPub_2614345_0105 - 04_3031797_01.fm
Personnel Requirement . . . . . . . . . . . . . . . . . . . . i - 5
Declaration of Conformity . . . . . . . . . . . . . . . . . . . i - 11
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i - 12
TechPub_2614345_0105 - 04_3031797_01.fm
This page intentionally left blank
Personnel Requirement
The sentences below are translations of the text “The rebuilding must only be
performed by personnel mandated by Tetra Pak” located on the front page of
this manual.
BG
Реконструкцията трябва да се извършва само от персонал,
упълномощен от Tetra Pak.
CS
Rekonstrukce musí být prováděna pouze pracovníky pověřenými firmou
Tetra Pak.
DA
Ombygningen må kun udføres af personale bemyndiget af Tetra Pak.
NL
Het reviseren mag uitsluitend door Tetra Pak erkend personeel worden
uitgevoerd.
ET
Ümberehitust tohivad teostada ainult Tetra Paki poolt volitatud töötajad.
FI
TechPub_2614345_0105 - 04_3031797_01.fm
(Cont'd)
PT
A remodelação só deve ser feita por pessoal mandado pela Tetra Pak.
RO
Reconstrucţia trebuie realizată numai de către personal mandatat de
Tetra Pak.
SL
Predelavo lahko izvede le osebje, ki je v Tetra Pak-u odgovorno za
vzdrževanje.
SK
Prestavba musí byť vykonávaná iba pracovníkmi poverenými firmou
Tetra Pak.
ES
Solamente personal con mandato de Tetra Pak debe llevar a cabo la
reconstrucción.
SV
Ombyggnaden får endast utföras av personal som bemyndigats av Tetra Pak.
IS
TechPub_2614345_0105 - 04_3031797_01.fm
Endursmíð má aðeins vera í höndum starfsmanna sem Tetra Pak hefur
viðurkennt.
NO (Bokmål)
Ombyggingen skal kun utføres av personer som er oppnevnt av Tetra Pak.
NO (Nynorsk)
Ombyggingen skal kun utføres av personer som er oppnevnt av Tetra Pak.
RH Right Hand
SPC Spare Parts Catalogue
TBA Tetra Brik Aseptic
TeM Technical Manual
TP Tetra Pak
UL Underwriters Laboratories Inc.
TechPub_2614345_0105 - 04_3031797_01.fm
these documents are described in the Installation Instructions chapter.
• The UP Updates of Manuals chapter contains Update Log pages for use
in older manuals not provided with those pages.
Page Layout
For information about page layout and numbering, consult the Introduction
chapter of the machine’s existing Maintenance Manual.
Every main page in a manual contains a header and a footer. The page header
contains the chapter name (1) and the section name (2). The page footer
contains the page number (3), and the document number (4). See also the
Page Numbering section.
1 2
4 3
1 Chapter name
2 Section name
3 Page number
4 Document number
Page Numbering
A page number has three parts:
• chapter number (1)
• consecutive page number (2) within the chapter
• total number of pages (3) in the chapter.
Typographical Conventions
Controls on the operator panel, emergency stop devices, and program steps
are printed in CAPITAL LETTERS.
Menu names, button names and other text displayed in software are printed
in Courier.
Cross-references are underlined.
TechPub_2614345_0105 - 04_3031797_01.fm
Symbols
Symbols used in illustrations.
A pointer arrow indicates the position of an object.
Manufacturer
This Tetra Pak equipment has been manufactured by:
Tetra Pak Packaging Solutions AB
Ruben Rausings gata
221 86 Lund
Sweden
Tetra Pak.
Declaration of Conformity
A copy of the Declaration of Conformity can be found in the 2 Enclosed
Documentation chapter. The signed Declaration of Conformity is delivered
separately with the equipment.
Orientation
The temperature controllers are located in the electrical cabinet. See the
standard manuals for your equipment.
The illustration shows the location of temperature controllers for a TBA/19.
TechPub_2614345_0105 - 04_3031797_01.fm
WARNING
Read all safety precaution instructions throughout this manual and on
safety signs attached to this equipment.
Failure to follow all safety precaution instructions could result in death or
serious injury.
TechPub_2614345_0105 - 03_3031798_01.fm
Personnel Requirements . . . . . . . . . . . . . . . . . . ii - 6
Skilled Person . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii - 6
Instructed Person. . . . . . . . . . . . . . . . . . . . . . . . . . ii - 6
Personal Protection. . . . . . . . . . . . . . . . . . . . . . . ii - 7
Supply Systems. . . . . . . . . . . . . . . . . . . . . . . . . . ii - 8
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii - 8
Residual Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . ii - 8
Other Supply Systems. . . . . . . . . . . . . . . . . . . . . . ii - 8
TechPub_2614345_0105 - 03_3031798_01.fm
TechPub_2614345_0105 - 03_3031798_01.fm
This page intentionally left blank
Personnel Requirements
Note! Personnel includes all persons working on or near this equipment.
Only skilled or instructed persons are allowed to work with this equipment.
Skilled Person
A skilled person must have relevant education and experience to enable him
or her to identify hazards, analyse risks, and avoid hazards which electricity,
machinery, chemicals, other energies, and supply systems on this equipment
can create.
Skilled persons must meet local regulations, such as certifications and
qualifications for working with these energies and systems.
Instructed Person
An instructed person must be adequately advised or supervised by a skilled
person. The skilled person enables the instructed person to identify hazards,
analyse risks, and avoid hazards which electricity, machinery, chemicals,
other energies, and supply systems on this equipment can create.
TechPub_2614345_0105 - 03_3031798_01.fm
Personal Protection
Follow the Safety Precautions for the equipment in which the temperature
controller is included.
TechPub_2614345_0105 - 03_3031798_01.fm
Supply Systems
Power Supply
DANGER
Hazardous voltage and moving machinery
The electrical supply disconnecting device must be turned off and secured
with a lock before any maintenance.
Note! The key to the lock must be removed by the technician and retained in
his/her possession until all work is completed.
Follow the Safety Precautions for the equipment in which the temperature
controller is being included.
Certain procedures may require power supply systems to be on. These
exceptions are clearly stated in the installation instructions.
Residual Voltage
DANGER
Hazardous voltage.
Do not touch any terminals immediately after the electrical supply
disconnecting device is turned off. Ensure that no residual voltage remains
TechPub_2614345_0105 - 03_3031798_01.fm
on the capacitors before touching. Wait five minutes. Failure to observe this
information will cause death or serious injury.
After the electrical supply disconnecting device is turned off, residual
voltage remains in the capacitor circuits.
TechPub_2614345_0105 - 04_3031799_01.fm
1.2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 6
1.2-1 Temperature Controller - Replace Philips 19”
Limiter and Regulator . . . . . . . . . . . . . . . . . . . . . 1 - 6
1.2-2 Temperature Controller - Register Parameters . . . 1 - 7
1.2-3 Temperature Controller - Remove . . . . . . . . . . . 1 - 10
1.2-4 Temperature Controller - Change Connections . 1 - 11
1.2-5 Temperature Controller - Set Switches . . . . . . . 1 - 15
1.2-6 Temperature Controller - Set Manually . . . . . . . 1 - 17
1.2-7 Temperature Controller - Install BlueLoader . . . 1 - 20
1.2-8 Temperature Controller - Setup USB Port . . . . . 1 - 24
1.2-9 Temperature Controller - Set Parameters
with BlueLoader . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 28
1.2-10 Temperature Controller - Identify the
Correct Parameter File . . . . . . . . . . . . . . . . . . . . 1 - 34
TechPub_2614345_0105 - 04_3031799_01.fm
TechPub_2614345_0105 - 04_3031799_01.fm
This page intentionally left blank
1.2 Installation
1.2-1 Temperature Controller - Replace Philips 19” Limiter
and Regulator
Machine Status Electrical supply disconnecting device in pos I (ON)
Special Equipment Communication cable, TP No. 90603-0388
AT-compatible PC with CD-ROM drive
SPC Reference 90600-6032
WARNING
Hazardous voltage.
Will shock, burn or cause death.
Take care when working inside the electrical cabinet. For personal
protection, follow the local regulations.
Note! For replacement of Philips 19" rack regulator (90410-0020, 90410-
0021, 90410-0027, 90410-0034, 90410-0035, 90410-0040, 90410-0042),
the adaptor 90600-6033 is needed. Remove the old limiter/regulator.
Assemble the adaptor 90600-6033 and assemble the KS 50-1 temperature
controller (90600-6032) in this adaptor. Download the parameter set
according to section 1.2-9 Temperature Controller - Set Parameters with
BlueLoader.
TechPub_2614345_0105 - 04_3031799_01.fm
Note! The unit contains ESD-sensitive components.
WARNING
Hazardous voltage.
Will shock, burn or cause death.
Take care when working inside the electrical cabinet. For personal
protection, follow the local regulations.
This procedure is intended as a reference if a manual setup of the controller
is required.
a) Press the MENU button (1) for three seconds to step to the parameter
level.
b) Press the MENU button several times until the parameter Loc is
displayed.
c) Use the INCREASE button (2) and the DECREASE button (3) to set the
Loc parameter to “0”.
TechPub_2614345_0105 - 04_3031799_01.fm
d) Press the MENU button for three seconds to step to the parameter level.
W2
1
°C
3 2
1 MENU button
2 INCREASE button
3 DECREASE button
(Cont'd)
(Cont'd)
e) Register all current parameter values of the obsolete temperature
controller in the left “Value” column of the parameter conversion table
on page 1-9: Pb1, ti, td, t1, W, SPL, SPH, SP2, LCL1, LCH1, LCL2
and LCH2. This will make certain that the new temperature controller
performance will be similar to that of the obsolete temperature
controller.
f) Press the MENU button (1) once to return to the operating level.
g) Press the MENU button for five seconds to step to the configuration
level.
h) Register the Con1 and the Con2 parameters. See the parameter
conversion table on page 1-9.
W2
1
°C
TechPub_2614345_0105 - 04_3031799_01.fm
1 MENU button
(Cont'd)
(Cont'd)
i) Transfer each parameter value from the left “Value” column to the right
“Value” column. If required, recalculate the parameter value using the
formula given in the “Recalculation” column of the table.
t1 (regulating parameter) t1
W (setpoint) SP
value)
LCH1 (Higher limit alarm 1) H1
WARNING
Hazardous voltage.
Will shock, burn or cause death.
Follow lockout procedure before maintenance. See chapter ii Safety
Precautions.
Note! The unit contains ESD-sensitive components.
Get a grip on top and bottom of the front panel (1), using thumb and
forefinger, and pull out the controller from the housing (2).
...
TechPub_2614345_0105 - 04_3031799_01.fm
1
1 Front panel
2 Housing
DANGER
Hazardous voltage.
Will shock, burn or cause death.
Follow lockout procedure before maintenance. See chapter ii Safety
Precautions.
a) Disconnect all cable lugs (3) from the terminals (2) on the back panel of
the temperature controller housing (1).
1 2 3
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
b) For each of the disconnected cables:
Replace the cable lug (3) with a cord end terminal (4). If two cables are
connected to the same terminal pin, use a twin cord end terminal (5).
3
4
TechPub_2614345_0105 - 04_3031799_01.fm
3 Cable lug
4 Cord end terminal (for example TP No. 353001-0113)
5 Twin cord end terminal (for example TP No. 353210-0075)
(Cont'd)
(Cont'd)
c) For each of the disconnected cables:
Replace the old cable marking with a new one according to the table
below.
KS 40 marking Function KS 50-1 marking
27 N 2
26 L 230 VAC 1
24 -Alarm 1 4
23 +Alarm 1 5
20 -Alarm 2 7
19 +Alarm 2 8
18 + Heating Logic 11
21 + continuous 0/4..20mA 11
17 - Heating Logic 10
22 - continuous 0/4..20mA 10
10 W/W" SP1/SP2 12
9 W/W" SP1/SP2 14
1 + Thermocouple input 15
2 - Thermocouple input 14
TechPub_2614345_0105 - 04_3031799_01.fm
4 + Current input 13
2 - Current input 14
6 HF Ground not used
(Cont'd)
(Cont'd)
d) Remove the two screws (6) and remove the old temperature controller
housing (1).
e) Install the new temperature controller housing using the two screws (6).
f) Connect the cables to the terminals on the back panel of the temperature
controller housing.
1 6
TechPub_2614345_0105 - 04_3031799_01.fm
6
2 1
1 Front panel
2 Temperature controller housing
(Cont'd)
(Cont'd)
CAUTION
Risk of damaged equipment.
The switch (4) must always be set in LH or RH position. Leaving this switch
open may lead to faulty functions.
b) Check that the switches are set correctly, see illustration.
– Switch (3) in closed position
– Switch (4) in position RH (mA/Pt)
– Switch (5) in position LH (U)
5
U I
TechPub_2614345_0105 - 04_3031799_01.fm
3 4
Loc 10V mA/Pt
3 Switch (Loc)
4 Switch
5 Switch
c) Put the temperature controller back into the housing and push it firmly
until it is in place.
WARNING
Hazardous voltage.
Will shock, burn or cause death.
Take care when working inside the electrical cabinet. For personal
protection, follow the local regulations.
As an alternative, the parameter setting can be downloaded, see section 1.2-
10 Temperature Controller - Identify the Correct Parameter File.
a) Press the ENTER button (1) for at least three seconds to enter the
SETTING MODE.
b) Use the ENTER button (1) and the ARROW buttons (2) and (3) to set
the temperature controller parameters.
For the complete setting sequence, comprising all parameters, see the
illustration on the next page. Retrieve the parameter values from the
TechPub_2614345_0105 - 04_3031799_01.fm
3
1 ENTER button
2 ARROW button, up
3 ARROW button, down
(Cont'd)
(Cont'd)
Pb1
ti1
td1
t1
SPLO
TechPub_2614345_0105 - 04_3031799_01.fm
SPHi
SP2
SPbo
tbo
(Cont'd)
(Cont'd)
L1
H1
dEL1
L2
TechPub_2614345_0105 - 04_3031799_01.fm
H2
dEL2
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
d) Click the NEXT button.
(Cont'd)
(Cont'd)
f) Click the NEXT button.
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
h) Wait for installation to finish, then click the FINISH button.
TechPub_2614345_0105 - 04_3031799_01.fm
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
d) In ‘System’ select the ‘Device Manager’ tab.
(Cont'd)
(Cont'd)
f) Select the ‘Silicon Labs...’ port, right click and select ‘Properties’.
g) In ‘Properties’ select the tab ‘Port Settings’ and then select
‘Advanced...’.
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
h) In ‘Advanced Settings...’ for the port, make sure the ‘COM Port
Number’ is not above 7.
In case the port number is above 7 (like 9, or 14 etc), then change to a port
from 1 to 7 (port 4-7 recommended).
Despite of warnings that may appear on the computer, the changes can be
applied. Some computer issues may also appear.
TechPub_2614345_0105 - 04_3031799_01.fm
TechPub_2614345_0105 - 04_3031799_01.fm
1
1 Communication port
(Cont'd)
(Cont'd)
d) Start the BlueLoader program and select File/Open or click F4.
e) In the next pop-up window, locate the correct *.bct file and click
OPEN.
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
f) In the next pop-up window, choose Device/Save data to
device or click F8.
g) In the next pop-up window, tick the ‘Store data to device’ and ‘Show
available com ports’ options, choose the com port marked ‘(USB)’ and
click OK.
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
h) In the next pop-up window, check the uploading process in the window
Store data to device and click OK when finished.
j) Disconnect the communication cable between the controller and the PC.
(Cont'd)
(Cont'd)
k) Turn the electrical supply disconnecting device OFF. Pull out the
controller from the housing and set the switch (Loc) (2) in open position,
see illustration.
l) Put back the temperature controller into the housing and push it firmly in
place.
TechPub_2614345_0105 - 04_3031799_01.fm
2 Switch (Loc)
(Cont'd)
m) With the electrical supply disconnecting device ON, use the ARROW
buttons to set offset correction. The illustration on page 1-38 explains the
meaning of this parameter.
n) Press ENTER twice to leave the SETTING MODE.
o) Pull out the controller from the housing.
p) Set the switch (6) in open position.
q) Put a label (7) on the controller, see illustration below.
r) Put back the temperature controller into the housing and push it until it is
firmly in place.
7
TechPub_2614345_0105 - 04_3031799_01.fm
3 Switch
4 Label
TechPub_2614345_0105 - 04_3031799_01.fm
locate and open the KS 50 Masters.pdf file.
b) Find the correct master file to use.
c) Locate the file in the ZIP archive.
If the regulator performance is unstable, a’self tuning’ of the parameters can
be performed to optimize the PID parameters.
To run the procedure, the power to the heating circuit must be ON.
Note! During the ‘self tuning’ cycle the heat is turned off and an alarm might
occur.
(Cont'd)
(Cont'd)
d) To start ‘self tuning’, press the ENTER key (A) and the ARROW UP
key (B) simultaneously. The Ada LED (C) goes ON or blinks. Wait for it
to go OFF.
B
A ENTER key
B ARROW UP key
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
See examples of ‘self tuning’ sequences below:
Start - heating power switched on
Heating power Y (see below) is switched off (1). When the change of
process (value X) has been constant during one minute (2), the power is
switched on (3). At the reversal point (see below), the ‘self tuning’ process is
finished and the new parameter is used to control the setpoint W (see below).
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
Start - heating power switched off
The temperature controller waits for 1,5 minutes (1). Heating power Y (see
below) is switched on (2). At the reversal point (see below), the ‘self tuning’
process is finished and the regulator will be using the new parameters.
TechPub_2614345_0105 - 04_3031799_01.fm
Note! Before calibration, be sure the calibrator has already been set
(according to the Pentronic calibration certificate), see instruction 1.2-12
Calibrator - Set Micromite II or 1.2-13 Calibrator - Set Fluke 714.
Calibration must be performed when a temperature controller is changed, or
once a year, as a minimum.
The measured value can be matched in the calibration menu (CAL) using
offset correction, which can be performed on-line at the process.
standard setting
offset correction
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
(Cont'd)
Note! The unit contains ESD-sensitive components.
a) Squeeze the top and bottom of the front panel (1) between thumb and
forefinger and pull the controller firmly from the housing (2).
2 1
1 Front panel
TechPub_2614345_0105 - 04_3031799_01.fm
(Cont'd)
Note! The temperature reading must be stable before calibration can be
performed.
c) Press the ENTER button (3) for at least three seconds to enter the
SETTING MODE.
d) Use the ENTER button and the ARROW buttons (4) and (5) to navigate to
display the InL.1 parameter. Note down this parameter value. Wait for
the temperature reading to become stable.
e) Press the ENTER button to display the OuL.1 parameter value. This
value should equal the InL.1 parameter value. Use the ARROW
buttons (4) and (5) to set the parameter value.
PArA
ConF
TechPub_2614345_0105 - 04_3031799_01.fm
CAL InP.1 InL.1
4
5
3 ENTER
4 ARROW, up
5 ARROW, down
1 2
TechPub_2614345_0105 - 04_3031799_01.fm
3
4
(Cont'd)
f) Select the thermocouple type. Move the flashing cursor to the right or to
the left by pushing the UP (9) or DOWN (7) buttons.
g) Push the ENTER button (8) when the cursor is indicating type K.
11 3
10
9 7
TechPub_2614345_0105 - 04_3031799_01.fm
8
5
3 SENSOR 9 UP
5 SELECT 10 OUTPUT 1
7 DOWN 11 INPUT
8 ENTER
WARNING
Hazardous voltage.
Will cause death or serious injury. Be careful when working with the
calibrator. Follow the safety information in the Instruction Sheet delivered
with the calibrator.
Set the calibrator as follows:
a) Press the ON/OFF button (2) to switch on the calibrator.
b) Press the C/F button (8) to toggle °C or °F on the display (6).
c) Press the TC TYPE button (7) to show the thermocouple TYPE K (3).
d) Connect the type K thermocouple to the calibrator connection (11).
TechPub_2614345_0105 - 04_3031799_01.fm
5 6
4
INPUT F 7
3 TYPE K
8
2
9
TC C/F
TYPE
1 INPUT
OUTPUT
10
30V
MAX
11
(Cont'd)
(Cont'd)
Thermocouple Value
Press the INPUT/OUTPUT button (1) to show INPUT (4) on the display (6).
Actual temperature (5) is shown.
Temperature Output Value
Press the INPUT/OUTPUT button (1) to show OUTPUT (4) on the
display (6). Set the temperature (5) with the STEP UP/DOWN buttons (9),
and (10).
For further information on the calibrator, see the Instruction Sheet delivered
with the calibrator.
5 6
4
INPUT F 7
3 TYPE K
8
2
9
TC C/F
TYPE
1 INPUT
OUTPUT
10
TechPub_2614345_0105 - 04_3031799_01.fm
30V
MAX
11
1 2 3 4
1 Display
2 FUNC
3 UP
4 DOWN
(Cont'd)
(Cont'd)
e) Detach the machine thermocouple and place it in one of the cavities (5)
in the oven.
f) Put the calibrated thermocouple (to be found in the calibration kit) in an
adjacent cavity in the oven (6).
Note! Make sure that the two thermocouples are inserted equally deep.
g) Use the extension wire to connect the calibrator Micromite II (7) to the
thermocouple from the machine. Note the temperature reading on the
display (8) on the Micromite II (7).
h) Connect the Micromite II (7) to the calibrated thermocouple. Note the
temperature reading on the display (8).
TechPub_2614345_0105 - 04_3031799_01.fm
6 5 7 8
5 Cavity
6 Oven
7 Micromite II
8 Display
(Cont'd)
(Cont'd)
i) Find in the Pentronic Calibration Certificate the real correction value for
the calibrated thermocouple (thermocouple fault plus Micromite II
fault).
j) If the value of the machine thermocouple deviates by more than ± 1.1 °C
from the value of the calibrated thermocouple, change the machine
thermocouple.
k) When the measurement is complete, let the oven stay switched on and
cool it by setting the temperature value to 0. This cools down the oven
more effectively.
TechPub_2614345_0105 - 04_3031799_01.fm
3 1
9 2
5
10
6
11 7
4 8
16 12
14 13
15
TechPub_2614345_0105 - 04_3031799_01.fm
LED colours
LED 1, 2 and 3 yellow
LED OK green
Other LEDs red
(Cont'd)
(Cont'd)
Operation
After supply voltage switch-on, the unit starts in OPERATING MODE. The
unit is in the condition which was active before power-off. If the temperature
controller was in MANUAL OPERATING MODE before power-off, the
controller starts with the last correcting value after switching on again.
AUTOMATIC MANUAL
OPERATING
MODE
time out
Error list (if errors exists)
EXTENDED
OPERATING MODE
(Cont'd)
(Cont'd)
In the upper display line, the process value (3) is always displayed. In
parameter, configuration, calibration as well as extended operating mode, the
bottom display line changes cyclically between parameter name and
parameter value.
3 Process value
TechPub_2614345_0105 - 04_3031799_01.fm
With one or several errors, the extended operating level always starts with
the error list. Signalling an actual entry in the error list (alarm, error) is done
by the Err LED (1) in the display. This is applicable only if at least one
limit value function, the loop alarm or the heating current alarm is activated.
The error signal is displayed until the error is acknowledged, or until its
cause has been eliminated.
For display of the error list, press the ENTER button (2) twice.
2
TechPub_2614345_0105 - 04_3031799_01.fm
1 Err LED
2 ENTER
(Cont'd)
(Cont'd)
Error Indication
Err LED status Signification Proceed as follows
flashes Alarm due to existing - Determine the error type in the error list via the error number
(Status 2) error - The device changes to status 1 after error removal
lit Error removed, - Acknowledge the alarm in the error list pressing the ARROW UP
(Status 1) Alarm not acknowledged button or the ARROW DOWN button
- The alarm entry was deleted (Status 0)
off No error - all alarm - Not visible except when acknowledging
(Status 0) entries deleted
Error list
Name Description Cause Possible remedial action
E.1 Internal error - cannot be - for example defective - Contact manufacturer service
removed EEPROM - Return unit to our factory
E.2 Internal error - can be reset - for example EMC trouble - Keep measurement and electrical
supply cables in separate runs
- Ensure that interference suppression
of contactors is provided
E.4 Hardware error - Code-number and - Replace part
hardware are not identical - Claim part
TechPub_2614345_0105 - 04_3031799_01.fm
FbF.1 Sensor break INP1 - Sensor defective - Replace INP1 sensor
- Faulty cabling - Check INP1 connection
Sht.1 Short circuit INP1 - Sensor defective - Replace INP1 sensor
- Faulty cabling - Check INP1 connection
POL.1 INP1 polarity error - Faulty cabling - Reverse INP1 polarity
AdA.H Self-tuning heating alarm - See Self-tuning heating - See Self-tuning heating error status
(ADAH) error status
(Cont'd)
(Cont'd)
Tip! Saved alarms (Err LED (1) is lit) can be acknowledged and deleted
with the digital input di1/2/3, the function button F (3) or the MANUAL
MODE/SPECIAL FUNCTION button (4).
If an alarm is still valid, indicating that the cause of the alarm is not removed
so far (Err LED (1) flashes), then other saved alarms cannot be
acknowledged and deleted.
3
TechPub_2614345_0105 - 04_3031799_01.fm
1 Err LED
3 Freely programmable function button F
4 MANUAL MODE/SPECIAL FUNCTION
(ConF / LOGI)
TechPub_2614345_0105 - 04_3031799_01.fm
Log pages in the EM. If the Update Log pages are missing, new pages are
provided in the UP Updates of Manuals chapter.
TechPub_2614345_0105 - 04_3031799_01.fm
This page intentionally left blank
TechPub_2614345_0105 - 02_3031800_01.fm
2.2 Declarations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 7
2.2.1 Declaration of Conformity – EC . . . . . . . . . . . . . . 2 - 7
2.2.2 Declaration of Conformity – UL . . . . . . . . . . . . . . 2 - 9
TechPub_2614345_0105 - 02_3031800_01.fm
TechPub_2614345_0105 - 02_3031800_01.fm
This page intentionally left blank
TechPub_2614345_0105 - 02_3031800_01.fm
This page intentionally left blank
2.2 Declarations
2.2.1 Declaration of Conformity – EC
See the next page.
TechPub_2614345_0105 - 02_3031800_01.fm
TechPub_2614345_0105 - 02_3031800_01.fm
TechPub_2614345_0105 - 02_3031800_01.fm
TechPub_2614345_0105 - 02_3031801-01.fm
MM Update Pages . . . . . . . . . . . . . . . . . . . . . . . UP - 5
Update Log for Doc. No. MM-_______-____. . . . UP - 6
EM Update Pages. . . . . . . . . . . . . . . . . . . . . . . . UP - 9
Update Log for Doc. No. EM-_______-___ . . . . UP - 10
TechPub_2614345_0105 - 02_3031801-01.fm
This page intentionally left blank
MM Update Pages
The following Update Log pages can be used to log changes to the
Maintenance Manual for the machine.
TechPub_2614345_0105 - 02_3031801-01.fm
TechPub_2614345_0105 - 02_3031801-01.fm
This page intentionally left blank
TechPub_2614345_0105 - 02_3031801-01.fm
EM Update Pages
The following Update Log pages can be used to log changes to the existing
Electrical Manual for the machine.
TechPub_2614345_0105 - 02_3031801-01.fm
TechPub_2614345_0105 - 02_3031801-01.fm
This page intentionally left blank
TechPub_2614345_0105 - 02_3031801-01.fm
TechPub_2614345_0105 - 02_3031801-01.fm
This page intentionally left blank
TechPub_2614345_0105 - 02_3031801-01.fm
TechPub_2614345_0110 - TeM_3038450_0104_lab.fm
Label for 80 mm binder Note! This page is generated automatically.
TechPub_2614345_0110 - TeM_3038450_0104_lab.fm