KIL2189 - 200 - 0003 - REV05 - Proposed Details Sheet 2
KIL2189 - 200 - 0003 - REV05 - Proposed Details Sheet 2
KIL2189 - 200 - 0003 - REV05 - Proposed Details Sheet 2
Any discrepancies should be referred to the Engineer prior to work being put in
hand.
This drawing is the property of Kiloh Associates Limited, and the drawing is
2No. 50x50 S355 ANGLE FORMED issued on the condition that it is not copied reproduced, retained or disclosed to
any unauthorised person, either wholly or in part without the consent in writing of
FROM 2mm FOLDED PLATE. ON 6mm Kiloh Associates Limited, Unit 6, Pitreavie Court, Pitreavie Business Park,
2No. LINDAPTER HBCSK08-1 Ø BEAD OF BUTYL RUBBER SEALANT. Dunfermline, KY11 8UU t 0131 629 3434
20x35 THIOFLEX FIXED TO WALL PANELS WITH 2No.
KINGSPAN KS1100 CS COUNTERSUNK HEAD HOLLO
GEOSEAL EXISTING BRICKWORK INTERNAL ROWS OF EVOLUTION TSTF5-85-5
170x200mm QUADCORE INSULATED WALL BOLTS TIGHTENING TORQUE
CONCRETE KICKER
ENCASEMENT KINGSPAN KS1100 CS
POST FIXED TO WALL PANEL PANEL VERTICALLY LAID
FLASHINGS
23Nm. CENTRES IN ACCORDANCE CSK SCREWS @300mm C/C GENERAL NOTES
QUADCORE INSULATED WALL WITH MANUFACTURERS DETAILS
PANEL VERTICALLY LAID WITH 2No. ROWS OF EVOLUTION
TSTF5-85-5 CSK SCREWS VISION PANEL 1. DO NOT SCALE THIS DRAWING. ANY DISCREPANCY IS TO BE
@400mm C/C VERTICAL REPORTED TO THE ENGINEER IMMEDIATELY.
100x20 FOAM CELL
2 No.188mm x 75mm*
30
+SSL 2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
2 No.188mm x 75mm* ENGINEER'S OR OTHER RELEVANT DRAWINGS AND SPECIFICATIONS.
EXTERNAL
2 No.188mm x 75mm* FLASHINGS 3. ALL DIMENSIONS AND LEVELS ARE TO BE CHECKED ON SITE BY THE
30 CONTRACTOR PRIOR TO PREPARING ANY WORKING DRAWINGS OR
VISION PANEL TO COMMENCING ON SITE.
CONCRETE KICKER TO BRICKWORK WALL PANEL TO DOOR FRAME DETAILS * CHANNEL SECTION FORMED WALL PANEL INTERFACE DETAIL
WINDOW FRAME DETAILS - PLAN
ISOLATION JOINT DETAIL SCALE 1:10 FROM 4mm THICK HOT ROLLED
SCALE 1:10
SCALE 1:10 4. THE CONTRACTOR MUST ENSURE AND WILL BE HELD RESPONSIBLE
SCALE 1:10 STEEL PLATE, GRADE S275 FOR THE OVERALL STABILITY OF THE
BUILDING/STRUCTURE/EXCAVATION AT ALL STAGES OF THE WORK.
STAINLESS STEEL STITCHING SCREWS 10mm NOTCH IN 5. ALL WORK BY THE CONTRACTOR MUST BE CARRIED OUT IN SUCH A
@300mm C/C FIXED THROUGH CHANNEL POST WAY THAT ALL REQUIREMENTS UNDER THE HEALTH AND SAFETY AT
45 188x75x4mm *
PREDRILLED 7mm Ø HOLES WORK ACT ARE SATISFIED.
1.5mm Thk PPC
GALVANISED CHANNEL PLATE FIXED TO WALL 6. ALL WORK IS TO BE CARRIED OUT IN COMPLIANCE WITH THE
45
WITH BUTT JOINTS SEALED PANEL WITH EVOLUTION REQUIREMENTS OF THE RELEVANT STATUTORY AUTHORITIES AND
TSTF5-85-5 CSK SCREWS 100x100x6 RSA 125mm Lg 75
45
FIXED TO CHANNEL SECTIONS 25 REGULATIONS.
@400mm C/C VERTICAL 25
WITH 4No. M12 (8.8) BOLTS
EXISTING 14mm Ø HOLES IN STEEL
BRICKWORK WALL
45
188x75x4mm *
NOTE:
KINGSPAN KS1100 CS DETAIL 1 1) ALL STEELWORK (INCLUDING HANGER RODS &
QUADCORE INSULATED WALL ASSOCIATED STEELWORK) WINDOWS, PANELS
PANEL VERTICALLY LAID
SCALE 1:10
05 & SEALANTS TO BE 60 MINUTE FIRE RATED.
100x100 S355 ANGLE FORMED 0.7mm Thk EXTERNAL HEAD FLASHING WITH
2) EDGE DISTANCES FOR STEEL COMPONENTS
FROM 2mm FOLDED PLATE FIXED 100mm SEALED LAPS. FLASHING TO BE 435x95x8mm Thk CLEAT PLATE FIXED SHOULD BE IN ACCORDANCE WITH DIN EN
INTO EXISTING MASONRY WALL POWDER COATED FOR PROTECTIVE & INTO EXISTING MASONRY WITH 2No. DETAIL ON OPPOSITE
1993-1-3: 2010 (EUROCODES).
WITH HILTI HY 270 M10 RESIN DECORATIVE PURPOSES, COLOUR TO BE HILTI HY 270 M12 RESIN ANCHORS SIDE SIMILAR
ANCHORS @400mm C/C VERTICAL APPROVED BY GSK. FIXINGS IN ACCORDANCE 100mm MINIMUM EMBEDMENT
EXISTING STEEL COLUMN WITH MANUFACTURERS DETAILS
80mm MINIMUM EMBEDMENT
50x50 S355 ANGLE FORMED FROM MINERAL WOOL COMPOSITE STEEL
10
WALL PANEL TO EXISTING COLUMN INTERFACE DETAIL - SOUTH 2mm FOLDED PLATE. ON 6mm Ø BEAD SHEET 100mm Thk WITH A 60 MINUTE 50x50 S355 ANGLE FORMED FROM 2mm
=
SCALE 1:10 OF BUTYL RUBBER SEALANT. FIXED TO FIRE RATING. SIZE TO FORM FIRED FOLDED PLATE. ON 6mm Ø BEAD OF
95
=
U/S OF COMPOSITE SHEET & WALL RATED CEILING OVER ROLLER DOOR BUTYL RUBBER SEALANT. FIXED TO 188x75x4mm
PANEL WITH EVOLUTION TSTF5-85-5 COMPOSITE SHEETS WITH EVOLUTION RESTRAINT 4mm ARFW 120
CSK SCREWS @300mm C/C TSTF5-85-5 CSK SCREWS @300mm C/C TO CLEAT PLATE 30
+2.560
CHANNEL FIXED INTO EXISTING EXISTING STEEL COLUMN
MINERAL WOOL COMPOSITE DETAIL 2
MASONRY ENCASEMENT WITH 188x75x4mm STEEL SHEET 100mm Thk SCALE 1:10
BURGESS
HILTI HY 150 M10 RESIN ANCHORS
@400mm C/C VERTICAL 80mm
CONCEALED GRID CHANNEL RESTRAINT 660 05
+2.400 +2.400
0.7mm Thk EXTERNAL HEAD MINIMUM EMBEDMENT
FLASHING WITH 100mm SEALED 260x260x10mm Thk END PLATE FIXED
STAINLESS STEEL STITCHING SCREWS
LAPS. FLASHING TO BE POWDER INTO EXISTING CONCRETE WITH 4No. 100x100x6 RSA STUBS 365mm Lg
@300mm C/C FIXED THROUGH 175
COATED FOR PROTECTIVE & EXISTING CONCRETE HILTI HY 150 M10 RESIN ANCHORS EDGE OF CONCRETE
PREDRILLED 7mm Ø HOLES @300mm C/C FIXED TO
DECORATIVE PURPOSES, COLUMN ENCASEMENT 80mm MINIMUM EMBEDMENT COLUMN ENCASEMENT
CHANNEL WITH 2No. M12 (8.8)
COLOUR TO BE APPROVED BY BURGESS CEP ET181
U/S CEILING KINGSPAN KS1100 CS QUADCORE BOLTS 14mm Ø HOLES IN STEEL
30
GSK. FIXINGS IN ACCORDANCE PERIMETER CHANNEL 80
+2.200 APPROX INSULATED WALL PANEL
WITH MANUFACTURERS DETAILS 75
100x100x6 RSA
2No. ALBION C14615 SECTION BEAMS
REBATE JOINT SQUARE. ANY +1.980 0.7mm Thk FLASHING BACK TO BACK WITH 5mm Ø LIGHT
STUB 6mm ARFW
200
+1.960 WITH 100mm SEALED TO END PLATE
GAPS FILLED USING FR CANISTER
1.5mm Thk PPC LAPS AS ABOVE DUTY TEK SCREWS @600mm C/C
APPLIED INSULATION TO MAINTAIN
GALVANISED CHANNEL 188x75x4mm - CHANNEL SECTION STAGGERED IN 2No. ROWS. FIXED TO
CONTINUITY OF INSULATION HEAD OF ROLLER 188x75x4mm *
WITH BUTT JOINTS SEALED U/S OF COMPOSITE SHEET WITH
FORMED FROM 4mm THICK HOT SHUTTER DOOR
30
KINGSPAN KS1100 CS 50x50x1.5mm Thk WHITE PPC 5mm Ø TEK SCREWS @300mm C/C 200
ROLLED STEEL PLATE, GRADE S275
QUADCORE INSULATED WALL GALVANISED ANGLE BEDDED ON 6mm Ø
BEAD OF BUTYL RUBBER SEALANT. FIXED 30 30
PANEL VERTICALLY LAID
TO WALL PANEL WITH 2No. STAINLESS
STEEL STITCHING SCREWS @300mm C/C DETAIL 3 HEAD RESTRAINT SECTION SIZE & ORIENTATION AMENDED.
05 29/11/23 DETAILS AMENDED TO SUIT. ORIGINAL DOOR BASEPLATE JB MM
SCALE 1:10
WALL PANEL TO EXISTING COLUMN INTERFACE DETAIL - NORTH 05 05 REINSTATED
DETAILS AMENDED TO SUIT EXISTING SERVICE LOCATIONS &
SCALE 1:10 04 24/11/23
ROLLER SHUTTER DOOR RELOCATION. DETAIL 3 ADDED.
JB MM
ROLLER SHUTTER HEAD & BASE DETAILS AMENDED. WALL
INTERFACE DETAIL ADDED
HANGERS REMOVED AT DOOR HEAD & GALVANISED CHANNELS
03 27/09/23 JB MM
ADDED TO CEILING PANEL ENDS. PFC WALL RESTRAINT RAISED
F10 EDGE OF F10 ROLLER SHUTTER DOOR DETAILS & SECTION B-B AMENDED TO
EXISTING COLUMN KINGSPAN KS1100 CS 02 15/09/23 JB MM
ENCASEMENT B B SUIT LEVEL & DOOR CHANGES. ISSUED FOR CONSTRUCTION
QUADCORE INSULATED DETAIL 2 DETAIL 3
BEHIND DETAIL 2
DETAIL 3 DETAIL 1 WALL PANEL 01 01/08/23 ISSUED FOR WARRANT JB MM
+2.560 KEGGING AREA +2.560
AIR-LOCK 00 27/06/23 ISSUED FOR CONSTRUCTION JB MM
+2.400 DISSO ROOM 188x75x4mm **
188x75x4mm ** U/S CEILING U/S CEILING Rev Date Description Dr'n Ch'd
+2.200 APPROX DOOR MOTOR +2.200 APPROX
500
Amendments
305 180
+2.200 APPROX
188x75x4mm ** 188x75x4mm ** Project
+1.980 +1.960 +1.960 +1.980
05 ROLLER SHUTTER DOOR
100x100x6 RSA 100x100x6 RSA
188x75x4mm **
DISSO ROOM
EXISTING EXISTING
WALL PANEL FIXED TO EXISTING BRICKWORK WALL CONCRETE
188x75x4mm **
188x75x4mm **
*DIMENSIONS PROVIDED
188x75x4mm **
188x75x4mm **
BY CONTRACTOR BY CONTRACTOR
Client
** CHANNEL SECTION FORMED
FROM 4mm THICK HOT ROLLED ** CHANNEL SECTION FORMED
FROM 4mm THICK HOT ROLLED NEW RAPID OPEN DOOR
STEEL PLATE, GRADE S275 170x200mm "DYNACO S-535 CAT.3 ATEX
CONCRETE KICKER STEEL PLATE, GRADE S275
COMPACT" (BY OTHERS) FIXED TO
PFC POSTS WITH 5.5mm Ø TEK Kiloh Associates
SCREWS @250mm C/C VERTICAL Local Engineering for Local Clients
05 Unit 6, Pitreavie Court,
+FFL = 0.00
170x200mm 170x200mm 170x200mm CONCRETE 170x200mm CONCRETE Pitreavie Business Park,
CONCRETE KICKER CONCRETE KICKER +SSL KICKER BEHIND KICKER BEHIND Dunfermline, Fife,
+FFL = 0.00 +FFL = 0.00 KY11 8UU
+SSL +SSL t: 0131 629 3434
145 135 e:en [email protected]
www.kiloh.co.uk
*215 1400 *340 *340 1400 *215 05 Status