11-TMSS-10 R.0
11-TMSS-10 R.0
11-TMSS-10 R.0
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Ratings
4.3 Materials
4.4 Cable Marking and Identification
5.0 TESTS
1.0 SCOPE
This TMSS shall also be read in conjunction with SEC Transmission Purchase Order
or Contract Schedules for project, as applicable.
The latest revision/amendments of the Codes and Standards listed hereunder shall be
applicable for the equipment/material covered in this specification. In case of conflict,
the vendor/manufacturer may propose equipment/materials conforming to one group
of Industry Codes and Standards quoted hereunder without jeopardizing the
requirements of this TMSS.
3.2 IEC 60502-1 Power Cables with Extruded Insulation and their
Accessories for Rated Voltages from 1 kV up to 30 kV,
Part 1: Cables for Rated Voltages of 1 kV and 3 kV
3.5 ASTM B-33 Tinned Soft or Annealed Copper Wire for Electrical
Purposes
3.8 ICEA S-95-658 / Standard for Non-Shielded Power Cables Rated 2000
NEMA WC 70 Volts or Less for the Distribution of Electrical
Energy
3.9 ICEA T-27-581/ Standard Test Methods for Extruded Dielectric Power,
NEMA WC 53 Control, Instrumentation and Portable Cables
4.1 General
4.1.2 The cable shall be designed for use in all low voltage power and/or
control circuits and for installation in conduits, underground ducts or
cable trays/raceways or for directly buried installations as specified in
the Data Schedule.
4.1.3 For GIS applications, the control cable shall be properly shielded over
the assembled cores per IEEE C37.122.1 in the 1-30 MHz frequency
range.
4.2 Ratings
4.3 Materials
4.3.1 Conductor
4.3.2 Insulation
4.3.3 Binder
When required, the binder (or separator) shall be a mylar tape, PVC
binder tape or extruded PVC layer applied over the assembled cores.
The average thickness of the binder shall not be less than 1 mm.
4.3.5 Armor
Size of Armor
Size of Circuit Conductor (Minimum Size of
Ground Conductor)
mm² AWG/kcmil mm² AWG
2.5 14 2.5 14
4 12 4 12
6 - 10 10 - 8 6 10
16 - 25 6-4 10 8
30 - 70 3 - 2/0 16 6
85 - 130 3/0 – 250 25 4
150 - 200 300 – 400 35 3
230 - 330 450 – 650 35 2
350 - 450 700 - 900 50 1
500 1000 70 1/0
630 1250 - -
4.3.6 Jacket
The jacket shall be black, ST2 type, extruded PVC per IEC 60502-1
with heat, moisture, oil, sunlight, acid, alkali and flame resistant
properties. For flame retardancy, a minimum oxygen index level of
30 % is required.
4.4.1 The outer surface of the cable shall be durably and legibly marked in
English language and Arabic numerals at intervals of 1 (one) meter
with the following minimum information:
a. Rated voltage
b. Insulation Material
e. Year of manufacture
4.4.2 The jacket of all cables, excluding building wires, shall be marked
with the cumulative length at every one meter, with the highest length
mark on the outer end of the cable.
The length marking shall start at one meter distance from the inner
end of the cable, and shall not coincide with the markings described
in subclause 4.4.1.
4.4.5 For systems with ground or neutral application, the black color shall
indicate the neutral conductor.
5.0 TESTS
All test results shall be provided for review and acceptance by SEC.
All type (design) tests prescribed in the IEC 60502-1 or ICEA T-27-581
(NEMA WC 53) shall be performed on a representative unit or on the first unit
of every new design or rating to be supplied to SEC.
In lieu of the actual type (design) tests, certified test reports of type (design)
tests performed on an identical unit may be submitted to SEC for review and
approval during bidding stage.
6.1 The cable shall be delivered without splices on nonreturnable standard size
reels properly packed and lagged externally to provide physical protection for
the cable shipment and to facilitate field handling and long term storage.
Wood lagging shall have a minimum thickness of 25 mm.
6.2 The cable ends shall be sealed with a waterproof, heat shrinkable plastic or
elastomeric end cap with adhesive type sealing compound. Cable ends shall be
properly secured to the reel.
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.1 General
Cable installation
(conduit, duct, trays, direct burial, GIS etc.)
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Number of conductors *
Number of conductors *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
5.0 TESTS
Official Seal/Stamp
of the Company &
Date