18EE71-Module-5-Part 1 Notes - 2022
18EE71-Module-5-Part 1 Notes - 2022
Transient Stability
Steady State Stability
involves the study of The ability of a power
studies are restricted
the power system system to maintain
to small and gradual
following a major stability under gradual
changes in the system
disturbance. disturbances changing
operating conditions.
with time
i. Each synchronous machine is represented by a constant voltage source behind the direct axis
transient reactance.
ii. The governor’s action are neglected and the input powers are assumed to remain constant.
iii. Using the pre-fault bus voltages, all loads are converted to equivalent admittances to ground
and are assumed to remain constant.
iv. Damping or asynchronous powers are ignored.
v. Mechanical rotor angle of each machine coincides with the angle of the voltage behind the
machine reactance.
vi. Machines belonging to the same station swing together and together are represented by one
equivalent machine.
Swing Equation
r t
where
δ is the angular position in radians with respect to the synchronously rotating reference
frame
or
d 2
M 2 PS Pe
dt
where
The transient stability analysis requires the solution of a system of coupled non-linear
differential equations. In general, no analytical solution of these equations exists. However,
techniques are available to obtain approximate solution of such differential equations by
numerical methods and one must therefore resort to numerical computation techniques
commonly known as digital simulation. Some of the commonly used numerical techniques
for the solution of the swing equation are:
1. First, compute the angular position δ, and angular speed at the end of the time
interval using the formal solution of the swing equation from the knowledge of the
assumed value of the accelerating power and the values of δ, and d δ, /dt a the
beginning of the interval
2. Then compute the accelerating power of each machine from the knowledge of the
angular position at the end of the interval as computed in step 1.
Assumption: The accelerating power during the interval is assumed constant at its value
calculated for the middle of the interval. The desired formula for computing the change
in δ during the nth time interval is
t 2
n n 1 Pa ( n 1)
M
where,
Due attention is given to the effects of discontinuities in the accelerating power P a which
occur, for example, when a fault is applied or removed or when any switching operation
takes place. If such a discontinuity occurs at the beginning of an interval, then the average
of the values of Pa before and after the discontinuity must be considered. Thus, in
computing the increment of angle occurring during first interval after a fault is applied at
t=0, the above equation becomes:
t 2 Pa 0
1
M 2
Pa0+ is the accelerating power immediately after the occurrence of the fault.
if the fault is cleared at the beginning of the mth interval, then for this interval,
Where
If the discontinuity occurs at the middle of the interval, no special treatment is needed.
Figure 1 shows a passive (linear) n-bus network in which branch with a branch impedance
Zb is added to the new bus ‘ k ’ and the reference bus ‘ r ‘. Now
Branch impedance ‘Zb’ is added from new bus k to the old bus j as in Fig. 2. It follows from
this figure that
Zb connects an old bus (j) to the reference bus (r) as in Fig. 3. This case follows
from Fig. 3 by connecting bus k to the reference bus r, i.e. by setting Vk = 0.
Zb connects two old buses as in Fig. 4. Equations can be written as follows for all the
network buses.
1. Modern Power System Analysis, D.P. Kothari, McGraw Hill, 4th Edition 2011.
2. Power System Analysis, Haadi Sadat, McGraw Hill, 2nd Edition 2002.