56-SDMS-09 Rev 02 Specification For Unit Substations Up To 36 KV
56-SDMS-09 Rev 02 Specification For Unit Substations Up To 36 KV
56-SDMS-09 Rev 02 Specification For Unit Substations Up To 36 KV
56-SDMS-09
Rev.02
This document contains proprietary information developed by and for exclusive use of Saudi Electricity
Company (SEC) Distribution Network. Your acceptance of the document is an acknowledgment that it
must be used for the identified purpose/application and during the period indicated. It cannot be used or
copied for any other purposes nor released to others without prior written authorization of SEC
Distribution Sector. SEC shall assume no responsibility for any type of misuse and/or misapplication,
and any arm resulting there from. SEC also reserves the right take any necessary actions to protect its
interest against unauthorized use.
Saudi Electricity Company
Revision History
Table of Contents
1. SCOPE ............................................................................................................ 4
2. CROSS REFERENCES .................................................................................. 4
3. APPLICABLE CODES AND STANDARDS ................................................ 4
4. DESIGN AND CONSTRUCTION REQUIREMENTS ................................. 5
5. TESTING ...................................................................................................... 11
6. SUBMITTALS .............................................................................................. 11
7. DATA SCHEDULE ...................................................................................... 13
1. SCOPE
This SEC Distribution Material Specification (SDMS) specifies the minimum technical
requirements of design, engineering, manufacturing, inspection; testing and performance
of outdoor unit substation intended to be used in MV system of the Saudi Electricity
Company (SEC), Saudi Arabia. A unit substation combines power transformer and LV
distribution panel in a single transportable unit ready for operation on being fixed in
position on prepared plinth and connected to the power system. The MV switchgear is not
an integral part of the unit substation.
2. CROSS REFERENCES
This SEC material standard specification shall always be read in conjunction with SEC
specification No. 01-SDMS-01, titled “General Requirements for All
Equipment/Materials”, which shall be considered as an integral part of this SDMS, These
standard specifications shall be also read in conjunction with SEC Purchase Order (PO)
requirements.
3.4 37-SDMS-02 LV Molded Case Circuit Breakers For LV distribution panels 400 A.
3.5 37-SDMS-04 Interface Low Voltage Main Circuit Breakers
3.6 11-SDMS-03 XLPE Insulated Power Cables from 15 kV up to 36 kV
Saudi Electricity Company
4.2.1.3 Adequate ventilation for the medium voltage termination box to the
back side of low voltage compartment shall be provided to permit
natural air circulation. The ventilation apertures shall be screened with
galvanized double steel mesh to prevent entry of vermin and other
foreign bodies.
4.2.1.4 All parts of equal size and shape shall be interchangeable. The general
design shall be made with minimum number of joints.
4.2.1.5 All Insulating materials shall be non-hygroscopic and resistant to
tracking.
4.2.1.6 All bolted electrical joints shall be secured by means of corrosion proof
steel nuts and bolts. All bolts, nuts, and washers shall be plated to type
II of ASTM B 633.
4.2.1.7 Except for the transformer, all nuts and bolts shall not be accessible
from outside of the unit substation.
4.2.2 TRANSFORMER
Transformer shall be suitable for unit substation, outdoor ground-mounted type
and generally shall comply with all applicable clauses of SEC specifications 51-
SDMS-03 / 51-SDMS-04 (latest revision) according to requested in the tender.
Including the following requirements.
4.3 Dimensions
Maximum overall dimensions of unit substation shall be as given in the Table 2 and Table
3 below:
SEC shall approve location and samples of danger & monogram plates prior to
installation.
5. TESTING
Unit substation shall be tested in accordance with the latest standards and as specified
herein. All test results shall be provided for review and acceptance by SEC.
6. SUBMITTALS
6.1 The vendor shall complete and submit filled-in the Data Schedule and clause by
clause compliance of (latest revision) of the following specifications with the
quotations:
01-SDMS-01.
12-SDMS-01.
31-SDMS-09.
37-SDMS-02.
Saudi Electricity Company
37-SDMS-04.
38-SDMS-03
50-SDMS-01
51-SDMS-03/51-SDMS-04.
6.2 The following dimensional drawings shall be provided with the quotation for each
unit substation rating:
7. DATA SCHEDULE
UNIT SUBSTATION UP TO 36 kV
(Sheet 1 of 3)
SEC Inquiry No. ___________________ Item No. _____________
VENDOR
SEC SPECIFIED
Clause DESCRIPTION PROPOSED
VALUES
VALUES
4.0 DESIGN AND CONSTRUCTION REQUIREMENTS
1. Nominal Unit S/S rating 500 KVA
1000 KVA
1500 KVA
2. MV Rating 13.8 kV
36 kV
3. LV Rating: Single Secondary. 400/230 V
Dual Secondary. 230/133- 400/230 V
4.. Number of Distribution units
5. Main Circuit Breaker
Type, Model & Make
Rated current
4.2 UNIT SUBSTATION COMPONENTS /COMPARTMENTS
1. Length, mm
2. Width, mm
3. Height, mm
4. Length of MV termination box, mm
5. Center to center distance between MV
bushings, mm
6. Horizontal clearance between the outer
MV bushing(s) and the wall of the
MV termination box, mm
7. Center to center distance between 150
MCCBs, mm
8. Space between MCCBs, mm 10
9. Phase bus-bar current rating, A
10. Phase bus-bar size, mm
11. Neutral bus-bar current rating, A
12. Neutral bus-bar size, mm
Table 6: Technical Data Schedule 1.
Saudi Electricity Company
DATA SCHEDULE
UNIT SUBSTATION UP TO 36 kV
(Sheet 2 of 3)
SEC Inquiry No. ___________________ Item No. _____________
VENDOR
SEC SPECIFIED
Clause DESCRIPTION PROPOSED
VALUES
VALUES
4.5 PROVISION FOR GENERATOR CABLES
Diameter of hole on the bus-bar, mm 13
4 each for
Number of holes on each phase bus-bar 1500kVA & 1000kVA
2 each for
500kVA
2 each for
Number of holes on neutral bus-bar 1500kVA & 1000kVA
1 each for
500kVA
4.6 ACCESSORIES
DATA SCHEDULE
Name of Company
Date