V.D Calculations - 01

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

VOLT

PROJECT NAME:- PANEL's REF:- LOCATION:- MOUNTING:-


AGE:-
AL-MOSA VIEW DP-1 380V /220V,3PH,4W,60Hz GARDEN 03 FREE STAND
ACTUAL CONNECTED ACTUAL CONNECTED
WIRE SIZE C.B. LOAD VA PER PHASE CKT. CKT. LOAD VA PER PHASE C.B. WIRE SIZE
LOAD DESCRIPTION LOAD DESCRIPTION
mm² SIZE NO. NO. SIZE mm²
R Y B 3 PH R Y B
800 1 2 1000
L1 4X10MM2 40 800 3 4 1000 40 4X10MM2 L2
700 5 6 1000
200 7 8 2135.83
L3 4X10MM2 40 200 9 10 2135.83 40 4X10MM2 WATER PUMP 01
300 11 12 2135.83
2135.83 13 14 2135.83
WATER PUMP 02 4X10MM2 40 2135.83 15 16 2135.83 40 4X10MM2 WATER PUMP 03
2135.83 17 18 2135.83
13 14
SPARE 40 15 16 40 SPARE
17 18
SUB-TOTAL / PHASE 3135.83 3135.83 3135.83 MAIN BUS 5271.67 5271.67 5271.67
250A
TOTAL / PHASE 8407.5 8407.5 8407.5 RATING:-

CONNECTED LOAD ANALYSIS Load Current - A - MAIN BREAKER FEED FROM

Conn .Load Demand Predicted Load


LOAD DESCRIPTION VA Factor % VA
38.32 A + 25% Spare = 47.90 A 250AT/250AF S-30834

LIGHTING 6000 100 6000 Cable (4C x 120 MM2 )


SOCKETS 80 0 Selected
A/C 100 0
MOTORS 19222.5 100 19222.5
EWH 100 0

TOTAL 25222.5 25222.5


VOLT
PROJECT NAME:- PANEL's REF:- LOCATION:- MOUNTING:-
AGE:-
AL-MOSA VIEW DP-2 380V /220V,3PH,4W,60Hz GARDEN 06 FREE STAND
ACTUAL CONNECTED ACTUAL CONNECTED
WIRE SIZE C.B. LOAD VA PER PHASE CKT. CKT. LOAD VA PER PHASE C.B. WIRE SIZE
LOAD DESCRIPTION LOAD DESCRIPTION
mm² SIZE NO. NO. SIZE mm²
R Y B 3 PH R Y B
600 1 2 500
L1 4X10MM2 40 600 3 4 500 40 4X10MM2 L2
600 5 6 600
300 7 8
L3 4X10MM2 40 300 9 10 40 SPARE
200 11 12
13 14 0
SPARE 40 15 16 0 40 SPARE
17 18 0
SUB-TOTAL / PHASE 900 900 800 MAIN BUS 500 500 600
250A
TOTAL / PHASE 1400 1400 1400 RATING:-

CONNECTED LOAD ANALYSIS Load Current - A - MAIN BREAKER FEED FROM

Conn .Load Demand Predicted Load


LOAD DESCRIPTION VA Factor % VA
6.38 A + 25% Spare = 7.98 A 250AT/250AF S-30834

LIGHTING 4200 100 4200 Cable (4C x 120 MM2 )


SOCKETS 80 0 Selected
A/C 100 0
MOTORS 100 0
EWH 100 0

TOTAL 4200 4200


VOLT
PROJECT NAME:- PANEL's REF:- LOCATION:- MOUNTING:-
AGE:-
AL-MOSA VIEW DP-3 380V /220V,3PH,4W,60Hz GARDEN 09 FREE STAND
ACTUAL CONNECTED ACTUAL CONNECTED
WIRE SIZE C.B. LOAD VA PER PHASE CKT. CKT. LOAD VA PER PHASE C.B. WIRE SIZE
LOAD DESCRIPTION LOAD DESCRIPTION
mm² SIZE NO. NO. SIZE mm²
R Y B 3 PH R Y B
400 1 2 700
L1 4X10MM2 40 400 3 4 700 40 4X10MM2 L2
400 5 6 700
600 7 8 800
L3 4X10MM2 40 600 9 10 800 40 4X10MM2 L4
700 11 12 700
600 13 14 1000
L5 4X10MM2 40 600 15 16 1000 40 4X10MM2 L6
600 17 18 900
2000 19 20 600
L7 4X10MM2 40 2000 21 22 600 40 4X10MM2 L8
2000 23 24 700
2000 25 26 2000
L9 4X10MM2 40 2000 27 28 2000 40 4X10MM2 L10
2000 29 30 2000
SUB-TOTAL / PHASE 5600 5600 5700 MAIN BUS 5100 5100 5000
250A
TOTAL / PHASE 10700 10700 10700 RATING:-

CONNECTED LOAD ANALYSIS Load Current - A - MAIN BREAKER FEED FROM

Conn .Load Demand Predicted Load


LOAD DESCRIPTION VA Factor % VA
48.77 A + 25% Spare = 60.96 A 250AT/250AF S-30589

LIGHTING 32100 100 32100 Cable (4C x 120 MM2 )


SOCKETS 80 0 Selected
A/C 100 0
MOTORS 100 0
EWH 100 0

TOTAL 32100 32100


PROJECT NAME:- ROAD LIGHTING

AC-01 : GARDEN LIGHTING


CIRCUI
TOTAL CIRCUIT CIRCUIT BRAKER T CABLE CURRENT CIRCUIT MV/ %VOLAGE
CKT-NO FEEDING CABLE
POWER S CURRENT (I) CURRENT (ICB) RATIN (I CABLE) LENGTH A/M DROP
G (CB)
1R 240 0.36 0.46 32 34.04 161 5.226 0.10 (3X6)MM2
1Y 420 0.64 0.80 32 34.04 364 5.226 0.40 (3X6)MM2
1B 270 0.41 0.51 32 34.04 270 5.226 0.19 (3X6)MM2
1B 180 0.27 0.34 32 34.04 10 5.226 0.00 (3X6)MM2
AC-02 : GARDEN LIGHTING
CIRCUI
TOTAL CIRCUIT CIRCUIT BRAKER T CABLE CURRENT CIRCUIT MV/ %VOLAGE
CKT-NO FEEDING CABLE
POWER S CURRENT (I) CURRENT (ICB) RATIN (I CABLE) LENGTH A/M DROP
G (CB)
1R 1125 1.71 2.14 32 34.04 127 5.226 0.37 (3X6)MM2
1Y 1125 1.71 2.14 32 34.04 60 5.226 0.18 (3X6)MM2
1B 750 1.14 1.42 32 34.04 100 5.226 0.20 (3X6)MM2
2R 750 1.14 1.42 32 34.04 60 5.226 0.12 (3X6)MM2
2Y 120 0.18 0.23 32 34.04 90 5.226 0.03 (3X6)MM2
2B 1040 1.58 1.98 32 34.04 215 5.226 0.58 (3X6)MM2
3R 380 0.58 0.72 32 34.04 10 5.226 0.01 (3X6)MM2
AC-03 : GARDEN LIGHTING
CIRCUI
TOTAL CIRCUIT CIRCUIT BRAKER T CABLE CURRENT CIRCUIT MV/ %VOLAGE
CKT-NO FEEDING CABLE
POWER S CURRENT (I) CURRENT (ICB) RATIN (I CABLE) LENGTH A/M DROP
G (CB)
1R-1Y-1B 40000 60.78 75.97 100 106.38 20 0.971 0.39 (4X35)MM2
2R-2Y-2B 190000 288.68 346.42 350 372.34 60 0.252 1.38 (3X185+95)MM2
3R 3260 4.95 6.19 32 34.04 165 5.226 1.40 (3X6)MM2

0.00 0.00
AC-04 : GARDEN LIGHTING
CIRCUI
TOTAL CIRCUIT CIRCUIT BRAKER T CABLE CURRENT CIRCUIT MV/ %VOLAGE
CKT-NO FEEDING CABLE
POWER S CURRENT (I) CURRENT (ICB) RATIN (I CABLE) LENGTH A/M DROP
G (CB)
1R 390 0.59 0.74 40 42.55 420 5.226 0.43 (3X6)MM2
1Y 300 0.46 0.57 40 42.55 331 5.226 0.26 (3X6)MM2
1B 330 0.50 0.63 40 42.55 300 5.226 0.26 (3X6)MM2
2R 1500 2.28 2.85 40 42.55 75 5.226 0.29 (3X6)MM2
2Y 1125 1.71 2.14 40 42.55 135 5.226 0.40 (3X6)MM2
2B 1125 1.71 2.14 40 42.55 75 5.226 0.22 (3X6)MM2
3R 210 0.32 0.40 40 42.55 278 5.226 0.15 (3X6)MM2
3Y 120 0.18 0.23 40 42.55 110 5.226 0.03 (3X6)MM2
0.00 0.00 0.00
0.00 0.00 0.00
AC-05 : GARDEN LIGHTING
CIRCUI
TOTAL CIRCUIT CIRCUIT BRAKER T CABLE CURRENT CIRCUIT MV/ %VOLAGE
CKT-NO FEEDING CABLE
POWER S CURRENT (I) CURRENT (ICB) RATIN (I CABLE) LENGTH A/M DROP
G (CB)
1R-1Y-1B 46800 71.11 88.88 100 106.38 20 0.971 0.45 (4X35)MM2
2R-2Y-2B 173000 262.85 328.57 350 372.34 80 0.252 1.74 (3X185+95)MM2
3R 300 0.46 0.57 32 34.04 361 5.226 0.28 (3X6)MM2

AC-06 : GARDEN LIGHTING


CIRCUI
TOTAL CIRCUIT CIRCUIT BRAKER T CABLE CURRENT CIRCUIT MV/ %VOLAGE
CKT-NO FEEDING CABLE
POWER S CURRENT (I) CURRENT (ICB) RATIN (I CABLE) LENGTH A/M DROP
G (CB)
1R-1Y-1B 79000 120.03 150.04 160 170.21 45 0.408 0.72 (3X95+50)MM2
2R-2Y-2B 53000 80.53 100.66 100 106.38 20 0.971 0.51 (4X35)MM2
3R 420 0.64 0.80 32 34.04 300 5.226 0.33 (3X6)MM2
3Y 450 0.68 0.85 32 34.04 420 5.226 0.49 (3X6)MM2