Nroom Technical Data Standard Units Update 02.2023
Nroom Technical Data Standard Units Update 02.2023
Nroom Technical Data Standard Units Update 02.2023
0/30
Water
pressure
drop
kPa
0.1
0.3
1.4
0.1
0.2
0.9
0.1
0.2
0.3
0/60 70/50
Water Heating Exhaust air Water
pressure power of a temperatur Water flow pressure
drop heater e drop
0/30
Water
pressure
drop
kPa
0.1
0.72
1.26
0.1
0.45
0.81
0.1
0.18
0.27
Technical data of water heaters
- NR1-025-ECV1HR... (heat recovery exchanger) -Table 12
/30
Water
pressure
drop
kPa
2.7
6.7
14
1.9
4.7
9.6
1.2
2.9
5.9
/60 70/50
Water Heating Water
Exhaust air
pressure power of a Water flow pressure
temperature
drop heater drop
/30
Water
pressure
drop
kPa
2.7
6.7
14
1.9
4.7
9.6
1.2
2.9
5.9
Line NRoom-100-e
Unit type NR1-010-ECxxHR…
Recovery exchanger type HRV
Temperature %
AIRFLOW
efficiency Current (A)
(m3/h)
(EN308)
1. 28 87 0.13
2. 41 85.1 0.14
3. 53 83.5 0.15
4. 66 81.7 0.18
Degree of air output
5. 78 80 0.21
6. 90 78.3 0.26
7. - nominal 100 77 0.3
8. BOOST* 215 N/A 1.32
* BOOST mode - intensive ventilation for 10 minutes
81
EFFICIENCY (%)
60
80
79 50
78 40
77
30
76
75 20
74
10
73
72 0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 20 25 30
60
50
40
30
20
10
0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
FLOW RATE (m3/hr)
Line NRoom-250-e
Unit type NR1-025-ECxxHR…
Recovery exchanger type HRV
Temperature %
AIRFLOW
efficiency Current (A)
(m3/h)
(EN308)
1. 64 86.1 0.17
2. 95 85.0 0.20
3. 126 84 0.25
4. 157 83 0.32
Degree of air output
5. 188 82 0.45
6. 219 81 0.52
7. - nominal 250 80.5 0.61
8. BOOST* 350 N/A 1.42
* BOOST mode - intensive ventilation for 10 minutes
86.0
85.0
84.0
83.0
EFFICIENCY (%)
82.0
81.0
80.0
79.0
78.0
77.0
45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270
FLOW RATE (m3/hr)
NRoom-250-efficiency of heat and humidity recovery
R… NR1-025-ECxxER…
ERV
Temperature % Humidity
Power supply AIRFLOW Power supply
efficiency efficiency % Current (A)
(W) (m3/h) (W)
(EN308) (EN308)
13.5 62 85 73 0.17 13.5
17 92 82.5 70 0.20 17
23 121 81 67 0.25 23
30 151 79.5 64 0.32 30
40 180 78 60.5 0.45 40
51 210 76.5 58 0.52 51
61 240 75 54.5 0.61 61
169 335 N/A N/A 1.42 169
80
70
60
EFFICIENCY (%)
50
40
30
20
10
0
45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270
FLOW RATE (m3/hr)
Unit type Circuit breaker capacity Number of phases x voltage
1. The unit does not start The main switch is in position 0 - set the switch to position I
Hold down button 2 (ON/OFF) for a short - hold down button 2 (ON/OFF) until the LED above
time, approx. 3 sec button 2 lights up
Loosened M6x20 bolts with plastic head - securely tighten the bolts on the front metal
position 23 of the front metal cover cover with your hand, Section 3.2.11.
No or low ventilation output even Clogged filter - replace the filter according to Section 6.
4. when the unit is set to the maximum
power Contaminated - blocked piping, unit
- Check and clean the unit according to Section 7.
outlets
The night cooling function cannot be - switch off the BOOST functions according to
BOOST function active
switched on (button 6.) - all the status Section 5.4.2. Tab.17
8.
diodes flash once (at buttons 6, 4, 7, - switch off the child lock function according to
10), the function does not switch on Active child lock function
Section 5.4.2. Tab.17
The BOOST mode cannot be switched 3 flashes - very low outdoor temperature - wait for the outdoor temperature to rise
on - status diodes flash once or 3 times
9.
(at buttons 6, 4, 7, 10), the function - switch off the child lock function according to
does not switch on 1 flash - child lock function is active
Section 5.4.2. Tab.17
3 flashes - unit is not fitted with any AQS - You probably bought the unit without the AQS
sensor sensors or the external sensor is not connected
- diodes 1; 2; 3; 4
12. The unit is Supply fan failure
are flashing
inoperable and the
- turn off the unit on the controller, then by the
4 LEDs on the - diodes 5; 6; 7; 8
13. Exhaust fan failure unit's main switch to position 18, leave the unit off
range for adjusting are flashing for approx. 10 sec - restart of the unit
the ventilation
- diodes 1; 2; 7; 8 - if the error persists even after restarting the unit,
14. power on the Faulty "room temperature sensor"
are flashing contact the unit supplier, contact the unit supplier
control panel are
after restarting the unit
continuously
flashing - diodes 3; 4; 5; 6
15. Faulty anti-freeze sensor
are flashing
- description of buttons
- Switches from the control mode to ventilation and temperature setting mode - Switching between setting the range of
Reduction of ventilation and
1. Button - Press the button to reduce the required level by one degree on the range of ventilation power or the ventilation power or required
temperature performance
temperature setting temperature is done using button 2.
Unit switching on - By holding the button for 3 seconds, switch the unit on (LED lights up) or off - in the cold and water versions, the display button
Toggle and (signalling)/switching off - if the LED flashes after the unit is switched off, the heating is cooled down. Once finished, it will turn off has only the on/off function
status
2.
indication
button Switching between ventilation - In setting mode, you switch between the fan setting and temperature ranges. Indication of the selected - Switching is only for the electric version
power and temperature setting range is displayed by flashing of symbols 7 and 10. (NR1-xxx-ECE1...)
Start of intensive ventilation - - Pressing the button for 3 seconds starts the intensive ventilation. To switch it off before 10 minutes pass, press the - The function start indication is a flashing
Toggle BOOST button again for 3 seconds and the ventilation returns to the pre-start mode. diode 12.
3. function
button Increase ventilation and - Switches from the control mode to ventilation and temperature setting mode - switch between the ranges using button
temperature power levels - Press the button to increase the requirement on the range of the ventilation or temperature performance setting 2.
- The clogged filter indication is triggered after approx. 6 months of unit operation (only if the unit is
Status - Replace and reset the filter according to
5. Filter clogged indication ventilating).
indication Section 6.
- The indication is expressed by a flashing red LED.
- Press the button to start the night cooling function. Night cooling is used to cool the ventilated area in the
- It is recommended to activate the
Double- Night cooling - on summer with night cold air. The function is active for 8 hours from pressing the button.
function after 10 p.m. During the summer
function and (signalling)/off - The intensity of the supplied air can be changed even when the function is activated. When the function is
months, the air is coldest around 5 a.m.
6. status completed, the values return to the settings before the function started.
indication - When attempting to change the
button - protection against manipulation by unauthorised persons. It is activated/deactivated by pressing the
Child lock parameters during the activated function,
button for more than 6 sec. Activation/deactivation is indicated by 3 flashes of all the status LEDs
all the status LEDs flash once
- in the control mode, the diode is lit - the unit is ventilating - When ventilation is switched off (all the
Status Ventilation operation status - in the setting mode, the diode flashes - you are in the required ventilation power setting mode range diodes are off), all the heating
10.
indication diode - ventilation can be switched off independently of the heating requirement. In the setting mode, reduce the requirements remain operational and
output (button 1) until the last diode on the range turns off. satisfied.
- ventilation range indication display
Control
descriptio Symbol
n number
11.
12.
Display description
Control
description Symbol Display description
number
Indication of temperature setting in
1st LED
8. 1st LED
2nd to 7th LED
LED in the separate MAX field - signals t
temperature requirement (ap
9.
Note:
The assignment of LEDs to the individual temperatures is only indicative. They cannot under any circumstances
Display description Note
dication of temperature setting in the selected range.
1st LED
Flake - anti-freeze temperature 5 - 7 °C
Regular temperature setting 19 - 24 °C setting in approx. 0.5 °C increments - LED
flashes
n the separate MAX field - signals the maximum possible
temperature requirement (approx. 28 °C)
19.8
-
800/937
3.7/4.7
up to 90
up to 85
NR1-025-ECE1...P…
ERV
electric
electric
240/335
1
42.2
-
1480/1709
7.3/8.2
up to 86
up to 75
-34,4)
Installation EPS box
Thermal
Type of installation EPS box conductivity thermal resistance approximate bulk
ordering code coefficient λ RD density
W/m.K m2.K/W kg/m3
NR-010-EPS-BOX
0.037 5.4 18 - 23
NR-025-EPS-BOX
*Number of pieces on the pallet
compressive stress packaging
at 10% compression fire reaction class net/gross weight dimensions
kPa - kg m (H x W x L)/pc*
0.9/1 0.45 x 0.2 x 0.5/32
100 E
1.1/1.2 0.54 x 0.2 x 0.5/32