Air Conditioner Service Manual

10.5 Examples of repairing


10.5.1 Display E1 or E2
Reasons:
1) The sensor connection terminal loose or not plugged in.

Solution: Check the connecter of sensor and slot (CN6), if loose or not plugged in, please connect
again.
2) Room temperature sensor (IRT) and Indoor pipe (coil) temperature sensor (IPT) damage (short or
broken).

Solution: check the resistance of the sensor R (25℃) =5 kΩ, if short or broken please replace it.

Fail OK

3) The PCB fail.


Solution: Replace the indoor main PCB.

10.5.2 Display E6
Reasons:
1) The indoor motor connection terminal loose or not plugged in.

Solution: Check the connecter of indoor motor and slot (CN3) and (CN4), if loose or not plugged in, please
connect again.
2) The indoor motor damage.
Solution: Check and replace the motor.

28
Air Conditioner Service Manual

3) The indoor main PCB damage.

Solution: Replace the indoor main PCB.


10.5.3 Display E3, E7
Reasons:
1) Outdoor pipe temp sensor, outdoor temp sensor connection terminal loose or not plugged in.

Solution: Check the connecter of sensor and slot, if loose or not plugged in, please connect again.
2) Outdoor pipe temp sensor and outdoor temp sensor damage (short or broken).
Solution: Check and replace the sensor.

OK
Fail

3) Outdoor PCB damage.


Solution: Check and replace the outdoor PCB.
10.5.4 Display E8
Reasons:
1) Outdoor discharge pipe temp sensor connection terminal loose or not plugged in.

Solution: Check the connecter of sensor and slot, if loose or not plugged in, please connect again.
29
Air Conditioner Service Manual

2) Outdoor pipe temp sensor damage.

Fail OK

Solution: Check and replace the sensor.


3) Outdoor PCB damage.
Solution: Check and replace the outdoor PCB.
10.5.5 Display E0,E5
Reason: Indoor / outdoor communication damage.
Solution:
1) Check if the indoor and outdoor connections are correct. The terminal L and N which connect to indoor
unit shall correspond to each other on indoor and outdoor units. Measure the voltage on outdoor
terminal L and N (before display of E0 fault). If the voltage is “0”, please replace indoor main PCB.

1 N L

2) If the 1 & N which connect to indoor unit voltage is normal, measure the voltage between the outdoor
terminal 1 and N. If the voltage change occurs between 0~24V (change pulse voltage), please replace
indoor PCB.

1 N L

3) If the 1 & N which connect to indoor unit voltage is normal, measure the voltage between the outdoor
terminal 1 and N. If the voltage change occurs between 0~12V( change pulse voltage), but there is no
24V, please replace outdoor PCB.

1 N L

4) If the 1 & N voltage is normal, measure the voltage between the outdoor terminal 1 and N. If the
voltage has no change, firstly replace the indoor main PCB. If the fault remains unsolved, replace the
outdoor PCB.

30
Air Conditioner Service Manual

1 N L

5) Communication fault if resistance or optical coupler broken, replace outdoor PCB.

Communication
circuit

6) Is there any burnt on PCB? If no, test the rectifier, FRD, IGBT etc. any component broken, replace
PCB.

Any of 2 pins should be


no short circuit

Any of 2 pins should be


no short circuit

Any of 2 pins should be


no short circuit

7) Test the DC voltage between DC+ and DC-. If the voltage is less than 50V approximately, please
replace outdoor PCB.

DC-
DC+

10.5.6 Display EA
Reason: Current sensor fault.
Solution:
1) Check for refrigerant leakage, to find the leakage point and recharge the refrigerant.
2) Current sampling circuit broken on the outdoor PCB and replace outdoor PCB.

Current sampling
circuit

31
Air Conditioner Service Manual

10.5.7 Display E9(first display P0 or P9)


Reason: Outdoor PCB drive circuit damage.
Solution:
Re-energize and check the protection code on display. Firstly display P0.
1) If this code is displayed when the compressor is started for several seconds or even not started, check
the compressor connection for correctness, if no insert wrong, replace outdoor PCB.

Compressor U,V,W connection

2) Check if the outdoor module is tightly installed onto the radiating fins and if the silicone is applied
evenly, fix the screws again if loose.

Heat radiation problem easily happened


while the screw is not fixed tightly.

Fixing screw

3) Check the system pressure, recharge refrigerant if the pressure is low, and discharge some
refrigerant if the pressure is too high.
4) Check the outdoor ventilation and if there is any obstruction that affects the normal radiating of the air
conditioner, and installation again.
5) If the above inspections are normal, but the fault remains unsolved, please replace the outdoor PCB.
Re-energize and check the protection code on display. Firstly display P9.
a) Check the Compressor U,V, W connection, if is correctness or loose please connect again.

Compressor U, V, W connection

b) If this code is displayed when the compressor is started for several seconds or even not started,
check the compressor connection for correctness, if no insert wrong, replace outdoor PCB.
10.5.8 Display EU.
Reason: Voltage sensor damage.
Solution: Please replace outdoor PCB.

Voltage sensor

32
Air Conditioner Service Manual

10.5.9 Display EE
Reason: EEPROM fault.
Solution: Shut down power supply and reenergize it, if the fault remains there, check the EEPROM
installation, if no problem, please replace outdoor PCB.

EEPROM

10.5.10 Display CL
Cause: Air filter duty, the unit operation Cumulative time 500 hours, the controller will confirmation the filter
dirty and display CL.
Solution: Clean the air filter then cut off the power and supply again.
10.6 MALFUNCTION (PARTS) CHECK METHOD

10.6.1 Procedure for determining defective outdoor unit IPM/compressor


The following flow chart shows a procedure for locating the cause of a malfunction when the compressor
does not start up and a DC overcurrent indication error occurs.

Use the remote operates


the air conditioner

No No
P9 Does compressor start up Does the wire Connects wire
connects right again
Yes No
Compressor star up Yes
Does low or high press
valve opened Open

Yes
Does indoor unit LED Yes
display error code. No Replace the
Operates again after 3 Mins
inverter PCB

Yes
No

Normal Replace the compressor


Normal

P0 Does compressor start

Yes

Clean indoor or outdoor No Does the wire Connects wire


Clean indoor heat exchange again
heat exchange and outdoor heat exchange connects right

Normal

Not enough
Add gas Check the refrigerant
amount

Normal

Normal
Check the installation condition Replace the inverter PCB

Installation again

33
Air Conditioner Service Manual

10.6.2 DC Over Current Error


Error memory is
recorded
Start

Are valves (2-way Yes


or 3-war) close?

Full open stop valves

Does compressor Yes


rotates?

No Does compressor Yes


rotates more than
30 seconds?

No Is IPM PWB floating Yes


from the heat sink?

Fix IPM PWB with screws


No securely.
Check IPM lead Abnormal
wire (UVW)

Check the AC power


Modify the connection of supply voltage when
Normal compressor lead wire on compressor rotate.(rated
PWB voltage±10%)

Check IPM short Normal


circuit.
Abnormal

Yes
Replace P WB. Cooling mode?.
Normal

No
Check outdoor
Abnormal exchange sensor Abnormal
Check compressor
and discharge
Check indoor sensor
exchange sensor Abnormal
Modify compressor terminal and discharge Modify or replace
Normal marking sensor the sensor.
Modify or replace Normal
Replace PWB Normal the sensor.

Check outdoor Abnormal


Check indoor heat exchange
heat exchange.
Abnormal
Does compressor
rotates? Clean outdoor
Clean indoor heat heat exchange
Normal exchange

No

Check the refrigerant


Replace compressor amount

Check the discharge Check the installation


press condition

34
Air Conditioner Service Manual

10.6.3 E0,E5 Error

Display E5 Replace inverter board and power


Start supply board or outdoor PCB
assembly

Display E0

Shut off power and supply Display E5 Display E5


Shut off power Replace inverter board
again and observe 10 Mins and supply again

Display E0

Check the wire Not OK Connects the Display E0 first and then
connections wire again display E5 and keep

OK
OK If the indicator on the Yes
Check the terminal OK Solve as E0
outdoor PCB blink?
L and N voltage
No
OK Abnormal Check wire connected
Check terminal L&N
voltage and replace indoor PCB
Yes
If the voltage is Replace indoor
Normal
0V PCB
Damage
No Check the rectifier
bridge, fast recovery Replace PFC board or
diode (FRD) and IGBT outdoor PCB assembly
Check the terminal
N and 1 voltage Normal

Test the DC voltage If the voltage is


If the voltage Yes between DC+ and DC- approx. 300V
Replace indoor
change occurs
PCB
between 0~24V
If the voltage is
Replace power supply
approx. zero
board or outdoor PCB
If the voltage change Yes Replace power supply assembly
occurs between board or outdoor PCB
0~12V not 13~24V assembly
Replace PFC board
or outdoor PCB
assembly
If the voltage no change

If the problem cannot be solved


Replace indoor PCB, if by using the methods above
unsolved replace power
supply board or outdoor
PCB assembly

Replace the indoor main PCB,


power source board, and PFC
board or outdoor PCB assembly

35
Air Conditioner Service Manual

10.6.4 E4 Error

Start

E4
Enough OK
Check the pressure Check the sensor resistance Replace outdoor PCB

Not enough Fail

Add Freon Replace the sensor

10.6.5 F4 Error

Start

F4

Check the valve open or not

Not

Open the valve

Start again

10.6.6 Fy Error

Start 9 minutes

Fy

Check the pipe No leak Check the pipe sensor No Check the
connect and pipe leak position temperature evaporator pipe
change block up

Yes
Tighten again or Whether have1.5 ℃ change Replace the evaporator
welding leak
between start and after
10minutes

Charging gas again Yes


Check the sensor resistance

Fail

Replace the sensor

36