TROUBLE SHOOTING ERRORI SKY Agg. 30.08.2019
TROUBLE SHOOTING ERRORI SKY Agg. 30.08.2019
TROUBLE SHOOTING ERRORI SKY Agg. 30.08.2019
Solution: Check the connecter of sensor and slot (CN6), if loose or not plugged in, please connect
again.
2) Room temperature sensor (IRT) and Indoor pipe (coil) temperature sensor (IPT) damage (short or
broken).
Solution: check the resistance of the sensor R (25℃) =5 kΩ, if short or broken please replace it.
Fail OK
10.5.2 Display E6
Reasons:
1) The indoor motor connection terminal loose or not plugged in.
Solution: Check the connecter of indoor motor and slot (CN3) and (CN4), if loose or not plugged in, please
connect again.
2) The indoor motor damage.
Solution: Check and replace the motor.
28
Air Conditioner Service Manual
Solution: Check the connecter of sensor and slot, if loose or not plugged in, please connect again.
2) Outdoor pipe temp sensor and outdoor temp sensor damage (short or broken).
Solution: Check and replace the sensor.
OK
Fail
Solution: Check the connecter of sensor and slot, if loose or not plugged in, please connect again.
29
Air Conditioner Service Manual
Fail OK
1 N L
2) If the 1 & N which connect to indoor unit voltage is normal, measure the voltage between the outdoor
terminal 1 and N. If the voltage change occurs between 0~24V (change pulse voltage), please replace
indoor PCB.
1 N L
3) If the 1 & N which connect to indoor unit voltage is normal, measure the voltage between the outdoor
terminal 1 and N. If the voltage change occurs between 0~12V( change pulse voltage), but there is no
24V, please replace outdoor PCB.
1 N L
4) If the 1 & N voltage is normal, measure the voltage between the outdoor terminal 1 and N. If the
voltage has no change, firstly replace the indoor main PCB. If the fault remains unsolved, replace the
outdoor PCB.
30
Air Conditioner Service Manual
1 N L
Communication
circuit
6) Is there any burnt on PCB? If no, test the rectifier, FRD, IGBT etc. any component broken, replace
PCB.
7) Test the DC voltage between DC+ and DC-. If the voltage is less than 50V approximately, please
replace outdoor PCB.
DC-
DC+
10.5.6 Display EA
Reason: Current sensor fault.
Solution:
1) Check for refrigerant leakage, to find the leakage point and recharge the refrigerant.
2) Current sampling circuit broken on the outdoor PCB and replace outdoor PCB.
Current sampling
circuit
31
Air Conditioner Service Manual
2) Check if the outdoor module is tightly installed onto the radiating fins and if the silicone is applied
evenly, fix the screws again if loose.
Fixing screw
3) Check the system pressure, recharge refrigerant if the pressure is low, and discharge some
refrigerant if the pressure is too high.
4) Check the outdoor ventilation and if there is any obstruction that affects the normal radiating of the air
conditioner, and installation again.
5) If the above inspections are normal, but the fault remains unsolved, please replace the outdoor PCB.
Re-energize and check the protection code on display. Firstly display P9.
a) Check the Compressor U,V, W connection, if is correctness or loose please connect again.
Compressor U, V, W connection
b) If this code is displayed when the compressor is started for several seconds or even not started,
check the compressor connection for correctness, if no insert wrong, replace outdoor PCB.
10.5.8 Display EU.
Reason: Voltage sensor damage.
Solution: Please replace outdoor PCB.
Voltage sensor
32
Air Conditioner Service Manual
10.5.9 Display EE
Reason: EEPROM fault.
Solution: Shut down power supply and reenergize it, if the fault remains there, check the EEPROM
installation, if no problem, please replace outdoor PCB.
EEPROM
10.5.10 Display CL
Cause: Air filter duty, the unit operation Cumulative time 500 hours, the controller will confirmation the filter
dirty and display CL.
Solution: Clean the air filter then cut off the power and supply again.
10.6 MALFUNCTION (PARTS) CHECK METHOD
No No
P9 Does compressor start up Does the wire Connects wire
connects right again
Yes No
Compressor star up Yes
Does low or high press
valve opened Open
Yes
Does indoor unit LED Yes
display error code. No Replace the
Operates again after 3 Mins
inverter PCB
Yes
No
Yes
Normal
Not enough
Add gas Check the refrigerant
amount
Normal
Normal
Check the installation condition Replace the inverter PCB
Installation again
33
Air Conditioner Service Manual
Yes
Replace P WB. Cooling mode?.
Normal
No
Check outdoor
Abnormal exchange sensor Abnormal
Check compressor
and discharge
Check indoor sensor
exchange sensor Abnormal
Modify compressor terminal and discharge Modify or replace
Normal marking sensor the sensor.
Modify or replace Normal
Replace PWB Normal the sensor.
No
34
Air Conditioner Service Manual
Display E0
Display E0
Check the wire Not OK Connects the Display E0 first and then
connections wire again display E5 and keep
OK
OK If the indicator on the Yes
Check the terminal OK Solve as E0
outdoor PCB blink?
L and N voltage
No
OK Abnormal Check wire connected
Check terminal L&N
voltage and replace indoor PCB
Yes
If the voltage is Replace indoor
Normal
0V PCB
Damage
No Check the rectifier
bridge, fast recovery Replace PFC board or
diode (FRD) and IGBT outdoor PCB assembly
Check the terminal
N and 1 voltage Normal
35
Air Conditioner Service Manual
10.6.4 E4 Error
Start
E4
Enough OK
Check the pressure Check the sensor resistance Replace outdoor PCB
10.6.5 F4 Error
Start
F4
Not
Start again
10.6.6 Fy Error
Start 9 minutes
Fy
Check the pipe No leak Check the pipe sensor No Check the
connect and pipe leak position temperature evaporator pipe
change block up
Yes
Tighten again or Whether have1.5 ℃ change Replace the evaporator
welding leak
between start and after
10minutes
Fail
36