BGR ENERGY SYSTEMS LTD

ELECTRICAL PROJECTS DIVISION


PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

6.0 DESIGN OF FOUNDATION Designation of Footing - CF1


6.2.1 CHECK FOR SOIL BEARING PRESSURE FOR COMBINED FOOTING Designation of Footing - CF1
Design Data Geotechnical Data Characteristic Strength of Materials
Length of the footing along X, Lx = 2150 mm Unit weight of soil, gs = 18 kN/m3 Grade of Concrete, fck = 30 N/mm2
Length of the footing along Y, Ly = 1350 mm Allowable Net SBC of Soil, g n, sbc = 250 kN/m2 Grade of Reinf.steel, fy = 500 N/mm2
Thickness of the footing, D = 450 mm Depth of footing from NGL, FD = 6.200 m (16.2-10) Sketch
Length of C1 along X, C1x = 450 mm Overburden Pressure, OP = 18 x 6.2 = 111.6 kN/m 2
X
Length of C1 along Y, C1y = 450 mm Allowable Gross SBC of Soil, g g, sbc = g n, sbc + OP = 250 + 111.6

675
Length of C2 along X, C2x = 450 mm = 361.6 kN/m2 (Long Term)
Length of C2 along Y, C2y = 450 mm C2
Finished Floor Level, FFL (+) RL = 13.41 m For Short Term Load Combination,
Finished ground Level, FGL (+) RL = 12.85 m Allowable Net SBC of Soil, g n, sbc = 1.25 (g n, sbc) = 1.25 x 250

800
M

2150
Founding Level, (+) RL = 10.00 m = 312.5 kN/m2 Y Y o
Surcharge = 20.00 kN/m2 Allowable Gross SBC of Soil, g g, sbc = g n, sbc + OP = 312.5 + 111.6 d
i
Avg. Height of Soil above Footing, TOF = 2.40 m = 424.1 kN/m2 (Short Term) f
[12.85 -(10 )- (0.45) ] . C1 i
e

675
Section Modulus about X, Zx = Lx Ly2 / 6 = 0.65 m3 d
Self weight of footing,Wf = 25 x 2.15 x 1.35 x (0.45 ) = 32.65 kN Section Modulus about Y, Zy = Ly Lx2 / 6 = 1.04 m3
b
Avg. Height of Soil above Footing, Hs = 2.400 m Max. Pr Fx Fy Fz Mx My Mz X
Joint L/C e
Weight of Soil above footing, Ws = 107.89 kN (kN/m2) (kN) (kN) (kN) (kN-m) (kN-m) (kN-m) 675 675 a
r
Surcharge = 49.95 kN
135.56 - 129 8.400 0.400 8.600 2.764 65.244 0.000 i
Total Load Wt = 190.5 kN 1350 n
g

p
Loads from Design Force / Moment Maximum base Pressure at four edges of the footing Loss of contact
r
Case Load Combination SBC Check e
Fx (kN) Fy (kN) Fz (kN) Mx (kNm) My (kNm) Mz (kNm) P (kN) Mx (kNm) My (kNm) P1 (kN/m2) P2 (kN/m2) P3 (kN/m2) P4 (kN/m2) % Check s
### s
u
Max Fx 129 8.40 0.40 8.60 2.76 65.24 0.00 199.1 2.8 65.2 135.56 10.10 127.09 1.63 SAFE 0.00 SAFE ### r
e
Min Fx 141 -8.40 -0.40 7.40 -2.76 -65.24 0.00 197.9 2.8 65.2 135.14 9.68 126.68 1.22 SAFE 0.00 SAFE ###
(
Max Fy 108 -1.00 2.00 7.00 7.82 -6.41 0.00 197.5 7.8 6.4 86.18 73.85 62.23 49.90 SAFE 0.00 SAFE ### k
N
/
Min Fy 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00 199.5 9.8 6.4 89.93 77.61 59.86 47.53 SAFE 0.00 SAFE ### m
2

Max Fz 124 1.40 -0.40 14.40 -2.76 8.77 0.00 204.9 2.8 8.8 83.26 66.39 74.80 57.92 SAFE 0.00 SAFE ### )

Min Fz 148 -3.80 0.40 1.60 1.16 -26.76 0.00 192.1 1.2 26.8 93.69 42.24 90.13 38.67 SAFE 0.00 SAFE ###

Max Mx 109 1.00 2.00 7.00 9.82 6.41 0.00 197.5 9.8 6.4 89.24 76.92 59.17 46.84 SAFE 0.00 SAFE ###

Min Mx 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00 199.5 9.8 6.4 89.93 77.61 59.86 47.53 SAFE 0.00 SAFE ###

Max My 129 8.40 0.40 8.60 2.76 65.24 0.00 199.1 2.8 65.2 135.56 10.10 127.09 1.63 SAFE 0.00 SAFE ###

Min My 141 -8.40 -0.40 7.40 -2.76 -65.24 0.00 197.9 2.8 65.2 135.14 9.68 126.68 1.22 SAFE 0.00 SAFE

Note:
As per NPCIL soil report vide page no: 16 of 21 - BH-08, natural ground level is at RL +16.285 m level. Hence to consider the overburden effect on the Net SBC, the height difference for calculating gross SBC from net SBC is considered
as RL +16.2 to founding depth of RL +10.00 m level - i.e 6.20 m
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

6.2.2 DESIGN OF COMBINED FOOTING Footing ID - CF1

Design Data: Characteristic Strength of Materials:

Length along X direction, lx = 2150 mm Grade of Concrete, fck = 30 N/mm2


Length along Y direction, ly = 1350 mm Grade of Reinf.steel, fy = 500 N/mm2
Thickness of the footing, D = 450 mm Density of Soil, gs = 18 kN/m3
Finished Floor Level, FFL = 13.41 m (+) RL
Finished ground Level, FGL = 12.85 m (+) RL x
Depth of footing from FGL D = 2.85 m (12.85-10)

675
l2
Net Safe Bearing Capacity, gnet = 250 kN/m2 C2
C1 Size along X dir. lx1' = 450 mm
C1 Size along Y dir. ly1' = 450 mm y y lx

800
C2 Size along X dir. lx2' = 450 mm
C2 Size along Y dir. ly2' = 450 mm

l3
Calculations:
C1

675
l1
Design data from SBC Check,
x

Max. Pr Mx My Mz ly
(kN/m2) Jt L/C Fx (kN) Fy (kN) Fz (kN) (kN-m) (kN-m) (kN-m)

135.56 - 129 8.40 0.40 8.60 2.76 65.24 0.00

Force in X dir, Fx = 13.440 kN


Force in Y dir, Fy = 0.640 kN
Force in Z dir, Fz = 13.760 kN
Moment about X dir, Mx = 4.420 kNm
Moment about Y dir, My = 104.390 kNm
Moment about Z dir, Mz = 0.000 kNm
(Forces and Moments considered for design are taken from above table with a factor of 1.6 for the conservative side)

Section modulus of footing, Zx = lx ly2 / 6 = 0.65 m3


Zy = ly lx2 / 6 = 1.04 m3
Area of Footing, A = 2.15 x 1.35 = 2.9025 m2
kN
Selfweight of Footing = 25 x 2.15 x 1.35 x (0.45) = 32.65 kN
Ave. Height of soil on footing projection = 2.40 m
Weight of soil on footing projection = 18 x ( (2.15 x 1.35)-((0.45 x 0.45 )+(0.45x0.45 ) x 2.4 = 107.89 kN
Surcharge load = 20 kN/m2
= 20 x ( (2.15 x 1.35)-((0.45 x 0.45 )+(0.45x0.45 ) = 49.95 kN

Total weight = 32.65 + 107.89 + 49.95 = 190.49 kN

Eccentricity along X-axis = 0.000 m


Eccentricity along Y-axis = = 0.000 m
Additional moment about X-axis = 0x318.54 = 0.000 kN-m
Additional moment about Y-axis = 0x318.54 = 0.000 kN-m

Design Force of Footing in vertical dir., P = 13.76 + 1.6x32.65 +1.6x(107.89+49.95) = 318.54 kN


Design moment about X-axis, Mx = (4.42) + (0) = 4.42 kN-m
Design moment about Y-axis, My = (104.39) + (0) = 104.39 kN-m
On the conservative side, the footing is designed for the maximum net soil pressure acting as uniform throughout the foundation.
Design soil pressure for footing, w = (318.54 / 2.9025) + (4.42 / 0.65) + (104.39 / 1.04) = 216.92 kN/m2
(P/A)+(Mx/Zx)+(My/Zy)

Design of footing along Y direction;


Cantilever length of footing along Y direction, lyy = ( ly - ly' ) / 2 Clear cover = 50 mm
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

= 450 mm Effective depth of footing at


Max Bending Moment at face of column,/L Muy = ( w lyy2 ) / 2 column face,
= 21.963 kNm d = 450 - 50 - (16/2)
Therefore, Muy / bd2 = 0.140 pt = 0.032 % = 392 mm
Design steel reinforcement, Ast = 125 mm2 pt, min = 0.18 %

Ast required along Y direction Ast req. = 810 mm2 Ast, min = 810 mm2

Provide Y 16 @ 200 c/c along Y direction at bottom Ast provided = 1005 mm2 OK

Top Reinforcement
pt, min = 0.12 %
Ast, min = 540 mm2

Ast required along Y direction Ast req. = 540 mm2

Provide Y 12 @ 200 c/c along Y direction at top Ast provided = 565 mm2 OK

Design of footing along X direction:


Cantilever length of footing along X direction, lxx' = Max( l1-lx1'/2),(l2-lx2'/2) Clear cover = 66 mm
= 450 mm Effective depth of footing at
Max Bending Moment at face of column, Mux = ( w lxx2 ) / 2 column face,
= 21.963 kNm d = 450 - 66 - (16/2)
Therefore, Mux / bd2 = 0.16 pt = 0.037 % = 376 mm
Design steel reinforcement, Ast = 139 mm2 pt, min = 0.18 %

Ast required along X direction Ast req. = 810 mm2 Ast, min = 810 mm2

Provide Y 16 @ 200 c/c along X direction at bottom Ast provided = 1005 mm2 OK

Top Reinforcement
Distance between supports along X direction, l3' = 350 mm Clear cover = 66 mm
Effective depth of footing at
Max Bending Moment at face of column, Mux = 𝑤/2 column face,
( 〖𝑙 3′ 〗 ^2/4−
〖𝑙𝑧𝑧〗 ^2 )
= -18.642 kNm d = 450 - 66 - (12/2)
Therefore, Mux / bd2 = 0 pt = 0% = 378 mm
Design steel reinforcement, Ast = 0 mm2 pt, min = 0.12 %

Ast required along X direction Ast req. = 540 mm2 Ast, min = 540 mm2

Provide Y 12 @ 200 c/c along X direction at top Ast provided = 565 mm2 OK

Check for One Way Shear at a distance 'd' (effective depth) from face of column:

Along X direction: 392


Effective depth at critical section, d = 392 mm CXn 58

AERB/SS/CSE-1 - Cl. 3.6.2


Shear strength of concrete, tc = (1/gc) R(fk) = 0.657 N/mm2
R(fk) = [0.18 d (fck) ]
1/2
0.18 x 1 x ^0.5 = 0.986 N/mm2
tc(max) = (1/gc) 0.88((fck)1/2 (1/1.5)x0.88x30^0.5 = 3.213 N/mm2
CXn
Bending moment @ section, M (216.92 x (0.058) ^ 2) / 2 = 0.365 kNm
tan b = 0
Shear force acting along CXn / metre, Vux = 216.92 x 0.058
= 12.581 kN
Shear stress developed / metre, tv = (Vux - (M/d) tan b ) / bd
= 0.032 N/mm2 < 0.657 Hence OK
< 3.213
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

Along Y direction: 376


Effective depth at critical section, d = 376 mm CXn 74.00

AERB/SS/CSE-1 - Cl. 3.6.2


Shear strength of concrete, tc = (1/gc) R(fk) = 0.657 N/mm2
R(fk) = [0.18 d (fck) ]
1/2
0.18 x 1 x 30^0.5 = 0.986 N/mm2
tc(max) = (1/gc) 0.88((fck)1/2 (1/1.5)x0.88x30^0.5 = 3.213 N/mm2
CXn
Bending moment @ section, M (216.92 x (0.074) ^ 2) / 2 = 0.594 kNm
tan b = 0

Shear force acting along CXn / metre, Vuy = 216.92 x 0.074


= 16.052 kN
Shear stress developed / metre, tv = (Vuy - (M/d) tanb ) / bd
= 0.043 N/mm2 < 0.657 Hence OK
< 3.213

Check for Two way Shear


Critical section lies at a distance d/2 from the periphery of the column where d is the effective depth of slab
Permissible shear stress, ks tc where, ks = (0.5 + bc), but not greater than 1. tc = 0.25 fck
bc = Ratio of short side to long side of column = 450 / 450 = 1
ks = 1 tc = 1.37 N/mm2
Permissible shear stress = 1.37 N/mm2
Punching force, Vtws =(Fz) = 13.76 kN
Effective depth of slab , = 392 mm
Perimeter of critical section, bo = (2 x (450 + 392)) + (2*(450 + 392)) = 3368 mm
Punching shear stress, tv, tws = Vtws / (bod) = 0.01 N/mm2 < 1.37 N/mm2 Hence OK

Check for Overturning

About X axis
Overturning Moment about X axis, Mxo = = 2.76 kNm
Restoring Moment about X axis, Mxr = (0.9xP ly)/2 = 120.95 kNm
Factor of safety = Mxr / Mxo = 43.78 > 1.5 ; Hence OK

About Y axis
Overturning Moment about Y axis, Myo = = 65.2 kNm
Restoring Moment about Y axis, Myr = (0.9xP lx)/2 = 192.62 kNm
Factor of safety = Myr / Myo = 2.95 > 1.5 ; Hence OK

Check for Uplift

Uplift force (9.81x2.15x1.35x2.85) = 81.1 kN


Resisting force (0.9xP) = 0.9 x 318.54 / 1.6 = 179.2 kN
Factor of safety against uplift = 2.2 > 1.2 Hence OK
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

6.2 a COMBINED FOOTING- FORCES & SUMMARY (AT BOTTOM OF RAFT C.G)

Design forces for frame elements - Refer Annexure 1a for force extraction

a). For Load Point LP-711

Case L/C Fx Fy Fz Mx My Mz
Max Fx 128 8.00 -0.40 10.40 -0.76 58.28 0.00
Min Fx 140 -8.00 0.40 5.60 0.76 -58.28 0.00
Max Fy 108 -1.00 2.00 7.00 7.82 -6.41 0.00
Min Fy 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00
Max Fz 124 1.80 -0.40 13.40 -2.76 14.34 0.00
Min Fz 148 -3.80 0.40 2.60 0.76 -27.16 0.00
Max Mx 109 1.00 2.00 7.00 9.82 6.41 0.00
Min Mx 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00
Max My 128 8.00 -0.40 10.40 -0.76 58.28 0.00
Min My 140 -8.00 0.40 5.60 0.76 -58.28 0.00

b). For Load Point LP-710

Case L/C Fx Fy Fz Mx My Mz
Max Fx 128 8.00 -0.40 10.40 -0.76 57.28 0.00
Min Fx 140 -8.00 0.40 5.60 0.76 -57.28 0.00
Max Fy 108 -1.00 2.00 7.00 7.82 -6.41 0.00
Min Fy 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00
Max Fz 124 1.80 -0.40 13.40 -2.76 13.94 0.00
Min Fz 148 -3.80 0.40 2.60 0.76 -26.76 0.00
Max Mx 109 1.00 2.00 7.00 9.82 6.41 0.00
Min Mx 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00
Max My 128 8.00 -0.40 10.40 -0.76 57.28 0.00
Min My 140 -8.00 0.40 5.60 0.76 -57.28 0.00

c). For Load Point LP-709

Case L/C Fx Fy Fz Mx My Mz
Max Fx 128 8.00 -0.40 9.40 -1.16 57.28 0.00
Min Fx 140 -8.00 0.40 4.60 1.16 -57.28 0.00
Max Fy 108 -1.00 2.00 6.00 7.82 -7.41 0.00
Min Fy 106 -1.00 -2.00 8.00 -9.82 -5.41 0.00
Max Fz 124 1.80 -0.40 12.40 -3.16 13.94 0.00
Min Fz 148 -3.80 0.40 1.60 1.16 -26.76 0.00
Max Mx 109 1.00 2.00 6.00 9.82 5.41 0.00
Min Mx 106 -1.00 -2.00 8.00 -9.82 -5.41 0.00
Max My 128 8.00 -0.40 9.40 -1.16 57.28 0.00
Min My 140 -8.00 0.40 4.60 1.16 -57.28 0.00

d). For Load Point LP-308

Case L/C Fx Fy Fz Mx My Mz
Max Fx 128 8.00 -0.40 10.40 -0.76 57.88 0.00
Min Fx 140 -8.00 0.40 5.60 0.76 -57.88 0.00
Max Fy 108 -1.00 2.00 7.00 7.82 -7.41 0.00
Min Fy 106 -1.00 -2.00 9.00 -9.82 -5.41 0.00
Max Fz 124 1.80 -0.40 13.40 -2.76 13.94 0.00
Min Fz 148 -3.80 0.40 2.60 0.76 -26.76 0.00
Max Mx 109 1.00 2.00 7.00 9.82 5.41 0.00
Min Mx 106 -1.00 -2.00 9.00 -9.82 -5.41 0.00
Max My 129 8.00 0.40 9.60 2.76 58.68 0.00
Min My 141 -8.00 -0.40 6.40 -2.76 -58.68 0.00
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

e). For Load Point LP-306

Case L/C Fx Fy Fz Mx My Mz
Max Fx 129 8.40 0.40 8.60 2.76 65.24 0.00
Min Fx 141 -8.40 -0.40 7.40 -2.76 -65.24 0.00
Max Fy 108 -1.00 2.00 8.00 7.82 -10.41 0.00
Min Fy 106 -1.00 -2.00 10.00 -9.82 -8.41 0.00
Max Fz 124 1.40 -0.40 14.40 -2.76 8.77 0.00
Min Fz 160 -1.40 0.40 1.60 2.76 -8.77 0.00
Max Mx 109 1.00 2.00 6.00 9.82 8.41 0.00
Min Mx 106 -1.00 -2.00 10.00 -9.82 -8.41 0.00
Max My 129 8.40 0.40 8.60 2.76 65.24 0.00
Min My 141 -8.40 -0.40 7.40 -2.76 -65.24 0.00

f). For Load Point LP-304

Case L/C Fx Fy Fz Mx My Mz
Max Fx 116 8.00 -0.40 10.40 -2.76 61.08 0.00
Min Fx 152 -8.00 0.40 5.60 2.76 -61.08 0.00
Max Fy 108 1.00 2.00 7.00 7.82 9.41 0.00
Min Fy 106 1.00 -2.00 9.00 -9.82 7.41 0.00
Max Fz 124 3.80 -0.40 13.40 -2.76 29.96 0.00
Min Fz 148 -1.80 0.40 2.60 0.76 -13.14 0.00
Max Mx 109 -1.00 2.00 7.00 9.82 -7.41 0.00
Min Mx 106 1.00 -2.00 9.00 -9.82 7.41 0.00
Max My 116 8.00 -0.40 10.40 -2.76 61.08 0.00
Min My 152 -8.00 0.40 5.60 2.76 -61.08 0.00

g). For Load Point LP-109

Case L/C Fx Fy Fz Mx My Mz
Max Fx 116 7.00 -0.40 10.40 -3.16 52.87 0.00
Min Fx 152 -7.00 0.40 5.60 3.16 -52.87 0.00
Max Fy 108 1.00 2.00 7.00 7.82 6.41 0.00
Min Fy 106 1.00 -2.00 9.00 -9.82 4.41 0.00
Max Fz 124 3.40 -0.40 13.40 -3.16 24.39 0.00
Min Fz 148 -1.40 0.40 2.60 1.16 -13.57 0.00
Max Mx 109 -1.00 2.00 7.00 9.82 -4.41 0.00
Min Mx 106 1.00 -2.00 9.00 -9.82 4.41 0.00
Max My 116 7.00 -0.40 10.40 -3.16 52.87 0.00
Min My 152 -7.00 0.40 5.60 3.16 -52.87 0.00

h). For Load Point LP-110

Case L/C Fx Fy Fz Mx My Mz
Max Fx 116 8.00 -0.40 10.40 -2.76 57.28 0.00
Min Fx 152 -8.00 0.40 5.60 2.76 -57.28 0.00
Max Fy 108 1.00 2.00 7.00 7.82 6.41 0.00
Min Fy 106 1.00 -2.00 9.00 -9.82 6.41 0.00
Max Fz 124 3.80 -0.40 13.40 -2.76 26.76 0.00
Min Fz 148 -1.80 0.40 2.60 0.76 -13.94 0.00
Max Mx 109 -1.00 2.00 7.00 9.82 -6.41 0.00
Min Mx 106 1.00 -2.00 9.00 -9.82 6.41 0.00
Max My 116 8.00 -0.40 10.40 -2.76 57.28 0.00
Min My 152 -8.00 0.40 5.60 2.76 -57.28 0.00
BGR ENERGY SYSTEMS LTD
ELECTRICAL PROJECTS DIVISION
PROJECT TITLE
KUDANKULAM NUCLEAR POWER PROJECT - 3 & 4
DOCUMENT NO
REV
GID-379-CV-UAD-CA-2203
DESIGN OF FOUNDATION FOR 230kV OUTDOOR GIBD SUPPORT STRUCTURE R0

i). For Load Point LP-111

Case L/C Fx Fy Fz Mx My Mz
Max Fx 116 8.00 -0.40 10.40 -2.76 58.28 0.00
Min Fx 152 -8.00 0.40 5.60 2.76 -58.28 0.00
Max Fy 108 1.00 2.00 7.00 7.82 6.41 0.00
Min Fy 106 1.00 -2.00 9.00 -9.82 6.41 0.00
Max Fz 124 3.80 -0.40 13.40 -2.76 27.16 0.00
Min Fz 148 -1.80 0.40 2.60 0.76 -14.34 0.00
Max Mx 109 -1.00 2.00 7.00 9.82 -6.41 0.00
Min Mx 106 1.00 -2.00 9.00 -9.82 6.41 0.00
Max My 116 8.00 -0.40 10.40 -2.76 58.28 0.00
Min My 152 -8.00 0.40 5.60 2.76 -58.28 0.00

SUMMARY OF FORCES FOR 9 LOAD POINTS

L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m


Max Fx 129 8.40 0.40 8.60 2.76 65.24 0.00
Min Fx 141 -8.40 -0.40 7.40 -2.76 -65.24 0.00
Max Fy 108 -1.00 2.00 7.00 7.82 -6.41 0.00
Min Fy 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00
Max Fz 124 1.40 -0.40 14.40 -2.76 8.77 0.00
Min Fz 148 -3.80 0.40 1.60 1.16 -26.76 0.00
Max Mx 109 1.00 2.00 7.00 9.82 6.41 0.00
Min Mx 106 -1.00 -2.00 9.00 -9.82 -6.41 0.00
Max My 129 8.40 0.40 8.60 2.76 65.24 0.00
Min My 141 -8.40 -0.40 7.40 -2.76 -65.24 0.00