RBM-CA-BW-SDG-DET-0005 - 01 - Code B

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

KEY PLAN

N
RC SLAB T14 IN WHOLE WITH DIA
T14 IN WHOLE WITH DIA OF 16MM
A
OF 16MM
DET-0005
1A RC SLAB
1C
DET-0005 DET-0005
RC SLAB
TIE-COLUMN SPACING ≤ 4 M

100
RC SLAB

150

240
±0.00 = +76.80m
DOOR STRUCTURAL 1F
RC LINTEL
PLASTER DET-0005 GENERAL NOTES
OPENING WIDTH BLOCK WALL

300
1F 1. DO NOT SCALE FROM THE DRAWING

HEIGHT
DET-0005 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN

200
METER, UNLESS NOTED OTHERWISE.
RC LINTEL BLOCK WALL 3. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH
VERTICAL STIFFNER REINFORCEMENT
4T12 OTHER RELEVANT SHOP DRAWING AND SECTIONS.
COLUMNS FOR 4T12,STIRRUPS T8/250MM PLASTER
BLOCK WORK STIRRUPS (IN RC VERT.ELEMENT)
T8/250
1E
DET-0005

NOTES: NOTES:

DOOR STRUCTURAL
DOOR STRUCTURAL

ANCHOR FOR CONNECTIONS OF BLOCK WALL STRUCTURE

OPENING HEIGHT
ANCHOR FOR CONNECTIONS OF BLOCK WALL STRUCTURE
OPENING HEIGHT

TO BE INSTALLED WITH CHEMICAL ANCHOR FIX. TO BE INSTALLED WITH CHEMICAL ANCHOR FIX.
HOLES SHOULD BE FILLED WITH EPOXY BINDER. HOLES SHOULD BE FILLED WITH EPOXY BINDER.

1A VERTICAL STIFFENER COLUMN - 1C TYPICAL TOP CONNECTION ANCHOR FITTING


DET-0005 TYPICAL RC SLAB TOP CONNECTION DET-0005 BLOCK WALL TO THE RC SLAB

RC SLAB
RC SLAB
FFL
SSL
REINFORCEMENT
4T12,STIRRUPS T8/250
(IN RC VERT.ELEMENT)

1D 1B A SECTION
SCALE 1 : 20 REINFORCEMENT
DET-0005 DET-0005 DET-0005

600
4T12,STIRRUPS T8/250
(IN RC VERT.ELEMENT)
ELEVATION RC SLAB
SCALE 1 : 20
REFER SCHEDULE

CEMENT MORTAR BELOW


WALL THICKNESS

BLOCK WALL

MAX 200mm
THE FIRST ROW OF BLOCKS;
VERTICAL STIFFENER COLUMNS LAYER 10-30MM SCREED
200 CONCRETE POST FOR
RC SLAB
200 THICK BLOCK WORK
200 200
PLASTER

DRILLED IN WITH APPROVED 01 REVISED AS PER CONSULTANT 09-07-2021 TJ


MATERIAL AND HOLES SHOULD COMMENTS
BE FILLED WITH EPOXY BINDER. 00 ISSUED FOR APPROVAL 29-06-2021 TJ
Rev Description Date By
4T12 BLOCK WALL
STIRRUPS T8/250MM WITH HOOKS OF Certified for Coordination and Compliance with the Contract documents
NOTES:
135 DEGREES Date. Subcontractor Sig.
ANCHOR FOR CONNECTIONS OF BLOCK WALL STRUCTURE
MEP - ELECTRICAL
TO BE INSTALLED WITH CHEMICAL ANCHOR FIX.
MEP - PLUMBING
MEP - HVAC

3 VERTICAL STIFFENER - LINEAR POSITIONING 1B VERTICAL STIFFENER COLUMN - 1D TYPICAL BOTTOM ALUMINUM
OTHERS
DET-0005 TYPICAL RC SLAB BOTTOM CONNECTION DET-0005 CONNECTION TO THE RC SLAB
DET-0005 NON-LOAD BEARING BLOCK WALL AERATED BLOCK
ROBERTS REVIEW
Date: Signature:

RC SLAB
CLIENT:
ANCHOR FITTINGS
Belgrade Waterfront d.o.o.
DROP PANEL Karađorđeva 48,
11000 Belgrade

ARCHITECT AND AUTHOR:


RC SLAB
HEIGHT

POLYURETHANE FOAM naccach. mar mansour str. gebrayel bldg tel


+961 4 524 124 fax +961 4 524 224 70344
SIKA BOOM / SIKA BOOM FR antelias - lebanon www.erga.com

MIN 20mm
dubai abu dhabi fujairah doha manama jeddah riyadh
HORIZONTAL cairo damascus tangier algeria abuja paris miami

ANCHORAGE
RC LINTEL RESPONSIBLE DESIGNER FOR DESIGN FOR CONSTRUCTION:
200mm MIN. BLOCK WALL AERATED BLOCK PLASTER
END BEARING Ulica Cerska br. 29
CLEAR SPAN 11 000 Beograd
Serbia
RC COLUMN T: +381 11 3089 627
Email: [email protected]

MAIN-CONTRACTOR:

1E TYPICAL STRANDED LINTELS FOR


DET-0005 NON-LOAD BEARING BLOCK WALL
1H TYPICAL BLOCK WALL JOINT TO 1F TYPICAL PUF DETAIL
DET-0005 RC SLAB / COLUMN AT DROP PANEL LOCATION DET-0005 SCALE 1 : 5

PROJECT
LINTEL BEAM SCHEDULE Residential Commercial Building Simfonija
BELGRADE WATERFRONT
ARP Response Plot 12B; Zone S1
LINTEL SIZE REINFORCEMENT PLOT 12b - SIMFONIJA
CLEAR B – Approved as Noted Belgrade
SPAN [mm] WIDTH DEPTH A B STIRRUPS The Designer performed a review of all clouded areas only if any in subject DRAWING TITLE
drawings and hereby confirms that instructions given through the RFIs are
A APPROVED Shop Drawing

UPTO 2000 200 200 4T12 4T12 T8/250 TYPICAL AERATED BLOCK WORK
reflected on the drawings. This preliminary Designer's approval does not X B APPROVED AS NOTED
relieve the Contractor from any design responsibility and liability to SECTIONS AND DETAILS
functionally implement design changes in comprehensive documentation. C NOT APPROVED. RETURNED SHEET 5 OF 8
1f Typical Puf detail has been changes and acrylic sealant omitted. It is
D OTHER
feasible only if the Contractor guaranty and remediate all edge cracks. Drawn:
TJ
Checked:
RA
Authorised:
RBM
Risto Terzic SCALE SHEET DATE
SIGNATURE: DATE: 18.08.2021. As indicated A1 29-06-2021
DRAWING No. REV.
19.08.2021. RBM-CA-BW-SDG-DET-0005 01
09-07-2021 11:54:37