Bs 7870 4-10-12!7!22kv Aluminium Mdpe Cable
Bs 7870 4-10-12!7!22kv Aluminium Mdpe Cable
Bs 7870 4-10-12!7!22kv Aluminium Mdpe Cable
APPLICATION STANDARDS
Medium Voltage cable for power distribution and power supply BS 7870-4.10, BS EN 60228, HD620 S2 Part 10O / 11O
stations used in Utility and Industrial applications, for the rated
voltage of 12.7/22 (24)kV.
THE CABLE LAB®
AN ISO/IEC 17025 AND IECEE CBTL ACCREDITED FACILITY
CHARACTERISTICS Our world-class testing facility assures the quality and compliance of this cable
Voltage Rating Uo/U through a continuous and rigorous testing regime.
12.7/22 (24)kV
Temperature Rating
Maximum conductor operating temperature: +90ºC
Initial temperature at S.C.C for metallic screen: +80°C
Maximum conductor temperature during S.C: +250ºC SUSTAINABILITY COMMITMENT
We are on a journey to Net Zero.
Minimum Bending Radius
We've committed to near-term emissions reductions and a net-zero target with the
20 x overall diameter Science Based Targets initiative and we're a signatory to the United Nations Global
Compact Sustainable Development Goals.
Learn more about embodied carbon and our carbon emissions reduction actions,
CONSTRUCTION our comprehensive recycling services, and wider ESG activities for sustainable
Conductor operations at: www.elandcables.com/company/about-us/esg-sustainability
Class 2 Stranded Aluminium
Conductor Screen
Semi-conductive extruded XLPE (Cross-linked Polyethylene)
(Bonded)
Longitudinal Waterblock
Semi-conductive waterblocking tape
Metallic Screen
Copper Wires And Open Helix Copper Tape
Longitudinal Waterblock
Non-conductive waterblocking tape
Outer Sheath
MDPE (Medium Density Polyethylene)
Sheath Colour
Black
DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL INSULATION NOMINAL SCREEN NOMINAL SHEATH NOMINAL OVERALL NOMINAL
CORES SECTIONAL AREA THICKNESS SECTIONAL AREA THICKNESS DIAMETER WEIGHT
mm2 mm mm2 mm mm kg/km
ELECTRICAL CHARACTERISTICS
NOMINAL MAXIMUM MAXIMUM CAPACITANCE CHARGING DIELECTRIC REACTANCE S.C.C FOR 1 SEC CURRENT RATING
CROSS CONDUCTOR CONDUCTOR mF/Km CURRENT LOSSES AT 50 HZ KA A
SECTIONAL DC AC A/Km W/Km ohm/km
AREA RESISTANCE RESISTANCE
mm2 AT 20 °C AT OPERATING
Ω/Km TEMP. AND
50HZ
Ω/Km
70 0.443 0.569 0.203 0.81 41.16 0.136 6.559 4.1 222 247
95 0.32 0.411 0.223 0.889 45.14 0.130 8.9015 4.1 266 298
120 0.253 0.325 0.241 0.961 48.83 0.125 11.244 4.1 306 344
150 0.206 0.265 0.269 1.075 54.61 0.118 14.055 4.1 339 391
185 0.164 0.211 0.281 1.121 56.96 0.116 17.3345 4.1 388 449
240 0.125 0.161 0.312 1.244 63.22 0.111 22.488 4.1 445 534
300 0.1 0.129 0.341 1.362 69.20 0.107 28.11 4.1 498 615
400 0.0778 0.101 0.375 1.495 75.94 0.103 37.48 4.1 574 714
500 0.0605 0.079 0.418 1.668 84.73 0.099 46.85 4.1 646 838
630 0.0469 0.062 0.47 1.876 95.31 0.097 59.031 4.1 756 966
800 0.0367 0.049 0.531 2.119 107.68 0.093 74.96 4.1 855 1113