Enclosure 6360 AC Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Enclosure 6360 AC

The Enclosure 6360 is a compact multi-


purpose site cabinet designed to support
a multitude of equipment such as ERS
Baseband, Transport, Li-Ion battery and
3PP vendor equipment. It also provides a
highly capable power system and battery
back-up - all in a streamlined design and
minimized footprint to support cost
efficient expansion of mobile broadband.

Its small form factor makes it the perfect


choice for cramped sites in dense urban
areas - or for quick expansion of existing
sites with e.g. additional bands. As it can
support both internal and external
equipment it is very suitable for TowerCo
sites where it can provide good capacity
while still minimizing the foot print and
subsequently the rental costs.

With a robust design, IP65 compliance


and a sealed Heat Exchanger (HEX)
climate system the Enclosure 6360
ensures optimal environmental protection
of the active equipment - enabling them
for a long-lasting service. The complete
system is also integrated and verified for
the entire Ericsson Radio System and
ensures best-in-class service.

Offering AC power system and 6U of


equipment space it is a very capable
enclosure in a super-compact format. The
rack space is vendor agnostic, allowing
other telecom equipment than ERS.

In addition to both tower and wall


installation kits there is also a possibility to
install it directly on the ground using a
base frame - enabling use in all typical
site scenarios.

Enclosure 6360 is equipped with a cabinet


controller - allowing it to be visible in ENM
and used for both internal and external
alarm handling. The cabinet also provides
an open O&M interface for integration to
3PP O&M systems.
Technical specification for Enclosure 6360 AC
CAPACITY
Rack space user equipment 6U (19” rack)

Hardware capabilities Power and CPRI support for multi-standard remote radios (RRU or AIR)

ERS Baseband and Transport units

Li-Ion batteries

3PP equipment

Additional power feed available as option

Stackable with additional Enclosure 6360 AC or Enclosure 6360 DC

MECHANICAL SPECIFICATION
Weight 93 kg (excluding active equipment)
205 lbs (excluding active equipment)
Dimension (H x W x D) 880 x 650 x 570 mm (incl. Base frame)
35 x 26 x 23 in. (incl. Base frame)
Base frame height 150 mm
6 in.
Mounting position Ground / Pole / Wall
Enclosure material Aluminum
Color Power paint NCS 2002-B
Door Front access
Rack type 19” (IEC 60297-3-100)
Locking type Pad lock or Cylinder
POWER SYSTEM
Input voltage 3P+N+PE: 346/200-415/240 VAC
2P+N+PE: 208/120-220/127 VAC
1P+N+PE: 200-250 VAC
Input power <15kW
Output load (-48VDC) 10.5kW
Total capacity (-48VDC) 14kW
AC SPD Class 2/Type 2
DC SPD Class 2/Type 2
PSU Slots 4x
Service outlet Optional
Priority load 8x Circuit Breaker
LLVD 1 6x Circuit Breaker
LLVD 2 6x Circuit Breaker
CB ratings 3A / 5A / 10A / 15A / 20A / 25A / 30A / 40A / 50A / 60A / 80A / 100A
Battery Interface 1x Circuit Breaker
Battery Circuit Breaker rating 300A

Telefonaktiebolaget LM Ericsson
SE-164 80 Stockholm, Sweden 287 01-FGC 101 1407 Rev A
www.ericsson.com © Ericsson AB 2018
PSU capacity 3500W
PSU efficiency 96%
PSU output voltage (nominal) -48VDC
PSU rated current 73A
PSU power factor ≥0.99
PSU emissions EN 55022 Class B
Ingress protection power system IP20

DC/DC Voltage booster PSU 48 13 - 3x -58V ports


PDU 02 03 - 3x -58V ports/4x -48V ports
Both units are optional

ENVIRONMENTAL SPECIFICATION
Ingress protection IP65
Environment Class 1.2 (Storage)
Class 2.3 (Transport)
Class 4.1 (Operation)
ETSI EN 300 019-1-1
Relative humidity 15-100%

CLIMATE SYSTEM
Type Heat Exchanger
Temperature range -33°C to +50°C*
Cooling capacity 1200W
Heater Optional

STANDARDS COMPLIANCE
UL 62368-1
UL 60950-22
UL 50E
Telcordia GR-63-CORE

Telcordia GR-487-CORE

Telcordia GR-1089-CORE

CABLE I/O
Entry point Bottom
Plinth cable access Rear and side access
AC In 1x Ø16-35mm
DC Out (shielded) 32x Ø10-18mm
DC In (battery feed) 6x Ø19mm
Signal Cable Outlet 10x Ø10mm
Signal Cable Inlet 8x Ø6mm
Optical 32x Ø6mm
Conduits knock-out plates 6x Ø2”
Punched holes 3x Ø26mm

REMOTE MANAGEMENT
Controller interface northbound IP / Electrical Ethernet
External Alarms 32x
Fault Management Following alarms are sent to ENM:

- Battery temp sensors missing/faulty


- AC Mains failure per rectifier
- Rectifier over temperature alarm
- Battery CB trip
- Load CB trip
Telefonaktiebolaget LM Ericsson
SE-164 80 Stockholm, Sweden 287 01-FGC 101 1407 Rev A
www.ericsson.com © Ericsson AB 2018
- Rectifier failure
- Battery not possible to charge
- External alarms
- LLVD/BLVD disconnect

Alarms can be set for all Performance Data parameters


Performance Management Following data is sent to ENM:

- System Voltage
- System Current
- System Power
- Total Delivered Energy
- Battery Temperature
- Battery Voltage
- Battery Current
- Battery State of Charge
- Rectifier Output Voltage
- Rectifier Output Current
- Rectifier Input Voltage
- Rectifier run time
Configuration Management Following parameters can be set remotely from ENM:

- Float Charge Voltage


- Elevated Charge Voltage
- Battery Disconnect Voltage
- Load Disconnect Voltage
- Temperature Compensation
- Battery Capacity
- Alarm limits for all analogue values
- Rectifier Current Limit
- Battery temperature sensors
- State of health test
- Compensation factor
- Charging algorithm, float, temperature compensation, boost and equalization
Inventory Management The inventory record from production is stored in Cabinet controller and can be
fetched remotely. Inventory record can be updated in case of HW replacement

Inventory record covers:


- Cabinet Controller
- Power Controller
- Rectifiers
- Cabinet
- Battery Test Record
*Configuration dependent – please refer to CPI

Telefonaktiebolaget LM Ericsson
SE-164 80 Stockholm, Sweden 287 01-FGC 101 1407 Rev A
www.ericsson.com © Ericsson AB 2018