Enclosure 6360 AC Datasheet
Enclosure 6360 AC Datasheet
Enclosure 6360 AC Datasheet
Hardware capabilities Power and CPRI support for multi-standard remote radios (RRU or AIR)
Li-Ion batteries
3PP equipment
MECHANICAL SPECIFICATION
Weight 93 kg (excluding active equipment)
205 lbs (excluding active equipment)
Dimension (H x W x D) 880 x 650 x 570 mm (incl. Base frame)
35 x 26 x 23 in. (incl. Base frame)
Base frame height 150 mm
6 in.
Mounting position Ground / Pole / Wall
Enclosure material Aluminum
Color Power paint NCS 2002-B
Door Front access
Rack type 19” (IEC 60297-3-100)
Locking type Pad lock or Cylinder
POWER SYSTEM
Input voltage 3P+N+PE: 346/200-415/240 VAC
2P+N+PE: 208/120-220/127 VAC
1P+N+PE: 200-250 VAC
Input power <15kW
Output load (-48VDC) 10.5kW
Total capacity (-48VDC) 14kW
AC SPD Class 2/Type 2
DC SPD Class 2/Type 2
PSU Slots 4x
Service outlet Optional
Priority load 8x Circuit Breaker
LLVD 1 6x Circuit Breaker
LLVD 2 6x Circuit Breaker
CB ratings 3A / 5A / 10A / 15A / 20A / 25A / 30A / 40A / 50A / 60A / 80A / 100A
Battery Interface 1x Circuit Breaker
Battery Circuit Breaker rating 300A
Telefonaktiebolaget LM Ericsson
SE-164 80 Stockholm, Sweden 287 01-FGC 101 1407 Rev A
www.ericsson.com © Ericsson AB 2018
PSU capacity 3500W
PSU efficiency 96%
PSU output voltage (nominal) -48VDC
PSU rated current 73A
PSU power factor ≥0.99
PSU emissions EN 55022 Class B
Ingress protection power system IP20
ENVIRONMENTAL SPECIFICATION
Ingress protection IP65
Environment Class 1.2 (Storage)
Class 2.3 (Transport)
Class 4.1 (Operation)
ETSI EN 300 019-1-1
Relative humidity 15-100%
CLIMATE SYSTEM
Type Heat Exchanger
Temperature range -33°C to +50°C*
Cooling capacity 1200W
Heater Optional
STANDARDS COMPLIANCE
UL 62368-1
UL 60950-22
UL 50E
Telcordia GR-63-CORE
Telcordia GR-487-CORE
Telcordia GR-1089-CORE
CABLE I/O
Entry point Bottom
Plinth cable access Rear and side access
AC In 1x Ø16-35mm
DC Out (shielded) 32x Ø10-18mm
DC In (battery feed) 6x Ø19mm
Signal Cable Outlet 10x Ø10mm
Signal Cable Inlet 8x Ø6mm
Optical 32x Ø6mm
Conduits knock-out plates 6x Ø2”
Punched holes 3x Ø26mm
REMOTE MANAGEMENT
Controller interface northbound IP / Electrical Ethernet
External Alarms 32x
Fault Management Following alarms are sent to ENM:
- System Voltage
- System Current
- System Power
- Total Delivered Energy
- Battery Temperature
- Battery Voltage
- Battery Current
- Battery State of Charge
- Rectifier Output Voltage
- Rectifier Output Current
- Rectifier Input Voltage
- Rectifier run time
Configuration Management Following parameters can be set remotely from ENM:
Telefonaktiebolaget LM Ericsson
SE-164 80 Stockholm, Sweden 287 01-FGC 101 1407 Rev A
www.ericsson.com © Ericsson AB 2018