Iec62271307 Eng
Iec62271307 Eng
Iec62271307 Eng
1. INTRODUCTION
The document IEC TR 62271-307 began to be prepared in 2011 and was published in 2015. Its title is High-voltage
Switchgear and Controlgear – Part 307: Guidance for the extension of validity of type tests of AC metal and solid-insulation
enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV. Sergio Feitoza Costa is
coauthor and was a member of the IEC working group that prepared it along several international meetings.
This IEC Report (TR) focuses on medium/high voltage switchgear of the IEC 62271-200 and 62271-201 standards and
provides a method to avoid unnecessary repetition of costly tests. These opportunities can only be taken advantage of by
manufacturers who have test reports on hand that transparently describe the details of the equipment that was actually
tested. For reference, the information that must be included in a complete test report for this purpose is like in the
document http://www.cognitor.com.br/TR_071_ENG_ValidationSwitchgear.pdf . The more relevant information is
presented in the tables of next pages. The manufacturer going to test the “original” equipment must be careful to alert
the testing laboratory the information to include in the test reports.
To help understand the concepts involved in replacing laboratory tests with rules and/or calculations, it is also worth
mentioning the standards for low voltage switchgear. The ways to avoid tests in the IEC 60439 series (TTA / PTTA) were
only for temperature rise and short circuit tests (electrodynamic forces only). Repetition of tests is replaced by comparing
a tested design with the untested derived design. In the series of IEC 61439 standards that replaced 60439, the so-called
“Design Rules” were added. These “Rules” allow even to avoid tests and calculations. Table 1 below shows the
fundamentals of the design rules. There are more details on this topic in the book “Switchgear, Busways and other
Substation Equipment” (free download at: http://www.cognitor.com.br/Book_SE_SW_2013_ENG.pdf )
This TR allows, if certain rules are met, a report of tests carried out on a certain panel representative of a family of panels,
to be used as the basis for a study that demonstrates that if the tested one passed the tests, the non-tested one would
also pass.
The extension of the validity of test reports seeks to avoid unnecessary repetition of tests of IEC 62271-200 and 62271-
201 standards. It can be used to extend type tests performed on one sample with a defined set of ratings for another
switchgear of the same family with a different set of ratings or different arrangements. The IEC TR62271-307 describes:
• The use, parameters and application of extension criteria and the use of calculations
• The information necessary to extend the validity (which must be included in the test reports)
• Specific aspects to extend the validity of, one by one, dielectric tests, temperature rise tests, mechanical tests, short-
duration and crest withstand current tests, interruption and internal arc tests.
• The extension of validity of a test report to other functional units (situation a)
• Validation of a family by selecting test objects (situation b)
• Validation of a set of existing test reports (situation c)
• Validation of a project modification (situation d)
• Justification for extension criteria
• Examples of extending the validity of type tests such as:
o Design modification of a cable terminal in an air-insulated switchgear (AIS)
o Modification of the design of a functional unit by adding current transformers
o Modification of the design of a key-lock on the door of an AIS functional unit
o Extension of reports from a” ring main unit GIS” to functional units with greater width
o Extension of a family of gas insulated assemblies (GIS) to a functional unit
The section “Use of Extension Criteria” explains that due to the wide variety of functional unit types and possible
component combinations, it is not practical to perform type tests with all possible switchgears. Therefore, the
performance of a particular assembly can be evaluated against reports of type testing done on other assemblies in the
same assembly family. For each type of test type, a non-exhaustive list of design parameters is shown, which must be
analysed for the extension of validity. The analysis must be based on solid technical principles, physics, experience, and
calculations.
Each design parameter listed in Tables 2 to 6 must be compared between tested and untested designs under the criteria
provided in the tables. A simple example to visualize is that in the temperature rise test (line 5 of table 2) , if the current
density of the conductors of the untested equipment is lower than that of the one tested, the criterion is accepted as it
will heat up less. If any of the criteria is not clearly met, it is necessary to use other arguments such as calculations,
explanations and simulations or even additional tests.
Calculations and simulations can only be applied in a comparative sense based on the design parameters and acceptance
criteria. The tools must be previously validated and the simulation reproducible. Validation of software tools and
calculation methods are outside the scope of the TR IEC.
The IEC TR 60890 document provides calculation procedures that can be applied to compare fluid temperatures inside
enclosures. The calculation is made based on the Watts dissipated, the area of the compartment walls, the number of
horizontal partitions, and the area of the ventilation openings. Simulations are generally carried using tools like the
SwitchgearDesign software whose validation is at http://www.cognitor.com.br/TR_071_ENG_ValidationSwitchgear.pdf
4 Minimum pressure of insulating gas Same gas; for gas insulated switchgear
5 Current density of conductors The conductors have the same physical arrangement
6 Resistance per unit length of Compare conductor material and cross-section
conductors
9 Permissible temperature of contact Including metallic coatings having the same or lower
materials of connections / joints resistivity
10 Effective ventilation area of partitions Note 3
and enclosure
11 Power dissipation of components Here the main switching devices, fuses and current
transformers are considered.
14 Total coated surface area of The emission coefficient of the coating should be the
enclosure for heat transfer same.
15 Temperature class of insulating
material in contact with conductors
The dielectric performance of two switchgears may, if necessary, involve simulating and comparing the strength of electric
fields using software tools.
2.4) CRITERIA FOR THERMAL AND ELECTRODYNAMIC STRESSES DURING SHORT CIRCUIT
Calculations include determining electromagnetic forces between conductors and the mechanical stress that can bend
bars and cause damage to insulators. The calculation methods used in the SwitchgearDesign software in:
◼ IEC 61117, Method for assessing the short-circuit withstand strength of partially type-tested assemblies (PTTA)
◼ IEC 60865-1, Short-circuit currents – Calculation of effects – Part 1: Definitions and calculation methods.
Cell phone: +55-21-9 88874600
E-mail: [email protected] Site: http://www.cognitor.com.br
Consultancy, R&D Training
◼ IEC TR 60865-2, Short-circuit currents – Calculation of effects – Part 2: Examples of calculation.
Table 5 – Extension criteria for performance regarding thermal and electrodynamic short-circuit stresses.
Item Design parameter Acceptance Condition Criteria
criterion attended?
(1) (2) (3) (4)
1 Centre distance between
phases
2 Electro-dynamic forces The conductors have the same physical arrangement.
due to current path Note 1
Comparing the performance of electric panels in withstanding overpressure in the compartments is the analysis to be
carried out. Overpressure is a function of arc currents, areas of depressurization openings and internal volumes. The
evaluation of the force on the switchgear walls can be done for simple geometries using a calculation formula,
otherwise using finite element analysis for mechanical stress.
The flow of hot gases expelled can be simulated by CFD programs and the burning of indicators can be simulated, but no
one to date has validated this type of calculation. It would be very expensive to do as it would require a lot of testing.
The basis for the assessment are the values obtained for the overpressure’s curves. These concepts are well detailed in
the pages 177 to 191 of this book authored by Sergio http://www.cognitor.com.br/Book_SE_SW_2013_ENG.pdf
The worldwide reference for this theme is the brochure CIGRÈ 602 / 2014 Tools for the Simulation of The Effects of the
Internal Arc in T&D Switchgear. Sergio is coauthor of this Cigrè document and was member of CIGRE working group that
prepared it. https://www.e-cigre.org/publications/detail/602-tools-for-simulation-of-the-internal-arc-effects-in-hv-and-mv-switchgear.html
Table 7 – Extension criteria for internal arc tests (equipment)
Item Design parameter Acceptance Condition The criteria
criterion were
attended?
2 Clearance to earth same This concerns the region where the arc is initiated.
5 Cross-section of conductors This concerns the region where the arc is initiated.
6 Raw material of conductors same This concerns the region where the arc is initiated.
(Al or Cu or their alloys)
7 Location of the point of arc same Applying the rules of IEC 62271-200 or IEC 62271-201
initiation
12 Mechanical strength of the This also includes the strength of partitions and
enclosure and compartment bushings
Note 2
13 Thickness of the enclosure Same material
walls
Note 2
14 Mechanical strength of the Note 2
doors and covers
2 Clearance to earth
3 Enclosure/compartment volume Only to be validated, if the fluid (gas or liquid) in
the volume is involved in the making and breaking
process.
4 Pressure of insulating gas The travel characteristic is within the permissible
tolerances.
Note 3
8 Mechanical strength of the Note 3
enclosure/ partitions / bushings
Information from the switchgear that is required in type tests in accordance with IEC 62271 1 and IEC 62271-200 must be
collected. Furthermore, the relevant parameters information is that shown in Tables 2 to 7 for each specific test and
functional unit under evaluation. Applicable type test reports of the tested switchgear shall be provided for comparison
of “tested” and “untested” assemblies.
For this reason, it is recommended that the manufacturer inform clearly the testing laboratory that need that the relevant
information on the design parameters listed in tables 2 to 7 be included in the test reports (even if the product standard
does not request it). Relevant and detailed drawings are essential as part of this information. It is recommended to use
testing laboratories that have technical resources to obtain essential information, e.g. measuring overpressures in internal
arc tests.
More details, free Publications and training program in the site https://www.cognitor.com.br
Publications : https://www.cognitor.com.br/downloads1.html
CV https://www.cognitor.com.br/Curriculum.html
If you need an evaluation, with high recognition and a third-party report, with the
experience of Sergio Feitoza Costa, one of the co-authors of this IEC TR, please
contact us via email at [email protected]