Esure Rectifier R48 4000e
Esure Rectifier R48 4000e
Esure Rectifier R48 4000e
R48-4000e
eSURE™ RECTIFIER
R48-4000e
Description
Features and Benefits
The eSure™ R48-4000e rectifier For a higher load capacity, rectifiers
converts standard AC supply voltages can be connected in parallel and
Rectifier, 48 VDC, 4000 W into stable nominal-48V DC voltage intelligent control can be added with
adjustable to the needs of the applica- the help of a separate controller.
• Optimized depth-reduced footprint tion. The R48- 4000e is a constant
allows installation in short-depth power rectifier designed with the latest
racks and cabinets patented switchmode technology
using DSP (Digital Signaling Processor)
• DSP (Digital Signaling Processor) functionality for efficient operation.
- means fewer components,
optimized operation and active load
sharing for increased reliability
E ciency
eSure Rectifier
98% E ciency Curve
96%
94%
92%
90%
88%
86%
84%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Load
eSURE™ RECTIFIER
R48-4000e
Technical Specifications
Output power vs. input voltage
AC INPUT
and Vo >48Vat Tamb 50ºC
Input Voltage, Nominal 100 VAC to 250 VAC
85 184 300
Input Voltage, Permitted Variation 85 VAC to 300 VAC
% of output power
120
100
Line Frequency 45 Hz to 65 Hz 80
60
40
Max Input Current 23 .5 A 20
0
Power Factor 0.99 0 50 100 150 200 250 300 350
THD (Total Harmonic Distortion) < 5% from 50 to 100% rated load Input Voltage (VAC)
DC OUTPUT
Output Power vs. Temperature
Output Voltage, Adjustment Range -42 VDC to -58 VDC at 264V ≥ Uin ≥ 184VAC
Output Power 4000 W@Vout >48VDC
120
% of output power
Output Power, Derated for Input Voltage See diagram 100
80
Output Current 83.3 A 60
40
20
Output Current Limit Set Point 6.9 to 83.3 A 0
-40 -20 0 20 40 60 80 100 120
Psophometric noise (system) 95.3%
Temperature (ºC)
Peak Efficiency < 2 mV at 70% max load
Temperature Derating See diagram
Output voltage vs. Output current
CONTROL AND MONITORING
at max. power 4000 W
Rectifier Alarm and Signaling Alarm and status reported via CAN bus to system controller 60
Output Voltage(V)
50
Green LED: Normal Operation 40
Visual Indications Yellow LED: Alarm 30
20
Red LED: Failure 10
Flashing Red LED: Fan Failure 0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
MECHANICS
Dimensions (H x W x D) 132 x 85.3 x 293 (mm) / 5.2 x 3.36 x 11.5 (inches)
Weight 3.5 kg / 7.7 lbs
OTHER PARTS
Controller Units See separate ACU+ and SCU+ datasheets
Ordering Information
PRODUCT CODE DESCRIPTION
1R484000eXXX Rectifier 48v, 4000w
VertivCo.com I E-mail : [email protected] I Toll free : 1-800-2096070
Vertiv Energy Private Limited I Plot C-20, Rd No.19, Wagle Ind Estate, Thane (W), 400604. India
© 2017 Vertiv Co. All rights reserved.