General EJX430A
Specifications Gauge Pressure Transmitter

GS 01C25E01-01EN [Style: S2]

The high performance gauge pressure transmitter


EJX430A features single crystal silicon resonant
sensor and is suitable to measure liquid, gas, or
steam pressure. The EJX430A outputs a 4 to 20 mA
DC signal corresponding to the measured pressure.
It also features quick response, remote setup and
monitoring via BRAIN or HART communications, and
diagnostics. The multi-sensing technology provides
the advanced diagnostic function to detect such
abnormalities as an impulse line blockage or heat
trace breakage. FOUNDATION Fieldbus and PROFIBUS
PA protocol types are also available.
All EJX series models in their standard configuration,
with the exception of the Fieldbus and PROFIBUS
types, are certified as complying with SIL 2 for safety
requirement.

 STANDARD SPECIFICATIONS
Refer to GS 01C25T02-01EN for Fieldbus
communication type and GS 01C25T04-01EN for
PROFIBUS PA communication type for the items
marked with “◊.” Reference Accuracy of Calibrated Span
(includes the effects of terminal-based linearity,
hysteresis, and repeatability)
□ SPAN AND RANGE LIMITS
Measurement span H
Measurement psi bar kgf/cm2
MPa Reference X ≤ span ±0.04% of Span
Span/Range (/D1) (/D3) (/D4)
accuracy X > span ±(0.005+0.0049 URL/span)% of Span
2.5 to 500 10 to 2000
Span 0.025 to 5 0.025 to 5 X 70 kPa (280 inH2O)
kPa inH2O
H −400 URL
−100 to 500 kPa (2000 inH2O)
Range to 2000 −1 to 5 −1 to 5 (upper range limit)
500 kPa
inH2O
0.0175 to 0.175 to 0.175 to Measurement span A B
Span 2.5 to 500
3.5 35 35
A Reference X ≤ span ±0.04% of Span
−14.5 to
Range −0.1 to 3.5 −1 to 35 −1 to 35 accuracy X > span ±(0.005+0.0035 URL/span)% of Span
500
Span 0.08 to 16 12 to 2300 0.8 to 160 0.8 to 160 X 0.35 MPa (50 psi) 1.6 MPa (230 psi)
B −14.5 to URL
Range −0.1 to 16 −1 to 160 −1 to 160 3.5 MPa (500 psi) 16 MPa (2300 psi)
2300 (upper range limit)

[When /HAC is specified]


□ PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted Measurement span H
parts material code ‘S’ and silicone oil, unless Reference X ≤ span ±0.025% of Span
otherwise mentioned. accuracy X > span ±(0.005+0.0028 URL/Span) % of Span
For Fieldbus and PROFIBUS PA communication X 70 kPa (280 inH2O)
types, use calibrated range instead of span in the
URL
following specifications. (Upper Range Limit)
500 kPa (2000 inH2O)
Specification Conformance
EJX series ensures specification conformance to at
Measurement span A B
least ±3σ.
Reference X ≤ span ±0.025% of Span
accuracy X > span ±(0.010+0.0015 URL/Span) % of Span
X 0.35 MPa (50 psi) 1.6 MPa (230 psi)
URL
3.5 MPa (500 psi) 16 MPa (2300 psi)
(Upper Range Limit)

Yokogawa Electric Corporation GS 01C25E01-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Feb. 2004
Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 35th Edition Dec. 2023
<<Contents>> <<Index>> 2
Ambient Temperature Effects per 28°C (50°F) Damping Time Constant (1st order)
Change Amplifier’s damping time constant is adjustable from
0.00 to 100.00 s by software and added to response
Capsule Effect time.
H ±(0.04% Span + 0.0125% URL) Note: For BRAIN protocol type, when the software
A and B ±(0.04% Span + 0.009% URL) damping is set to less than 0.5 s, communication
may occasionally be unavailble during the
Stability (All normal operating condition) operation, especially while output changes
±0.1% of URL per 15 years dynamically. The default setting of damping
ensures stable communication.
Power Supply Effects(Output signal code D, E
and J) Update Period “◊”
±0.005 % per Volt (from 21.6 to 32 V DC, 350Ω) Pressure: 45 ms
Vibration Effects Zero Adjustment Limits
Amplifier housing code 1 and 3: Zero can be fully elevated or suppressed, within the
Less than 0.1% of URL when tested per the lower and upper range limits of the capsule.
requirements of IEC60770-1 field or pipeline External Zero Adjustment
with high vibration level (10-60 Hz, 0.21 mm External zero is continuously adjustable with
displacement/60-2000 Hz 3 g) 0.01% incremental resolution of span. Re-range
Amplifier housing code 2: can be done locally using the digital indicator with
Less than ±0.1% of URL when tested per the rangesetting switch.
requirements of IEC60770-1 field with general Integral Indicator (LCD display) “◊”
application or pipeline with low vibration level (10-60 5-digit numerical display, 6-digit unit display and bar
Hz 0.15mm displacement /60-500 Hz 2g) graph.
Mounting Position Effects The indicator is configurable to display one or up to
Rotation in diaphragm plane has no effect. Tilting three of the following variables periodically.;
up to 90 degree will cause zero shift up to 0.4 kPa pressure in %, scaled pressure, measured pressure.
(1.6 inH2O) which can be corrected by the zero See also “Factory Setting”.
adjustment. Local Parameter Setting (Output signal code D, E,
Response Time (All capsules) “◊” and J)
90 ms Parameter configuration by the external zero
150 msec for H capsule with Wetted Parts Material adjustment screw and push button (Integral indicator
code H, M, T, A, D, B and W. code E) offers easy and quick setup for parameters
When software damping is set to zero and including of Loop test, Tag number, Unit, LRV, URV, Damping,
dead time of 45 ms (nominal) Output mode (linear/square root), Display out 1, and
Re-range by applying actual pressure (LRV/URV)
□ FUNCTIONAL SPECIFICATIONS and Device Information.
Output “◊” Burst Pressure Limits
Two wire 4 to 20 mA DC output with digital 69 MPa (10,000 psi)
communications, linear or square root programmable. Self Diagnostics
BRAIN or HART FSK protocol are superimposed on CPU failure, hardware failure, configuration error,
the 4 to 20 mA signal. and over-range error for pressure and capsule
Output range: 3.6 mA to 21.6 mA temperature.
Output limits conforming to NAMUR NE43 can be User-configurable process high/low alarm for
pre-set by option code C2 or C3. pressure is also available, and its status can be
Failure Alarm (Output signal code D, E and J) output when optional status output is specified.
Output status at CPU failure and hardware error; Advanced Diagnostics (optional) “◊”
Up-scale: 110%, 21.6 mA DC or more (standard) Applicable for Output signal code E, J and F.
Down-scale: −5%, 3.2 mA DC or less • Impulse line blockage detection
Analog output status at process abnormality (Option The impulse line condition can be calculated and
code /DG6); detected by extracting the fluctuation component
The result of process abnormality detected by the from the static pressure signal.
advanced diagnostic function can be reflected to • Heat trace monitoring
an analog alert status. The following three setting The change of the flange temperature calculated by
modes are available. using the two temperature sensors built in the EJX
enables to detect the heat trace breakage or the
Mode abnormal temperature due to the failure.
Burnout Fall back Off Signal Characterizer (Output signal code D, E
110%, and J)
Standard
21.6mA or more Holds to a User-configurable 10-segment signal characterizer
-2.5%, specified value for 4 to 20 mA output.
/C1
3.6mA or less within the
Normal output
Option -1.25%, output range
/C2
Code 3.8mA or less from 3.6mA to
103.1%, 21.6mA
/C3
20.5mA or more

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 3
Status Output (optional, output signal code D, E Minimum Pressure Limit
and J) See graph below
One transistor contact output (sink type) to output
the status of user configurable high/low alarm for
pressure. 100(14.5) Atmospheric
Contact rating : 30 V DC, 120 mA DC max. pressure
Refer to ‘Terminal Configuration’ and ‘Wiring Example Working
for Analog Output and Status Output.’ pressure
kPa abs
SIL Certification (psi abs)
All the EJX series transmitters except Fieldbus and
Applicable range
PROFIBUS PA communication types are certified in
compliance with the following standards; 10(1.4)
IEC 61508: 2010;
Functional Safety of Electrical/electronic/
programmable electronic related systems; SIL 2
2.7(0.38)
capability for single transmitter use, SIL 3 capability
for dual transmitter use.
Reliability Data different depending on hardware and 1(0.14)
software revision. -40 0 40 80 120
For details, refer to Functional Safety Data Sheet. (-40) (32) (104) (176) (248)
(Document number: TI 01C25A05-01EN or TI Process temperature °C (°F)
01C25A05-21EN for option code SLT ) F01E.ai
The document can be downloaded from the website
of Yokogawa. Figure 1. Working Pressure and Process Temperature
(Website address: https://www.yokogawa.com/
solutions/products-platforms/field-instruments/) Supply & Load Requirements
(Output signal code D, E and J. Optional
□ NORMAL OPERATING CONDITION features or approval codes may affect electrical
(Optional features or approval codes may requirements.)
affect limits.) With 24 V DC supply, up to a 550Ω load can be
used. See graph below.
Ambient Temperature Limits
−40 to 85°C (−40 to 185°F)
−30 to 80°C (−22 to 176°F) with LCD display
Process Temperature Limits 600
−40 to 120°C (−40 to 248°F)
E-10.5
Ambient Humidity Limits R=
External 0.0244 Digital
0 to 100% RH load Communication
Maximum Over Pressure resistance range
BRAIN and HART
Capsule Pressure 250
H and A 16 MPa (2300 psi)
B 25 MPa (3600 psi)*
R (Ω)
*: 24 MPa (3400 psi) for Wetted Parts Material code
H, M, T, A, D, B and W.
Working Pressure Limits (Silicone oil) 25.2 42
10.5 16.6
Maximum Pressure Limits Power supply voltage E (V DC)
F02E.ai

Capsule Pressure
Figure 2. Relationship Between Power Supply
H 500 kPa (2000 inH2O) Voltage and External Load Resistance
A 3.5 MPa (500 psi)
B 16 MPa (2300 psi)

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 4
Supply Voltage “◊” Non-wetted Parts Materials
10.5 to 42 V DC for general use and flameproof type. Bolting
10.5 to 32 V DC for lightning protector B7 carbon steel, 316L SST or 660 SST
(option code /A.)
10.5 to 30 V DC for intrinsically safe, type n, or non- Housing
incendive type. • Low copper cast aluminum alloy
Minimum voltage limited at 16.6 V DC for digital • Low copper cast aluminum alloy with corrosion
communications, BRAIN and HART resistance properties (copper content ≤ 0.03%,
iron content ≤ 0.15%) (optional)
Load (Output signal code D, E and J) • ASTM CF-8M Stainless steel (optional)
0 to 1290Ω for operation
250 to 600Ω for digital communication Coating of housing
[for aluminum housing]
Communication Requirements “◊” Polyester resin powder coating
(Approval codes may affect electrical requirements.) Mint-green paint (Munsell 5.6BG 3.3/2.9 or its
BRAIN equivalent)
Communication distance [for option code /P or /X2]
Up to 2 km (1.25 miles) when using CEV Epoxy and polyurethane resin solvent coating
polyethylene-insulated PVC-sheathed cables. Degrees of protection
Communication distance varies depending on type of IP66/IP67, Type 4X
cable used. Cover O-rings
Load capacitance Buna-N, fluoro-rubber (optional)
0.22 µF or less Name plate and tag
Load inductance 316 SST
3.3 mH or less Fill fluid
Input impedance of communicating device Silicone, Fluorinated oil (optional)
10 kΩ or more at 2.4 kHz. Weight
EMC Conformity Standards [Installation code 7, 8 and 9]
EN 61326-1 Class A, Table2 2.8 kg(6.2 lb) for wetted parts material code S and
EN 61326-2-3 L, without integral indicator, mounting bracket, and
EN 61326-2-5 (for fieldbus) process connector.
European Pressure Equipment Directive Add 1.5 kg (3.3lb) for Amplifier housing code 2.
2014/68/EU Connections
Sound Engineering Practice Refer to “MODEL AND SUFFIX CODES.”
EU RoHS Directive Process connection of cover flange: IEC61518
EN IEC 63000
Safety Requirement Standards < Related Instruments>
EN 61010-1, C22.2 No.61010-1 FieldMate Versatile Device Management Wizard:
• Installation category: I Refer to GS 01R01A01-01E.
(Anticipated transient overvoltage 330 V) BRAIN TERMINAL: Refer to GS 01C00A11-00E
• Pollution degree: 2 Power Distributor: Refer to GS 01B04T01-02E or
• Indoor/Outdoor use GS 01B04T02-02E

□ PHYSICAL SPECIFICATIONS < Reference >


1. is a registered trademark of Yokogawa
Wetted Parts Materials
Electric Corporation.
Diaphragm, cover flange, process connector, 2. FieldMate; Trademark of Yokogawa Electric
capsule gasket, and vent/drain plug Corporation.
Refer to “MODEL AND SUFFIX CODES.” 3. Teflon; Trademark of E.I. DuPont de Nemours &
Process connector gasket Co.
PTFE Teflon 4. Hastelloy; Trademark of Haynes International Inc.
Fluorinated rubber for option code N2 and N3 5. HART®: Registered trademark of the FieldComm
Group.
6. FOUNDATION Fieldbus; Trademark of the
FieldComm Group.
7. PROFIBUS; Registered trademark of Profibus
Nutzerorganisation e.v., Karlsruhe, Germany.
Other company names and product names used in
this material are registered trademarks or trademarks
of their respective owners.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 5
 MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJX430A ............................... Gauge pressure transmitter
Output signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5 protocol)
-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5 / HART 7 protocol)
(Refer to GS 01C25T01-01EN)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C25T02-01EN)
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
GS 01C25T04-01EN)
Measurement H . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 to 500 kPa (10 to 2000 inH2O)
span (capsule) A . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0175 to 3.5 MPa (2.5 to 500 psi)
B . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.08 to 16 MPa (12 to 2300 psi)
Wetted parts  . . . . . . . . . . . . . . . . . . . . . . . . . Refer to “Wetted Parts Material” Table.
material *1
Process connections 0 . . . . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
See the table in the next 1 . . . . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
page for the codes for a 2 . . . . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
diaphragm seal system. 3 . . . . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material J . . . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . . . 660 SST
Installation -3 . . . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection down side
-7 . . . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection down side
-8 . . . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . . . . . . Bottom Process Connection, left side high pressure*2
-U . . . . . . . . . . . . . . . . . Universal flange*2
Amplifier housing 1 . . . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties *3
2 . . . . . . . . . . . . . . ASTM CF-8M stainless steel *4
Electrical connection 0 . . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . . G1/2 female, two electrical connections and a blind plug *5
7 . . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug *5
9 . . . . . . . . . . . M20 female, two electrical connections and a blind plug *5
A . . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . . Digital indicator *6
E . . . . . . . . Digital indicator with the range setting switch (push button) *7
► N . . . . . . . . (None)
Mounting bracket ► B . . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
P . . . . . . 316 SST 2-inch pipe mounting, position adjustable L type (for vertical piping)*8
N . . . . . . (None)
Optional Codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*2: Applicable only for Wetted parts material code S.
*3: Not applicable for electrical connection code 0, 5, 7, 9 and A. Content rate of copper in the material is 0.03% or less and
content rate of iron is 0.15% or less.
*4: Not applicable for electrical connection code 0, 5, 7 and 9.
*5: Material of a blind plug; aluminum alloy for code 5 and 9, and SUS304 for code 7.
*6: Not applicable for output signal code G.
*7: Not applicable for output signal code F.
*8: For position adjustable bracket, refer to SD 01C25B14-01EN.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
<<Contents>> <<Index>> 6
Table. Wetted Parts Materials
Wetted parts Cover flange and process
Capsule Capsule gasket Vent/Drain plug
material code connector
Hastelloy C-276 (Diaphragm)
*2
S# ASTM CF-8M *1*8 Teflon-coated 316L SST 316 SST
F316L SST, 316L SST (Others)
Hastelloy C-276 *2 (Diaphragm)
L# ASTM CF-3M *7*8 Teflon-coated 316L SST 316L SST
F316L SST, 316L SST (Others)
H# ASTM CF-8M *1*8 Hastelloy C-276 *2 PTFE Teflon 316 SST
M# ASTM CF-8M *1*8 Monel PTFE Teflon 316 SST
T ASTM CF-8M *1*8 Tantalum PTFE Teflon 316 SST
A# Hastelloy C-276 equivalent *3 Hastelloy C-276 *2 PTFE Teflon Hastelloy C-276 *2
D Hastelloy C-276 equivalent *3 Tantalum PTFE Teflon Hastelloy C-276 *2
B# Monel equivalent *4 Monel PTFE Teflon Monel
W# Super Duplex SST equivalent *5 Hastelloy C-276 *2 PTFE Teflon Super Duplex SST *6
*1: Cast version of 316 SST. Equivalent to SCS14A.
*2: Hastelloy C-276 or ASTM N10276.
*3: Indicated material is equivalent to ASTM CW-12MW.
*4: Indicated material is equivalent to ASTM M35-2.
*5: Indicated material is equivalent to ASTM A995 Grade5A.
*6: ASTM S32750 or EN 10272 1.4410.
*7: Cast version of 316L SST. Equivalent to SCS16A.
*8: Intergranular corrosion test passed according to ASTM A262 Practice E.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO 15156.
Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.

[Process Connections Code for Diaphragm Seal System]


The table below shows the codes dedicated for the combination with a diaphragm seal system. They are only
available when the transmitter is ordered in combination with a diaphragm seal system. Please also refer to GS
01C25W01-01EN.

Process Connections Code High Pressure Side Low Pressure Side


B With C80F, C82F or C70S diaphragm seal Open to atmosphere
With C80F or C82F diaphragm seal for high
G Open to atmosphere
vacuum use
C80F, C82F, and C70S stand for C80FW or C80FE remote mount flanged diaphragm seal, C82FA inner diaphragm
adapter connection seal, or C82FD inner diaphragm flanged seal, and C70SW or C70SE remote mount hygienic diaphragm seal
respectively.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 7
 OPTIONAL SPECIFICATIONS (For Explosion Protected type) “◊”
For other agency approvals and marine approvals, please refer to GS 01C25A20-01EN.
Please select appropriate equipment in accordance with the laws and regulations of the relevant country/region, when
it is used in a location where explosive atmospheres may be present.

Item Description Code


Factory Mutual FM Explosionproof Approval *1
(FM) Applicable Standard: FM3600, FM3615, FM3810, NEMA 250, ANSI/UL 61010-1, ANSI/UL 61010-2-30
Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1,
FF1
Groups E, F and G, in Hazardous locations, indoors and outdoors (Enclosure: Type 4X)
“FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Temperature class: T6, Amb. Temp.: –40 to 60°C (–40 to 140°F)
FM Intrinsically safe Approval *1*2
Applicable Standard: ‌FM 3600, FM 3610, FM 3611, FM 3810, ANSI/ISA-60079-0, ANSI/ISA-60079-11,
ANSI/ISA-61010-1, NEMA 250
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2, FS1
Groups F & G, Class I, Zone 2, Group IIC, in Hazardous Locations
Enclosure: Type 4X, Temp. Class: T4, Amb. Temp.: –60 to 60°C (–75 to 140°F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G] Vmax=30 V, Imax=200 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
[Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
Combined FF1 and FS1 *1*2 FU1
ATEX ATEX Flameproof Approval *1
Applicable Standard: EN IEC 60079-0, EN 60079-1, EN 60079-31
Certificate: KEMA 07ATEX0109 X
II 2 G Ex db IIC T6...T4 Gb, II 2 D Ex tb IIIC T85°C Db
Degree of protection: IP66/IP67
KF22
Amb. Temp. (Tamb) for gas-proof :
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Process Temp. for gas-proof (Tp):
T4; –50 to 120°C (–58 to 248°F), T5; –50 to 100°C (–58 to 212°F), T6; –50 to 85°C (–58 to 185°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: –30 to 85°C) *3
ATEX Intrinsically safe Approval *1*2
Applicable Standard: EN IEC 60079-0, EN 60079-11
Certificate: DEKRA 11ATEX0228 X
II 1 G Ex ia IIC T4 Ga, II 2 D Ex ia IIIC T85°C T100°C T120°C Db
Degree of protection: IP66/IP67
KS21
Amb. Temp. (Tamb) for EPL Ga: –50 to 60°C (–58 to 140°F)
Maximum Process Temp. (Tp) for EPL Ga:120°C
Electrical data: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 µH
Amb. Temp. for EPL Db: –30 to 60°C *3
Max. surface Temp. for EPL Db: T85°C (Tp: 80°C), T100°C (Tp: 100°C), T120°C (Tp: 120°C)
Multiple types of protection (KF22, KS21 or Intrinsically safe Ex ic) *1*2
Applicable Standard: EN IEC 60079-0, EN 60079-11
KU22
II 3 G Ex ic IIC T4 Gc, Amb. Temp.: –30 to 60°C (–22 to 140°F) *3
Ui=30 V, Ci=27.6 nF, Li=0 μH

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 8
Item Description Code
Canadian CSA Explosionproof Approval *1
Standards Certificate: 2014354
Association Applicable Standard: C22.2 No. 25, C22.2 No. 30, CAN/CSA-C22.2 No. 94,
(CSA) CAN/CSA-C22.2 No. 61010-1, CAN/CSA-C22.2 No. 61010-2-030, CAN/CSA-C22.2 No. 60079-0,
CAN/CSA-C22.2 No. 60079-1, CAN/CSA-C22.2 No. 60529
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: Type 4X,
Temp. Code: T6...T4 CF1
Ex d IIC T6...T4 Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *3
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA-12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *1*2
Certificate: 1606623
[For Division System]
Applicable Standard: C22.2 No.0, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1,
C22.2 No.61010-2-030
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.: –50 to 60°C(–58 to 140°F) *3
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0 µH
[Nonincendive] Vmax=30V, Ci=10nF, Li=0 µH
CS1
[For Zone System]
Applicable Standard: CAN/CSA-C22.2 60079-0, CAN/CSA-E60079-11, CAN/CSA-E60079-15,
CAN/CSA-C22.2 No.60529
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *3, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0 µH
[Ex nL] Ui=30V, Ci=10nF, Li=0 µH
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA-12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*2 CU1

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Dec. 29, 2023-00
<<Contents>> <<Index>> 9
Item Description Code
IECEx IECEx Flameproof Approval *1
Scheme Applicable Standard: IEC 60079-0, IEC 60079-1, IEC 60079-31
Certificate: IECEx DEK 14.0046X
Enclosure: IP66/IP67
Ex db IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Amb. Temp. (Tamb) for gas-proof : SF22
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Process Temp. for gas-proof (Tp):
T4; –50 to 120°C (–58 to 248°F), T5; –50 to 100°C (–58 to 212°F),
T6; –50 to 85°C (–58 to 185°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: –30 to 85°C) *3
IECEx Intrinsically safe and SF22 *1*2
Intrinsically safe Ex ia
Certificate: IECEx DEK 11.0081X
Applicable Standard: IEC 60079-0, IEC 60079-11
Ex ia IIC T4 Ga Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F), Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V, Ii=200mA, Pi=0.9W, Ci=27.6nF, Li=0 μH
Intrinsically safe Ex ic SU22
Certificate: IECEx DEK 13.0061X
Applicable Standard: IEC 60079-0, IEC 60079-11
Ex ic IIC T4 Gc IP code: IP66
Amb. Temp.: –30 to 60°C(–22 to 140°F) *3, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V,Ci=27.6 nF, Li=0 μH
Flameproof
Refer to SF22
Combination of Combination of KU22, FU1 and CU1 *1*2*4
V1U1
Approval
*1: Applicable for Electrical connection code 2, 4, 7, 9, C and D.
*2: Not applicable for option code /AL.
*3: Lower limit of temperature is –15°C (5°F) when /HE is specified.
*4: When this option code is specified, a wired tag plate (as of N4 option) shall be used for tag number.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Feb. 1, 2022-00
<<Contents>> <<Index>> 10
 OPTIONAL SPECIFICATIONS
Item Description Code
High Accuracy type*23*29 Reference accuracy: ±0.025% of Span HAC
Painting Color change Amplifier cover only*9 P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating*1 X2
316 SST exterior parts 316 SST zero-adjustment screw and setscrews*10 HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C (5°F) HE
Lightning protector Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically safe type,
9 to 32 V DC for Fieldbus communication type.)
A
Allowable current: Max. 6000 A ( 1×40 µs ), Repeating 1000 A ( 1×40 µs ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output*2 Transistor output (sink type)
AL
Contact rating: 30 V DC, 120 mA DC(max ) Low level: 0 to 2 V DC
Oil-prohibited use*3*29 Degrease cleansing treatment K1
Degrease cleansing treatment and fluorinated oilfilled capsule.
K2
Operating temperature −20 to 80°C (−4 to 176°F)
Degrease cleansing treatment K41
Degrease cleansing treatment and fluorinated oilfilled With certificates
capsule. K42
Operating temperature −20 to 80°C (−4 to 176°F)
Oil-prohibited use with Degrease cleansing and dehydrating treatment K5
dehydrating treatment*3*29 Degrease cleansing and dehydrating treatment with fluorinated oilfilled capsule.
K6
Operating temperature −20 to 80°C (−4 to 176°F)
Degrease cleansing and dehydrating treatment K45
Degrease cleansing and dehydrating treatment with With certificates
fluorinated oilfilled capsule. K46
Operating temperature −20 to 80°C (−4 to 176°F)
Capsule fill fluid*29 Flourinated oil filled in capsule
K3
Operating temperature −20 to 80°C (−4 to 176°F)
Calibration units*4 P calibration (psi unit) D1
bar calibration (bar unit) (See Table for Span and Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Plug option*24*25*29 Long vent*5: Total length: 119 mm (standard: 34 mm); Total length when combining with
U1
optional code K1, K2, K5, and K6: 130 mm. Material: 316 SST U1.
Without vent and drain plugs UN
Gold-plated capsule gasket*11*29 Gold-plated 316L SST capsule gasket. Without drain and vent plugs. GS
Gold-plated diaphragm*12*29 Surface of isolating diaphragms are gold plated, effective Gold plate thickness: 3 μm A1
for hydrogen permeation. Gold plate thickness: 10 μm A2
Output limits and failure Failure alarm down-scale : Output status at CPU failure and hardware error is −5%, 3.2mA DC
C1
operation*6 or less.
Failure alarm down-scale: Output status at CPU
NAMUR NE43 Compliant C2
failure and hardware error is −5%, 3.2 mA DC or less.
Output signal limits:
3.8 mA to 20.5 mA Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Body option*7*29 Right side high pressure, without drain and vent plugs N1
Terminal N1 and Process connection, based on IEC61518 with female thread on both sides of cover
Side N2
flange, with blind kidney flanges on back
L H N2, and Material certificate for cover flange, diaphragm, capsule body, and blind kidney flange N3
F03E.ai

Wired tag plate 316 SST tag plate wired onto transmitter N4
Data configuration at factory*8 Data configuration for HART
Software damping, Descriptor, Message CA
communication type
Data configuration for BRAIN
Software damping CB
communication type
Data configuration for HART Software damping, Descriptor, Message,
CJ
communication type External zero adjustment prohibition setting
Data configuration for BRAIN Software damping, External zero adjustment
CK
communication type prohibition setting
Advanced diagnostics*13 Multi-sensing process monitoring
• Impulse line blockage detection *14 DG6
• Heat trace monitoring

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
<<Contents>> <<Index>> 11
Material certificate*15*29 Cover flange *16 M01
Cover flange, Process connector *17 M11
Cover flange, Diaphragm, Capsule body*16*30 MA1
Cover flange, Process connector, Diaphragm, Capsule body*17*27 MC1
Cover flange, Bolt and Nut for cover flange, Diaphragm, Capsule body, Vent and Drain plugs,
MG1
Vent screw, Capsule gasket*16*24*26
Cover flange, Process connector, Bolt and nut for cover flange, Bolt for process connector,
MH1
Diaphragm, Capsule body, Vent and Drain plug, Vent screw, Capsule gasket*17*24*26
Calibration certificate Text, Traceability L4
Text, Traceability, Primary standards list L5
Text, Traceability, Primary standards list, Calibration equipment list L6
Text, Traceability, Primary standards list, Calibration equipment list, Calibration equipment
L9
certificate
Pressure test/ Test Pressure: 500 kPa (2000 inH2O)*18 T11
Leak test certificate*22*29 Nitrogen Gas*21
Test Pressure: 3.5 MPa (500 psi)*19 T01
Retention time: one minute
Test Pressure: 16 MPa (2300 psi)*20 T12
Parameter list*31 List of setting and adjustment parameters YP
Bug screen*32 A bug screen is installed to the hole open to the atmosphere on the low pressure side cover flange BS
Additional blind plug*33 Additional blind plug is attached to the conduit connection on both sides for storing transmitter PP
Functional safety(SIL)*28 Low temperature expansion of functional safety Amb.Temp.: −55 to 85°C SLT
*1: Not applicable with color change option.
*2: When this option code is specified, check terminals are not available. Not applicable for output signal code F and G.
*3: Applicable for wetted parts material code S, M, H and T.
*4: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*5: Applicable for vertical impulse piping type (installation code 3 or 7) and wetted parts material code S, M, H and T.
*6: Applicable for output signal codes D, E and J. The hardware error indicates faulty amplifier or capsule.
*7: Applicable for wetted parts material code S, M, H and T.; process connection codes 3, 4, and 5; installation code 9; and
mounting bracket code N. Process connection faces on the other side of zero adjustment screw.
*8: Also see ‘Ordering Information’.
*9: Not applicable for amplifier housing code 2 and 3.
*10: 316 or 316L SST. The specification is included in amplifier code 2.
*11: Applicable for wetted parts material code S; process connection code 0 and 5; and installation code 8 and 9.
Not applicable for option code U1, N2, N3 and M11. No PTFE is used for wetted parts.
*12: Applicable for wetted parts material code S or L. /A2 is not applicable with FM approval.
*13: Applicable only for output signal code E and J.
*14: The change of pressure fluctuation is monitored and then detects the impulse line blockage.
See TI 01C25A31-01E for detailed technical information required for using this function.
*15: Material traceability certification, per EN 10204 3.1B.
*16: Applicable for process connections code 0 and 5.
*17: Applicable for process connections code 1, 2, 3, and 4.
*18: Applicable for capsule code H.
*19: Applicable for capsule code A.
*20: Applicable for capsule code B.
*21: Dry nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, K6, K41, K42, K45, and K46).
*22: The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
*23: Refer to “PERFORMANCE SPECIFICATIONS.” Applicable for wetted parts material code S or L. Not applicable for option
code /A1, /A2, /K2, /K3, /K6, /K42 and /K46.
*24: Not applicable with plug option code UN.
*25: Not applicable for installation code -U.
*26: Not applicable with option code N1, N2, N3 and GS.
*27: Applicable for option code UN and N1.
*28: Not applicable for output signal code F, G, and process connections code for diaphragm seal system.
*29: Not applicable with process connections code for diaphragm seal system B and G.
*30: Applicable for option code UN, N1, and GS.
*31: Applicable only for output signal code D, E and J.
*32: Applicable for process connection codes 0, 1, 2, 3, 4, 5, C, D, Q, and R.
*33: Not applicable for electrical connection codes 0, 2, and 4.

 OPTIONAL SPECIFICATIONS (FOR DIAPHRAGM SEAL SYSTEM)


The table below shows the code dedicated for the combination with a diaphragm seal system. It is only available when
the transmitter is ordered in combination with a diaphragm seal system. Please also refer to GS 01C25W01-01EN

Item Descriptions Code


Capsule fill fluid Fluorinated oil filled in capsule K13
Operating temperature −20 to 80°C (−4 to 176°F)
Material certificate Bolt and nut for cover flange M51

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
<<Contents>> <<Index>> 12
 DIMENSIONS
Unit: mm (approx.inch)

● Vertical Impulse Piping Type


Wetted Parts Material Code: S, L

Electrical connection
Process connector downside for code 5, 9, A, and D.
(Installation code 7)

6(0.24)
242(9.53) 110(4.33)
175(6.89)

(2.13)
12 39

54
97 129(5.08) 2-inch pipe
(3.82) (0.47) (1.54)
(O.D. 60.5 mm)
Mounting bracket External indicator Process connector upside
(L-type,optional) Conduit connection (Installation code 6)
(2.05)

(optional)
52

Integral indicator Process connection


Vent/Drain
(optional) plugs*5
97(3.82)
223(8.78)

67(2.64)

(1.61)
ø78(3.07)

138(5.43)*2
95(3.74)

ø70(2.76)

41
(1.61)
67(2.64)

223(8.78)
41

97(3.82)
Process
Conduit connector
Process connection connection*7 (optional)
27
Zero adjustment High Low

(2.05)
pressure (1.06) pressure

52
Ground terminal side*1 side*1
Open to atmosphere*6
ø10(0.39) F04E.ai

● Horizontal Impulse Piping Type (Installation code 9)


Wetted Parts Material Code: S, L

External indicator 89(3.50) 67 Conduit connection*7 Zero 110(4.33)


Conduit connection (2.64) adjustment 12 39
Integral indicator
(optional) 95(3.74) (optional) (0.47) (1.54)
54
ø78(3.07)

(2.76)

(2.13)
ø70

6
175(6.89)
145(5.71)

129(5.08)

(0.24)
Vent plug, Ground
Dran plug*3*5 terminal

Electrical connection Vent plug*3*5


for code 5, 9, A, and D. Drain plug*3*5 Open to atmosphere*6
124(4.88)

ø5(0.20)
41 Process connection 27(1.06)
(1.61) High
Low
Process connector pressure
(1.63)

115(4.53) pressure
41.3

side
(optional) side
(1.85)
47

Mounting bracket 2-inch pipe


(Flat-type,optional) (O.D. 60.5 mm)

65*2
(2.56) F06E.ai

*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When option code K1, K2, K5, K6, K41, K42, K45, or K46 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: Not available when option code GS is specified.
*4: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit
connection.
*5: When option code UN is specified, Vent/Drain holes and plugs are not applicable.
*6: When option code BS is selected, the hole open to atmosphere on the cover flange of low pressure side is threaded and a
bug screen is attached in it.
*7: When option code PP is selected, a blind plug is attached to the conduit connection on both sides.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
<<Contents>> <<Index>> 13
Unit: mm (approx.inch)

● Vertical Impulse Piping Type


Wetted Parts Material Code: H, M, T, A, B, D, W

Electrical connection
for code 5, 9, A, and D.
Process connector downside

6(0.24)
(Installation code 7)
256(10.10) 110(4.33)
194(7.64)

(2.13)
12*5 39

54
97 143(5.63) 2-inch pipe
(3.82) (0.47) (1.54)
(O.D. 60.5 mm)
External indicator
Mounting bracket Conduit connection Process connector upside
(2.05)

(L-type,optional) (optional)
52

Process connection (Installation code 6)


Integral indicator Vent/Drain
(optional) plugs*4
102(4.02)
234(9.21)

72(2.83)

(1.81)
148(5.83)*2
ø78(3.07)

46
(3.74)

(2.76)
ø70
95
(1.81)

234(9.21)
72(2.83)
46

102(4.02)
Conduit
connection*7 High 27 Low
Process connection pressure pressure
Zero adjustment side*1 (1.06)

(2.05)
Ground terminal side*1

52
Process connector
(optional) Open to atmosphere*6
ø10(0.39)
F06E.ai

● Horizontal Impulse Piping Type (Installation code 9)


Wetted Parts Material Code: H, M, T, A, B, D, W

Conduit connection*7
External indicator 94(3.70) 72(2.83) 110(4.33)
Conduit connection Zero
(optional) 95(3.75) adjustment 12*5 39
Integral indicator
(optional) (0.47) (1.54)
54
ø78(3.07)

(2.13)
6
(2.76)
ø70

(0.24)
159(6.26)

143(5.63)
194(7.64)

Ground terminal
Electrical connection
for code 5, 9, A, and D. Vent plug*4

Drain plug*4 Open to atmosphere*6


124(4.88)

46 Process connection ø5(0.20)


(1.81) 54
Process connector (2.13)
125(4.92)
(optional)
(1.63)

2-inch pipe
41.3

(1.85)

(O.D. 60.5 mm)


47

Mounting bracket
(Flat-type,optional)
67*2
(2.64) F07E.ai

*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, K6, K41, K42, K45, or K46 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.
*4: When option code UN is specified, Vent/Drain holes and plugs are not applicable.
*5: When measurement span code H is selected, 9 mm(0.35 inch) for installation code 6, 7 and 9, or 15 mm(0.59 inch) for
installation code 2, 3 and 8.
*6: When option code BS is selected, The hole open to atmosphere on the cover flange of low pressure side is threaded and a bug
screen is attached in it.
*7: When option code PP is selected, a blind plug is attached to the conduit connection on both sides.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
<<Contents>> <<Index>> 14
Unit: mm (approx.inch)

● Universal Flange (Installation code U)


58 67 110(4.33)
(2.28) (2.64) Zero
External indicator adjustment
Conduit connection Conduit connection*3 12 39
95(3.74)
(optional) Integral indicator (0.47) (1.54)
54 (optional)

ø78(3.07)
(2.13)
6

(2.76)
ø70
145(5.71)

(0.24)

129(5.08)
175(6.89)
Ground terminal

Electrical connection
for code 5, 9, A, and D.
Open to atmosphere
Drain plug Process connection ø10(0.39)
41 65*1 Open to atmosphere
Vent plug (1.61) (2.56)
(1.63)

High Low ø5(0.2)


41.3

115(4.53) pressure pressure


Process connector side side
Drain plug (optional)
F08E.ai

*1: When Option code K1, K2, K5, K6, K41, K42, K45, or K46 is selected, add 15 mm(0.59 inch) to the value.
*2: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.
*3: When option code PP is selected, a blind plug is attached to the conduit connection on both sides.

● Bottom Process Connection (Installation code B)


54
(2.13) 95(3.74) 188(7.40)
6
73 Integral indicator
(0.24) Zero 110(4.33)
(2.87) (optional)
adjustment
12 39
Conduit connection*5
(0.47) (1.54)
Electrical connection
ø78(3.07)

for code 5, 9, A, and D. (2.76)


ø70

109(4.29)
159(6.26)

Extenal indicator
Conduit connection
(optional)
Ground terminal

Vent plug*3
High Low
(2.36)

Mounting bracket*1 pressure pressure


60

(optional) side side

Process connector
2-inch pipe 27
(optional)
(O.D. 60.5 mm) (1.06) Open to
Process connection atmosphere*4
65*6 129 ø10(0.39)
(2.56) (5.08)
41.3
(1.63) F09E.ai

*1: A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe.
*2: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.
*3: When option code UN is specified, Vent holes and plugs are not applicable.
*4: When option code BS is selected, The hole open to atmosphere on the cover flange of low pressure side is threaded and a bug
screen is attached in it.
*5: When option code PP is selected, a blind plug is attached to the conduit connection on both sides.
*6: When option code K1, K2, K5, K6, K41, K42, K45, or K46 is selected, add 15 mm(0.59 inch) to the value in the figure.

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
<<Contents>> <<Index>> 15

● Terminal Configuration ● Terminal Wiring


+ 1
Power supply and output terminals
SUPPLY – 2

CHECK + 3 External indicator (ammeter) terminals*1*2


– 2
or or
+ 3 Status contact output terminals*2
ALARM – 2 (when /AL is specified)
Ground terminal
*1: When using an external indicator or check meter, the internal
resistance must be 10 Ω or less. A check meter or indicator
cannot be connected when /AL option is specified.
Terminal 1 Terminal 3 *2: Not available for FOUNDATION Fieldbus and PROFIBUS PA
Terminal 2 communication types. F10E.ai

● Wiring Example for Analog Output and Status Output

Connection Description
Analog output EJX electrical terminal
Distributor

+ + 24V DC
SUPPLY
– 250Ω
*1
CHECK A *1: Either A or + –

Analog and EJX electrical terminal Distributor


status output Shielded cable
+ 24V DC
(when /AL is specified) SUPPLY +

– – 250Ω
If shield cable is not
*1
used, communication ALARM A
is not possible. *1: Either A or +
Magnetic
External power supply valve
30V DC, 120mA max

Use two-wire separately shielded cables.


AC power supply
F11E.ai

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Nov. 7, 2016-00
<<Contents>> <<Index>> 16

< Ordering Information > “◊” < Factory Setting > “◊”
Specify the following when ordering
Tag number As specified in order
For output signal code –J, refer to GS 01C25T01-
01EN. Software
‘2.00 s’ or as specified in order
damping *1
1. Model, suffix codes, and option codes
Calibration range
2. Calibration range and units lower range value
As specified in order
1) Calibration range can be specified with range
Calibration range
value specifications up to 5 digits (excluding upper range As specified in order
any decimal point) for low or high range limits value
within the range of -32000 to 32000. When
Selected from mmH2O, mmH2O(68°F),
reverse range is designated, specify Lower mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
Range Value(LRV) as greater than Upper Range Calibration range kPa, MPa, mbar, bar, gf/cm2,
Value(URV.) units kgf/cm2, inH2O, inH2O(68°F), inHg, ftH2O,
2) Specify only one unit from the table, ‘Factory ftH2O(68°F) or psi. (Only one unit can be
Settings’ when shipped.’ specified)
3. Display scale and units (for transmitters equipped Designated value specified in order.
Display setting
with integral indicator only) (%, or user scaled value.)
Specify either 0 to 100 % or engineering unit scale
and ‘Range and Unit’ for engineering units scale: *1: To specify this item at factory, option code /CA,
/CB, /CJ or /CK is required.
Scale range can be specified with range limit
*2: Not available for HART protocol type.
specifications up to 5 digits (excluding any decimal
point) for low or high range limits within the range
of -32000 to 32000. The unit display consists of < Material Cross Reference >
6-digit, therefore, if the specified unit is longer than
ASTM JIS
7 characters excluding ‘/’, the first 6 characters will
be displayed on the unit display. 316 SUS316
4. Tag Number (if required) F316 SUSF316
Specified characters (up to 16 characters for 316L SUS316L
BRAIN, 22 characters for HART, or 16 characters F316L SUSF316L
for /N4 tag) are engraved on the stainless steel tag 304 SUS304
plate fixed on the housing. F304 SUSF304
5. SOFTWARE TAG (for HART only. If required)
660 SUH660
Specified characters (up to 32 characters) are set
as “Tag” (the first 8 characters) and “Long tag”*1 B7 SNB7
(32 characters) in the amplifier memory. Use CF-8M SCS14A
alphanumeric capital letters.
When the “SOFTWARE TAG” is not specified,
<Information on EU WEEE Directive>
specified “TAG NO” is set as “Tag” (the first 8
EU WEEE (Waste Electrical and Electronic Equipment)
characters) and “Long tag”*1 (22 characters) in the
Directive is only valid in the EU.
amplifier memory.
*1: applicable only when HART 7 is selected. This instrument is intended to be sold and used only
6. Other factory configurations (if required) Specifying as a part of equipment which is excluded from WEEE
option code /CA, /CB, /CJ or /CK will allow further Directive, such as large-scale stationary industrial
configuration at factory. Following are configurable tools, a large-scale fixed installation and so on, and,
items and setting range. therefore, subjected to the exclusion from the scope
[/CA, /CJ : For HART communication type] of the WEEE Directive. The instrument should be
1) Descriptor (up to 16 characters) disposed of in accordance with local and national
2) Message (up to 30 characters) legislation/regulations.
3) Software damping in second (0.00 to 100.00)
[/CB, /CK : For BRAIN communication type]
1) Software damping in second (0.00 to 100.00)

All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation GS 01C25E01-01EN Jan. 31, 2023-00
Subject to change without notice.