TY4235
TY4235
TY4235
www.tyco-fire.com
Contacts
NOTICE Data
The TYCO Series DS-8 Dry-Type Sprin-
klers described herein must be installed Approvals
and maintained in compliance with this UL and C-UL Listed
document, as well as with the applica- Note: For more information, see Table A and
ble standards of the NATIONAL FIRE Table B.
PROTECTION ASSOCIATION (NFPA), Maximum Working Pressure
in addition to the standards of any other 175 psi (12,1 bar)
authorities having jurisdiction. Failure
to do so may impair the performance Inlet Thread Connections
of these devices. 1 in. NPT
ISO 7-R 1
The owner is responsible for main-
docs.jci.com/tycofire/tfp513 Discharge Coefficient
taining their fire protection system
and devices in proper operating con- K=8.0 gpm/psi½ (115,2 lpm/bar½)
Number (SIN)
Compression Screw �����������������������������������Brass
DS-8 Standard Response (5 mm bulb) Deflector ���������������������������������������������������Bronze
sprinklers, see technical data sheet Frame ���������������������������������������������������������Brass
TFP503. TY4235 ���������������������������������Pendent Guide Tube ���������������������������������� Stainless Steel
TY4335 ���������������Horizontal Sidewall Water Tube ���������������������������������� Stainless Steel
Spring. . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Sealing Assembly. . Beryllium Nickel w/TEFLON
Escutcheon. . . . . . Brass Plated, Chrome Plated
Polyester, or Stainless Steel
TABLE B
SERIES DS-8 DRY-TYPE SPRINKLERS, 8.0K, QUICK RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP513
Page 3 of 8
INLET
CASING BAND WRENCH
FLAT
GUIDE WATER
TUBE TUBE PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
3 mm BULB BULB
WRENCHING AREA
SEAT
FIGURE 3
W-TYPE 7
FRAME WRENCH
VENT HOLE
Temperatures for
COMPRESSION Heated Area(1)
SCREW DEFLECTOR Ambient
Temperature 40°F 50°F 60°F
FIGURE 1 Exposed to (4°C) (10°C) (16°C)
SERIES DS-8 PENDENT DRY-TYPE SPRINKLER, 8.0K, Discharge
QUICK RESPONSE ASSEMBLY End of Minimum Exposed
Sprinkler Barrel Length(2),
in.
(mm)
INLET YOKE INLET WATER CASING BULB VENT DEFLECTOR
BAND TUBE SEAT HOLE 40°F 0 0 0
(4°C)
30°F 0 0 0
(-1°C)
20°F 4 0 0
(-7°C) (100)
10°F 8 1 0
(-12°C) (200) (25)
0°F 12 3 0
PLUG WITH PLUG GUIDE FRAME 3 mm COMPRESSION (-18°C) (305) (75)
SEALING SPRING TUBE BULB SCREW -10°F 14 4 1
ASSEMBLY (-23°C) (355) (100) (25)
FIGURE 2 -20°F 14 6 3
SERIES DS-8 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER, 8.0K, (-29°C) (355) (150) (75)
QUICK RESPONSE ASSEMBLY
-30°F 16 8 4
(-34°C) (405) (200) (100)
Operation The glass bulb contains a fluid that
expands when exposed to heat. When -40°F 18 8 4
When TYCO Series DS-8 8.0K Pendent the rated temperature is reached, the (-40°C) (455) (200) (100)
and Horizontal Sidewall, Quick fluid expands sufficiently to shatter -50°F 20 10 6
Response, Standard Coverage Dry- the glass bulb, and the bulb seat is (-46°C) (510) (255) (150)
Type Sprinklers are in service, water is released.
-60°F 20 10 6
prevented from entering the assembly Once the bulb seat is released, the (-51°C) (510) (255) (150)
by the plug with sealing assembly as compression holding the sealing
shown in Figure 1 and Figure 2 in the assembly is released. The spring is Notes:
1. For protected area temperatures that occur
inlet of the sprinkler. then able to flip off to the side and out between values listed above, use the next cooler
of the waterway. This action pushes the temperature.
water tube as well as the guide tube 2. These lengths are inclusive of wind velocities up
to 30 mph (18,6 kph).
outward. This action allows the sprin-
kler to activate and water to flow. TABLE C
EXPOSED SPRINKLER BARRELS
IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED
LENGTHS
TFP513
Page 4 of 8
STRAP TIES
DS-8
(ENDS ON
SHOWN WITH
OPPOSING
STANDARD
SIDES OF
ESCUTCHEON
FIGURE 13 BOOT)
FIGURE 12 SPRINKLER FITTING FIGURE 16
EXPOSURE LENGTH UNHEATED AREA MODEL DSB-2 DRY SPRINKLER
BOOT WITH HORIZONTAL
STRAP TIES SIDEWALL SERIES
(ENDS ON DS-8 DRY-TYPE SPRINKLER
TO WET SIDE
SYSTEM OUTLET OPPOSING
PLUGGED
SIDES OF
BOOT) Installation
HEATED TYCO Series DS-8 8.0K Pendent and
DSB-2 BOOT
AREA Horizontal Sidewall, Quick Response,
ADHESIVE Standard Coverage Dry-Type Sprin-
SPRINKLER klers must be installed in accordance
DSB-2 1-3/4" DIA.
FITTING with this section.
INTENDED (44,5 mm)
(SEE DESIGN
FOR FREEZER CLEARANCE General Instructions
STRUCTURES CRITERIA HOLE
SECTION) Series DS-8 Dry-Type Sprinklers must
only be installed in fittings that meet
INSULATED
the requirements of the Design Cri-
FREEZER
STRUCTURE
teria section. See the Design Criteria
section for other important require-
DS-8 ments regarding piping design and
SHOWN WITH sealing of the clearance space around
STANDARD the sprinkler casing.
ESCUTCHEON
Do not install any bulb-type sprinkler
FIGURE 15 if the bulb is cracked or there is a loss
FIGURE 14 MODEL DSB-2 DRY SPRINKLER of liquid from the bulb. With the sprin-
SPRINKLER FITTING BOOT WITH PENDENT SERIES kler held horizontally, a small air bubble
HEATED AREA DS-8 DRY-TYPE SPRINKLER should be present. The diameter of the
air bubble is approximately 1/16 in. (1,6
mm) for the 135°F (57°C) rating to 1/8 in.
(3,2 mm) for the 360°F (182°C) rating.
TFP513
Page 7 of 8
NOTES
1. Escutcheon Finish applies to sprinklers provided with escutcheons.
2. The stainless steel escutcheon finish is available for the pendent sprinkler only.
3. 135°F (57°C) and 175°F (79°C) temperature ratings apply to pendent sprinkler assemblies only.
4. Dry-type sprinklers are furnished based upon “Order Length” as measured according to Figures 3 to 6, as applicable, and for each individual sprinkler where it is to be
installed. After the measurement is taken, round it to the nearest 1/4 in. increment.
* Use Prefix “I” for ISO 7-R 1 Connection (for example, I-65-361-9-180).
TABLE D
SERIES DS-8 DRY-TYPE SPRINKLERS
8.0 K-FACTOR, 1 IN. NPT, QUICK RESPONSE, STANDARD COVERAGE
PART NUMBER SELECTION
Procedure
Brass Plated . . . . . . . . . . . . . . . . . 91-106-2-007
Note: For information on ISO Inlet Chrome Plated . . . . . . . . . . . . . . . 91-106-9-007
Thread Connections, contact John- Stainless Steel . . . . . . . . . . . . . . . 91-106-8-007
Contact your local distributor for avail- son Controls Technical Services. Standard Horizontal Sidewall
ability. When placing an order, indi- • Temperature Rating Brass Plated �������������������������������������������� 854922
cate the full product name, including Signal White (RAL9003) �������������������������� 854902
description and part number (P/N). • Sprinkler Finish Chrome Plated ���������������������������������������� 854912
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC