AT-03B - PARTITION TYPES Rev.2 Markup
AT-03B - PARTITION TYPES Rev.2 Markup
NUMBER LEGEND
1 LAYER 5/8" GYPSUM 2 LAYERS 5/8" GYPSUM 2 LAYERS 5/8" GYPSUM 1 LAYER 5/8"
WALLBOARD WALLBOARD WALLBOARD GYPSUM WALLBOARD
_ NON−RATED
FRAMING TO STRUCTURE
GWB TO STRUCTURE
3 1/2" BATT INSULATION ON
BOTH SIDES OF WALL 1 LAYER 15/32" MIN. OSB SHEATHING
2 LAYERS 5/8" EXTERIOR GYPSUM 1 LAYER 15/32" MIN. 1 LAYER EXTERIOR
SHEATHING OSB SHEATHING GYPSUM SHEATHING
NON−RATED
1 1/2" FIRE SAFING
EXTERIOR FACING
_P PARTIAL HEIGHT PARTITION
FRAMING & GWB TO X’−0" AFF (SEE DETAIL)
HEAD HEAD HEAD HEAD HEAD
1 1/2" PERIMETER SPACE
EXTERIOR FACING
NON−RATED
WOOD STUDS WOOD STUDS − SEE
STRUCTURAL FOR SPACING
WOOD STUDS − SEE STRUCTURAL FOR
SPACING
WOOD STUDS − SEE STRUCTURAL
WOOD STUDS − SEE STRUCTURAL FOR
SPACING _C FRAMING & GWB TO FINISHED CEILING
PROVIDE BRACING AS REQUIRED
5/8" TYPE "X" GYPSUM FOR SPACING
THIS DRAWING IS THE PROPERTY OF RULE JOY TRAMMELL + RUBIO, LLC AND MAY NOT BE REPRODUCED WITHOUT WRITTEN CONSENT ©
ARCHITECTURE INTERIOR DESIGN
WALLBOARD ON 2X4
WOOD STUDS AT 16" O.C.
PLAN PLAN PLAN PLAN PLAN NON−RATED
_CS
BASE AS SCHEDULED P.T. SILL PLATE SET IN BED OF SPRAY P.T. SILL PLATE SET IN BED OF SPRAY P.T. SILL PLATE SET IN BED OF P.T. SILL PLATE SET IN BED OF
LLC
FOAM SEALANT @ CONCRETE FLOOR FOAM SEALANT @ CONCRETE FLOOR SPRAY FOAM SEALANT @ CONCRETE SPRAY FOAM SEALANT @
www.rjtrdesign.com
BOTH SIDES BOTH SIDES BOTH SIDES SIDES CONT. BOTH SIDES 4’ WIDE SAB ABOVE CEILING CTRD ON PARTITION
TOP OF FLOOR STRUCTURE TOP OF FLOOR STRUCTURE TOP OF FLOOR STRUCTURE TOP OF FLOOR STRUCTURE TOP OF FLOOR STRUCTURE
NON−RATED
12" x 12"
DUCT
3"
86
4 5/8" 2x4 WOOD STUDS
84
6" 2x4 WOOD STUDS
82
5 1/4" 2x4 WOOD STUDS
80
4 3/4" 2x4 WOOD STUDS
_S FRAMING & GWB TO STRUCTURE
3" SOUND ATTENUATION BLANKETS, U.N.O.
18" x 18"
FLOOR OPENING 2x6 WOOD STUDS
6 5/8" 1 HOUR FIRE−RATED
2’ 2 1/4"
87 85
8" 2x6 WOOD STUDS
83
7 1/4" 2x6 WOOD STUDS
81
6 3/4" 2x6 WOOD STUDS
1−_ FRAMING & GWB TO STRUCTURE
THERMAL INSULATION PER UL REQUIREMENTS
SYSTEM F−C−7036
2−_ INSULATED
MECHANICAL VENTILATION SHAFT WALL
TYPICAL NON−LOAD BEARING EXTERIOR WALL
(FIRE SEPARATION DISTANCE = 10’<X< 30’)
LOAD−BEARING EXTERIOR WALL
(FIRE SEPARATION DISTANCE LESS THAN 10’)
TYPICAL LOAD−BEARING EXTERIOR WALL
(FIRE SEPARATION DISTANCE GREATER THAN 10’)
NON−LOAD−BEARING EXTERIOR WALL
(FIRE SEPARATION LESS THAN 10’) _T FRAMING & GWB TO STRUCTURE
BATT INSULATION R−VALUE PER WALL SECTION PRINTED
Rev Date Issue/Revision
BOTTOM OF FLOOR / ROOF BOTTOM OF FLOOR / ROOF BOTTOM OF FLOOR / ROOF
STRUCTURE STRUCTURE STRUCTURE #
ABUSE−RESISTANT SUFFIXES FINISH DESIGN APPLICATION SUFFIXES
CMU EXTENDS TO UNDERSIDE 12/15/22 ISSUE FOR PERMIT
SEALANT EACH SIDE SEALANT EACH SIDE
SEALANT EACH SIDE OF ROOF DECK W/ SEALANT EACH SIDE 02/01/23 ISSUE FOR GMP SET
1"
COMPRESSIBLE FIRE SAFING CUT 2x SINGLE TOP PLATE CUT 2x SINGLE TOP PLATE NOTE: SUFFIX MAY BE
(2) 1" SHAFT LINERS CLIPPED TO 1 LAYER 5/8" TYPE "X" GYPSUM WALLBOARD ON 5/8" GWB EACH SIDE (2 LAYERS
ADDED TO ANY OF THE 1 05/03/23 PERMIT REISSUE
WOOD STUDS IN CONTINUOUS PLYWOOD SHEATHING ABOVE PARTITIONS CEMENT −
EACH SIDE AT 2−HR PARTITION)−
BOARD 2 06/05/23 PERMIT REISSUE
ACCORDANCE WITH UL U373 (2 LAYERS OF GWB AT 2 HOUR RATED WALL) SEE NOTE BELOW 5/8" GWB EACH SIDE (2
8" CMU ABUSE−RESISTANT GYPSUM CBS
HEAD
CORRIDOR
WEATHER BARRIER
BASE AS SCHEDULED POWER ANCHOR 2. PROVIDE RATED WALLS ACCORDING TO THE FULL REQUIREMENTS OF THE INDICATED TEST NUMBER.
ACOUSTICAL BASE AS SCHEDULED ACOUSTICAL SEALANT POWER ANCHOR
SEALANT CONT. BOTH CONT. BOTH SIDES SEALANT EACH SIDE 3. MARKING AND IDENTIFICATION OF FIRE AND SMOKE RATED WALLS AND PARTITIONS SHALL BE
SILL SIDES SEALANT CONT SILL SILL SEALANT EACH SIDE SILL IDENTIFIED WITH PERMANENT MARKINGS OR STENCILING IN CONFORMANCE WITH LOCAL BUILDING CODE
REQUIREMENTS, AND AUTHORITY HAVING JURISDICTION.
TOP OF FLOOR TOP OF FLOOR TOP OF FLOOR STRUCTURE FLOOR AS SCHEDULED 1" AIR SPACE FLOOR AS SCHEDULED
3/4" 2" 3/4" 4. FOR RATED WALLS THAT EXTEND TO FLUTED STEEL DECK/CONCRETE FLOOR ASSEMBLY, COMPLY WITH
STRUCTURE STRUCTURE FIRE-RATING REQUIREMENTS OF U.L. SYSTEM No. HW-D-0001 OR HW-D-0002.
5 3/4" (1−HR)
W/ PLYWD. 9 1/4" (1 HR) 2x4 WOOD STUDS
79 11 3/4"
2x4 WOOD STUDS
77 14 3/4"
2x6 WOOD STUDS
72
2x4 WOOD STUDS
70 69
11 1/4" (1 HR) 2x4 & 2x6 WOOD STUDS 5. APPLY SEALANT TO WALLS AS REQUIRED TO MEET THE INDICATED STC OR FIRE RATING. APPLY
SEALANT TO ENTIRE PARTITION PERIMETER AND PENETRATIONS PER MFR’S RECOMMENDATIONS OR UL
REQUIREMENTS.
7 3/4" (1−HR) 13 1/4" (1 HR) 2x6 WOOD STUD
2x4 WOOD STUDS
W/ PLYWD.
71 6. STAGGER ELECTRICAL OUTLETS 12" MINIMUM AT ALL PARTITIONS.
78 12 3/4"
73
2x6 WOOD STUDS
_S 7. PROVIDE IN WALL BLOCKING FOR MILLWORK, ARTWORK, FURNISHINGS, HARDWARE, WALL STOPS,
TOILET ACCESSORIES, GRAB BARS, CLOSET RODS, HANDRAILS, WALL BUMPERS, MODULAR OFFICE WALLS,
STC 54 PER NRCC TL−93−280 ETC.
_S NOTE: STC 40 WITHOUT S
8. ALL VERTICAL PIPING EXPOSED IN ROOMS SHALL BE FURRED WITH SAME MATERIAL AS ADJACENT
_S _S _S 9 1/4" (1 HR)
2 x 4 STUDS
SUFFIX PER USG−860808 SIM.
1−_
11 1/4" (1 HR) UL DESIGN U341 WALLS. EXCEPTIONS ARE: MECHANICAL ROOMS, ELECTRICAL ROOMS, TELEPHONE ROOMS.
UL DESIGN U341 9. METAL STUD PARTITIONS BEHIND ALL PLUMBING AND OTHER FIXTURES SHALL BE BRACED TO
15/32" STRUCTURAL PLYWOOD REQUIRED 1−_ 12 1/2 (2−HR) UL DESIGN U342
STRUCTURE WHERE REQUIRED TO SUPPORT THE EQUIPMENT PROVIDED.
2−_
UL DESIGN U373
2−_ 2 HOUR RATING
SEE PARTITION TYPE 2−40
FOR RATING INFO 2−_ UL DESIGN
GA 610−13 WITH 2 LAYERS TYPE "X" GWB ON BOTH SIDES
NOTE: USE 1 LAYER OF EXTERIOR GYP. SHEATHING ON EACH
SIDE OF EXTERIOR BALCONY WALLS BETWEEN 1L AND 1C.
UNIT DEMISING WALLS AT PLUMBING STACKS (ONE SIDE)−
INDEX OF NOT MORE THAN 450.
SEE PARTITION TYPE 70 FOR NOTES AT SHEAR WALL 12. METAL STUD NON LOAD−BEARING INTERIOR PARTITION SHOP DRAWINGS AND CALCULATIONSTO BE
CONDITION PROVIDED BY CONTRACTOR.
TYPICAL 2−HR FIRE WALL TYPICAL LOAD BEARING ELEVATOR/STAIR WALL TYPICAL UNIT CORRIDOR WALL AND 2 HR FIRE RATED CORRIDOR TYPICAL UNIT DEMISING WALL AND 2 HR FIRE RATED CORRIDOR
PARTITION TYPES
_S
UL DESIGN U305
7/8" FURRING CHANNEL
1−_ 2w/2
2−1/8"
2 LAYERS GWB
COMMISSION NO: 17-177
DRAWING NO:
UL DESIGN U301
2−_ AT−03B
AMENITY RESTROOMS TYPICAL CHASE WALL TYPICAL TWO SIDED WALL TYPICAL ONE SIDED WALL