Visual Specification Method For IEC 61850 Based Substation
Visual Specification Method For IEC 61850 Based Substation
measuring systems, independent phase and ground logical pole trip under single-phase faults.
units, with quadrilateral characteristic three (3) zones
• Synchronism-check – ANSI 25: To perform the
forward, one (1) zone backward and an extended zone,
synchronism-check, the relay must allow adjusting the
with easy to interchange the direction of any zones and
differences in angle ǻĭ, frequency ǻf and voltage ǻV.
single-pole and three-pole tripping command.
• Power swing blocking – ANSI 68: The relay must emit
• Overvoltage – ANSI 59: With measurement per phase
blocking signals to some zones of the distance protection
and two stages with definite time curve.
for a specified time and must have unblocking by current.
• Undervoltage – ANSI 27: With measurement per phase In case of a subsequent fault, the relay must allow to have
and two stages with definite time curve. some zones of the distance protection, in order the distance
protection can operate, the relay must allow the user to
• Fault Closing - ANSI 50HS: With a definite time
customize the blocking zones (Z1, Z2, Z3).
bidirectional overcurrent stage and the relay must allow
implantation of activation logic of the 50HS function by This is quite a bit of text for just one overhead line
breaker status changes and/or binary inputs related to the protection definition. Imagine the amount of text need to
closing command from any level of control. describe the entire substation functionality. In addition all
these texts may leave room for interpretation by the reader and
• Phase Directional overcurrent - ANSI 67: With three-
therefore the same text can lead to different implementations.
pole tripping command, an IEC inverse time curve, two
However there is a better way of describing this by using
curves of definite time and polarization with zero-sequence
pictures and this is where the VSM comes in.
components of voltage and current variables.
The distance function – ANSI 21 is taken as an example to
• Phase and Ground bidirectional overcurrent – ANSI 67N:
work out the main components of the VSM step by step.
With three-pole tripping command, an IEC inverse time
curve, two curves of definite time and polarization with
V. SINGLE LINE DIAGRAM FOR THE CHOSEN FUNCTION
zero-sequence components of voltage and current
variables. The single line diagram applicable for the distance function
is that of the 115 kV overhead line. This is shown in figure 3
• Phase overcurrent 50/51: Function per phase with IEC
inverse time curve and one definite time curve and three-
pole tripping command.
• Neutral overcurrent 50N/51N: Function per phase with
IEC inverse time curve and one definite time curve and
three-pole tripping command.
• Breaker Failure – ANSI 50BF: Activated by the operation
of any protection function of the multifunctional relay and
by means a binary input. The operation of the function
50BF must be executed in two stages, the first stage is the
confirmation of the single-pole and/or three-pole tripping
and the second stage is a final tripping.
• Reclosing – ANSI 79: Enabled by the operation of the
distance function in Z1 and/or operation of the
teleprotection scheme, according to the type of fault, the
reclosing will be executed single-pole for single-phase
faults and three-pole for faults between phases. The
reclosing function must be capable to detect evolving Figure 3: Applicable single line diagram overhead lines
faults, with this type of fault; the relay will emit an The next step is the allocation of the logical nodes that
opening three-pole command and initiate a three-pole describe the distance protection function on the single line
reclosing cycle. The algorithm of the reclosing function diagram shown in figure 2.
must consider the function blocking before detection of a
manual closing by means a binary input. VI. LOGICAL NODE ALLOCATION
• PUTT and POTT tele-protection schemes: The operation The IEC 61850 concept of free allocation of logical nodes
of PUTT and POTT functions must produce a single-pole means that the definition of the system functionality is
trip under single-phase faults. possible without defining the hardware upfront. The approach
• Directional comparison tele-protection scheme: The trip also allows to group logical nodes per system level. In a
occurs when each extreme detects the fault and receives substation these levels are known as Process-level, Bay-level
permission from the other extreme and must operate by the and Station-level. The reason to group logical nodes on these
following scheme. The operation of Directional levels is because the type of communication (the message
comparison tele-protection function must produce a single- types) between and within the different levels can be different.
An example of logical node allocation per system level is
4
shhown in Figuree 4. P
Process Level:
The choice of the logicall nodes is stroongly related to the - Circuit Brreaker – XCB
BR – single phase trippinng is
fuunction, but off course addittional logical nodes can be added required sso three XCB
BR Logical N
Nodes are neeeded,
foor specific funnctionality (e.g. the IHMI tto model the HMI). one per phhase
After all the reequired logicaal nodes have been placed in the
A
- Bypass Sw witch – XSW WI – the stattus of the byypass
thhree substationn levels, the nnext step is to define the logical
switch is uused to determmine whether tthe trip goes too the
coommunicationn paths betweeen these logicaal nodes.
local circuuit breaker or tto a remote cirrcuit breaker
System
mLevels - Currents – TCTR – m measurements are necessaryy per
phase andd neutral so ffour TCTR Logical
L Nodess are
Processs Bay Station
n required
- Voltages – TVTR – m measurements are necessaryy per
phase andd neutral so ffour TVTR L
Logical Nodess are
LN
LN LN
LN
N LN required
B
Bay Level:
LN
LN - Distance ZZones – PDISS– three (3) zoones forward, one
LN L
LN LN (1) zone bbackward and an extended zone are requuired
so five PD
DIS Logical Noodes are needeed
Figure 4: System
m levels and Logiccal Nodes
- Teleprotecction schemess – PSCH – tthis Logical N
Node
can be useed for PUTT aand POTT schhemes so onlyy one
At this stagee of the VSM the communiication paths hhave to is needed
bee taken into acccount and thiss includes:
- Trip Connditioning – P PTRC – Thee trips from the
1.. Communicaation between logical nodess that is inextrricable protectionn functions in aan IEC 618500 based schem
me go
bound to a specific
s system
m function. E..g., interlockinng data to a trip coonditioning Loogical Node
(CILO) neeeded to perfoorm a control action on a high
If we translate this to the sinngle line diagrram it should look
voltage com
mponent; like figure 5
2.. Communicaation between logical nodes needed to trransfer
user specific informationn. E.g., the sum
m of switchedd amps
(SumSwAR Rs,CSWI) thatt can be used for conditionn based
monitoring.
When definiing the logicaal communicaation paths it should
bee considered that
t the comm munication deffined in step 1) will
noormally be im mplemented bby IED manuufacturers andd may
paartly not be visible as it occurs inside the IED and partlly may
bee made avaiilable throughh communicaation servicess (e.g.
G
GOOSE for trippping). As ann end-user it iss therefore oftten not
poossible nor waanted to redefifine this type oof communicaation in
a different waay. The com mmunication ddefined in sttep 2),
hoowever, has evverything to ddo with end-usser requiremennts and
is closely relateed to the data aand communiccation servicess made Figure 5: Logiccal Node Allocation
avvailable by thee IED manufaacturer. For exxample: the ennd-user
SumSwARs shhall be commuunicated to a station
sppecifies that S VII. IEC 61850 SEERVICE DEFINITIONS
coomputer (HM MI) by buuffered repoorting. Not every
m
manufacturer shhall be able too comply withh this requiremment as Itt is necessary to connect thhe Logical Nodes to the proocess
SuumSwARs iss an optionaal data of C CSWI and buuffered and to each otheer in order to define whichh elements off the
reeporting mightt not be supported by the IED. I The VSM M will systtem need to exxchange inform mation.
hoowever unmisstakably makee clear that thiis is required by the Starting with the process level, the connections cann be
S
ennd-user. definned as followss.
As can be seeen in figure 2 the distancee protection fuunction Since the higgh voltage prrocess is connventional all the
S
is applied in a rredundant fashion, or in othher words twoo IEDs Loggical Nodes connected too the processs level willl be
arre required that implement the distance protection funnction. connnected hardwiired. The Circuit Breaker w
will receive thee trip
Siince both IEDDs are identicaal as far as thee distance prottection infoormation usingg GOOSE messsages. The cuurrent and volltage
fuunction ANSI 21 is concerneed the Logicall Nodes necessary to transformers use sampled vallues to comm municate withh the
deescribe each ofo these redunndant functionns are identiccal and distaance protectiion zones. TThe trip condditioning Loggical
arre as follows. Noddes send GOO OSE messages. Finally the llogic to determmine
5
w
whether the loccal circuit breeaker or a rem
mote circuit breaker
b D
Data Object(s) Data Attribu
ute(s) Msg. tyype PC
shhall be trippedd also uses GO
OOSE messagees. P
Pos stVal, q, t 3 P2(TT2))
This can easily
e be reppresented graaphically usinng the O
OpCntRs stVal,q,t 3 P2(TT2))
noomenclature ffor the differennt connection types as definned by
thhe VSM as shoown in figure 55. …
Table 1:
1 The communiccation and perform
mance table
L
Like in real syystems it is posssible to use tthe VSM to deefine
multtiple links forr a single logiical communiccation path. TTable
1 shhows there are two links. EachE link deffines one or m
more
dataa objects and / or data attribbutes. In case the data attriibute
coluumn is empty the whole datta object with all its Mandaatory
dataa attributes shhall be includded. The messsage type column
Figure 5:: Graphical repressentation of comm
munication servicees
definnes which off the 7 messaage types [3] shall be usedd. In
All input annd output linnks of the deffined set of logical Table 1 link A reequires twice the message ttype 3 to be uused,
D) can be reeplaced by one or more of the
noodes (the IED but also different message typees can be com mbined for a siingle
coommunicationn services desccribed in figuree 5. link.
The IEC 61850 service ddefinitions are an importantt factor F
Following thiss principle andd the definitioons of IEC 611850
inn the VSM. A At some point in the designn process the logical part 5 for the exaample of the ddistance proteection selectedd for
noodes are alloccated to real devices.
d By drrawing a dotteed line this paper this reesults in the final diagram m for the distaance
arround a set off logical nodees the designeer indicates thhat the prottection functioon that includees the perform
mance table foor all
enncircled logicaal nodes beloong to a certaain IED. This set of of thhe connectionss as shown in figure 7.
loogical nodes sshall be givenn a meaningfuul name (tag) which
prreferably follows the nam ming conventions as definned in
ISSO/IEC 813466 [2]. This nname can thenn be re-used in the
deefinition of a different systeem function (iin the VSM thhis is a
diifferent page) that resides inn the same IED
D.
If this is appplied to the eexample the rresult is as giiven in
figgure 6.
T
The process is then repeatedd to describe eevery functionn that
is paart of the systtem, resulting in several diaagrams that caan be
seenn as functionall layers and thhat together deescribe the ovverall
Figure 6: Logical Nodes coonnected by comm
munication servicces
funcctionality of thhe IEC 61850 based system..
VIII. COMMUNICATTION AND PERFFORMANCE
IX. THE SSD FILE
After specify
fying and defiining the singgle line diagraam, the
T
The ultimate step for inclluding the obbtained graphhical
Loogical Nodess and logical communicatiion paths, the next
definnitions in a sppecification baased on part 6 of IEC 618550 is
sttage of the VVSM is the deefinition the communicatioon and
the creation of thhe SSD file. Since the VSM M already incluudes
peerformance tabble. In this tabble, each data to be communnicated
the Single Linne Diagram,, the Logiccal Nodes, the
(thhe link) is deefined in termms of the Daata Object, thee Data
com
mmunication seervices to be uused and descrribes the hardw ware
A
Attribute(s), thhe Message T Type and the Performance Class
and the redundanccy required thiis final step is very easy.
(PPC) with the aassociated Traansfer Time ((TT). Each m message
tyype defines onne or more peerformance claasses (PC) annd each
X. CONC
CLUSIONS
peerformance claass has a transsfer time (TT)) [3]. This deffinition
is currently part of Editioon 2 of IEC C 61850, but these Inn conclusion the visual speecification meethod as preseented
deefinitions can also be used ffor systems baased on Editioon 1 of in tthis paper is a new methhod that allow ws to graphiccally
thhe standard. speccify IEC 618850 functionss and system ms. It providees a
num
mber of advanttages includingg the followinng.
6
XI. REFERENCES
[1] 2009, IEC 61850 Communication networks and systems
in substations, parts 6, 7-2, 7-3, 7-4, IEC, Switzerland.
[2] 2009, ISO/IEC 81346 Industrial systems, installations and
equipment and industrial products -- Structuring
principles and reference designations, ISO/IEC,
Switzerland
[3] 2010, Draft CDV IEC 61850 Communication networks
and systems in substations part 5, TC57 WG10.
XII. BIOGRAPHY
Marco C. Janssen is the CEO of
UTInnovation. He received his BSc degree in
Electrical Engineering from the Polytechnic in
Arnhem, The Netherlands.
He has worked for over 21 years in the field of
Smart Grid, Protection, Control, Monitoring,
Advanced Metering Infrastructures and Substation
Automation.
He is member of IEC TC57 WG 10, 17, 18, 19, the IEEE
PES Power System Relaying Committee and CIGRE B5 and
D2 working groups. He is editor of the Quality Assurance
Program for the Testing Subcommittee of the UCA
International Users Group, holds one patent, has authored and
presented more than 38 technical papers and is the author of
the “I think” column in the PAC World magazine.