TOCF Based Control For Optimum Operation of A Grid Tied Solar PV System
TOCF Based Control For Optimum Operation of A Grid Tied Solar PV System
TOCF Based Control For Optimum Operation of A Grid Tied Solar PV System
Abstract—In this work, a third order complex filter (TOCF) load and to the grid at UPF (Unity Power Factor) with reduced
based control technique is used for a double stage grid tied solar harmonics. The references for the harmonics and distortion, are
photovoltaic (PV) system. The PV array generates the real power recommended in [2], [3].
and provides it to the load connected and remaining to the utility.
The voltage source converter functions as a distribution static Ropp et al. [4] have recommended a design method of the PV
compensator and improves power quality of the grid by mitigating source, which realization is generic in nature. Another method
harmonics, balancing of the grid currents with unity power factor. for PV array modeling and MPP (Maximum Power Point) for
It also performs well under weak grid scenario like voltage dis- extraction of maximum power in nonuniform solar irradiance, is
tortion, grid faults, DC offset, voltage unbalances and swell/sag. explained in [5]. A modified P&O (Perturb and Observe) based
The main objective of this work is positive sequence components
extraction from unbalanced voltages for unit templates estima- MPP is demonstrated in [6] to avoid fluctuations around MPP
tion and TOCF algorithm extracts the fundamental component during irradiation variation. There are various controls related to
of the load currents. A PV power term is applied for improved MPP techniques described in [7] like P&O, estimated P&O, INC
system performance. This work demonstrates the effectiveness of (Incremental Conductance), fuzzy logic and neural network.
control algorithm at various dynamic conditions by simulating the Other MPP algorithms are demonstrated in [8].
behavior of the system in MATLAB. Tests are conducted on an
experimental setup realized in the laboratory at different abnor- A grid tied solar PV source offers a benefit of PQ improvement
mal situations like load unbalancing, voltage unbalance, voltage and transmits PV source energy to connected loads and to the
distortions, voltage swell/sag, insolation change, DSTATCOM-PV utility, thus moderating the electricity production requirement
mode and PV-DSTATCOM mode etc. The system operation is from conventional resources. When sunlight is absent, VSC
found satisfactory and distortion levels in grid currents are found works in DSTATCOM mode and delivers power to the load from
in bounds, as suggested in IEEE standard-519.
the grid with enhanced PQ. The enhancement in PQ, relies on
Index Terms—MPP, P&O, power quality, PV array, TOCF, the effectiveness of VSC control, for the estimation of the grid
voltage distortion.
reference currents. Various controls have been demonstrated in
I. INTRODUCTION the text. Few of them are instantaneous reactive power theorem
(IRPT), least mean square and fourth (LMS & LMF) [9]–[11].
N TODAY’S situation, green energy production is evolving
I as substitute to fossil fuels for electric energy generation.
Easy availability and green nature of PV energy make it remark-
Adaline-LMS, SRF and IRPT comparison have been illustrated
in [12].
The DC offset in the load current, occurs mainly due to mea-
able substitute of power production. However, grid situations surement problems, digital signal processing, analog to digital
are extremely weak, unpredictable and ruined with a problem converter (ADC), rectifiers. Due to drift in analog circuit and
of poor power quality (PQ) i.e., existence of harmonics and the nonlinear characteristics of ADC and sensors (current and
distortions [1]. PQ disturbances result in malfunctioning and voltage), an unavoidable DC offset is introduced in the mea-
unpredictable failure of devices tied in the system. Thus, it sured signal. The occurrence of grid faults, rectifier operation,
becomes a challenging assignment to incorporate renewable transformer saturation etc. are the other causes of the DC offset
systems to the weak grid, due to their irregular nature. These PQ [13]–[15]. When the DC offset current flows in the grid, working
disturbances are reduced by VSC (Voltage Source Converter). of the distribution transformer is greatly affected. The DC offset
It operates as distribution static compensator (DSTATCOM) as in the current shifts the operating point of the transformer and
explained in the text [1]. It feeds PV energy to the connected it increases the magnetizing current, which results in the over-
heating of the transformer winding and decreases the lifetime of
Manuscript received April 23, 2019; revised August 21, 2019, December 5, the transformer. It also results in electrochemical corrosion in
2019, and February 21, 2020; accepted April 6, 2020. Date of publication April
27, 2020; date of current version August 20, 2020. This work was supported in the grounding systems. Overall, it effects the normal operation
part by the Government of India under Grant RP03391 and in part by J. C. Bose of a grid connected PV system with nonlinear loads [16]–[18].
Fellowship (RP03128). Paper no. TEC-00424-2019. (Corresponding author: During DC offset, all the above stated control algorithms
Vandana Jain.)
The authors are with the Electrical Engineering, Indian Institute of Tech- provide poor performance to obtain the load current fundamental
nology Delhi, New Delhi 110016, India (e-mail: [email protected]; component (FCLC) at point of common interconnection (PCI)
[email protected]). under grid anomalies of voltage sag/swell and grid voltage
Color versions of one or more of the figures in this article are available online
at https://ieeexplore.ieee.org. distortion. For the rejection of DC offset, GIs (Generalized
Digital Object Identifier 10.1109/TEC.2020.2990907 Integrators) are used. The SOGI-QSG (Second Order GI) does
0885-8969 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
1172 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 3, SEPTEMBER 2020
not offer ideal DC-offset rejection and does not eliminate all the
higher order harmonics. Rodridguez et al. [19] have proposed
adaptive notch filter (ANF) control on three phase system. Practi-
cal application of a NF, is extremely difficult due to its amplitude
ideality and characteristics of the phase and its sensitivity to the
variations in the system parameters, that makes it unrealistic for
real-world applications. Thus, to overcome shortcomings of the
existing GI’s, an enhanced GI having good DC-offset elimina-
tion capacity with higher order harmonics elimination ability
with a third order complex filter (TOCF) is used in this work.
A weak grid has a frequent problem of voltage fluctuations.
An unexpected failure of grid may cause in the deficit of the
electricity production. Generally, a grid tied system is provided
with suitable protection schemes for the voltage fluctuations.
However, the relay operates on a narrow range that may lead
to VSC malfunctioning. The malfunctioning in VSC leads to
PV transmission loss to the grid and creating add-on burden on Fig. 1. System Configuration.
the grid for meeting the total generation requirement. Thus, in
order to overcome this problem, a double stage PV system is
used with DC link adaptive voltage control. The first stage is a
boost converter (DC-DC), which supports PV array to operate
at MPP and another stage is the VSC pulse generation control
to transfer the PV power to the utility.
In this work, a TOCF control is used for FCLC extraction in
a two-stage solar PV source tied to a grid (three phase), with
an improvement of PQ at grid abnormal circumstances of grid
faults, DC offset, voltage unbalances, distortion and voltage fluc-
tuations. The FCLC is applied to obtain grid reference currents
(GRC’s). The P&O based MPP is applied on a solar PV array. To
accomplish a quick transient response, a PV feed-forward term is
also used. The system is examined at several abnormal situations Fig. 2. Control algorithm.
like load unbalancing, voltage unbalances, voltage sag/swell,
voltage distortion, erratic PV conditions etc.
Key contributions of this work, are as follows. II. SYSTEM OUTLINE
r The TOCF (Third Order Complex Filter) based control
The outline of three phase two stage grid tied PV source is
estimates the PSCs (Positive Sequence Components) from demonstrated in Fig. 1. This scheme comprises of a grid, AC
unbalanced voltages and FCLC from the distorted grid inductors, PV source, RC filter, nonlinear load and capacitor.
currents effectively to reduce harmonics distortion.
r The TOCF based control improves the power quality of The RC filters mitigate switching ripples from PCI voltages.
The boost converter draws the peak power from the PV array
the system by decreasing current and voltage harmonics and this peak power is transferred to the utility at UPF (Unity
during the distortion caused by either the load (nonlinear) Power Factor) via VSC. This VSC is interfaced to the PV array
or by the supply voltage.
r A decrease in electricity provided by the utility in the day using AC inductors (Interfacing Inductors). A capacitor in the
DC link is used for the connection of the boost converter with
because of the energy produced by PV source tied to the VSC.
grid at UPF.
r The term for the PV generation, is applied for the reduction
of grid current fluctuation during system dynamics. III. CONTROL STRUCTURE
r To minimize the losses due to VSC switching, an adaptive
control for the DC-link voltage is implemented according Fig. 2 represents the control scheme. It is segregated in two
to the PCI voltage variation. major sections: (1) MPP control through DC-DC converter and
r An instinctive-protection scheme is used during grid faults (2) VSC control.
for protection of entire system and equipment.
To examine the system performance, a double stage grid
interfaced PV source is tested and a system prototype is realized. A. MPP Control
Test results are recorded at perturbation in the load, erratic PV in- The P&O based MPP is realized through a DC-DC converter
solation and abnormal grid situations of unbalances, distortion, for the withdrawal of maximum power from the PV source.
sag and swell in the grid voltage. It provides duty cycle (D) for DC-DC boost converter. It is
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
SINGH AND JAIN: TOCF BASED CONTROL FOR OPTIMUM OPERATION OF A GRID TIED SOLAR PV SYSTEM 1173
where kpd and kid are gains coefficients. wsp = wLpa + wcp − wpv (9)
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
1174 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 3, SEPTEMBER 2020
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
SINGH AND JAIN: TOCF BASED CONTROL FOR OPTIMUM OPERATION OF A GRID TIED SOLAR PV SYSTEM 1175
Fig. 5. Operation at (a) perturbation in load (b) IM load (c) change in PV irradiation (d) PCI variable voltage (e-f) grid fault (L-L-L) (e) without any control
imposition (f) with control imposition.
a decrease in PV current magnitude and PV power. Moreover, grid voltages. It is understood from Fig. 7(a) that during load
during a dip in solar insolation, some oscillations are observed unbalancing, the three phase grid voltages and currents are
in the DC link voltage and the grid currents. Due to a decrease sinusoidal and are in phase with each other validating the UPF
in the PV power, there is a dip in grid currents and VSC currents operation. Fig. 7(b) displays waveforms of iLa with DC offset of
as the PV array now supplies less power to the utility while 5 A, extracted FCLC (iLF ) and unit templates (up ) using TOCF
the load current remains constant. To reduce the grid current based control. The detailed DC-offset elimination procedure is
and DC link voltage oscillations, a PV feedforward term is explained in Appendices. As unit templates are sinusoidal with
included. Figs. 6(c)–(d) display the system performance with accurate magnitude and are well balanced. Thus harmonics and
the inclusion of the PV feedforward term. During the dip, in the DC offset have been eliminated from the FCLC as illustrated in
PV irradiation from1000 W/m2 to 600 W/m2 , there is dip in PV Fig. 7(b).The performance of TOCF is illustrated in Fig. 7(c).
current magnitude and PV power. In addition, during the dip The system performance is verified at odd grid circumstances
in solar insolation, no oscillations are observed in the DC link like sag, swell, distortion and unbalance in the grid voltage.
voltage and the grid currents as in the previous case. Due to an Fig. 7(c) depicts the grid voltages, PSCs, unit templates (UTs)
decrease in the PV power, there is dip in the grid currents and and grid currents. It is validated that during adverse grid states,
VSC currents as the PV array is now feeding less power to the the grid currents are balanced and sinusoidal. PSCs and UTs are
grid while the load current remains constant. estimated accurately.
Fig. 7(a) demonstrates the UPF operation of the grid during Fig. 8(a) demonstrates the comparative analysis between this
dynamics in load unbalancing and solar irradiation variation. TOCF and conventional controls - SOGI-Q and SOGI-D. More-
Fig. 7(a) exhibits the waveforms during disconnection of phase over, different types of nonlinear loads are linked at PCI, that
‘a’ load, phase ‘a’ load current, grid currents and three phase contribute to the harmonics distortion (higher order) and DC
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
1176 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 3, SEPTEMBER 2020
Fig. 6. System performance without/with PV feedforward term Fig. 7. Efficiency of TOCF control at (a) load unbalancing (grid currents are
(a) G, Vdc , Ipv , Ppv (b) vsabc , isabc , iLa , ivsc (c) G, Vdc , Ipv , Ppv scaled up) (b) DC offset and harmonics (c) voltage sag, voltage swell, voltage
(d) vsabc , isabc , iLa , ivsc . unbalance and voltage distortion.
V. EXPERIMENTAL PERFORMANCE
To verify the simulated performance of TOCF control, a three
phase grid tied double stage PV system is built in the laboratory. Fig. 8. Bode plot (a) Comparison with other controls (b) DC offset and
The system response is logged during dynamics in the load, harmonics filtering capacity.
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
SINGH AND JAIN: TOCF BASED CONTROL FOR OPTIMUM OPERATION OF A GRID TIED SOLAR PV SYSTEM 1177
TABLE I
HARMONICS REJECTION CAPABILITIES
TABLE II
COMPARATIVE ANALYSIS BETWEEN VARIOUS ALGORITHMS
Fig. 9. Steady state operation of the system (a) vsab and ivsca (b) ivsca and
iLa (c) vsab and isa (d) Pvsc (e) PL (f) Ps (g)–(j) distortion of (g) iLa (h) isa
(i) vsa .
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
1178 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 3, SEPTEMBER 2020
Fig. 11. System operation at erratic PV circumstances (a-b) increase in PV insolation from 600 W/m2 to 1000 W/m2 (c)–(d) decrease in solar irradiation from
1000 W/m2 to 600 W/m2 .
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
SINGH AND JAIN: TOCF BASED CONTROL FOR OPTIMUM OPERATION OF A GRID TIED SOLAR PV SYSTEM 1179
Fig. 13. Dynamic response at grid voltage unbalance (a)–(c) before VSC switching (a) grid voltage and grid currents (b) Harmonic Spectra of vsab (c) Harmonic
Spectra of isa (d)–(f) after VSC switching (d) grid voltages with balanced grid currents (e) Harmonic Spectra of vsab (f) Harmonic Spectra of isa .
Fig. 14. Operation during distortions in voltage (a)–(c) prior to VSC switching (a) vsab and isa (b) Harmonic Spectra of vsab (c) Harmonic Spectra of isa
(d)–(f) after VSC switching (d) vsab and isa (e) Harmonic Spectra of vsab (f) Harmonic Spectra of isa .
the THDs are pushed to the limits provided by the IEEE-519 Figs. 14(d)–(f) show operation after VSC switching. It shows
standard as depicted in Fig. 13(e)–(f). Therefore, the system is that the distortions in grid voltages and grid currents consid-
capable of improving power quality at the PCI even when the erably lessen while the currents assume the sinusoidal shape.
grid voltages are unbalanced. Consequently, it is seen that the THDs are pushed down to well
within the limits given by the IEEE standard-519. Therefore,
system is capable of improving power quality at the PCI even
E. Operation at Distortion in Grid Voltage and Sag/Swell when the grid voltages are distorted.
Figs. 14(a)–(c) show operation of the system at distortion in Figs. 15(a)–(b) exhibit system operation at voltage sag/swell.
the voltage of the grid before VSC switching. Figs. 14(a)–(b) Fig. 15(a) demonstrates the waveforms of grid voltage (vsab ),
present the grid voltages and currents under voltage distortion grid current (isa ), VSC current (ivsca ) and load current (iLa )
conditions. Figs. 14(b)–(c) depict the THD’s of voltages and during voltage swell in the network. When an increase in level
currents of the grid, which are visibly distorted and the THDs of voltage of the grid is seen, abrupt fall in level of grid currents,
of the voltages and the currents are clearly above permissible is observed as depicted in Fig. 15(b). Likewise, during the
limits. grid voltage sag, the magnitude of the grid voltage decreases
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
1180 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 35, NO. 3, SEPTEMBER 2020
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.
SINGH AND JAIN: TOCF BASED CONTROL FOR OPTIMUM OPERATION OF A GRID TIED SOLAR PV SYSTEM 1181
to have DC offset elimination capability. [18] L. Cristaldi, A. Ferrero, M. Lazzaroni, and R. Ottoboni, “A linearisation
method for commercial hall-effect current transducers,” Proc. 17th IEEE
Instrum. Meas. Technol. Conf. [Cat. No. 00CH37066], Baltimore, MD,
i L = i1 USA, 2000, vol. 3, pp. 1220–1225.
(25)
ilq = i2 − i3 [19] P. Rodridguez, A. Luna, I. Candela, R. Mujal, R. Teodorescu, and F.
Blaabjerg, “Multiresonant frequency-locked loop for grid synchronization
of power converters under distorted grid conditions”, IEEE Trans. Ind.
Electron., vol. 58, no. 1, pp. 127–138, Jan. 2011.
[20] K. W. Martin, “Complex signal processing is not complex,” IEEE Trans.
REFERENCES Circuits Syst. I: Regular Papers, vol. 51, no. 9, pp. 1823–1836, Sep. 2004.
[21] F. Briz, M. W. Degner, and R. D. Lorenz, “Analysis and design of
[1] A. A. Sundararajan, A. Moghadasi, and A. Sarwat, “High-penetration grid- current regulators using complex vectors,” in Proc. IEEE Ind. Appl. Conf.
tied photovoltaics: Analysis of power quality and feeder voltage profile,” Thirty-Second IAS Annu. Meeting, New Orleans, LA, USA, vol. 2, 1997,
IEEE Ind. Appl. Mag., vol. 25, no. 5, pp. 83–94, Sep./Oct. 2019. pp. 1504–1511.
[2] IEEE recommended practice and requirement for harmonic control on [22] Zhang, X. Zhao, X. Wang, X. Chai, Z. Zhang, and X. Guo, “A grid
electric power system, IEEE std. vol. 519, 2014. synchronization PLL method based on mixed second- and third-order gen-
[3] X. J. Zong, P. A. Gray, and P. W. Lehn, “New metric recommended for eralized integrator for DC offset elimination and frequency adaptability,”
IEEE standard 1547 to limit harmonics injected into distorted grids,” IEEE IEEE J. Emerg. Sel. Topics Power Electron., vol. 6, no. 3, pp. 1517–1526,
Trans. Power Del., vol. 31, no. 3, pp. 963–972, June 2016. Sep. 2018.
[4] M. E. Ropp and S. Gonzalez, “Development of a MATLAB/Simulink [23] W. Li, X. Ruan, C. Bao, D. Pan, and X. Wang, “Grid synchronization
model of a single-phase grid-connected photovoltaic system,” IEEE Trans. systems of three-phase grid-connected power converters: A complex-
Energy Convers., vol. 24, no. 1, pp. 195–202, Mar. 2009. vector-filter perspective,” IEEE Trans. Ind. Electron., vol. 61, no. 4,
[5] K. Ding, X. Bian, H. Liu, and T. Peng, “A MATLAB-simulink-based pp. 1855–1870, Apr. 2014.
PV module model and its application under conditions of non uniform [24] A. Kulkarni and V. John, “A novel design method for SOGI-PLL for
irradiance,” IEEE Trans. Energy Convers., vol. 27, no. 4, pp. 864–872, minimum settling time and low unit vector distortion,” in Proc. 39th Annu.
Dec. 2012. Conf. IEEE Ind. Electron. Soc., Vienna, Austria, Nov. 2013, pp. 274–279.
[6] S. K. Kollimalla and M. K. Mishra, “A novel adaptive P&O MPPT
algorithm considering sudden changes in the irradiance,” IEEE Trans.
Energy Convers., vol. 29, no. 3, pp. 602–610, Sep. 2014.
[7] T. Esram and P. L. Chapman, “Comparison of photovoltaic array maximum
power point tracking techniques,” IEEE Trans. Energy Convers., vol. 22,
no. 2, pp. 439–449, June 2007.
[8] S. B. Kjær, “Evaluation of the “Hill Climbing” and the “Incremental Bhim Singh (Fellow, IEEE) was born in Rahama-
Conductance” maximum power point trackers for photovoltaic power pur, Bijnor (UP), India, in 1956. He has received
systems,” IEEE Trans. Energy Convers., vol. 27, no. 4, pp. 922–929, his B.E. (Electrical) from the University of Roorkee
Dec. 2012. (Now IIT Roorkee), India, in 1977 and his M.Tech.
[9] T. S. Win, Y. Hisada, T. Tanaka, E. Hiraki, M. Okamoto, and S. R. (Power Apparatus & Systems) and Ph.D. from the IIT
Lee, “Novel simple reactive power control strategy with DC capacitor Delhi, India, in 1979 and 1983, respectively. In 1983,
voltage control for active load balancer in three-phase four-wire distri- he joined the Department of Electrical Engineering,
bution systems,” IEEE Trans. Ind. Appl., vol. 51, no. 5, pp. 4091–4099, University of Roorkee, as a Lecturer. He became a
Sep./Oct. 2015. Reader there in 1988. In December 1990, he joined
[10] E. Eweda, N. J. Bershad, and J. C. M. Bermudez, “Stochastic analysis of the Department of Electrical Engineering, IIT Delhi,
the recursive least squares algorithm for cyclostationary colored inputs,” India, as an Assistant Professor, where he has become
IEEE Trans. Signal Process., Early Access. an Associate Professor in 1994 and a Professor in 1997. He has been Head of
[11] J. Castelló, J. M. Espí, and R. G.-Gil, “A new generalized robust predictive the Department of Electrical Engineering at IIT Delhi from July 2014 to August
current control for grid-connected inverters compensates anti-aliasing 2016. He has been Dean, Academics at IIT Delhi, August 2016 to August 2019.
filters delay,” IEEE Trans. Ind. Electron., vol. 63, no. 7, pp. 4485–4494, He is JC Bose Fellow of DST, Government of India since December 2015.
Jul. 2016. He is CEA Chair Professor since January 2019. Prof. Singh has guided 83
[12] Mortezaei, C. Lute, M. G. Simões, F. P. Marafão, and A. Boglia, “PQ, DQ Ph.D. dissertations, and 167 M.E./M.Tech./M.S.(R) theses. He has been filed 52
and CPT control methods for shunt active compensators — A comparative patents. He has executed more than eighty sponsored and consultancy projects.
study,” in Proc. IEEE Energy Convers. Congr. Expo., Pittsburgh, PA, 2014, His areas of interest include solar PV grid interface systems, microgrids, power
pp. 2994–3001. quality monitoring and mitigation, solar PV water pumping systems, improved
[13] N. T. Stringer, “The effect of DC offset on current operated relays,” power quality AC-DC converters.
in Proc. IEEE Ind. Commercial Power Syst. Tech. Conf.. Conf. Record,
Philadelphia, PA, USA, 1997, pp. 154–159.
[14] S. Nam, J. Park, S. Kang, and M. Kezunovic, “Phasor estimation in the
presence of DC offset and CT saturation,” IEEE Trans. Power Del., vol. 24,
no. 4, pp. 1842–1849, Oct. 2009.
[15] E. Emanuel, D. J. Pileggi, and F. J. Levitsky, “Direct current generation in
single-phase residential systems DC effects and permissible levels,” IEEE
Trans. Power App. Syst., vol. PAS-103, no. 8, pp. 2051–2057, Aug. 1984. Vandana Jain (Member, IEEE), received B.E. de-
[16] Kitamura, F. Yamamoto, H. Matsuda, K. Akhmad, and Y. Hamakawa, gree in electrical enginnering from CRSCE, Murthal,
“Test results on DC injection phenomenon of grid connected PV system India, in 2010, and the M.Tech. degree in power
at Rokko test center,” in Proc. Conf. Rec. Twenty Fifth IEEE Photovolt. systems from DCRUST, Murthal, India, in 2012. She
Specialists Conf. - Washington, DC, USA, pp. 1377–1379, 1996. is currently working toward the Ph.D. degree in power
[17] F. Berba, D. Atkinson, and M. Armstrong, “A new approach of prevention electronics, in the Department of Electrical Engineer-
of DC current component in transformerless grid-connected PV inverter ing, Indian Institute of Technology (IIT) Delhi. Her
application,” in Proc. IEEE 5th Int. Symp. Power Electron. Distrib. Gener. research interests include power electronics, power
Syst. (PEDG), Galway, 2014, pp. 1–7. quality in the distribution network, custom power
devices and renewable energy.
Authorized licensed use limited to: SASTRA. Downloaded on March 12,2021 at 09:41:49 UTC from IEEE Xplore. Restrictions apply.