600/1000 Volts Copper T Xlpe Power Cable (Un-Armoured) : Cu/Gmt/Xlpe/Lsoh/Lsoh

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

600/1000 VOLTS COPPER T XLPE POWER CABLE (UN-

ARMOURED)

CU/GMT/XLPE/LSOH/LSOH

Compliant with GEN. TO AS/NZS 5000.1:2005

BEFORE YOU START


1. The current ratings indicated in this Specification Sheet have been based on the calculation procedures as
recommended in IEC 60287and the following assumptions. Rating factors should be
a. Max continuous conductor temp = 90 °C
b. Ambient air temperature = °C
c. Ambient ground temperature = °C
d. Depth of laying = m
e. Thermal resistivity of soil = °C.m/W
2. The particulars given above are nominal & are subject to normal manufacturing tolerances.
3. Sequential length marking shall be provided at every one meter on outer sheath by hot foil indenting/Printing.
4. All the drums shall be packed by PP sheet over the outermost cable layer.

PARAMETER SPECIFICATION
Conductor Material & Shape Annealed Plain Copper - Stranded Circular Compacted
Class-2
CONSTRUCTION

Insulation XLPE
Separator Tape Flame Barrier
Core Identification By Red & Black Coloured Insulation
Inner Sheath Black LSOH
Outer sheath Black LSOH

Australasian Cables (A Division of EESA Pty Ltd) 711, High Street, Kew East, Vic 3102 Ph:0437720513
www.eesa.net.au / [email protected]
Std. Packing Length 1000 ± 1 %
Type of Drum Pine Drum
Overall Quantity Tolerance + 0% / -1 %
PACKING

Non Standard Length Non - Standard Length Not Less Than 100 Mtrs. Up To 5%
Of Order Qty.
APAR-UNICAB INDIA 0.6/1 KV ELECTRIC XLPE CABLE
Embossing/Printing
'CABLE SIZE' ‘Cable Designation' 'YEAR OF MFG'

PARAMETER SPECIFICATION
Max. Conductor Temperature at Rated Current 90°C
Ambient Air Temperature
CARRYING
CAPACITY
CURRENT

Ambient Soil Temperature


Soil Thermal Resistivity

Voltage Grade 0.6/1 KV


Permissible Voltage Variation ± 10%
PROPERTIES
ELECTRICAL

Permissible Frequency Variation ± 5%


Combined Voltage & Frequency Variation ± 10%
Max. Conductor Temperature at Rated Current 90°C
Max. Conductor Temp. at the End of Short Circuit 250°C

Min. Oxygen Index As Per ASTMD-2863 30%


Min. Temperature Index As Per ASTMD-2863 250%
PROPERTIES

Max. Acid Gas Generation As Per IEC 754(P-1) 0.5 % By Weight


LSOH

Max. Smoke Density Rating As Per ASTMD 2843 20%


Max. Light Transmission As Per ASTMD 2843 80%
Fire Survival Test As Per BS:6387/3 HRS CAT .CWZ

DIMENSIONS
No./
No. & Separator Packi
Nom. Insulation Inner Outer Approx Approx.
Size of Nom. Tape - ng
Cross (Nom./ Sheath Sheath . Net
Wire in Conduct Flame Lengt
Sectional Min. (Nom./Mi (Nom./Mi Overall Weight Type of
mm or Barrier h
Area of Thickness) n. n. Dia. of of Cable Drum
(Before Diameter (Nom. Per
Conduct in mm Thickness Thickness Cable in
Strandin in mm Thickness) Drum
or in ) in mm ) in mm in mm Kg/Km
g) in Sq.mm in m
Sq.mm
2C X 1.5
7 / 0.53 1.58 0.12 0.7/ 0.53 1.0 / 0.6 1.8 / 1.24 14.5 1000 240 Pine Drum
Sq.mm
2C X 2.5 Pine Drum
7 / 0.67 1.98 0.12 0.7/ 0.53 1.0 / 0.6 1.8 / 1.24 15 1000 280
Sq.mm
2C X 6 Pine Drum
7 / 1.05 3.09 0.12 0.7/ 0.53 1.0 / 0.6 1.8 / 1.24 17.5 1000 355
Sq.mm
2C X 16 4.9 Pine Drum
7 / 1.76 0.12 0.7/ 0.53 1.0 / 0.6 1.9 / 1.32 21 500 605
Sq.mm

Australasian Cables (A Division of EESA Pty Ltd) 711, High Street, Kew East, Vic 3102 Ph:0437720513
www.eesa.net.au / [email protected]
ELECTRICAL PROPERTIES
Short Circuit Max. D.C
No./Nom. Cross Max. A.C Zero Sequence
Rating Resistance Of Conductor Zero Sequence
Sectional Area Resistance at Resistance at
Conductor Conductor At Inductance @ Reactance At
of Conductor in 90°C in 20°C in
(Duration 1 20°C in 50hz And 90°C 50 Hz Ohm/Km
Sq.mm Ohm/Km Ohm/Km
Sec.) in KA Ohm/Km
2C X 1.5 Sq.mm 0.22 12.1 15.5 0.396
2C X 2.5 Sq.mm 0.36 7.41 9.49 0.376
2C X 6 Sq.mm 0.86 3.08 3.94 0.325
2C X 16 Sq.mm 2.29 1.15 1.47 0.285

CURRENT CARRYING CAPACITY

In non-
No./Nom.
metallic wiring
Cross
Non-metallic enclosure or
Sectional
Spaced from wiring unenclosed Completely surrounded by
Area of Spaced Touching
surface enclosure in partially thermal insulation
Conducto air surrounded by
r in thermal
Sq.mm insulation

2C X 1.5
Amps22 Amps21 Amps15 Amps15 10 Amps
Sq.mm
2C X 2.5
Amps32 Amps29 Amps22 Amps22 15Amps
Sq.mm
2C X 6
Amps53 Amps49 Amps39 Amps38 25Amp
Sq.mm
2C X 16
Amps98 Amps91 Amps74 Amps69 46Amps
Sq.mm

CURRENT CARRYING CAPACITY

Australasian Cables (A Division of EESA Pty Ltd) 711, High Street, Kew East, Vic 3102 Ph:0437720513
www.eesa.net.au / [email protected]
Buried direct Underground non-metallic wiring enclosure

No./Nom. Cross
Sectional Area of
Conductor in Sq.mm

2C X 1.5 Sq.mm Amps Amps Amps


2C X 2.5 Sq.mm Amps Amps Amps
2C X 6 Sq.mm Amps Amps Amps
2C X 16 Sq.mm Amps Amps Amps

INSTALLATION
No./Nom. Cross Sectional
Min. Safe Bending Radius of Cable
Area of Conductor in Sq.mm
2C X 1.5 Sq.mm 12 TIMES O.D
2C X 2.5 Sq.mm 12 TIMES O.D
2C X 6 Sq.mm 12 TIMES O.D
2C X 16 Sq.mm 12 TIMES O.D

MECHANICAL PROPERTIES
No./Nom. Cross Sectional Safe Pulling Force in N/Sq.mm (When Pulled By Pulling Eye)
Area of Conductor in Sq.mm
2C X 1.5 Sq.mm 50
2C X 2.5 Sq.mm 50
2C X 6 Sq.mm 50
2C X 16 Sq.mm 50

Notes

1. The particulars given above are nominal & are subject to normal manufacturing tolerances.
2. Sequential length marking shall be provided at every one meter on outer sheath by hot foil indenting/Printing.
3. All the drums shall be packed by PP sheet over the outermost cable layer.
4. Cables constructed will be tested to relevant AS/NZS standards. FAT report will be provided for all cables.

Australasian Cables (A Division of EESA Pty Ltd) 711, High Street, Kew East, Vic 3102 Ph:0437720513
www.eesa.net.au / [email protected]