Mini Modulo Direccion Apollo Advanced
Mini Modulo Direccion Apollo Advanced
Troubleshooting
Before investigating faults with the Mini Monitor Module, check all connections to the unit
and the wiring of the system. Many faults are caused by simple wiring errors. Earth faults on
a data loop or ancillary zone wiring may cause communication errors. Make sure that the
correct value end-of-line resistor is fitted.
Fault Finding
1. The Mini Monitor Module is not designed for outdoor use. Installation
The Mini Monitor Module, part no 55000-765, monitors the state of one or more single-pole
2. All circuits are power limited. volt-free contacts and may be used in installations where space is limited.
3. The unit must be installed in a dedicated suitable UL listed enclosure, employing only 1. Connect loop wiring to the SEMS terminals as shown in Fig 1.
power limited circuits.
2. Set the address using the DIL switch in accordance with the address table overleaf.
4. The SW1 / SW2 monitored input circuit uses Class B, Style A monitoring.
3. The eighth section of the DIL switch is used for setting the priority of the unit. Set to '1' for
priority and set to '0' for non priority.
In the USA: Apollo America Inc., 25 Corporate Drive, Auburn Hills, Michigan, 48326, USA 2. The unit can be attached to a standard 1 3/8" DIN rail, see Fig 2. To remove device, lift
Tel: (248) 332-3900 Fax: (248) 692-0888 the releasing clip and turn the unit anti-clockwise.
Email: [email protected] Website: www.apollo-fire.com
4 1
The Mini Monitor Module has three status LEDs: Address Setting
Red Indicates alarm condition The address of the Mini Monitor Module is set using the fi rst seven segments of the DIL switch.
Each segment of the switch must be set to “0” or “1”, using a small screwdriver or similar
Green Indicates normal polling tool. A complete list of address settings is shown below.
Note: Remote polling indication is achieved by connecting an LED across DIL switch DIL switch DIL switch DIL switch DIL switch
terminals three and four. setting setting setting setting setting
addr 1234567 addr 1234567 addr 1234567 addr 1234567 addr 1234567
Yellow pulsing, trouble on the monitored circuit
1 1000000 11 1101000 21 1010100 31 1111100 41 1001010
Wiring options for the Mini Monitor Module 2 0100000 12 0011000 22 0110100 32 0000010 42 0101010
Switches must be located 3 1100000 13 1011000 23 1110100 33 1000010 43 1101010
in the same room as the 4 0010000 14 0111000 24 0001100 34 0100010 44 0011010
module 5 1010000 15 1111000 25 1001100 35 1100010 45 1011010
6 0110000 16 0000100 26 0101100 36 0010010 46 0111010
6
7 1110000 17 1000100 27 1101100 37 1010010 47 1111010
L+ In/Out
SW1 8 0001000 18 0100100 28 0011100 38 0110010 48 0000110
9 1001000 19 1100100 29 1011100 39 1110010 49 1000110
1
R1 R2 R3
10 0101000 20 0010100 30 0111100 40 0001010 50 0100110
5
L- In
SW2 51 1100110 61 1011110 71 1110001 81 1000101 91 1101101
52 0010110 62 0111110 72 0001001 82 0100101 92 0011101
2
Alarm LED
53 1010110 63 1111110 73 1001001 83 1100101 93 1011101
4
L- Out
+R 54 0110110 64 0000001 74 0101001 84 0010101 94 0111101
55 1110110 65 1000001 75 1101001 85 1010101 95 1111101
3
Priority
Example:
Use UL listed resistors rated 10k for pre-alarm and 20k for end-of-line Address 78 =
3
0 1 1 1 0 0 1 1
2
1
0 1 2 3 4 5 6 7 8
ON = 0 /
4
5
6
2 3