Euserc Drawings
Euserc Drawings
TABLE OF CONTENTS
LIST OF DRAWINGS
Page 1 of 4
ELECTRICAL SERVICE REQUIREMENTS
ELECTRIC UTILITY SERVICE EQUIPMENT
REQUIREMENTS COMMITTEE, EUSERC
LIST OF DRAWINGS (Continued)
Page 2 of 4
ELECTRICAL SERVICE REQUIREMENTS
ELECTRIC UTILITY SERVICE EQUIPMENT
REQUIREMENTS COMMITTEE, EUSERC
LIST OF DRAWINGS (Continued)
Page 3 of 4
ELECTRICAL SERVICE REQUIREMENTS
ELECTRIC UTILITY SERVICE EQUIPMENT
REQUIREMENTS COMMITTEE, EUSERC
LIST OF DRAWINGS (Continued)
Page 4 of 4
LIST OF APPROVED ELECTRICAL UTILITY EUSERC-100
SERVICE REQUIREMENTS COMMITTEE
(EUSERC) DRAWINGS
EUSERC Page EUSERC Page
EUSERC # EUSERC #
Acceptability (a) Acceptability (a)
301 A 334 --
301A A 335 --
302 U 336 U
302A A 337 --
302B U 338 N/A
303 N/A 339 C
304 A 340 --
305 A 341 --
305A A 342 A
306 A 343 A
307 U 343A U
308 A 344 A
309 U 345 A
310 -- 346 --
311 A 347 A
312 A 348 A
313 C 349 C
314 C 350 --
315 A 351 C
316 U 352 --
317 U 353 A
318 U 354 A
319 A 401 C
320 A 402 --
321 A 403 --
322 A 404 C
323 A 405 --
324 A 406 --
325 C 407 C
326 C 408 C
327 C 409 C
328 -- 410 --
328A A 411 C
328B U 412 --
329 -- 413 --
329A A 414 C
329B U 415 --
330 A 416 C
331 A 417 --
332 A 418 C
333 A 419 --
420 U
I. SCOPE
A. This section contains minimum manufacturing requirements for utility metering and service
equipment rated 0-600V.
B. The following general notes apply to all drawings in this section where applicable. Each
drawing may also contain additional notes which should be considered unique to that drawing
unless reference is made to another specific drawing or section.
C. Refer to Section 200 for specific utility requirements and utility acceptability of these
requirements.
D. Refer to installation guide section for typical application and installation requirements.
These Requirements are based on practices that are necessary in order to supply uniform satisfactory
and safe service. Interpretations or clarifications of intent of these Requirements are subject to
EUSERC approval. Installations shall also conform to the provisions of applicable codes and
ordinances of local inspection authorities and the servicing agency.
A. Grounding, General
1. Lugs for terminating the customer’s ground wire (or other grounding conductors) shall be
located outside of the sealable section and shall be designed to readily permit the customer's
neutral system to be isolated, when necessary, from the serving agency.
2. Ground bus, when provided, shall be located at the rear of underground terminating
enclosures (i.e. pull boxes and pull sections).
B. Meter Sequence
The metering arrangement approved as standard and required by all the serving agencies
provides for the line current to enter first the meter and then the disconnecting means and
overload protective devices, (meter-switch-fuse sequence). For multiple meter installations,
refer to local codes.
C. Meter Access
Customer locking means for meter enclosures shall provide for independent access by the
serving agency.
D. Meter Heights
Meters shall be located not more than 75 inches and not less than 48 inches above the ground or
standing surface when installed outdoors. When meters are enclosed in a cabinet or indoors in a
meter room, the minimum height may be reduced to 36 inches. The meter height shall be
measured to the meter axis. Exception: Utilities in snow areas may require increased height.
Sheet 1
EUSERC Drawing 300
1. See Section 200 for tabulation of meter socket requirements of member utilities.
2. The socket and enclosure shall be designed in accordance with the latest revision of AEIC-
EEI-NEMA Standards for Watthour Meter Sockets, Publication ANSI C12.7, and
Underwriters Laboratories Standard for Meter Sockets UL414. Socket rim to jaw clearance
shall be no less than ANSI C12.7 (0.500”) or more than (0.690”).
Exception: The 0.690” dimension does not apply to transformer rated sockets and ground
and neutral clips on self-contained sockets.
a. For residential service applications, meter sockets shall have a maximum ampacity
rating not less than the ampacity rating of the associated service disconnect. The
maximum ampacity rating is 125% of the continuous-duty rating.
b. For commercial and industrial service applications, meter sockets shall have a
continuous-duty rating of 100 amperes for service disconnects rated up to 125
amperes (maximum) and a continuous-duty rating of 200 amperes for service
disconnects rated up to 250 amperes (maximum).
4. Sockets for self-contained meters shall be furnished, installed and wired by the customer.
Diagrams of connections are shown on Drawing G1 of the installation guides.
5. When self-contained meter sockets are installed in switchboards, they are to be wired by the
switchboard manufacturer. Consult Utility for use of lever bypass meter sockets.
6. Sockets for instrument transformer installations shall be furnished and installed by the
customer. The serving agency will furnish and install the normal secondary wiring from
the instrument transformers to the meter socket.
7. Potential taps, including the neutral potential tap, shall be located behind a sealed panel.
The customer's grounding electrode connection shall not be located within the meter socket
or socket area of a combination CT / meter enclosure.
8. Ring-type sockets shall be furnished with sealing rings. Consult Utility for use of ringless
sockets.
a. Hinged panels shall be fabricated and installed by the manufacturer for back
connection. See Dwg. 332 and 333
Note: Screws used to mount cast meter sockets to hinged panels shall provide a 1/8”
minimum clearance between the screw head and the back of the meter socket
ring.
b. Non-hinged panels shall be fabricated and installed by the manufacturer for front
connection. See Drawing 313, 314 and 339.
Note: Meter sockets shall be attached with machine screws so that they may be
interchanged or replaced. Sheet metal, self-tapping screws are not acceptable.
Sheet 2
EUSERC Drawing 300
10. All self-contained meter sockets shall be rigidly attached to the backwall of the socket
enclosure or to a stationary support connected to the enclosure. For ring-type meter panels,
the meter sockets shall be attached to the meter panel to assure alignment of the socket ring
to the socket jaws and prevent removal of the panel with the meter in place. Sheet metal or
self-tapping screws are not acceptable.
1. Sockets equipped with test-bypass disconnect facilities are required for some installations
and prohibited on others. For use in any particular locality, consult the serving agency.
1. The hinged meter panels shown on Drawings 332 & 333 are designed to accommodate only
transformer-rated socket meters. Self-contained sockets shall not be mounted on hinged
panels.
2. The nonhinged meter panels shall not be used in front of a current transformer section. For
a specially engineered switchboard, the nonhinged panel as shown on Drawing 336 will
accommodate a socket-type meter when used with current transformers
3. Not more than two meters shall be mounted on any removable meter panel.
4. Additional space may be required for recording or graphic demand meters (see Drawing
333).
5. Hinged meter panels and filler panels shall be equipped with stops to prevent inward
swinging beyond the front surface of the switchboards.
6. A hinged instrument transformer cabinet cover may be used provided there is proper
clearance to open the cover when the cabinet is installed. A cabinet with a hinged cover
shall be designed so that the cover cannot be removed by tampering with the hinges when
the cabinet cover is closed. Provisions shall be made for sealing the cabinet cover by use of
approved method.
7. All pull and termination section cover panels shall be removable, sealable, provided with
two lifting handles and limited to a maximum size of nine square feet in area.
H. Lifting Handles
1. When lifting handles are required on panels and covers, each handle shall be sized for full
hand grasping, securely attached and have strength to withstand handling stresses of a
minimum of 75 pounds.
Note: Chest type handles with a folding bale grasp are not acceptable.
I. Sealing
1. All cover panels, removable access panels and hinged panels for compartments containing
unmetered conductors shall be sealable. When a raceway or conduit for meter secondary
wiring is necessary, such a raceway or conduit shall be sealable. No removable panel or
cover requiring sealing shall be located behind other panels, covers or doors (except raintight
enclosure doors).
Sheet 3
EUSERC Drawing 300
Note: Carriage bolts may be used to secure cover panels in place of sealing provisions when
the bolts are installed at the factory and do not require field removal and installation to
complete assembly of the switchboard sections.
2. Sealable latches, stud and wing-nuts, or sealing screws shall be provided as the means of
sealing removable or hinged access covers.
3. Hinged cover panels shall be sealed on the side opposite the hinges.
4. Removable cover panels shall be sealed with stud and wing-nut assemblies on opposite
sides of the cover. Alternate sealing methods may be used if the removable covers are self-
supporting with the captive screws and sealing provisions removed.
a. Stud and wing-nut assemblies shall consist of a 1/4-inch x 20 (minimum) stud and an
associated wing-nut, each drilled 0.0635 inches (minimum) for sealing purposes. The
stud shall be securely attached so as to not loosen or screw out when being fastened.
b. Sealing screws shall be drilled 0.0635 inches (minimum) for sealing purposes.
c. Latching devices shall be designed to permit positive locking and be made of a durable
corrosion resistant material.
Test-bypass block compartment cover panels shall have a caution sign on the front reading "Do
Not Break Seal -- No Fuses Inside."
K. Unmetered Conductors
Customer unmetered service wires and metered load wires are not to be run in the same conduit,
raceway or wiring gutter. Metered and unmetered wires shall be separated by suitable barriers.
Metered wires from the customer's distribution section (branch circuits) shall not pass through
sealable sections. For exceptions, see Apartment Metering.
L. Bus Bars
1. Ampacity
a. The dimensions in these requirements are based on the use of rectangular bus bar.
Ampacities of bus bar conductors shall be based on UL-891. Standard for Dead-Front
Switchboard, including ampacities based on thermal limits provided for therein.
Maximum widths and number of bus bars shall conform to EUSERC requirements.
2. Plating
Sheet 4
EUSERC Drawing 300
Bus bars and other hardware attached to the outer walls of the enclosure shall be secured
with devices that may not be loosened from the outside. Screws or bolts requiring special
tools for installation or removal are not acceptable.
M. Service Disconnects
a. For each and every meter, the customer shall furnish and install a circuit breaker, fused
switch, or other approved disconnecting means with over-current protection referred to
in these requirements as a meter disconnect.
b. The meter disconnect shall control all of and only, the energy registered by its related
meter.
c. Where permitted by the serving agency, the meter disconnect may consist of up to six
separate devices.
(2) A lockable cover for each meter disconnect where the lock prevents the operation
of the disconnect and prevents removal of the cover, or
(3) A lockable cover for multiple meter disconnects where the lock prevents the
operation of any of the disconnects, prevents removal of the cover and all
disconnects are supplied from a single instrument transformer compartment.
(5) For fused disconnects, the fuse access cover shall be lockable when the disconnect
is in the off (open) position.
(6) All locking provisions for disconnects rated less than 400 amperes shall accept a
lock shank of not less than 1/4 inch.
(7) All locking provisions for disconnects rated 400 amperes and above shall accept a
lock shank of not less than 5/16 inch.
Sheet 5
EUSERC Drawing 300
a. A main service disconnect device is installed on the supply (line) side of a group of
meter sockets and may be a circuit breaker, fused disconnect, or other approved
disconnecting means.
b. A service disconnect shall be installed on the supply (line) side of more than six meter
sockets.
c. A service disconnect may be permitted on the supply side of two to six meter sockets.
Consult the serving agency for specific requirements.
d. A service disconnect is not permitted on the supply (line) side of a single meter socket
(Old Sequence).
e. The cover on a line side disconnect shall be sealable, (see Dwg 315 Note 5).
Manufacturers shall provide information and safety labels in utility compartments as follows:
1. Caution labels for switchboard pull sections shall be provided on the safety barrier and cover of each pull
section where energized bus is less than 4 inches from removable access cover panels. See drawing 347 for
additional requirements.
2. Torque labels shall be provided in each utility compartment where nut and bolt assemblies using cone-type
(Belleville) washers are used for utility terminations, test-bypass block circuit closing nuts, or for securing
current transformers or current transformer bus removable links. Labels shall be readily visible and shall
not be installed on any removable or hinged cover panel.
b. For current transformer installation labeling, see drawings 319, 320, 328A, 328B, 329A, 329B, 330,
and 331.
Self-contained meters are designed to carry rated current and be energized at line potential. They do
not require auxiliary instrument transformers to step down line current or voltage.
A. Residential, General
Four types of self-contained meters are commonly used for this application.
Sheet 6
EUSERC Drawing 300
B. Commercial, General
Class 100 or 200 socket-type meters are commonly used and test-bypass disconnect facilities are
required for this application. Some utilities allow Class 320 or Class 400 amp meters for
specialized installations (Go to www.euserc.com for specific utility requirements).
C. Multiple, Switchboard
1. The socket and socket enclosure shall be designed in accordance with the latest revision of
AEIC-EEI-NEMA Standards for Watthour Meter Sockets, Publication ANSI C12.7, and
with standard for Meter Sockets UL414.
2. The bussing or cables to each individual meter socket are to be installed so they can be
visibly traced.
3. Multiple meter enclosures that are not factory bussed shall have nonremovable, solid metal
barriers, to isolate the metered conductors from the unmetered conductors.
Sheet 7
EUSERC Drawing 300
4. The service termination enclosure, socket enclosures, raceways and sections for test-bypass
or manual circuit closing facilities shall have separate, removable and sealable access
panels (or plates). Meter socket enclosures shall have a separate sealable cover containing
no more than two meter positions.
1. The rules for spacing of socket meters in multiple residential meter installations shall be as
follows:
2. When these units are constructed with metered and unmetered conductors in the same
raceway behind adjacent meter sockets, the serving agency will require the following
additional specifications.
a. Metered and unmetered conductors shall be separated so that it is readily apparent that
all of the load is being metered (line and load conductors not cabled together).
b. Factory "harness-style" wiring (or equivalent) shall be used between the line wireway
and the line terminals of each meter socket and also between the load terminals of each
meter socket and the line side of the corresponding circuit breaker.
c. Connecting wires between meter socket load terminals and circuit breaker line
terminals shall be separately cabled for each position in the row.
d. When the installation is completed, all panels must be removable for inspection of
wiring.
e. Panel design shall permit convenient replacement of any individual meter socket.
A. General Requirements
1. Instrument transformer compartments are generally required when the connected load
exceeds 200 amperes. See Section 200 for exceptions and utility acceptability of these
requirements and Section 400 when the voltage between conductors exceeds 600 volts.
2. Meter, instrument transformers and test switches will normally be furnished and installed
by the serving agency. Any required conduits or raceways shall be furnished and installed
by the switchboard manufacturer or contractor, (See Section 200 for specific utility
requirements).
Sheet 7
EUSERC Drawing 300
1. For both standard and specially engineered switchboard service sections, all service or
supply conductors shall enter the service section through one end and leave through the
opposite end of the instrument transformer compartment. This stipulation applies to either
overhead or underground service or if two or more service sections are connected together.
The direction of feed shall be vertical through the instrument transformer compartment,
(See Drawing 345).
2. When more than one switchboard service section is installed, each service section shall be
completely barriered from other service sections, pull sections, or service switches or
disconnects. Barriers may have an opening to allow passage of un-metered conductors
between sections.
Note 1: The barrier between sealed utility metering sections and the pull section may be
1/8” minimum glastic or equivalent.
Note 2: The clearance between bus bar and glastic shall be a maximum of 3”. No barrier
shall be required between individual phases and neutral.
4. When two or more switchboard service sections are supplied from one set of service
conductors, the supply conductors are to be arranged so they are readily accessible without
disturbing the instrument transformers and associated secondary wiring.
5. Additional service connections may be made in the main service termination and pull
section where more than one metering installation is necessary, or where more than one
rate schedule is desired. Additional service connections shall not be made in the instrument
transformer compartment. Consult serving agency for approval.
6. Meter installations of six meters or less shall be connected "new sequence". Consult
serving agency for exceptions.
1. The general arrangement of a standard switchboard section is shown on Drawings 325 and
326.
2. A standard switchboard service section has a hinged meter panel located in front of the
instrument transformer compartment. Drawing 333 shows spacings for various
combinations of multiple meters.
3. Hinged meter panels must have handles and open a minimum of 90 degrees with meters
and test switches mounted to permit safe and ready access to the instrument transformers.
When hinged panels are recessed, the section shall have additional width to meet this
requirement. A recessed panel requires utility approval as a specially engineered section,
(see Drawing 354).
Sheet 8
EUSERC Drawing 300
4. Hinged meter panels must be sealable and easily removable, with the hinges readily
interchangeable from the right or left side on the job site.
5. The hinged meter panels on Drawings 332 and 333 are designed for transformer-rated,
socket-type meters.
Sheet 9
EUSERC Drawing 300
6. Meter panels and filler panels shall be equipped with stops to prevent inward swinging
beyond the front surface of the switchboard.
7. Not more than two meters shall be mounted on any removable meter panel.
9. For hinged socket meter panels, see Drawings 332 and 333.
1. Switchboards which do not conform to standard design criteria are considered specially
engineered and include installations:
b. Where the service breaker ampacity rating exceeds that of the standard service section.
b. If a hinged meter panel is located behind a door, a clear space of at least 11 inches
between the meter panel and the door is required, and shall be designed to open 90
degrees with meters and test switches in place. If needed, additional section width
shall be provided to meet this requirement.
c. A clear space in back of a meter panel shall be provided for the secondary wiring and
phase shifting device. For minimum dimensions between the hinged meter panel and
the nearest bus, see Drawings 319 through 324.
d. For nonhinged meter panels, a clear space of four inches minimum to any barrier or
obstruction shall be provided.
e. The nonhinged meter panels shall not be used in front of a current transformer section.
For a specially engineered switchboard, nonhinged panels will accommodate socket-
type instrument transformer-rated meters.
f. For minimum clearance between meters, (see Drawings 306, 333, 336, and 353).
g. Additional panel space is required for recording or graphic demand meters, see
Drawing 333.
Sheet 10
EUSERC Drawing 300
h. Not more than two meters shall be mounted on any removable meter panel.
j. The busses and current transformer mountings shall be designed so that each of the
current transformers may be withdrawn from its mounting position directly through the
access panel without disturbing any other current transformer. When multi-leaf busses
are used, the busses shall be oriented so that they appear "edgewise" when viewed from
the access panel.
E. Instrument-Transformer Compartments
1. For details of instrument transformer compartments, see Drawings 319 through 322.
2. Covers for instrument transformer compartments shall be made of code gauge metal; if
nonhinged panels are used as covers, they shall be provided with lifting handles and be
attached with sealable studs and wing-nuts or by other approved means.
3. Copper or aluminum bus bar shall be used on both the line and load sides of all current
transformers. When aluminum bus is used, the bus bars shall be plated, (see Bus Bar
Plating, Drawing 300).
4. When the serving agency requests links and supports for through-type current transformer,
the bus and removable links must be of a compatible material.
5. Instrument transformers supplied by the serving agency for metering shall not be utilized
for any other purpose
6. The ends of the current transformer bus stubs shall be located so the current transformers
can be installed without removing adjacent panels.
7. The current transformer bus stub supports in the instrument transformer compartment shall
be sufficiently rigid to maintain alignment of the bus when the conductors are installed.
The current transformers or bus links shall not provide bus support or alignment.
8. Except for factory-installed cross-bussing and conductors, either bus or cable, used to
supply the instrument-transformer compartment, no other conductors or devices shall be
installed in the instrument-transformer compartment or in the sealed area above the
instrument-transformer compartment.
Sheet 11
EUSERC Drawing 300
A. Switchboards Excluded
This paragraph of the Requirements applies to all meter and service equipment when not
installed on switchboards.
1. General
b. Service cable termination lugs or connectors shall be suitable for use with both
aluminum and copper conductors. The serving agency should be consulted for specific
lug or connector requirements.
c. Socket enclosures designed for single sockets rated up to, and including 200 amperes,
shall have service terminating lugs independently mounted from the socket jaw
support.
d. Tests for meter sockets shall be in accordance with the current Standard for Meter
Sockets UL414.
e. Service terminating space in enclosures rated greater than 200 amperes with multiple
meter sockets shall accommodate either compression-type lugs or screw-type
mechanical landing lugs. All bussing or cable conductors beyond the terminating lugs
shall be provided by the manufacturer or the customer's contractor. Bus stubs or
bussing in the service terminating space used for terminating the utility service lateral
shall have mounting bolts spaced in accordance with NEMA Standards. For
termination bus detail, see Drawing 343.
f. The service cable termination compression lugs, or screw type mechanical lugs shall be
compatible with the size and type of service being installed (i.e., aluminum-bodied AL-
CU with aluminum cables, etc.). The termination lug landings for the neutral and each
phase conductor shall be rigidly and permanently affixed in the service termination
space and all grouped at one location.
g. Wireways in the service termination space designed for terminating the utility service
lateral shall be clearly identified for such use. Service termination shall be made in the
service termination enclosure or in specially designated space of a meter panel which
has a separate removable and sealable access plate.
h. The layout or design of the service termination enclosure that requires bending the
utility service conductors, should provide space to permit a minimum cable bending
radius equal to four times the overall diameter of the cable measured from the inner
surface of the cable (from Minimum Bending Radius for Thermo-Plastic Insulated
Cables, IPCEA S-61-402 and NEMA WC-5-1961 Standards).
NOTE: The overall termination enclosure size is not predicated solely on the cable
bending radius. Adequate working space and electrical clearances are also
considered in establishing enclosure dimensions in these requirements.
Sheet 12
EUSERC Drawing 300
i. The service termination enclosure, socket enclosure and test-bypass disconnect block
section shall be sealable and isolated or barriered from other integral enclosure sections
which are accessible to the customer in order to effectively prevent unauthorized
connections to unmetered conductors or terminals.
j. The manufacturer's rating label, or other markings used in lieu of a label, shall show
among other things:
(1) Whether the socket or socket enclosure is designed for overhead service entry,
underground service entry, or both.
(2) That the terminating lugs are designed for both aluminum and copper conductors.
a. The socket and enclosure shall be specifically designed to receive service cables from
an underground supply system. Separate service terminating lugs supported
independent of the socket and connected to it by bus bars are required for single family
residential meter socket enclosures. (See Drawing 301.)
b. Wiring space for service lateral conductors shall be clearly identified as intended for
such use, shall be clear of all projections and shall be used exclusively for such
purposes.
c. A separate removable cover, independent of the meter panel, is required in front of the
pull section, (see Drawing 301.)
e. The service cable entry section and the meter socket section shall be sealable and
isolated or barriered from other integral enclosure sections which are accessible to the
customer in order to effectively prevent the attachment of unauthorized connections to
unmetered conductors or terminals.
f. The load wires from the distribution section (branch circuits) shall not pass through
any sealable section.
Sheet 13
EUSERC Drawing 300
B. Switchboards
a. For underground services, the serving agency will terminate its service conductors on
lug landings at the current transformer bus stubs only when the service is a single-
meter installation and the switchboard is rated 400 amperes or less.
NOTE: Some utilities require the service conductors to be terminated in the pull
section for switchboards rated less than 400 amperes.
(1) The serving agency will terminate its service conductors on lug landings in the
pull section when the service is for multiple metering or the switchboard is rated
401 amperes or larger, (see Figure 1 on Drawing 345).
(b) On switchboards rated 800 amperes, or with multiple meters, bus bars shall
extend from the service terminating lug landings into the current
transformer compartment or the meter sockets.
For overhead services, the customer shall furnish lugs and connect the cable to line and
load sides of the bus stubs in the current transformer compartment, (see Drawing 348).
Sheet 14
EUSERC Drawing 400
I. SCOPE
This section of the requirements applies only to revenue metering compartments of indoor and outdoor metal-
clad switchgear in 601 through 27,000 volt installations. See Drawings 401 and 404 for enclosure
requirements.
A. General
1. Drawing Approval
The manufacturer shall submit copies of the design drawings to the serving agency as required for
high-voltage metering equipment prior to fabrication. Such drawings shall indicate the customer's
name, the job address, the contact address, and the telephone number of the manufacturer's
representative.
Compartments of the metering enclosure shall be permanently labeled with machine engraved
laminated phenolic (or equal) tags. Tags shall have quarter-inch white letters and numbers on red
colored material that is readily visible and mechanically attached to the face of the following
designated compartment.
Bare bus 7 inches above and below the current transformers shall be provided to permit application
of serving agency safety grounds. A grounding knob shall be provided on the line and load side of
the bus at each current transformer location.
4. Meter Panel
Meter panel and hinges are to be designed to adequately support a 25 pound load applied at the
unsupported end with 1/8 inch maximum sag when open. Bond meter door to switchgear enclosure
with a #4 AWG flexible braided bond wire. See drawings 408 and 409 for meter panel layout.
5. Lifting Handles
When lifting handles are required on panels and covers, each handle shall be sized for full hand
grasping, securely attached and have strength to withstand handling stresses of a minimum of 75
pounds. See drawings 401, 408, 409 and 418.
Note: Chest type handles with a folding bale grasp are not acceptable.
B.I.L. (Basic Impulse Level) for the metering enclosure shall be not less than that for the customer's
associated switchgear. Reference shall be made to ANSI Standards for the minimum acceptable
B.I.L. ratings for high voltage switchboards built to the listed nominal voltages shown in the
applicable tables "Voltages and Insulation Levels for AC Switch gear Assemblies" and as tabulated
for Metal Enclosed Interrupter Switchgear. The metering cubicle shall be labeled with the B.I.L.
rating.
Working clearances (*) at the customer's job site may determine if the manufacturer is to furnish
either a single or double full height hinged rear door access. Provisions for a three point locking
mechanism with hardware for attachment of the utility-furnished padlock are required.
All external doors shall, when open, be equipped with a device to hold door at 90 degrees or more.
Enclosure sketches on the following drawings show equipment with weatherproof doors. The meter
panel shall be hinged on the side opposite that of the outer door on weatherproof units to permit 90
degrees opening with the meters and test facilities in place. The weatherproof doors may be omitted
if the equipment is located indoors. If the outer door is omitted, the meter panel must be lockable.
The front weatherproof door shall be a single door equipped with a latch-type handle to
accommodate the serving agency's padlock.
9. CT And VT Installation
Current transformers and voltage transformers, meters, testing facilities, and all normal secondary
wiring from the transformers to the meters will be furnished and installed by the serving agency.
(*Consult with utility for working clearance. Working clearances are governed by utility, code
and customer requirements. Clearances can vary.)
Only copper or manufacturer approved aluminum bus shall be used in the metering enclosure.
When the main switch or circuit breaker enclosure is adjacent to and on the source side of the
metering enclosure, connections from the load side of the main switch or circuit breaker to the line
side of the current transformers shall be made using bus bars.
Where full BIL insulation cables or buses pass through compartment walls, full voltage and BIL
insulation system shall be provided.
C. Terminations
For service ampacities up to 800 amperes, one landing position (*) shall be provided on each phase
and neutral bus for each 400 amperes, or portion thereof, of service ampacity. All bolts shall be
secured in place and provided with nuts and pressure maintaining spring washers. All parts must be
plated to prevent corrosion. Consult the serving agency for termination requirements when the
ampacity exceeds 800 amperes.
(*) Two 1/2 inch steel bolts on 1-3/4 inch vertical centers extending 1 inch minimum to 1-1/2 inches
maximum from the mounting surface. Terminating bolts must be secured in place. “Secured in
place” shall mean that the stud will not turn, back out, or loosen in any manner when tightening or
loosening terminal nuts (including cross-threaded situations).
When an insulated neutral is required, it shall have full-voltage rated insulation from the metering
cubicle. Consult the serving agency to determine if an insulated neutral is required.
Voltage transformer and current transformer mounting bases are to be provided by the manufacturer
(See Drawing 407).
1. Voltage Transformers
Locate the front or leading set of voltage transformer mounting holes 9 inches from the voltage
transformer compartment door.
The current transformer bus units shall be drilled and spaced to accept the current transformers of
the proper rating and class (See Drawing. 407, 2 of 2), and permit installation and removal of
individual transformers without disturbing adjacent transformers. Center bus shall include a
removable link dimensioned the same as the current transformer bars on the metered phases.
Lugs for voltage transformer phase and neutral connections shall be provided in the voltage
transformer compartment.
4. Fuse Specification
Voltage transformer fuses shall be furnished and installed by the serving agency. The manufacturer
shall provide mounting clips for indoor current limiting fuses with mounting clip separation and fuse
ferrule diameter appropriate for the voltage rating of the equipment. Fuses shall be accessible
through V.T. interlocked compartment door.
1. Kirk Key interlocking is required between the voltage transformer disconnect and the voltage
transformer compartment door so that, for personal safety, the voltage transformer compartment
cannot be entered until all of the following conditions are met:
b. When the voltage transformer disconnect is fully open, the disconnect blades must ground
automatically.
2. The interlock system must prevent closing of the disconnect without first closing and locking the
voltage transformer compartment.
3. The local utility will be provided with two keys for the interlock system.
4. Primary contacts for the voltage disconnect shall be of the blade and jaw design or equivalent to
assure continued adequate contact. Wiping contact or pressure contact is not acceptable.
5. Operating handle or lever of the voltage transformer disconnect switch shall be padlockable in the
closed position.
6. The voltage transformer compartment door shall provide unobstructed access to the voltage
transformer and fuses.
7. Voltage Transformer Disconnect shall have minimum voltage rating equal to the customer equipment
supplied. Voltage rating and BIL shall be as listed in Table on II.A.6.
1. As an alternate, the meter panel may be mounted in front of the CT/Termination compartment,
provided that when the meter panel is opened the compartment is fully isolated by a removable or
hinged barrier.
2. All external and internal doors providing access to the CT bus including the outer door, meter panel
door and hinged barrier shall be equipped with a device to hold them open at 90 degrees or more.
V. FUSE SPECIFICATION
Voltage transformer fuses shall be furnished and installed by the serving agency. The manufacturer
shall provide mounting clips for indoor current limiting fuses with mounting clip separation and fuse
ferrule diameter dimensions as shown on drawings No. 401 and 404.
A. Vertical busing in the pull section and C.T. compartment shall be spaced 18 inches on centerline
between phases, and the center phase shall be on the enclosure centerline.
B. Current and voltage transformers will be outdoor type. Provide transformer mounting bases and
busing configuration (in the C.T. compartment) to accommodate this style transformer. Consult
utility for manufacturer catalog number and obtain C.T. drawing.