Transformers
Transformers
Transformers
TRANSFORMERS
A transformer is a static electrical machine which transfers electrical power or
energy from one circuit to another circuit at constant frequency.
CONSTRUCTION OF SINGLE PHASE TRANSFORMER
Magnetic core:
• Made of high graded silicon steel. CRGO Steel
• thin sheets (called laminations) to reduce losses.
• The laminations are insulated from each other by enamel insulation coating.
• The core of the transformer mainly serves two purposes as,
1. It provides support to the windings.
2.It provides a low reluctance path to the magnetic flux.
•KȠ is a proportionality
•f is the supply frequency,
•Bmax is the maximum or peak value of the flux density.
Minimization: core is designed by using silicon steel material
EDDY CURRENT LOSS
➢ Due to circulating currents in the core within the body of conducting material
Output=
OC TEST AND SC TESTS ON 1-PH TRANSFORMER
OC TEST OR NO LOAD TEST
• Conducted to determine the no-load current and Iron losses.
• This test is performed on the LV of the transformer.
• HV Secondary winding is open circuited.
• The Apparatus required are
1. Single Phase Transformer:1-No
2. 1-Phase Variac Variac :1-No
3. Ammeter :1-No
4. Voltmeter :1-No
5. LPF Wattmeter :1-No all are connected to their primary winding.
• The nominal rated voltage is supplied to their primary winding with the help
of the ac source.
Procedure for Open Circuit Test
• Connect the circuit as shown in the figure.
• Keep the autotransformer at its minimum output voltage position.
• Switch on the power supply and adjust the autotransformer to get the rated
supply voltage.
• Now note down the current and power shown by the ammeter and wattmeter
respectively.
• Let these are Io and Wo.
• The wattmeter reads the no load input power
• Wo = Pi = Iron losses
SC TEST (SHORT CIRCUIT TEST)
• The test is conducted on the high-voltage (HV) side of the transformer
• the low-voltage (LV) side (or the secondary) is short-circuited.
• To determine
1. Copper losses at full load as well as any load.
2. equivalent circuit parameters of the transformer
3.Voltage regulation at any load and power factor
• The Apparatus required are
1. Single Phase Transformer:1-No
2. 1-Phase Variac Variac :1-No
3. Ammeter :1-No
4. Voltmeter :1-No
5. UPF Wattmeter :1-No all are connected to their primary winding
• The wattmeter Wsc shows full load copper losses of the transformer.
SHORT CIRCUIT TEST ON SINGLE PHASE TRANSFORMER
Procedure for Short Circuit Test of Transformer
• Connect the circuit as shown in the figure.
• Keep the auto transformer output at its minimum voltage position
• Switch on the AC supply.
• Increase the applied voltage very slowly, and adjust it to get the current equal
to the rated value of the winding.
• Note down the wattmeter, voltmeter and ammeter readings.
• Let these are Wsc, Vsc and Isc
Where X01 is the total equivalent reactance of the transformer referred to primary
REGULATION OF TRANSFORMER
• Definition: the change in secondary terminal voltage (V2) from no-load to full load
at constant primary voltage and temperature.
• When the transformer is loaded with continuous supply voltage, the terminal
voltage of the transformer varies.
• The variation of voltage depends on the load and its power factor.
• If E2 – secondary terminal voltage at no load
V2 – secondary terminal voltage at full load
Mathematically,