IT7100 HMI User Guide
IT7100 HMI User Guide
User Guide
Reader
This manual is intended for users who use or understand Inovance HMI products,
including: electrical engineers, software engineers, and system engineers.
Revision History
Safety Instructions
■■ Safety Disclaimers
1. Before installing, using, and maintaining this equipment, read the safety information and
precautions thoroughly, and comply with them during operations.
2
2. To ensure the safety of humans and equipment, follow the signs on the equipment and all
the safety instructions in this user guide.
3. The“CAUTION,”
“WARNING,”and "DANGER”signs are only supplements to the safety
instructions.
4. Use this equipment according to the designated environment requirements. Damage caused
by improper usage is not covered by warranty.
5. Inovance shall take no responsibility for any personal injuries or property damage caused by
improper usage.
■■ Safety Levels and Definitions
Danger : The "DANGER" sign indicates that failure to comply with the notice
will result in severe personal injuries or even death.
WARNING : The "WARNING" sign indicates that failure to comply with the notice may result
in severe personal injuries or even death.
WARNING
◆◆ Interlock circuits and other circuits such as emergency stop, conventional protection,
forward and reverse rotation must be set outside the equipment; devices for
preventing equipment damage (up, down and reciprocating movement limit) must be
set outside the equipment;
◆◆ Set a“fault protection circuit”outside the equipment to prevent unsafe accidental
mechanical movement (for example, unexpected movement in the input/output
control area that cannot be monitored by this equipment);
◆◆ A user program is required to protect the system when a display, control,
communication or power failure occurs on the equipment;
◆◆ When designing the system, ensure that a communication fault between the
equipment and its main controller will not lead to equipment malfunction, which
could result in personal injury or equipment damage.
◆◆ During operation, keep live objects away from the metal housing of the equipment.
3
CAUTION
◆◆ Do not set any switch that may result in personal injury of the operator or equipment damage
on the touch screen. A separate switch is required for important operation to avoid accidents
caused by abnormal output or faults;
◆◆ Do not set any switch on the equipment to control safety operation, such as emergency stop.
Use a dedicated physical switch instead; otherwise, severe personal injury or equipment
damage may occur;
◆◆ Do not use this equipment as an alarm device for serious accidents such as serious personal
injury, equipment damage or system shutdown. Use dedicated hardware and/or mechanical
interlock for designing important alarms and the related control/triggering devices.
Installation
WARNING
◆◆ This equipment must only be used indoor. Ensure that the environment meets the
requirements in "Basic Parameters" below;
◆◆ Keep the equipment away from strong magnetic field, direct sunlight, high temperature,
flammable gas, steam or dust, otherwise there is danger of explosion;
◆◆ Do not use this equipment in places with tremendous temperature fluctuation or high
humidity; otherwise, condensation may occur inside the equipment and result in equipment
damage;
◆◆ Ensure that all cables are securely connected to the equipment. Loose connection may cause
wrong input or output signals.
CAUTION
◆◆ The ambient temperature must be within the storage temperature range recommended in this
guide. Otherwise, the LCD screen may fail.
Wiring
Danger
◆◆ Before wiring, cut off all power supplies. Failure to comply may result in electric shock or
damage to the circuit;
◆◆ Wire the DC power supply to the dedicated terminal as described in this guide;
◆◆ When preparing screw holes and wiring, ensure that no metal filings or cable residues fall into
the equipment. Failure to comply may result in fire, failure or electronic component damage
◆◆ After wiring, check carefully and ensure that the operating voltage and positions of the
terminals are correct. Otherwise, fire or accidents may occur.
4
CAUTION
◆◆ Cut off the main power supply before connecting the power supply of the equipment. Failure to
comply may result in electric shock.
◆◆ The input power of the equipment is 24 VDC. If the power input is not within 24 VDC±20%,
the equipment may be damaged. Thus, check regularly that the DC power provided by the
switching-mode power supply unit is stable.
Operation and Maintenance
CAUTION
◆◆ During operation, use your finger, rather than any other tool, to tap the screen. The user shall
be liable for any damage caused by excessive external force;
◆◆ Retired lithium batteries, LCD screens, capacitors and any other matters that may contain
ingredients that are hazardous to health and the environment must be disposed of as industrial
wastes.
☞☞ Safety Recommendations
◆◆ In the position where the operator directly contacts the machinery part, for example, where a
machinery tool is loaded/unloaded, or where a machine runs automatically, the onsite manual
devices and any other alternative means must be carefully arranged and designed so that they
are independent of the PLC and can start or terminate the automatic running of the system.
◆◆ If programs need to be modified when the system is running, apply a lock or take any other
necessary measures to ensure that only authorized personnel can perform such modification.
Disposal
CAUTION
◆◆ Treat scrapped module as industrial waste. Dispose the battery according to local laws and
regulations.
5
1 Product Information
1.1 Appearance and Model Number
■■ Appearance
■■ Model Number
*5&
.BSL 5ZQF .BSL 4QFDJ珝DBUJPOT
6
Product Model
Item
IT7100E IT7100S
One Micro SD interface
SD card interface (Supports Micro SD cards, push-push No SD card interface
type)
COM1 (RS422/RS485)
Serial port COM2 (RS232) COM1 (RS422/RS485)
COM3 (RS485)
◆◆ The design life of the built-in button cell is 5 years, and the actual service life
varies according to the working conditions (temperature, humidity).
NOTE
7
2 Mechanical Design Reference
2.1 Installation Environment
This equipment operates stably only within -10° C to 55° C (14° F to 131° F).
Temperature out of this range may cause damage, malfunction or performance
degradation of components. For special occasions, please consult your supplier;
1) Install the equipment in an environment free from strong mechanical
vibration;
2) Install the equipment in a cabinet with a depth of over 100 mm and keep a
space of at least 25 mm around the equipment;
3) Ensure that the equipment is installed away from cables and equipment with
strong interference, including AC power cords, PLC output modules, inverters
and relays. The input and output cables of the equipment must be shielded
and properly grounded;
4) The front panel of this equipment is rated IP65. When the equipment is
installed in a IP65-rated cabinet, the cabinet must retain its IP rating, which
means liquid sprayed on the cabinet cannot get into it.
地坒坘坑块坌坑坊 圶坆坕坈坈坑
坋坒坏坈坖
Recommended
Overall Dimensions Installation
Display Size Screw Hole Size
Model LxWxD Dimensions W × H
(inch) (mm)
(mm) (mm)
W+2 H+2
IT7100E 10.1 271 × 213 × 36 258 x 200 260 202
IT7100S 10.1 271 × 213 × 36 258 x 200 260 202
8
2.3 Installation Method
1) Align the equipment with the mounting holes in the mounting plate;
2) Put the 4 clasps (delivered with the equipment) into the 4 mounting holes in
top and bottom sides or left and right sides of the equipment from the back of
the mounting plate;
.PVOUJOHQMBUF
ʍ1VUUIFDMBTQJOUP
UIFNPVOUJOHIPMF
ʎ5JHIUFOUIFTDSFX
3) Tighten the clasp screws until the equipment is securely fixed on the
mounting plate. Recommended torque: 6.0±0.5 kgfcm (to ensure water
resistance and prevent deformation).
9
3 Electrical Design Reference
3.1 Terminal Description
#BDL7JFX 'SPOU7JFX
#BDL7JFX EFUBJM
4JEF7JFX
10
No. Name Description No. Name Description
Mounts a Micro SD card for
Ethernet communication data read/write and project
Micro
Ethernet port (RJ45) for file download
(3) (8) SD card
port communicating with a PLC Note: No Micro SD card
interface
with a LAN port or a PC. interface is available in
IT7100S
ON: normal
The slave USB
Blinking: unstable
Mini USB communication port to Power
(4) (9) OFF: power is off
port download and debug user indicator
(Note: Power indicators are
programs in a PC
not available in IT7100S)
Firmware
(5) upgrade For firmware upgrade
port
3.2 Wiring
■■ Power Connection
This equipment is powered by a 24 VDC power supply. Connect the positive pole
of the external power supply to the +24V terminal, and the negative pole to the 0V
terminal. Connect the grounding wire to the terminal marked with . See the
figure below:
+24V
0V
11
●● It is recommended to use a separate #14AWG conductor as the conductor
of the grounding wire. Directly connect the grounding wire to the system
grounding point without passing any housing or terminal of other electrical
equipment. This ensures that the grounding conductor will not carry the
current of other circuit branches. Keep the conductor as short as possible.
We provide accessories used with the Power port including metal clamp and
terminal block (Order No. 98050285) :
Accessory No.
Power Terminal 1
Metal Clamp 4
Plastic Bag 1
■■ Communication Connection
This equipment provides a DB9 communication port (DB9 male connector) and
1–3 built-in independent serial communication ports for connecting the PLC,
AC drive, printer or other intelligent devices. This equipment supports multiple
communication protocols and is often used as a communication master to access
data from external devices. The following figure shows the DB9 male connector:
1 2 3 4 5
6 7 8 9
$0.<348>
$0.<34>
$0.<34>
%#NBMFDPOOFDUPS
Signal
Pin No. COM1[RS485] COM1[RS485] COM2 COM3
2 Wires 4 Wires [RS232] [RS485]
1 - - - RS485-
2 - - RS232 RXD (data reception) -
RS232 TXD (data
3 - - -
transmission)
4 - TX+ (transmission positive) - -
12
Signal
Pin No. COM1[RS485] COM1[RS485] COM2 COM3
2 Wires 4 Wires [RS232] [RS485]
5 GND (signal ground)
6 - - - RS485+
7 RS485- RX- (reception negative) - -
8 RS485+ RX+ (reception positive) - -
9 - TX- (transmission negative) - -
5 1
① ②
③ ④ ⑤
⑥ ⑦ ⑧
9 6
Cable Connector
DB9 Female Connector 8-Pin Din Round Connector
and Pin
Signal level RS422 RS422
Pin No. Signal Pin No. Signal
7 RX- 4 TX-
8 RX+ 7 TX+
Cable connection
9 TX- 1 RX-
4 TX+ 2 RX+
5 GND 3 GND
Inovance H1U/H2U/H3U RS422
IT7070/IT7100 HMI COM1[RS422]
Compatible HMI communication ports
and Port Note: This cable is not suitable
Mitsubishi FX1N/2N/3U/3G RS422
for IT7150E.
communication ports
13
HMI user program In the HMI user project, set the COM1 port as“RS422/RS485”;
setting The HMI and PLC must have the same communication protocol and
for this cable data format settings.
5 1
① ②
③ ④ ⑤
⑥ ⑦ ⑧
9 6
Cable Connector
DB9 Female Connector 8-Pin Din Round Connector
and Pin
RS232, built-in RS232-RS422 RS422
Signal level
switching circuit
Pin No. Signal Pin No. Signal
1 - 4 TX-
2 RXD 7 TX+
Cable connection
3 TXD 1 RX-
4 - 2 RX+
5 GND 3 GND
14
3) In case of communication failure, the screen displays“Connection failed:
connection_1, station 1. err:10001”until the communication is established.
4) If the communication cable is long or passes through an environment with
electrical noise, use a shielded cable.
■■ USB Port
Mini USB: used to connect the PC with a universal USB communication cable, to
upload/download user configuration program and set HMI system parameters;
Type A: used to connect a USB drive, USB mouse or USB keyboard, plug and play.
■■ Ethernet Connection
The 10M/100M adaptive Ethernet port, located on the back of the equipment, can
be used for:
1. HMI configuration upload/download, system parameter setting and on-line
configuration simulation;
2. Connection with multiple HMIs to achieve multi-HMI online communication;
3. Communication with the PLC;
4. Connection with a HUB or Ethernet switch through a standard Ethernet cable
to join a LAN, or connection with the Ethernet port of a PC through a crossover
cable. Note: Use a shielded cable to ensure stable communication.
15
4 Programming Reference
Before programming, ensure that you have the following:
A computer having InoTouchPAD installed
A programming cable
An InoTouch 7000 series HMI
■■ Software
InoTouchPAD is a programming tool developed by Inovance. For the latest
version, contact your HMI supplier or download it from our website (http://www.
inovance.com).
■■ Requirements on Computer Specifications
1. CPU: Intel or AMD, 2 GHz or faster
2. Memory: 1 GB or above
3. Hard disk space: at least 1 GB free space
4. Display: color display with resolution of 1024 x 768 or above
5. Ethernet port or USB port: for uploading/downloading screen program
6. Operating system: Windows 7 or Windows 10
Connect an Inovance PLC to the port of the product as shown in the figure below.
1PXFSTVQQMZDBCMF
%#GFNBMFDPOOFDUPS
64#"
&UIFSOFUDBCMF
NJOJ64#
16
5 Touch Screen Calibration
If the touch screen becomes unresponsive or malfunctions, you can use the touch
screen calibration program to fix the problem.
■■ Starting the Calibration Program
Access the program through the system setup menu: After the HMI is powered
on and the screen displays“Long press to enter the Setup screen”,gently press
the screen with your finger until the screen displays“Release to enter the Setup
screen”.After you enter the system setup password, the system setup menu pops
up. Tap the Calibrate menu item.
■■ Detailed Steps
1) After entering the calibration mode, you will see " " in the upper left
corner of the screen (as shown below).
2) Use the stylus or your finger to tap the center of " ". " " will move in the
route as shown by the arrows below. Tap each point where " " stops.
3) After the 5-point calibration is completed, " " will disappear. Tap the blank
space of the screen to exit; if the calibration fails, the crosshair will return to
the upper left corner of the screen and you must repeat the calibration.
④ ③
17
Warranty Agreement
The warranty period of the product is 18 months (The period is subject to the
date information indicated by the barcode on the product, or the terms and
conditions of the purchase contract if otherwise specified). During the warranty
period, if the product fails or is damaged under the condition of normal use by
following the instructions, Inovance will be responsible for free maintenance.
Within the warranty period, maintenance will be charged for the damages due to
the following causes:
1) Improper use or uninstallation/repair/modification without prior permission
2) Fire, flood, abnormal voltage, other disasters, and secondary disasters
3) Hardware damage caused by dropping or transportation after procurement
4) Failure to operate the product by observing the User Manual provided by
Inovance
5) Faults and damages caused by factors outside of the product (such as
peripheral devices)
If there is any failure or damage to the product, correctly fill out the Product
Warranty Card.
The maintenance fee is charged as the the latest Maintenance Price List of
Inovance.
The Product Warranty Card is not re-issued. Keep the card and present it to the
maintenance personnel when seeking maintenance.
If there is any problem during the service, contact us or our agent directly.
You are assumed to agree on terms and conditions of this warranty agreement
by purchase of the product. This agreement shall be interpreted by Inovance
Technology.
18