Satec pm135
Satec pm135
PM135 DATASHEET
Modbus
101/104
DNP3
OPEN
PROTOCOL
Specifications are subject to change without notice. Copyright © 2021-2022 SATEC Ltd. PM135 Datasheet June 2022
1
PM135
FEATURES
2
PM135
3
PM135
SOFTWARE SUPPORT
` SATEC’s Power Analysis Software (PAS) for
comprehensive configuration and data
acquisition is available for download (free):
www.satec-global.com/power-analysis-software.
Always make sure to update .exe file with latest
version on webpage
` SATEC’s Expertpower web-based energy
management platform (subscription). Please visit
www.satec-global.com/Expertpower
` Any 3rd party software supporting open-protocol
APPLICATIONS
4
PM135
TECHNICAL SPECIFICATIONS
5
PM135
RS-485 optically isolated port Supported protocols Modbus RTU, DNP3, SATEC ASCII,
IEC 60870-5-101
Isolation 3000V AC @ 1 min
Connector type Removable, 5 pins for RS-422/485
Baud rate up to 115.2 kbps and DB9 for RS-232
Supported protocols Modbus RTU, DNP3, SATEC ASCII, Wire size Up to 14 AWG (up to 1.5 mm²)
IEC 60870-5-101
Connector type Removable, 3 pins
Wire size Up to 14 AWG (up to 1.5 mm²)
REAL TIME CLOCK
» Battery-backed clock
» Accuracy—typical error:
7 seconds per month @ 25°C (±2.5ppm)
» Typical clock retention time: 36 months
6
PM135
DISPLAY CONSTRUCTION
3x2” / 76x49mm backlit LCD display Weight 0.70kg (1.54 lb.)
3 color LED load bar graph (40-110%) Dimensions [H×W×D] 114×114×109mm (4.5×4.5×4.3")
Keypad 6 push buttons
MATERIALS
ENVIRONMENTAL CONDITIONS Case enclosure plastic PC/ABS blend
Operating temperature -30°C to 60°C (-22°F to 140°F) Front panel plastic PC
Storage temperature -40°C to 85°C (-40°F to 185°F) PCB FR4 (UL94-V0)
Humidity 0 to 95% non-condensing Terminals PBT (UL94-V0)
Connectors-Plug-in type Polyamide PA6.6 (UL94-V0)
Packaging case Carton and Stratocell®
(Polyethylene Foam) brackets
Labels Polyester film (UL94-V0)
STANDARDS COMPLIANCE
7
PM135
ORDER STRING
MODELS
Power Version PM135P
Energy Only PM135E
Energy and Harmonic Version PM135EH
OPTIONS
CURRENT INPUTS
5 Ampere 5
1 Ampere 1
5A split core remote high accuracy current RS5
sensor (HACS), 50/60Hz only
High Accuracy Current Sensors (HACS), HACS
50/60Hz only. Requires ordering of 3 HACS
CALIBRATION AT FREQUENCY
25 Hz* 25HZ
50 Hz 50HZ
60 Hz 60HZ
400 Hz* 400HZ
DISPLAY RESOLUTION
Low Resolution 1A, 1V -
High Resolution 0.01A, 0.1V H
POWER SUPPLY
85-265V AC and 85-290V DC ACDC
9.5-18V DC 1DC
18.5-58V DC (24V DC, 48V DC) 23DC
COMMUNICATION PROTOCOL
Modbus and DNP 3.0 -
Modbus and IEC 60870-5-101/104** 870
MOUNTING
Panel Mount (standard) -
DIN Rail Mounting DIN
TESTING AND CERTIFICATE
Full functional test, calibration at various work -
loads & detailed test report
All of the above plus ISO 17025 and ILAC CC
certified calibration certificate
NOTES
* Supported by 1A and 5A models only
** -104 requires ETH, does NOT work over cellular network
8
PM135
EXPANSION MODULE *
ANALOG OUTPUTS
4 Analog Outputs: ±1mA AO1
4 Analog Outputs: 0-20mA AO2
4 Analog Outputs: 0-1mA AO3
4 Analog Outputs: 4-20mA AO4
4 Analog Outputs: 0-3mA AO5
4 Analog Outputs: ±3mA AO6
4 Analog Outputs: 0-5mA AO7
4 Analog Outputs: ±5mA AO8
ADDITIONAL COMMUNICATION PORTS
Communication: Ethernet (TCP/IP) ETH
Communication: PROFIBUS PRO
Communication: RS232/422/485 RS232
Communication: 2G/3G GSM Modem** T3G
Communication: 4G Modem ** T4x
x: G=Europe; V=Verizon (US); A=AT&T (US);
T=Telstra (AUS)
Communication: RF RF-x-y
DIGITAL INPUTS
4 Digital Inputs (Dry Contact) / DIOR
2 Relay Outputs 250V / 5A AC
4 Digital Inputs (Dry Contact) / DIOS
2 SSR Outputs 250V / 0.1A AC
8 Digital Inputs (Dry Contact) 8DI
12 Digital Inputs / 4 Relay Outputs 250V/5A AC 12DIOR 12DIOR-
Digital Inputs Rating - Dry Contact (DRC), DRC or 48V or
48V, 125V or 250V 125V or 250V
12 DIOR module communication port:
None -
RS-485 485
Ethernet ETH
CAN CAN
NOTES
* Max. 1 module per instrument. Can be ordered separately.
** Does not support 870 protocol. Supplied with bendable antenna.
Specifications are subject to change without notice. Copyright © 2021-2022 SATEC Ltd. PM135 Datasheet June 2022