0% found this document useful (0 votes)
68 views3 pages

Al1901 00 - en Us

This document provides specifications for an IO-Link master with a Profinet interface. The device has 8 IO-Link ports and supports both Profinet and MQTT communication over Ethernet. It operates from 20-30VDC and has digital and analog input/output capabilities.

Uploaded by

richard.mooh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views3 pages

Al1901 00 - en Us

This document provides specifications for an IO-Link master with a Profinet interface. The device has 8 IO-Link ports and supports both Profinet and MQTT communication over Ethernet. It operates from 20-30VDC and has digital and analog input/output capabilities.

Uploaded by

richard.mooh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

AL1901

IO-Link master with Profinet interface


IO-Link Master CL PN 8P IP20

Application
Application I/O modules for use in the control cabinet
Electrical data
Operating voltage [V] 20...30 DC; (US ; to SELV/PELV)
Current consumption [mA] 300...3900; (US)
Protection class III
Sensor supply US
Max. current load total [A] 3.6
Inputs / outputs
Total number of inputs and
16; (configurable)
outputs
Number of inputs and outputs Number of digital inputs: 8; Number of digital outputs: 8
Inputs
Number of digital inputs 8; (IO-Link Port Class A)
Switching level high [V] 11...30
Switching level low [V] 0...5
Digital inputs protected
yes
against short circuits
Outputs
Number of digital outputs 8; (IO-Link Port Class A)
Max. current load per output [mA] 300

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — AL1901-00 — 30.11.2023 —
AL1901
IO-Link master with Profinet interface
IO-Link Master CL PN 8P IP20

Short-circuit proof yes


Interfaces
Communication interface Ethernet; IO-Link
Ethernet - PROFINET
Transmission standard 100Base-TX
Transmission rate 100 MBit/s
Protocol PROFINET
Factory settings IP address: 0.0.0.0
subnet mask: 0.0.0.0
gateway IP address: 0.0.0.0
MAC address: see type label
Note on interfaces IO-Link Integration Edition 2
CC-C (Conformance Class C) (IRT-Switch)
S2 redundancy
Netload Class III
CiR (Configuration in Run)
SNMP (Simple Network Management Protocol)
MRP (Media Redundancy Protocol)
Supported network topologies: line
ring
Ethernet - Internet of Things
Transmission standard 10Base-T; 100Base-TX
Transmission rate 10 MBit/s; 100 MBit/s
Protocol MQTT JSON
Factory settings IP address: 169.254.x.x
subnet mask: 255.255.0.0
gateway IP address: 0.0.0.0
MAC address: see type label
Note on interfaces Safety protocol: HTTPS
IO-Link Master
Transmission type COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud)
IO-Link revision 1.1
Number of ports class A 8
Operating conditions
Ambient temperature [°C] -25...65
Storage temperature [°C] -25...85
Max. relative air humidity [%] 90
Protection IP 20
Tests / approvals
EMC EN 61000-6-2
EN 61000-6-4
Mechanical data
Weight [g] 317.9
Material housing: PA orange

ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — AL1901-00 — 30.11.2023 —
AL1901
IO-Link master with Profinet interface
IO-Link Master CL PN 8P IP20

Accessories
Items supplied cage clamps: 9
Remarks
Remarks Further information is available in the manual.
Pack quantity 1 pcs.
Electrical connection
voltage supply X31
1 GND (US)
2 GND (US)
3 + 24 V DC (US)
4 + 24 V DC (US)
IO-Link Port Class A X01...X08
1 Sensor supply (US) L+
2 Digital input
3 Sensor supply (US) L-
4 C/Q IO-Link
Electrical connection - Ethernet
Connector: RJ45

EtherNet IP X21, X22


1 TX +
2 TX -
3 RX +
4 not used
5 not used
6 RX -
7 not used
8 not used
IoT X23
1 TX +
2 TX -
3 RX x
4 not used
5 not used
6 RX -
7 not used
8 not used