Microtech III Dps
Microtech III Dps
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Trending . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Adjusting PI Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Trending Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Additional Instructions and Information . . . . . . . . . . . . . . . . 4 Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 About this Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
IFB Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Using the Keypad/Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Alarm Clearing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Navigation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Compressor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Edit Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Operator’s Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Service Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Determining Unit State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Keypad/Display Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Off Operating State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Quick Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Start Up Operating State . . . . . . . . . . . . . . . . . . . . . . . . . . 48
View/Set Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Mechanical Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Unit Status Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Off to Prestart Pressure Equalization . . . . . . . . . . . . . . . . . 48
Temperature Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Prestart Pressure Equalization to Off . . . . . . . . . . . . . . . . . 48
Flow Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Prestart Pressure Equalization to Initialization . . . . . . . . . . 48
RF/EF Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Initialization to Normal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SAF Spd Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Initialization to Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . 48
Time/Date Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Initialization to Standby for Restart . . . . . . . . . . . . . . . . . . 49
Commission Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Normal to Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Normal to Standby for Restart . . . . . . . . . . . . . . . . . . . . . . 49
Timer Settings Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pumpdown to Standby for Restart . . . . . . . . . . . . . . . . . . . 49
SAF Set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pumpdown to Initialization . . . . . . . . . . . . . . . . . . . . . . . . . 49
RF/EF Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Standby for Restart to Off . . . . . . . . . . . . . . . . . . . . . . . . . 49
Inverter Compressor Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Inverter Compressor Cooling Operation . . . . . . . . . . . . . . 49
Outdoor Air Fan Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Input Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Expansion Valve Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Defrost Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Compressor Control PI_Loop . . . . . . . . . . . . . . . . . . . . . . 50
Alarm Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Compressor Output Control . . . . . . . . . . . . . . . . . . . . . . . . 50
Alarm/Event Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Fixed Speed Compressor Step Transitions . . . . . . . . . . . . 50
Alarm Delays Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Inverter Compressor Cooling State Descriptions . . . . . . . . . . . . . . 51
Manual Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Cooling Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Manual Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Pre Start Pressure Equalization . . . . . . . . . . . . . . . . . . . . . 51
Service Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Save/Restore Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Normal Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Operating Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Active Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Standby for Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Alarm Log Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Determining Cooling Status . . . . . . . . . . . . . . . . . . . . . . . . 57
Alarm Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Determining Heat Status . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Analog Input Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Determining Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . 58
Universal I/O Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Determining Heat Capacity . . . . . . . . . . . . . . . . . . . . . . . . 58
Digital Input Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Determining Supply Air Fan Capacity . . . . . . . . . . . . . . . . 58
Digital Output Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Determining RF/EF Capacity . . . . . . . . . . . . . . . . . . . . . . . 58
Modbus Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Determining Outside Air Damper Position . . . . . . . . . . . . . 58
Sensor Offsets Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Determining System Mode . . . . . . . . . . . . . . . . . . . . . . . . . 58
OAT Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Unit Configuration Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Unit Configuration Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Introduction
This manual provides information regarding the MicroTech® III Additional Instructions and Information
control system. It specifically describes the operation and
programmable options for units with refrigeration only controls For installation and startup instructions and general information
(ROC). regarding a Rebel™ rooftop unit, refer to the applicable model-
specific installation and maintenance manual (Table 1).
The ROC MicroTech III Controller is a device that is not
capable of complete, stand-alone operation. Information in the
controller can be displayed and modified by using the keypad/ Table 1: Installation and Maintenance Resources
display in the units main control panel. The ROC systems Unit Manual
require a third-party controller for the Rebel unit to function.
MicroTech III Remote Unit Interface IM 1005
DPS 03 – 28 IM 1125
WARNING
Electric shock hazard. Can cause personal injury or
equipment damage.
This equipment must be properly grounded. Connections and service to the
control panel must be performed only by personnel that are knowledgeable
in the operation of the equipment being controlled.
Introduction
CAUTION
Static sensitive components. A static discharge while
handling electronic circuit boards can cause damage to
the components.
Discharge any static electrical charge by touching the bare metal inside the
main control panel before performing any service work. Never unplug any
cables, circuit board terminal blocks, relay modules, or power plugs while
power is applied to the panel.
Modbus Communication
01 02 04 06 IFB
SAF ExFan OA Fan VarCmp
ACS1
ACS2
ACS3
IRT
Heat Pump Only
IFB Board
The IFB board is used to translate between the MicroTech III interconnected forming the ACS1 communication loop. On
controller Modbus and the Daikin inverter compressor/outdoor 208/230V units the A4P board controls both INV and OF1. On
fan boards’ proprietary protocol. 460/575V units the A4P board controls only INV and there is
a separate A5P board that controls OF1. If a unit is equipped
There are three “ACS” communication current loop channels
with an OF2 it is controlled by a separate A5P control board.
available on the IFB board; ACS1, ACS2 and ACS3. ACS1 is
Figure 3 shows the three possible board/loop arrangements
use for control of the inverter compressor (INV) and one or two
that make up the ACS1 loop.
outdoor fans (OF1 and OF2). ACS3 is use for control of the
indoor expansion valve (EVI) and if the unit is a heat pump the Expansion valves EVI and if applicable EVO are controlled
outdoor expansion valve (EVO). ACS2 is not currently used. by an expansion valve driver board EVB. The EVB board is
connected to the IFB board forming the ACS3 communication
INV, OF1 and OF2 are controlled by a combination of
loop. Figure 3 shows the ACS3 communication loop.
circuit boards designated A4P and A5P. These boards are
The keypad/display consists of a 5-line by 22 character display, The keypad/display Information is organized into Menu groups;
three keys and a “push and roll” navigation wheel. There is an Main Menu, Quick Menu, View/Set Unit Menu, Commission
Alarm Button, Menu (Home) Button, and a Back Button. The Unit Menu, Manual Control Menu, Service Menu, Unit
wheel is used to navigate between lines on a screen (page) Configuration Menu and Alarm list Menus.
and to increase and decrease changeable values when editing. NOTE: Only menus and items that are applicable to the
Pushing the wheel acts as an Enter Button. specific unit configuration are displayed.
The Main Menu allows the user to enter a password, access
Figure 4: Keypad Controls the Quick Menu pages, view the current unit state, access the
Alarm List Menu as well as access to information about this
unit. The Quick Menu provides access to status information
indicating the current operating condition of the unit. The View/
Set Unit Menus include basic menus and items required to
setup the unit for general operation. The Commission Unit
Menus include more advanced items for “tuning” unit operation
The first line on each page includes the page title and the line such as PI loop parameters and time delays. The Manual
number to which the cursor is currently “pointing”. The line Control Menu allows service personnel to test unit specific
numbers are X/Y to indicate line number X of a total of Y lines operation manually. The Unit Configuration Menu allows the
for that page. The left most position of the title line includes an user to access to the unit specific configuration information.
“up” arrow to indicate there are pages “above” the currently These generally do not needing changing or accessing unless
displayed items, a “down” arrow to indicate there are pages there is a fundamental change to or a problem with the unit
“below” the currently displayed items or an “up/down” arrow operation. The Alarm Lists Menu includes active alarm and
to indicate there are pages “above and below” the currently alarm log information.
displayed page.
Each line on a page can contain status only information or
include changeable data fields. When a line contains status
only information and the cursor is on that line all but the value
field of that line is highlighted meaning the text is white with
a black box around it. When the line contains a changeable
value and the cursor is at that line, the entire line is highlighted.
Each line on a page may also be defined as a “jump” line,
meaning pushing the navigation wheel will cause a “jump” to
a new page. An arrow is displayed to the far right of the line to
indicate it is a “jump” line and the entire line is highlighted when
the cursor is on that line.
Passwords
Various menu functions are accessible or inaccessible, Figure 5: Password Main Page
depending on the access level of the user, and the password
AHU 01 1/5
they enter, if any. There are four access levels, including no
password, Level 2, Level 4, and Level 6, with Level 2 having Enter Password
the highest level of access. Without entering a password, the Quick Menu
user has access only to basic status menu items. Entering Unit State=________
the Level 6 password (5321) allows access to the Alarm Lists Alarm Lists
Menu, Quick Menu, and the View/Set Unit Menus group. About This AHU
Entering the Level 4 password (2526) allows similar access The password field initially has a value **** where each *
as Level 6 with the addition of the Commission Unit Menu, represents an adjustable field. These values can be changed
Manual Control, and Service Menu groups. Entering the Level by entering the Edit Mode described below.
2 password (6363) allows similar access as Level 4 with the
addition of the Unit Configuration Menu.
Figure 6: Password Entry Page
NOTE: Alarms can be acknowledged without entering a
password. Enter Password 1/1
The main password page is displayed when the keypad/display Enter Password ****
is first accessed, the Home Key is pressed, the Back Key is
pressed multiple times, or if the keypad/display has been idle
Entering an invalid password has the same effect as continuing
longer than the Password Timeout (default 10 minutes). The
without entering a password. Once a valid password has been
main password page provides access to enter a password,
entered, the controller allows further changes and access
access the Quick Menu, view the current Unit State, access the
without requiring the user to enter a password until either the
alarm lists or view information about the unit.
password timer expires or a different password is entered.
The default value for this password timer is 10 minutes. It is
changeable from 3 to 30 minutes via the Timer Settings menu.
The following is a description of the MicroTech III menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit configuration.
See page 39
About This Unit
SO_Item= 123456_12345
Unit SN= FBOU123456789
App Version= 2506017xxx
Cf1-15= xxxxxxxxxxxxxxxx
Cf6-29= xxxxxxxxxxxxxxxx
HMI GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
OBH GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
See page 31 — 31 See page 32 — 35 See page 32 See page 36 See page 16
Manual Control Service Menus Unit Maintenance Unit Configuration Alarm Lists
Manual Control= Normal Timer Settings ► Operating Hours Apply Changes= No Active Alarms ►
Supply Fan= Off Operating Hours ► Unit Type= DPS/DAH(3) Alarm Log ►
SAF Spd Cmd= 0% Save/Restore Settings ► Control Type= RefOnly(3)
SAF Spd Cmd= 0% Active Alarms ► Clg Type= INV(4) For more detail go to:
INV/OF Ena= Off Alarm Log ► Comp Config= 1V1F1C(M) Figure 12, page 16
INV Cmp= Off Event Log ► Gen Clg Stgs= NA
INV Spd Cmd= 0% Alarm/Event Config ► Low Ambient= NA(0)
Comp 3= Off Analog Input Status ► Cond Ctrl= INV(8)
OA Fan= Off Universal I/O Status ► OA Dmpr/Econ= AirEc(3)
OA Fan Cmd= 0% Digital Input Status ► OA Flow Stn= None(0)
4 Way Valve= Off Digital Output Status ► Htg Type= None(0)
RcvSol Valve=Off Modbus Status ► Htg Stages= 1
BP Sol Valve= Off IP Set-up ► Max Heat Rise= 100
EVI Cmd= 0% HMI Set-up ► SAF Type= EBMVAV(F)
EVO Cmd= 0% Sensor Offsets ► RAF Type= None(0)
RF/EF Fan= Off RF/EF Ctrl= NA(0)
RF/EF Spd Cmd= 0% For more detail go to: 2ndDSPSnsr= NA(0)
OAD/Econo= 0% Figure 12, page 16 EFT/LCT Snsr= NA(0)
Reheat Valve= 0% Enrgy Rec= None(0)
RH Output= Off Clg Circ Type= 1Air(2)
Alm Output= Off Head P Ctrl= NA(0)
Bypass Ctrl= NA(0)
Unit Size= 012
Refrig Type= R410A(2)
Reheat Type= None(0)
Unit Voltage= 460V/60Hz(2)
EV Type= EVBSag(1)
Apply Changes= No
See page 18 — 21
View/Set Unit
Unit Status/Settings ►
Temperatures ►
Flow Status ►
SAF Spd Control ►
RF/EF Control ►
Date/Time/Schedules ►
See page 18 — 19 See page 20 See page 20 See page 20 See page 20 See page 21
Unit Status/Settings Temperatures Flow Status SAF Speed Control RF/EF Control Date/Time/Schedules
System Mode= Local OA Temp= XXX°F Supply Fan= __________ SAF Speed= XXX% RF/EF Cap= XXX% Time= hh:mm:ss
Heat/Cool In= Heat/Cool DRT1= XXX°F Ret/Exh Fan= _________ Speed Cmd= XXX% RF/EF Spd Cmd= XXX% Date= MM/DD/YY
CmpIntrLock= _________ DRT3= XXX°F UTC Diff= -60min
CmpCapIn= ___________ SRT= XXX°F DAYLIGHT SAVINGS
SAFSSIn= ____________ DFT= XXX°F DLS Strt Mon= Mar
SAFCapIn= ___________ IRT= XXX°F DLS Strt Wk= 2nd Week
EAFSSIn= ____________ ORT= XXX°F DLS End Mon= Nov
EAFCapIn= ___________ INVCompTemp= XXX°F DLS End Wk= 1st Week
RhtVlvIn= ____________ DLS Enable= Auto
OADCapIn= ___________
AlmResetIn=__________
Dehum Status= ________
Clg Status= ___________
Htg Status= ___________
SuplHtgStatus= ________
Econo Status= _________
Clg Capacity= XXX%
Htg Capacity= XXX%
Supl Htg Cap= XXX%
Reheat Cap= XXX%
SAF Speed= XXX%
RF/EF Cap= XXX%
OAD/Econo Cap=XXX%
See page 22 — 30
Commission Unit
Unit Set-Up ►
Timer Settings ►
SAF Set-Up ►
RF/EF Set-Up ►
INV Cmp Set-Up ►
OA Fan Set-Up ►
Exp Valve Set-Up ►
Defrost Set-Up ►
Alarm/Event Config ►
See page 22 See page 22 See page 22 See page 23
Unit Set-Up Timer Settings SAF Set-Up RF/EF Set-Up
Eng Units= English Pwd Timeout= 10min Max Vent Speed= 100% Max Vent Spd= 100%
Unit Name= xxxxxxxxxxxx Clg Stg Time= 5min Max SAF RPM= 2600 Max RF/EF RPM= 2600
Max SAF Hz= 60.0Hz Max RF/EF Hz= 60Hz
CmpOp_MinSAF= 20% RF/EF Status= XXXXX
SAF Status= XXXXX
See page 32 — 35
Service Menus
Timer Settings ►
Operating Hours ►
Save/Restore Settings ►
Active Alarms ►
Alarm Log ►
Event Log ►
Alarm/Event Config ►
Analog Input Status ►
Universal I/O Status ►
Digital Input Status ►
Digital Output Status ► See page 22 See page 32 See page 32 See page 33
Modbus Status ► Timer Settings Operating Hours Save/Restore Settings Active Alarms
IP Set-up ► Pwd Timeout= 10min Supply Fan= XXXXXh Save Params= No Alm Count: xx Clr Alms= No
HMI Set-up ► Clg Stg Time= 5min Ret/Exh Fan= XXXXXh Rstr Params= No +Alarm 1: Alarm Type ►
Sensor Offsets ► OffHtCIDelay= 120s INV Comp= XXXXXh Rstr Factory= No +Alarm 2: Alarm Type ►
Comp 3= XXXXXh SaveToCard= No ●
Cmp Cooling= XXXXXh LoadFromCard= No ●
Cmp Heating= XXXXXh CreateTrace= No ●
Trace To SD= No +Alarm 10: Alarm Type ►
3
3, 4 See connection on page 16
See page 38
Trending
Trending Ena= No
Apply Chgs= No
Sample Time= 300s
TrendOnOff= Off
Export Data= No
Clear Trend= Done
TrendFull= Wrap
DefaultTrend= No
Points 1–8 ►
Points 9–24 ►
Points 25–30 ►
Points 1–8 Points 9–24 Points 25–30
Point 1= INV% Point 9= Clg St Point 25= SSH
Point 2= STDOut Point 10= Htg St Point 26= SSHSpt
Point 3= SAF% Point 11= Cap%In Point 27= HDRT1
Point 4= EF% Point 12= INVCmd Point 28= HDRT3
Point 5= OAD% Point 13= CmpInLk Point 29= OilSts
Point 6= RH% Point 14= PTD Point 30= OilMng
Point 7= H/C Out Point 15= PTS
Point 8= OAT Point 16= EVI%
Point 17= EVO%
Point 18= OAFCmd
Point 19= OF1Spd
Point 20= OF2Spd
Point 21= Tc
Point 22= TcSpt
Point 23= DSH
Point 24= Teg
1 2
See page 100 See page 42
Fault Code Details IFB Comm Status
ACTIVE FAULT CODES IFB SW Vers= VP0329008
INVAlarmCode=______ IFBCommStatus=____
Code Text PrvCommStatus=_______
OF1AlarmCode=_______ MM/DD/YYYY HH:MM:SS
Code Text ACS1 DataRcvd=_______
OF2AlarmCode=_______ ACS3 DataRcvd=_______
Code Text
PREVIOUS FAULT CODES
PrvINVAlmCode=_______
Code Text 3 4
MM/DD/YYYY HH:MM:SS See page 33 See page 33 See page 33
PrvOF1AlmCode=______ Alarm Lists Active Alarms Alarm Log Alarm Details
Code Text Active Alarms ► Alm Count: xx Clr Alms= No Log Count: xx Clr Log= No ► +/-Alarm 1: Alarm Type
MM/DD/YYYY HH:MM:SS Alarm Log ► +Alarm 1: Alarm Type ► +/-Alarm 1: Alarm Type ► MM/DD/YYYY HH:MM:SS
PrvOF2AlmCode=______ Event Log ► +Alarm 2: Alarm Type ► +/-Alarm 2: Alarm Type ►
Code Text ● ●
LogCt:** Clr Log= -:No
MM/DD/YYYY HH:MM:SS
+Event 1 ► ● ●
+Event 2 ► ● ●
● +Alarm 10: Alarm Type ► +/-Alarm 10: Alarm Type ►
● ●
● ●
●
+Event 49 ►
+Event 50 ► +/-Alarm 50: Alarm Type ►
Event Details ►
+Alarm: Alarm Type ►
Alarm Date
Alarm Time
Quick Menu
Items in the Quick Menu (see Table 2) contain basic unit operating status and control set point parameters. The items shown in the
Quick Menu are Read Only if a valid password has not been entered. The following are brief descriptions of the Quick Menu items.
No password is required to view the Quick Menu.
System Mode is an adjustable item that sets the status for OAD/Econo Cap is a status only item which indicates the
the for the unit to run on local with field inputs are ignored or percentage that the outdoor damper or economizer valve is
remote where operation is based on field inputs currently open.
Heat/Cool In is an adjustable item that only applicable Htg Capacity is a status only item which indicates the
on heatpump units to determine DX cooling or heatpump percentage of the unit maximum heating capacity currently
operation operating.
CmpInterLock is an adjustable input safety that can be used Reheat Capacity is a status only item which indicates the
to prevent compressor operation based on external system percentage of the unit maximum reheat capacity currently
safeties operating.
Dehum Status is a status only item which indicates the status SAF Capacity is a status only item which indicates the
of operation of the dehumidifier. The dehumidifier can be active capacity of the supply air fan.
or inactive. RF/EF Capacity is a status only item indicating the capacity of
Clg Capacity is a status only item which indicates the the return fan/exhaust air fans.
percentage of the unit maximum cooling capacity currently OA Temp is a status only item which displays the current
operating. temperature reading from the unit mounted outdoor air
temperature sensor. This sensor is standard on all units.
View/Set Menu
System Mode is an adjustable item that sets the status for Clg Status is a status only item which indicates whether or not
the for the unit to run on local with field inputs are ignored or mechanical cooling is currently allowed. If cooling is disabled,
remote where operation is based on field inputs the reason is indicated.
Heat/Cool In is an adjustable item that only applicable Htg Status is a status only item which indicates whether or
on heatpump units to determine DX cooling or heatpump not heating is currently allowed. If heating is disabled, the
operation reason is indicated. If the unit is a heat pump, this applies to
compressor heat.
CmpInterLock is an adjustable input safety that can be used
to prevent compressor operation based on external system Clg Capacity is a status only item which indicates the
safeties percentage of the unit maximum cooling capacity currently
operating.
CmpCapln is the adjustable input for the amount of DX output
desired Htg Capacity is a status only item which indicates the
percentage of the unit maximum heating capacity currently
SAFSSIn is the adjustable input for the supply fan start/stop
operating. If the unit is a heat pump, this applies to the
input
compressor heat.
SAFCapIn is adjustable input for the supply fan capacity
Reheat Capacity is a status only item which indicates the
desired
percentage of the unit maximum reheat capacity currently
EAFSSIn is the adjustable input for the exhaust fan start/stop operating.
input
SAF Capacity is a status only item which indicates the
EAFCapIn is the adjustable input for the exhaust fan capacity capacity of the supply air fan.
desired
RF/EF Capacity is a status only item indicating the capacity of
RhtVlvIn is the adjustable input for the amount of hot gas the return fan/exhaust air fans.
reheat desired
OAD/EconoCap is a status item which indicates the
OADCapIn is the adjustable input for the amount open desired percentage that the outdoor damper is currently open.
of outdoor air damper
AlarmResetIn the adjustable point from the field that can reset
applicable refrigeration alarms
Dehum Status is a status only item which indicates the status
of operation of the dehumidifier. The dehumidifier can be active
or inactive.
Temperature Menu
Menus in the Temperatures menu contain unit temperature status information.
OA Temp is a status only item which displays the current DFT (Heat Pump only) is a status only item which displays the
temperature reading from the unit mounted outdoor air current defrost temperature sensor reading.
temperature sensor.
IRT (Heat Pump only) is a status only item which displays the
DRT1 is a status only item which displays the current inverter current indoor refrigerant temperature sensor reading.
compressor discharge refrigerant line temperature sensor ORT (Heat Pump only) is a status only item which displays the
reading. current outdoor refrigerant temperature sensor reading.
DRT3 is a status only item which displays the current fixed INVCompTemp (15 ton unit size only) is a status only
compressor (Comp 3) discharge refrigerant line temperature item which displays the current inverter compressor body
sensor reading. temperature sensor reading.
SRT is a status only item which displays the current suction
refrigerant line temperature sensor reading.
Time/Date Menu
Table 8: Time/Date
Item Display Name Default Setting Range Password Level
Time= — 0 – 23: 0 – 59: 0 – 59 6
Date= — 1 – 12/0 – 31/1970 – 9999 6
UTC Diff= -60 — 4
NA
Jan
Feb
Mar
Apr
May
DLS Strt Mon= Mar Jun 2
Jul
Aug
Sep
Oct
Nov
Dec
1stSun
2ndSun
DLS Strt Wk= 2ndWeek 3rdSun 2
4thSun
5thSun
NA
Jan
Feb
Mar
Apr
May
DLS End Month= Nov Jun 2
Jul
Aug
Sep
Oct
Nov
Dec
1stSun
2ndSun
DLS End Week= 1stWeek 3rdSun 2
4thSun
5thSun
DLS Enable= Auto Off/Auto 2
Time is an adjustable item that sets the current time. DLS End Month is the adjustable item to select the month that
daylight savings locally ends
Date is an adjustable item that sets the current date.
DLS End Week is the adjustable item to select the week that
UTC Diff It is an adjustable parameter that can be set to
daylight savings locally ends
indicate how the local time where the unit is situated differs
from the Coordinated Universal Time (UTC). DLS Enable is an adjustable item that sets whether or not
daylight savings time is enabled
DLS Strt Mon is the adjustable item to select the month that
daylight savings locally begins
DLS Strt Wk is the adjustable item to select the week that
daylight savings locally begins
Commission Unit
RF/EF Set-Up
(See page 23 for more information)
Table 12: Return Fan/Exhaust Fan Set-up Menu
Item Display
Default Setting Range Password Level
Name
MaxVentSpd= 100% 0 – 100% N/A
Max RFEF RPM= 2600 0 – 5000 2
Max RF/EF Hz= 60.0Hz 0 – 100Hz 2
CompOp_
20% 10 – 100% 2
MinSAF=
OK
HLL
TFEI
TFM
TFE
BLK
“RF/EF Status=
— SKF 2
(EBM Fan)*”
PHA
UzLow
UzHigh
UeLow
UeHigh
NoComm
*See exhaust fan failure codes on page 98
Clg State is a status only item which displays the current Mechanical cooling operation is disabled when the outdoor air
compressor operating state when the unit is in the Cooling temperature sensor input falls below this set point.
operating state or when dehumidification operation is active. Clg OAT Diff is a status only item which indicates if the unit is in
See page 55 for compressor cooling operating state details. the deadband for the low ambient cooling lockout and will indicate
Htg State (Heat Pump only) is a status only item which when the unit is no longer in that lockout condition.
displays the current compressor operating state when the unit Htg Lo OAT Lk is an adjustable item that sets a low outdoor
is in the Heating or Min DAT operating state. See page 65 ambient temperature value below which compressor heating is
for compressor heating operation state details. locked out.
INV Cmp Spd is a status only item which displays the current Htg Hi OAT Lk is an adjustable item that sets a high outdoor
inverter compressor speed in percent of the maximum. ambient temperature value above which compressor heating is
INV Spd Cmd is a status only item that indicates the current locked out.
commanded speed of the inverter compressor. EffHtgOATLk is a status only item that displays the current
VCmpOilStatus is a status only item which displays if the unit is value that is being used for high outdoor ambient compressor
in oil boost mode or standard operation. Open indicates a low oil heating lock out. Normally this value reads the same as the Htg
reading Hi OAT Lk but can be lower due to the low differential pressure
limiting function while the unit is operating in the Heating or
Comp 3 is a status only item which displays the current on/off
MinDAT states.
status of the fixe compressor.
Htg OAT Diff is a status only item which indicates if the unit is the
INV Port Temp is a status only item which displays the current
deadband for the high ambient compressor heating lockout and
value of the calculated temperature (based on the current
will indicate when the unit is no longer in that lockout condition
suction pressure reading) at the inverter compressors inlet
port. This value is used in the inverter compressor discharge INV Period is an adjustable item that sets the sample period
line higher temperature limiting protection function. for the PI loop used to control the compressor capacity to
maintain the effective discharge air temperature set point.
INV Fin Temp is a status only item which displays the current
inverter compressor control board cooling fin temperature. INV Gain is an adjustable item that sets the Gain for the PI
This value is used in the inverter compressor fin temperature loop used for the PI loop used to control the compressor
limiting protection function. capacity to maintain the effective discharge air temperature set
point.
INV Amps is a status only item which displays the amps used by
the inverter compressor (3-15Ts only). This can indicate a high INV PAT is an adjustable item that sets the project ahead
amp unloading occurance. time for the PI loop used for the PI loop used to control the
compressor capacity to maintain the effective discharge air
Ctrl Card Tmp is a status only item which displays the drive
temperature set point.
temperature (16-28Ts only). This can indicate a high temp
unloading occurance. INV Max Chg is an adjustable item that sets the maximum
change value for the PI loop used for the PI loop used to
Heatsink Tmp is a status only item which displays the board
control the compressor capacity to maintain the effective
heat temperature (16-28Ts only). This can indicate a high temp
discharge air temperature set point.
unloading occurance.
OilManagement is a status only point that indicates if the unit
PTD is a status only item which displays the current value of
(16–28 Ton only) is in a oil boost mode or not.
the discharge line refrigerant pressure.
LowOilTime is an adjustable point to set the length of time,
PTS is a status only item which displays the current value of
while in oil return mode, the unit will verify oil level as adequitely
the suction line refrigerant pressure.
maintained.
4 Way Valve (Heat Pump only) is a status only item which
OilBoostTime is an adjustable point to set the length of time,
displays the current Heat/Cool (Closed/Open) status of the
while in oil return mode, the unit will actively accellerate the
heat pump four way reversing valve.
compressor speed to return oil to the compressor.
RcvrSol Valve (Heat Pump only) is a status only item which
VFD Status is a status only point from the inverter compressor
displays the current Open/Closed status of the heat pump
VFD (16–28 Ton only) indicating the current state of the drive.
receiver solenoid valve.
VFD Alm/Wrn is a status only point from the inverter
BP Sol Valve is a status only item which displays the current
compressor VFD (16–28 Ton only) indicating the drive fault
Open/Closed status of the refrigerant circuit bypass solenoid
codes.
valve. This valve is normally closed but opens when needed to
equalize the low and high side refrigerant pressures.
Clg Stg Time is an adjustable item used to set a minimum time
period between compressor stage changes
Clg Lo OAT Lk is an adjustable item which sets the low
outdoor air temperature mechanical cooling lockout point.
IRT (Heat Pump only) is a status only item which displays the OC SC Spt is an adjustable item that sets a base value for the
current indoor refrigerant temperature sensor reading. Eff SC Spt during cooling operation.
ORT (Heat Pump only) is a status only item which displays the OC SC DB is an adjustable item that sets a deadband around
current outdoor refrigerant temperature sensor reading. the Eff SC Spt during cooling operation.
SSH DB is an adjustable item that sets deadband around ClgSC EVO Min= is an adjustable item which sets a minimum
the Eff SSH Spt for superheat control of either the indoor outdoor expansion valve position for steady-state sub cooling
expansion valve (cooling operation) or outdoor expansion valve reset control during heat pump cooling operation.
(EVO). ManCtrl EV Op is an adjustable item that sets the mode of
SSH Lo Base is an adjustable item that sets a low limit for expansion valve control during Manual Control operation.
the EffSH Base value. This parameter is for test purposes and If set to “Auto” the expansion values are automatically
should not generally be changed in the field. controlled during Manual Control operation. If set to “Man”
the expansion valves are manually controlled during Manual
SSH Hi Base is an adjustable item that sets a high limit for
Control operation.
the EffSH Base value. This parameter is for test purposes and
should not generally be changed in the field. Expansion Valve Control (EVI or EVO, EVO supplied only
on heat pumps)
Htg EVI Method (Heat Pump only) is an adjustable item
that sets the method of control of the indoor expansion valve The EVI valve is modulated use a PI Loop during cooling
(EVI) during heating operation. If set to “STD” EVI is driven operation to maintain the effective suction superheat set point.
continuously to 100% open during heating operation. If set to On heat pump units EVI is either driven to the 100% open
subcooling “Sbc” then EVI is control to maintain the Eff SC Spt position or modulated to maintain the effective subcooling set
during heating operation. point during heating operation.
IC SC Spt is an adjustable item that sets a base value for the The EVO valve is modulated use a PI Loop during heating
Eff SC Spt during heating operation. operation to maintain the effective suction superheat set
point. EVO is either driven to the 100% open position or
IC SC DB is an adjustable item that sets a deadband around modulated to maintain the effective subcooling set point
the Eff SC Spt during heating operation. during cooling operation.
HtgSC EVI Min= is an adjustable item which sets a minimum
indoor expansion valve position for steady-state sub cooling
reset control during heat pump heating operation.
Clg EVO Method (Heat Pump only) is an adjustable item that
sets the method of control of the outdoor expansion valve
(EVO) during cooling operation. If set to “STD” EVO is driven
continuously to 100% open during cooling operation. If set to
“Sbc” then EVO is control to maintain the Eff SC Spt during
cooling operation.
Defrost Set-Up
(See page 67 for more information) Defrost State (Heat Pump only) is a status only item which
displays the current state of defrost operation. The states are
Off, Initialization, Execute and Terminate.
Table 16: Defrost Set Up Menu
Manual DF (Heat Pump only) is an adjustable item that allows
Item Display Default Range Password for manual initiation of defrost operation.
Name Setting Level
Off MinCmpOpTm (Heat Pump only) is an adjustable item that
Init sets minimum time that compressor heating operation must
Defrost State= — 4 active in the current run cycle before defrost operation can be
Exec
Term initiated.
No MinAccCmpTm (Heat Pump only) is an adjustable item that
Manual DF= No 4
Yes sets minimum accumulated compressor heating run time since
MinCmpOpTm= 10min 0 – 60min 2 the last defrost cycle before defrost operation can be initiated.
MinAccCmpTm= 40min 0 – 300min 2 MaxFrostTm (Heat Pump only) is an adjustable item that
MaxFrostTm= 120min 40 – 360min 2 defines the maximum time during periods of potential coil
Defrost Temp= — -64 – 64°F 2 frosting that can accumulated without initiating a defrost cycle.
Tdef Adj= 0°F -4.0 – 4.0°F 2 Defrost Temp (Heat Pump only) is a status only item
CmpOpTm= — 0 – 50000.0min 2 which displays the effective temperature value the defrost
AccCmpOpTm= — 0 – 50000.0min 2 temperature input must fall below before defrost operation is
LoFrstAccTm= — 0 – 50000.0min 2 initiated base on temperature.
HiFrstAccTm= — 0 – 50000.0min 2
Tdef Adj (Heat Pump only) is an adjustable item that allows a
manual bias adjustment to be used in the internal calculation
of the Defrost Temp. Increasing this value would cause defrost
to be initiated at a warmer defrost temperature value and vise
versa.
CmpOpTime (Heat Pump only) is a status only item which
displays the time that compressor heating operation has been
active in the current run cycle.
AccCmpOpTm (Heat Pump only) is a status only item which
displays the accumulated time of compressor heating operation
since the last defrost cycle.
LoFrstAccTm (Heat Pump only) is a status only item which
displays the accumulated time since the last defrost cycle of
low frost potential.
HiFrstAccTm (Heat Pump only) is a status only item which
displays the accumulated time since the last defrost cycle of
high frost potential.
Alarm Menus
Manual Control
The manual control of operation is a function that is used for INV Spd Cmd is an adjustable item that sets the speed of the
operating the unit during a service call only. The unit must not inverter compressor. Note that the inverter compressor speed
be operated in this mode for any extended period of time. cannot be manually adjusted until the compressor operating
state reaches Normal after the INV Comp output is turned ON.
Table 18: Manual Control Menu
Comp3 is an adjustable item used to turn the fixed speed
Item Display
Default Setting Range Password Level
compressor ON and OFF. Note that the fixed speed
Name compressor cannot be manually turned on unless the SAF Spd
Normal Cmd is first set to at least 33%.
Manual Ctrl= Normal 4
ManCtrl
Off OA Fan is an adjustable item used to turn the outdoor fan(s)
Supply Fan= Off 4 ON and OFF.
On
SAF Spd Cmd= 0% 0 – 100% 4 OA Fan Cmd is an adjustable item that sets the speed of
INV/OF Ena= Off
Off
4
the outdoor fan(s). Note that once the INV Comp or Comp3
On output is turned ON the outdoor fan speed cannot be manually
INV Cmp= Off
Off
4
adjusted until the compressor operating state reaches Normal.
On
INV Spd Cmd= 0% 0 – 100% 4
4 Way Valve (Heat Pump only) is an adjustable item used
Off
to change the 4 way reversing valve from the Cool to Heat
Comp 3= Off
On
4 position. Note that this setting determines whether the
Off
compressors operate in the cooling or heating mode when they
OA Fan= Off
On
4 are manually started.
OA Fan Cmd= 0% 0 – 100% 4 RcvrSol Valve (Heat Pump only) is an adjustable item used to
4 Way Valve= Off
Off
4
open and close the receiver solenoid valve.
On
BP Sol Valve is an adjustable item used to open and close the
Off
RcvrSol Valve= Off 4 bypass solenoid valve.
On
Off EVI Cmd is an adjustable item used to set the position of the
BP Sol Valve= Off 4
On indoor expansion valve. Note that this can only be manually
EVI Cmd= 0% 0 – 100% 4 adjusted when the ManCtrl EV Op parameter is set to “Man”.
EVO Cmd= 0% 0 – 100% 4
EVO Cmd (Heat Pump only) is an adjustable item used to set
Off
RF/EF= Off 4 the position of the outdoor expansion valve. Note that this can
On
only be manually adjusted when the ManCtrl EV Op parameter
RF/EF Spd Cmd= 0% 0 – 100% 4
is set to “Man”.
OAD/Econo= 0% 0 – 100% 4
Reheat Valve= 0% 0 – 100% 4 RF/EF is an adjustable item that turns ON the return/exhaust fan.
Off RF/EF Spd Cmd is an adjustable item for units with variable
RH Output= Off 4
On
speed supply air fan on the return/exhaust fans that sets the
Off
Alm Output= Off 4 speed of the return/exhaust fan.
On
OAD/Econo is an adjustable item which is used to set the
Manual Ctrl is an adjustable item that puts the unit into manual economizer damper position.
control. Major components of the unit are turned ON and OFF by
Reheat Valve is an adjustable item used to manually drive the
this control. The units normal control sequences are overridden
reheat valve open and closed.
in this state with the exception of all the “fault” alarms and the
cooling circuit high pressure and low pressure alarms. RHOutput a status point for if the unit is in reheat mode or not.
Supply Fan is an adjustable item that turns on the supply fan. Alm Output is an adjustable item which is used to turn ON/
OFF the alarm output.
SAF Spd Cmd is an adjustable item only on VAV units that
sets the speed of the supply air fan. When Manual Control is set to ManCtrl, the Control Mode is
set to OFF so that the unit will not restart automatically. When
INV/OF Ena is an adjustable item used to turn the inverter Manual Control is set to Normal all digital outputs in the Manual
compressor/outdoor fan enable output ON and OFF. Inverter Control menu are set to OFF and all the analog outputs are set
compressor or outdoor fans cannot be manually controlled to 0.0% so that all outputs are in the OFF or minimum position
without first turning this output ON. when Manual Control is set to ManCtrl
INV Comp is an adjustable item used to turn the inverter
compressor ON and OFF. Note that the inverter compressor
cannot be manually turned on unless the SAF Spd Cmd is first
set to at least 33% and the INV/OF Ena output is turned ON.
Service Menus
“ROC
Configuration Code Position Description Values (Default in Bold)
Applicability”
0=None ●
16 Return Fan Type 6=EBMVAV
7=EBMCAV
0=None ●
1=Tracking NA
Return/Exhaust Fan Capacity Control
17 2=Building Pressure NA
Method
3=Speed/Network NA
4=OADamper NA
0=No
18 Second Duct Pressure Sensor NA
1=Yes
0=No
19 Entering Fan Temp Sensor NA
1=Yes
0=None ●
1=ConstSpdWh/NoRH ●
2=VarSpdWhl/Danfoss ●
20 Energy Recovery 3=VarSpdWhl/MD2 NA
4=VarSpdWhl/MD3 NA
5=VarSpdWhl/ABB ●
6=ConstSpdWhl/wRH ●
0=Individual NA
21 Cooling Circuit Type 1=2,3 or 4 Circ. Water Condenser NA
2=2 Circ Air Condesner ●
0=No ●
22 Head Pressure Control
1=Yes NA
0=Slave ●
23 Bypass Valve Control
1=Bypass NA
24,25,26 Unit Size Three Digits (Default = 050) ●
0=R22 NA
27 Refrigerant Type 1=R407C NA
2=R410A ●
0=None ●
28 Reheat Type 2=ModHG ●
3=StdHtRht NA
0=208/60Hz ●
1=230/60Hz ●
2=460/60Hz ●
3=575/60Hz ●
29 Unit Voltage
4=208/50Hz ●
5=230/50Hz ●
6=460/50Hz ●
7=575/50Hz ●
0=None ●
30 Expansion Valve Type 1=EVBSag ●
4=MTIIIDF ●
Trending
Trending Menus
The Trending Menus allow for setting up and managing onboard Default
trending of up to 30 data points within the controller. This data
can then be exported to an SD card. The trending memory will There are thirty default trend points for ROC. They will only not
begin over-writing the oldest existing data in the controller’s be recorded if manually programmed not to record.
memory when the allocated trending memory fills up. If an
SD card is installed in the controllers SD card reader slot, an Table 31: Default Trends Menu
automatic export of the data will occur every night at midnight.
Item Display
Default Setting Range Password Level
Name
Table 30: Trending Menu Point 1= INV% INV% 2
Point 2= STDOut STDOut 2
Item Display
Default Setting Range Password Level Point 3= SAF% SAF% 2
Name
Trending Ena= No No/Yes 2 Point 4= EF% EF% 2
Apply Chgs= No No/Yes 2 Point 5= OAD% OAD% 2
Sample Time= 300s 1-3600s 2 Point 6= RH% RH% 2
TrendOnOff= Off Off/On 2 Point 7= H/COut H/COut 2
AutoExpTime= 1440m 0-1440m 2 Point 8= OAT OAT 2
Export Data= No No/Yes 2 Point 9= ClgSt ClgSt 2
Done 2 Point 10= HtgSt HtgSt 2
Clear Trend= Done ClrData 2 Point 11= Cap%In Cap%In 2
ClrCfg 2 Point 12= INVCmd INVCmd 2
TrendFull= Wrap Wrap/Stop 2 Point 13= CmpInLk CmpInLk 2
DefaultTrend= No No/Yes 2 Point 14= PTD PTD 2
Point 15= PTS PTS 2
Trending Ena is an adjustable item which enables and Point 16= EVI% EVI% 2
disables the on board trending function. Point 17= EVO% EVO% 2
Point 18= OAFCmd OAFCmd 2
Apply Changes is an adjustable item which must be set to
Point 19= OF1Spd OF1Spd 2
make changes to trending point definitions and sampling rate
Point 20= OF2Spd OF2Spd 2
take effect.
Point 21= Tc Tc 2
Sample Time is an adjustable item used to the sampling rate Point 22= TcSpt TcSpt 2
for trending data points. Point 23= DSH DSH 2
Point 24= Teg Teg 2
TrendOnOff is an adjustable item which starts and stops the
Point 25= SSH SSH 2
on board trending function.
Point 26= SSHSpt SSHSpt 2
AutoExpTime is the length of time a trend is to be captured Point 27= HDRT1 HDRT1 2
Export Data is an adjustable item which initiates a manual Point 28= HDRT3 HDRT3 2
export of the current on board trend data to an SD card. Point 29= OilSts OilSts 2
Point 30= OilMng OilMng 2
Clear Trend is an adjustable item used to either clear only the
current trend data or the entire trend configuration.
TrendFull is a writable input that allows the user to define
once the trend is recorded to either stop recording or begin to
overwright the beginning of the trend
DefaultTrend is a status to reset all trend reading back to the
unit default settings or not.
Alarms
Alarm Clearing
Active alarms can be cleared through the keypad/display. Outdoor Refrigerant Temperature Sensor
Alarms are automatically cleared when power is cycled. Alarms Problem (Heat Pump only) – (ORT Sensor:
are cleared only if the conditions required to initiate the alarm
do not exist. All alarms and groups of alarms can be cleared
Problem)
via the network or keypad by setting the ClearAlms variable to This alarm occurs when the ORT sensor input is outside the
a non-zero value as indicated in the table below. Emergency range of -4 to 150°F continuously for the Sensor Alarm Delay
Off Faults can be set to automatically clear once the condition (default 30 seconds).
that caused the alarm is corrected. This can be accomplished When this alarm is active compressor cooling operation is
by navigating to Commission Unit/Alarm Configuration/Emerg disabled if ClgEVOMethod is set to “Sbc”. Otherwise not action
Stop and changing the default ManClr value to AutoClr. is taken.
NOTE: The enumeration text is what shows up on the
The alarm must be manually cleared once corrective action is
keypad/display not the number. The value of this
variable automatically reverts to zero when the taken.
alarms are cleared. This variable may be set through
the keypad in the Active Alarm menu. It may be set Fixed Speed Compressor Discharge Line
via LON using nviClearAlarms and via BACnet using Refrigerant Temperature Sensor Problem –
the ClearAlarms object. (DRT3 Sensor: Problem)
Alarm List Menu – see page 33. This alarm occurs when the DRT3 sensor input is shorted or open
circuited for the Sensor Alarm Delay (default 30 seconds). It can
Table 33: Alarm Clearing also occur when the fixed speed compressor is off and the input is
Value Action above 329°F or the compressor has been off for 20 minutes and
0 None
the input is below -4°F.
1 Clear All Faults
2 Clear All Problems When this alarm is active the fixed speed compressor is disabled.
3 Clear All Warnings
4 Clear All Alarms The alarm must be manually cleared once corrective action is
taken.
Problems
Inverter Compressor Discharge Line
OAT Temperature Sensor Problem - (OAT Refrigerant Temperature Sensor Problem –
Sensor: Problem) (DRT1 Sensor: Problem)
If the outside air temperature sensor (OAT) is present, a valid This alarm occurs when the DRT1 sensor input is shorted or open
OAT value is not provided via the network and the local OAT circuited for the Sensor Alarm Delay (default 30 seconds). It can
sensor is either shorted or open circuited for longer than the also occur when the inverter compressor is off and the input is
Sensor Alarm Delay (default is 30 seconds), the Outside above 329°F or the compressor has been off for 20 minutes and
Air Sensor problem occurs. When the OAT Sensor problem the input is below -4°F.
occurs, the unit continues to operate with the following When this alarm is active compressor cooling and heating
modifications: operation are disabled.
• Compressor heating and cooling operations are locked out. The alarm must be manually cleared once corrective action is
• Cooling Reset and Heating Reset revert to none if they taken.
are set to OAT
• Economizer is locked out due to high OAT Inverter Compressor Problem – (INV Comp:
When the alarm condition is no longer present, the OAT Sensor Problem)
problem automatically clears. This alarm occurs whenever the inverter compressor board
generates an internal fault code. Refer to the troubleshooting
Indoor Refrigerant Temperature Sensor section of this document for fault code details.
Problem (Heat Pump only) – (IRT Sensor: When this alarm is active compressor cooling and heating
Problem) operation are disabled.
This alarm occurs when the IRT sensor input is outside the range The alarm must be manually cleared once corrective action is
of -4°F to 150°F continuously for the Sensor Alarm Delay (default taken.
30 seconds). When this alarm is active compressor heating
operation is disabled if HtgEVIMethod is set to “Sbc”. Otherwise
not action is taken. The alarm must be manually cleared once
corrective action is taken.
Defrost Temperature Sensor Problem (Heat Outdoor Fan Problem – (OA Fan: Problem)
Pump only) – (DFT Sensor: Problem) On a single outdoor fan unit this alarm occurs when compressor
This alarm occurs when the DFT sensor input is shorted or open operation is forced to the Standby state due to an outdoor fan
circuited for the Sensor Alarm Delay (default 30 seconds). It can internal fault for a third time in a 30 minute period.
also occur if the input is outside the range of -47°F to 194°F. On a two outdoor fan unit this alarm occurs when compressor
When this alarm is active compressor cooling and heating operation is forced to the Standby state due an outdoor fan 2
operation are disabled. internal fault for a third time in a 30 minute period. Note that
outdoor fan 2 in this configuration provides critical cooling for the
The alarm must be manually cleared once corrective action is inverter/outdoor fan control boards.
taken.
When this alarm is active compressor cooling and heating
Suction Line Refrigerant Temperature Sensor operation are disabled.
Problem – (SRT Sensor: Problem) The alarm must be manually cleared once corrective action is
This alarm occurs when the SRT sensor input is shorted or open taken.
circuited for the Sensor Alarm Delay (default 30 seconds). It can
also occur if the input is outside the range of -47°F to 194°F. Low Refrigerant Charge Problem – (Lo Charge:
Problem)
When this alarm is active compressor cooling and heating
operation are disabled. During compressor cooling operation this alarm occurs when the
indoor expansion valve (EVI) is fully open (greater that 95%),
The alarm must be manually cleared once corrective action is the super heat is well above set point (greater than 20°F) and
taken. the lower of the two discharge line temperature inputs (DRT1
and DRT3) is hot (greater than 150°F) for more than 30 minutes
High Inverter Compressor Discharge Line continuously.
Temperature Problem – (Hi DL Temp: Problem)
During compressor heating operation this alarm occurs when the
This alarm occurs when the High Discharge Line Temperature outdoor expansion valve (EVO) is fully open (greater that 95%)
Unloading function has forced compressor operation to the and the super heat is well above set point (greater than 20°F) for
Standby state for a third time in a 100 minute period. more than 60 minutes continuously.
When this alarm is active compressor cooling and heating When this alarm is active compressor cooling and heating
operation are disabled. operation are disabled.
The alarm must be manually cleared once corrective action is The alarm must be manually cleared once corrective action is
taken. taken.
Low Refrigerant Pressure Problem – Variable Compressor Oil Problem - (Var Comp
(Lo Press 1: Problem) Oil Problem)
This alarm occurs when either the Cooling Low Pressure This alarm occures when either the variable compressor
Unloading or the Heating Low Pressure unloading function has has been operating at the max speed or for the oil boost
forced compressor operation to the Standby state for a third time period and the low oil flag is still active or the maximum
time in a 30 minute period. number of oil boost cycles within a 24hr period have occurred.
When this alarm is active compressor cooling and heating When this alarm is active compressor cooling and heating
operation are disabled. operation is disabled.
The alarm must be manually cleared once corrective action is The alarm must be manually cleared once corrective action is
taken. taken.
Compressor Protection
Heating High Pressure Protection Control Fixed Speed Compressor High Discharge Line
Normal compressor operation is limited during heating operation Temperature Unloading Control
when high discharge pressure or high inverter compressor Normal fixed speed compressor operation is limited when high
discharge line temperature conditions occur while the inverter discharge line temperature (DRT3) conditions occur. When
compressor is operating alone (fixed speed compressor off or DRT3 rises above 275°F or above 248°F continuously for 5
not present) at low speed. This is an indication that too much minutes or when a calculated inverter compressor suction port
liquid is backing up in the condenser causing hot high pressure temperature (Tp) value rises above 293°F or above 275°F
conditions. When the DRT1 sensor input rises above 234°F or continuously for 10 minutes, the fixed is stopped.
the discharge pressure rises above 455 psi while the inverter Once active this limiting function remains active for 10 minutes.
compressor is operating alone at low speed, the inverter
compressor capacity is immediately reduced to minimum speed Inverter Compressor High Current Unloading
and the indoor expansion valve (EVI) is driven fully open. Note Control
the bypass solenoid valve is also opened if DRT1 is above
Normal compressor operation is limited when high inverter
234°F or if the pressure is above 469 psi.
compressor current conditions occur. When the internal inverter
Once active this limiting function remains active until the discharge compressor amp draw exceeds 14.7A (460/575V unit) or 26.5A
pressure falls back below 427 psi, DRT1 is below 225°F and (208/230V unit) the inverter compressor capacity is immediately
Heating High Pressure Unloading is inactive. reduced by one step and then reduced a further step every 15
seconds in an attempt to keep the amps below these values.
Heating Low Pressure Unloading Control Once active this limiting function remains active until the amps
Normal compressor operation is limited during heating operation are above these values and the inverter capacity is back to the
when low suction pressure conditions occur. When the suction normal unlimited value.
pressure falls below 24 psi the inverter compressor is reduced
by three steps then reduced a further step every 10 seconds in Inverter Compressor Request for Unloading
order to keep the pressure from falling below 19 psi. If reducing Control
the compressor capacity fails to keep the pressure above 19 psi, Normal compressor operation is limited when inverter
the inverter compressor is reduced to minimum and any fixed compressor control board provides a request to unload. This
speed compressor running is stopped. If the suction pressure can occur for a number of internal compressor board built-in
continues to fall below 10 psi, compressor operation is forced protection reasons (high amp draw for example). When the
to the Standby state where it remains for a heating stage time inverter unload request is active, the inverter compressor
period before being allowed to restart. If the unit is forced to capacity is immediately reduced by one step and then reduced
Standby in this manner 3 times in a 30 minute period, a low a further step every 15 seconds as long as the request remains
pressure alarm is generated requiring manual reset. active.
Once active this limiting function remains active until the suction Once active this limiting function remains active until the request
pressure rises back above 33 psi. becomes inactive and the inverter capacity is back to the normal
unlimited value.
Inverter Compressor High Discharge Line
Temperature Unloading Control High Compression Ratio Unloading Control
Normal compressor operation is limited when high inverter Normal compressor operation is limited when the ratio between
compressor discharge line temperature (DRT1) conditions the compression ratio between the discharge and suction
occur. When DRT1 rises above 239°F or a calculated suction pressure becomes too high. CmpRatio=(PTD + 14.7)/(PTS +
port temperature (Tp) value rises above 275°F, the inverter 14.7). Note: in this equation PTD and PTS are in PSI. When
compressor capacity is immediately reduced by one step and the compression ratio exceeds 8.5 the inverter compressor is
then reduced a further step every 30 seconds in an attempt to immediately reduced by three steps then reduced a further step
keep the temperatures from rising further. If DRT1 continues to every 10 seconds in an attempt to keep the compression ration
rise above 266°F or above 248°F continuously for 90 seconds, from continuing to increase. If the compression ratio continues to
the inverter compressor is reduced to minimum and any rise above 8.9, the inverter compressor is reduced to minimum
operating fixed speed compressor is stopped. If DRT1 continues and any operating fixed speed compressor is stopped.
to rise above 275°F or above 248°F continuously for 10 minutes
or Tp rises above 302°F, compressor operation is forced to the Once active this limiting function remains active until the
Standby state where it remains for a stage time period before compression ratio falls back below 8.0.
being allowed to restart. If the unit is forced to Standby in this
manner 3 times in a 100 minute period, a high inverter discharge
line temperature alarm is generated requiring manual reset.
Once active this limiting function remains active until DRT1 falls
back below 212°F and Tp is below 230°F.
Inverter Compressor High Board Temperature Low Differential Pressure Protection Control
Unloading Control Normal compressor operation is overridden when the
Normal compressor operation is limited when inverter differential pressure between the high and low side of the
compressor control board indicates an abnormally high board refrigeration circuit (PTD-PTS) is abnormally low. This
(fin) temperature value. This indicates the inverter compressor condition can inhibit proper oil return for lubricating the
board is not receiving problem ventilation. When the inverter inverter compressor. When the differential pressure falls
board temperature exceeds 183°F (460/575V unit) or 178°F below 85 psi continuously for 40 seconds, the inverter
(208/230V unit), the inverter compressor is immediately compressor capacity is increased by one step then increased
reduced by one step then reduced a further step every 15 a further step every 40 seconds in an attempt to increase
seconds in an attempt to keep the board temperature from the differential pressure. If the inverter compressor is at
continuing to increase. The outdoor fan(s) are increased to maximum speed for 40 seconds and the differential pressure
maximum speed. is still below 85 psi, compressor operation is forced to the
Standby state where it remains for a stage time period before
Once active this limiting function remains active until the being allowed to restart. If the unit is forced to Standby in
inverter board temperature falls 5.4°F below the high limit. this manner 3 times in a 30 minute period, a low differential
pressure alarm is generated requiring manual reset.
Once active this limiting function remains active until the
differential pressure rises back above 171 psi.
To prevent excessive cycling of the compressor heating on an
off during moderate heating load conditions, special steps are
taken if this protection function causes the unit to cycle out of
heating while it is active. If this occurs, the current effective
compressor heating ambient lock out setting is reduced 10°F
below the current outdoor air temperature which will lock out
compressor heating operation. The effective compressor
heating ambient lock out setting remains at this lower value
until any of the following occur:
• 120 minutes elapses
• The effective minimum outdoor damper position changes
by more that 10%.
• The effective discharge air heating set point changes by
more than 5°F.
• The outdoor air temperature falls below this lower
effective compressor heating ambient lock out setting.
Operator’s Guide
Initialization to Normal
Mechanical Cooling
The Compressor Cooling State transitions from Initialization
The unit enters the mechanical cooling operating state when to Normal when the initialization sequence is complete. See
cooling is called for by the third-party controller. Initialization state description in the Inverter Compressor
Cooling State Descriptions section, page 51.
Figure 14: Cooling State Diagram
Initialization to Pumpdown
The Compressor Cooling State transitions from Initialization to
Pumpdown if there is no longer a call for cooling operation.
Normal Cooling
In the Normal Cooling state the following are accomplished:
• Indoor coil expansion value is modulated to maintain the suction superheat at the suction superheat set point
• Outdoor coil expansion valve is controlled to maintain outdoor coil subcooling at the outdoor coil subcooling set point (heat
pump)
• Outdoor fan(s) are modulated to maintain the discharge saturation temperature at the discharge saturation temperature set
point
When in the Normal Cooling state the action of the cooling control devices is as follows:
A. The outdoor expansion valve position is either driven fully open (100%) or varied based on outdoor coil subcooling as follows:
• When the outdoor expansion valve Method is set to 100%, the outdoor expansion valve is driven to the 100% open
position.
• When the outdoor expansion valve Method is set to subcooling, the outdoor expansion valve is controlled to maintain
the outdoor coil subcooling temperature set point.
Normal Cooling Outdoor Fan (OA Fan PI_Loop) • If discharge pressure is high (above 162 psi) or the INV
Control Board (fin) Temp is low [below 172°F (169°F for 208/230
volt units) continuously for 15 seconds] the outdoor fan
One or two outdoor fans are controlled via Modbus speed is decreased by 2%. No further changes are made
connections to the Inverter Compressor Board via the IFB for 30 seconds.
communication board.
Outdoor Fan Fault Protection
The outdoor fan control PI_Loop is active only during the
Normal Cooling and Cooling Pumpdown operating states and If a unit is equipped with only one outdoor fan and it is shut off
the loop maintains the discharge saturation temperature at the on one of its internal faults, compressor operation enters the
set point between a minimum value of 86°F and a maximum Standby for Restart state.
value of 131°F. EER values will be improved by allowing the If a unit is equipped with two outdoor fans and either outdoor
lower set points when appropriate. fan 2 or both outdoor fans shut off on one of their internal
faults, compressor operation enters the Standby for Restart
Normal Heating OA Fan Control state. Note: In the case of two fans outdoor fan 2 provides
During the Normal Heating state the outdoor fan speed is first critical cooling for the inverter compressor/outdoor fan control
set at the maximum value and is then controlled as follows: boards.
• If discharge pressure is low (below 107 psi) or the INV Once compressor operation finishes the Standby for Restart
Board (fin) Temp is high [above 176°F (172°F for 208/230 state and if there is a call for cooling, compressor operation
volt units) continuously for 15 seconds] the outdoor fan is allowed to sequence to the Normal operating state in the
speed is increased by 2%. No further changes are made normal manner. If this cycle is repeated three times in a thirty
for 15 seconds. minute period an OA Fan: Problem alarm is generated, locking
out compressor operation, requiring a manual reset.
Pumpdown
When compressor operation is no longer needed, the compressor enters the Pumpdown state before entering the Standby for
Restart state from either the Initialization or Normal Cooling state.
The following describes the operation of the cooling control devices in the Pumpdown state:
A. The inverter compressor speed is at maximum with the outdoor expansion valve open, SVR closed, SVB open and the
indoor expansion valve closed for a maximum of 5 minutes. Step 1 is normally finished before 5 minutes when the suction
pressure drops below 72 psi. Step 1 is terminated if the inverter compressor discharge line temperature is above 230°F, the
inverter compressor port temperature is above 257°F or the discharge pressure is above 427 psi.
B. The inverter compressor speed is at minimum, the outdoor expansion valve is open 50% open, SVR closed, SVB open and
indoor expansion valve closed. Pumpdown is normally complete when the suction pressure drops below 36 psi. Pumpdown
is terminated if the inverter compressor port temperature rises above 320°F
Enabled Enabled
Mechanical cooling is enabled if all the following are true: In the heat pump, compressor heating is enabled if all of the
following are true:
• Control mode is not set via the keypad to fan only or heat
only • Control Mode is not set via the keypad to fan only or cool
• Control mode is set via the keypad to auto and not only
disabled via a third-party signal • Control Mode is set via the keypad to auto and heating is
• The outdoor air temperature (OAT) is high enough for not disabled via a network command
operation • The outdoor air temperature (OAT) is warm enough
• Compressor operation is not disabled by an alarm (above 0°F default) and cool enough (below 55°F default)
condition for compressor heating operation.
None None
Cooling capability is not provided. Unit is not a heat pump and heating capability is not provided
Determining Outside Air Damper Compressor cooling operation is disabled whenever the
outdoor air temperature falls below the Low Outdoor Air
Position Ambient Cooling Lockout Set Point. Whenever the outdoor
OAD/Econo Cap is a status only item which indicates the air temperature rises above the Low Outdoor Air Ambient
current outdoor air damper or economizer valve position. Cooling Lockout Set Point by more than the Cooling Lockout
Differential, compressor cooling operation is re-enabled.
Determining System Mode On non-heat pump units, heating is disabled whenever
The system can be set up for local or remote modes. the outdoor air temperature is above the High Outdoor Air
Ambient Heating Lockout Set Point. Whenever the outdoor
Off air temperature falls below the High Outdoor Air Ambient
Heating Lockout Set Point by more than the Heating Lockout
When the Net App Mode is set to “OFF,” the Unit Status is “Off Differential, heating operation is re-enabled.
Net” and the unit is completely disabled, including unoccupied
heating (night set back) and unoccupied cooling (night set up) Compressor cooling operation is disabled whenever the
operation. outdoor air temperature falls below the Low Outdoor Air
Ambient Cooling Lockout Set Point. Whenever the outdoor
Heat Only air temperature rises above the Low Outdoor Air Ambient
Cooling Lockout Set Point by more than the Cooling Lockout
When the Net App Mode is set to “Heat Only,” heating Differential, compressor cooling operation is re-enabled.
operation is allowed to operate as required to maintain the
heating set points. Cooling operation is disabled (Cooling
Status is “Off Net”).
Cool Only
When the Net App Mode is set to “Cool Only,” cooling
operation is allowed to operate as required to maintain the
cooling set points. Heating operation is disabled (Heating
Status is “Off Net”).
Fan Only
When the Net App Mode is set to “Fan Only,” the fans are
allowed to operate but cooling and heating operation is
disabled (Cooling Status and Heating Status are “Off Net”).
Normal to Pumpdown
The Compressor Heating State transitions from Normal to
Pumpdown if there is no longer a call for MinDAT or Heating
operation.
Heat Pump
A. Outdoor fan(s) are set to maximum and then decreased if the suction pressure is high (above 162.2 psi) or increased back
toward the maximum if the suction pressure is low (below 106.7 psi).
B. The indoor expansion valve is either driven fully open or varied based on indoor coil subcooling as follows:
When the Htg EVI Method is set to 100%, the indoor expansion valve is driven to the 100% open position.
When the Htg EVI Method is set to SbC, the indoor expansion valve is controlled to maintain the indoor coil subcooling at
the indoor coil subcooling temperature setpoint.
Pumpdown
Compressor heating operation enters the Pumpdown state before entering the Standby for Restart state from either the
Initialization or Normal Heating state.
The following describes the operation of the compressor heating control devices in the Pumpdown state:
A. Pumpdown is complete after 3 minutes or when the suction pressure drops below 34 psi. Pumpdown is terminated if either
the discharge superheat rises above 230°F or if the Inverter Compressor port temperature rises above 284°F.
Defrost Control
(See page 29 for more information) When a compressor is operating under these potential frosting
conditions for at least the MinCmpOpTm= period (Default=10
Defrost Operation – Heat Pump Units minutes) and the accumulated compressor operation time
since the last defrost cycle exceeds the MinAccCmpTm=
Only value (Default=40 minutes), the controller can initiate a defrost
This section applies to heat pump units only. Defrost cycle base on temperature, time or on a manual request as
operation is required when compressor operation is in the described in the following sections.
Normal Heating state when frost build up on the outdoor
coil interferes with the normal heat transfer from the outdoor Temperature Defrost
coil to the ambient air. When defrost operation is active, A defrost cycle is initiated based on temperature when the
compressor operation remains in the Normal Heating state Defrost Temperature (DFT) drops below a defrost temperature
but the device control is overridden until the defrost operation value (Tdef) and the saturated discharge temperature is below
is complete. While defrost operation is active, the auxiliary 109°F continuously for 3 minutes. The Tdef value is adjusted
supplemental heat source in the unit is required to maintain automatically between (+) 14°F and (-) 13.0°F based on
comfort conditions. outdoor air temperature. This value is not directly adjustable
but can be “biased” by setting the Tdef Adj= parameter
Defrost Operation State (Default=0°F) between -3.6°F and +3.6°F. Note: To improve
performance the Tdef value is also automatically adjusted after
When outdoor coil defrosting is required defrost operation
each defrost cycle depending on the length of the cycle.
transitions through the defrost states shown in the following
state diagram:
Timed Defrost
A defrost cycle is initiated based on time when the compressors
Figure 16: Defrost Operating States have accumulated enough time operating in potential frosting
conditions. The controller accumulates minutes of operation
in low frost potential (LoFrstAccTm=) and high frost potential
(HiFrstAccTm=) conditions. Whenever the HiFrstAccTm= time
plus ½ the LoFrstAccTm= time exceed the MaxFrostTm= setting
(Default=120minutes) a defrost cycle is initiated.
Manual Defrost
A defrost cycle is manually initiated when the Manual DF=
parameter is set from No to Yes. Note: Once the defrost cycle
begins the Manual DF= parameter automatically reverts to No.
Defrost Initialization
This state prepares the system for switching the 4-way valve to
the cooling position
Execute Defrost
The 4-way valve is switched to the cooling position to defrost
the coil. This state manages the refrigerant in the system and
assures the 4-way valve is seated before defrosting the coil.
Execute Defrost continues for 10 minutes or until the Defrost
Temperature (DFT) exceeds 51.8ºF or the discharge pressure
Defrost Initiation (Heat Pump) exceeds 426.7 psi.
DPS heat pump units require a defrost cycle to remove frost
Terminate Defrost
build-up that can accumulate on the outdoor coil during certain
heating operating conditions. The controller assumes there After the defrost operation is complete, the 4-way valve is
is a potential for frost build-up on the coil when the Defrost switched to the heating position. Terminate Defrost manages
Temperature (DFT) is less than 14.0°F and the saturated the system refrigerant and assures the 4-way valve is seated
suction temperature is below 32°F. before returning to normal heating compressor operation.
Defrost Inactive
When defrost operation is in the inactive state, action of the
compressor devices is a dictated by the applicable heating or
cooling compressor state.
4 Way Reversing Valve Control (4WV) – Bypass Solenoid Valve Control (SVB)
Heat Pump Units Only DPS units include a bypass solenoid valve that opens when
4WV is energized (On) when the unit is in the MinDAT or necessary to bypass refrigerant from the high to the low
Heating operating state. 4WVG is de-energized (OFF) when side of the inverter compressor to reduce the load on the
the unit is in the Cooling operating state. compressor. The bypass solenoid is closed most of the time.
Refer to the descriptions of the compressor operating states
NOTE: Once switched, the 4WV remains in the new position and protection control functions for details regarding when the
until the unit’s state changes from Cooling to MinDAT bypass valve is opened.
or Heating or viceversa.
Troubleshooting
The Check 1, Check 2 and Check 3 procedures on page 74 and 75 are used to troubleshoot many error codes.
CHECK 1
Check on connector of fan motor (Power supply cable)
1. Turn OFF the power supply.
Measure the resistance between phases of U,V,W at the
motor side connectors (three-core wire) to check that
the values are balanced and there is no short circuiting,
while connector or relay connector is disconnected.
CHECK 2
1. Turn OFF the power supply.
2. Measure the resistance between Vcc and each phase
of U, V, W, and GND and each phase at the motor side
connectors (five-core wire) to check that the values are
balanced within the range of ± 20 %, while connector or
relay connector is disconnected. Furthermore, to use a
multiple meter for measurement, connect the probe of
negative pole to Vcc and that of positive pole to GND.
Remote
Controller
Display E5
Method of Inverter PC board takes the position signal from UVW line connected between the inverter
Malfunction and compressor, and the malfunction is detected when any abnormality is observed in the
Detection
phase-current waveform.
Malfunction This malfunction will be output when the inverter compressor motor does not start up even
Decision
Condition in forced startup mode.
●●Inverter compressor lock
Supposed ●●High differential pressure (72.5psi or more)
Causes ●●Incorrect UVW wiring
●●Faulty inverter PC board
Remote
Controller
Display E7
Detect a malfunction based on the current value in the INVERTER PC board (as for motor
Method of 2 current value in the fan PC board).
Malfunction
Detection Detect a malfunction for the fan motor circuit based on the number of rotation detected by
hole IC during the fan motor operation.
●●Overcurrent is detected for INVERTER PC board (A2P) or fan INVERTER PC board
Malfunction (A5P) (System down is caused by 4 times of detection.)
Decision
Condition ●●In the condition of fan motor rotation, the number of rotation is below the fixed number
for more than 6 seconds. (System down is caused by 4 times of detection.)
●●Failure of fan motor
●●Defect or connection error of the connectors/ harness between the fan motor and PC
Supposed board
Causes
●●The fan can not rotate due to any foreign substances entangled.
●●Clear condition: Continue normal operation for 5 minutes
Remote
Controller
Display H7
Method of
Malfunction Detection of abnormal signal from fan motor.
Detection
Malfunction
Decision In case of detection of abnormal signal at starting fan motor.
Condition
●●Abnormal fan motor signal (circuit malfunction)
Supposed
Causes ●●Broken, short or disconnection connector of fan motor connection cable
●●Fan Inverter PC board malfunction (A2P)
Perform ●●Check 1 and Check 2 on page 74
Remote
Controller
Display L1
Malfunction is detected based on the current value during waveform output before starting
Method of compressor.
Malfunction
Detection Malfunction is detected based on the value from current sensor during synchronous
operation when starting the unit..
Overcurrent (OCP) flows during waveform output.
Malfunction
Decision Malfunction of current sensor during synchronous operation.
Condition
IPM failure.
●●Inverter PC board (A2P)
Supposed –– IPM failure
Causes –– Current sensor failure
–– Drive circuit failure
Check 3
Check 3
Remote
Controller
Display L4
Method of
Malfunction Fin temperature is detected by the thermistor of the radiation fin.
Detection
Malfunction
Decision When the temperature of the inverter radiation fin increases above 188.6°F.
Condition
●●Actuation of fin thermal (Actuates above 188.6°F)
Supposed
Causes ●●Defect of inverter PC board
●●Defect of fin thermistor
Thermistor Resistance/Temperature
Characteristics
Remote
Controller
Display L5
Method of
Malfunction Malfunction is detected from current flowing in the power transistor.
Detection
Malfunction When an excessive current flows in the power transistor.
Decision
Condition (Instantaneous overcurrent also causes activation.)
●●Defect of compressor coil (disconnected, defective insulation)
Supposed
Causes ●●Compressor start-up malfunction (mechanical lock)
●●Defect of inverter PC board
Check 3
Remote
Controller
Display L8
Method of
Malfunction Malfunction is detected from current flowing in the power transistor.
Detection
When overload in the compressor is detected. (Inverter secondary current 16.1A)
For 460V units
(1) 19.0A and over continues for 5 seconds.
Malfunction
Decision (2) 16.1A and over continues for 260 seconds.
Condition
For 230V units
(1) A current of 33.5A or more continues for a period of consecutive 5 sec.
(2) A current of 27.6A or more continues for a period of consecutive 260 sec.
●●Compressor overload
Supposed ●●Compressor coil disconnected
Causes ●●Defect of inverter PC board
●●Faulty compressor
Check 3
Remote
Controller
Display L9
Method of
Malfunction Detect the failure based on the signal waveform of the compressor.
Detection
Malfunction
Decision Starting the compressor does not complete.
Condition
●●Defective compressor
Supposed ●●Wiring connection error to the compressor
Causes ●●Large pressure difference before starting the compressor
●●Defective inverter PC board
NO
Correct the wiring; then restart
YES
Check if the NO
insulation resistance of the Replace the inverter compressor
compressor is 100kΩ
or over
NO
Check 3 *
NO
Check if the Replace the compressor inverter PC board
power transistor is
normal
YES
Recheck the compressor/refrigeration circuit
YES
Unusual YES
compressor Replace the inverter compressor
noise?
Remote
Controller
Display P1
Imbalance in supply voltage is detected in PC board.
Method of
Malfunction Imbalance in the power supply voltage causes increased ripple of voltage of the main
Detection
circuit capacitor in the inverter. Consequently, the increased ripple is detected.
“P1” will be displayed by pressing the inspection button.
Malfunction
Decision When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
Condition
minutes.
●●Open phase
●●Voltage imbalance between phases
Supposed ●●Defect of main circuit capacitor
Causes ●●Defect of inverter PC board
●●Defect of K2 relay in inverter PC board
●●Improper main circuit wiring
Remote
Controller
Display P4
Method of Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Detection “P4” will be displayed by pressing the inspection button.
Thermistor Resistance/Temperature
Characteristics
ERROR CODE: PJ – Faulty Field Setting after Replacing Main PC Board or Faulty Combination of PC Board
Remote
Controller
Display PJ
Method of
Malfunction This malfunction is detected according to communications with the inverter.
Detection
Malfunction Make judgment according to communication data on whether or not the type of the
Decision
Condition inverter PC board is correct.
Supposed ●●Faulty (or no) field setting after replacing main PC board
Causes ●●Mismatching of type of PC board
Recommended
Action ●●Contact the replacement parts supplier for resolution
Remote
Controller
Display U2
Method of
Malfunction Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Detection
When the voltage aforementioned is not less than 780V or not more than 320V, or when
Malfunction
Decision the current-limiting voltage does not reach 200V or more or exceeds 740V.
Condition
For 230V units: When the voltage aforementioned is not more than 190V.
●●Power supply insufficient
●●Instantaneous power failure
●●Open phase
●●Defect of inverter PC board
Supposed
Causes ●●Defect of outdoor control PC board
●●Main circuit wiring defect
●●Faulty compressor
●●Faulty fan motor
●●Faulty connection of signal cable
See CHECK3
on page 75
See CHECK3
on page 75
Appendix – General
Repeated occurrence:
Question: Do other fans show the same failure?
Yes: Systematically search for the cause of excessive ambient temperature. Perhaps use a data logger or read out
the electronics temperature via EC Control.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
Repeated occurrence:
Question: Do other fans show the same failure?
Yes: systematically search for the cause of excessive ambient temperature. Perhaps use a data logger or read out
the electronics temperature via EC Control.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
Repeated occurrence:
Question: Do other fans show the same failure?
Yes: Systematic search for the reason of too high ambient temperature, overload, overvoltage or low voltage.
Perhaps use a data logger.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
Repeated occurrence:
Question: • Does increasing the starting phase control factor improve the situation?
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
Repeated occurrence:
Question: • Do other fans show the same failure?
Yes: systematic search for peaks of disturbance voltage
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
Repeated occurrence:
Question: • Do other fans show the same failure?
• How often does the failure occur?
• Get big electrical consumer loads switched at the same time when the failure occurs in the surrounding area?
• Are compressors or large asynchronous motors applied within the arrangement?
Yes: Systematic search for external disturbance voltage peaks; If applicable, usage of data logger for a longer
period and analysis of the measured values.
• Are the voltage values within the specified range?
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
Figure 32: DPS005A, 208V with Gas Heat and Exhaust Fan
101
DS1
PB1
102 208V, 3 Phase, 60Hz
L1 T1 103A
L1
103 CUSTOMER L2 T2 104A
SUPPLIED L2
104 POWER
L3 T3 105A
L3
105 Wire for CW 60A GF-I
phase monitor 106A GFR1
MMP1 1
106 PB1 PB1
GLG1 GFR1
107A X3A
107B L1 T1 3
107 T1 T1
TB6
108A L2 T2 106A 2 106A EVB
108 T2 T2 1
(350)
109A L3 T3 107A 3 107A
109 T3 T3 3 X77A
GND2 NB
EVB208-I
110
112D
112A
112C
112B
111
A4PPWR-I
112 CMP1
CMP1-PI
113A U U
U NB
113 L1A L2A L3A E1
V
A4P V
114A V M
114 3
(350) W W GND
115A
W
115
U OFN1
116 BLK U
1 NB
PC0615-2(A)
V V M
X501A
117 WHT
2
3
118 W W CTRL
RED
3
119 1 YEL
P1 1
2 BLU
2
X502A
120 3 ORG
LR1 3
4 PNK
4
121 P2 5 GRY
5
122 X504A
PB1 PVM1 1 2
123A REC1
123 T1 3
LN-H LN-N
124 124A G
T2 4
LD-H LD-N
A4PJMP-I
125 125A
T3 5
126
MMP10 INDOOR_FAN
PB1 IFN-PI
127 NB
128A L1 T1 128B 1 L1
T1
128
T2
129A L2 T2 129B 2 L2 M
3
129 3
130A L3 T3 130B L3
T3
130 GND10 4
131A GND
131
132
MMP51 EXH_FAN1
EXH-PI NB
133 1
L1 T1 134A L1
134
L2 T2 135A 2 L2 M
3
135 3
L3 T3 136A L3
136 GND51 4
137A GND
137
138
139
140
141
142
143
144
145
146
147
148
154
TB1 F1C X1 X2 T1PWR2-I PL21 T1PWR1-I TB1
1 4 XF 5 3
155 160A 160A 155A 155A
120V SEC.
1 6A 3 3
156
1 3
157 6 3G
155A 155A
158
160A 155A
159 SPD
160A
155A
SPD-I
160A 120 COM T2B
1
160 120V CLASS 2 120 COM
120V_H 155A 120V_N
2 120V_N / (160) 75VA 120V
(202) 161A T2C (160)
161 GND TB1 3G
(302) CLASS 2 (202)
24V (302)
TB1 TB1 75VA
162 24 COM 24V
4 163A 163B 5 24 COM
164A
164B
163 5
T2B_24V T2B_N TB2 233 TB2 234
164 (248) (248)
(357) (357)
Figure 32 continued: DPS005A, 208V with Gas Heat and Exhaust Fan
(160) (160)
201 120V_H 120V_N
202
203
160A 155A
120 COM T2A
204
120V CLASS 2
75VA
205
TB1 GF1-I GF1-I TB1 24V TB1
206 6 GFR1 12 7
YEL YEL 207A 24 COM 207B
6 1 4 7
207 (105)
6 7
208 T2A_24V T2A_N
MCB 7G (213)
207C 207B
209 T1-G 207B
T1-G0
210
207B
T11-R3-4
211 T11-DI3
(346)
TB2 T12-+ A1+ /
212 TB2 Mod Bus (358)
218 SMOKE DETECTOR 219 207B Connection
207C 218 (347)
T12-- B1- /
213 (FIELD SUPPLIED) (358)
2 x 5VA AVAILABLE T2A_N / (207) 301G
RS485 (347)
GND1 /
214 (359)
TB2
COMPRESSOR_INTERLOCK 242
215 215A
T11-DI4
T7-AI1
216
DIRTY_FILTER(FIELD)
T10-DI1
217 T7-M1
T10-DI2
230 0-10VDC
T8-M1
EAF_CAP (FROM FIELD) TB2
231
275 232A
(260) / TB2_236 T9-X6
232 COMP_CAP (FROM FIELD)
0-10 VDC TB2
233A
233 T8-X1 TB2_236 / (260)
247
0-10 VDC
234
241
242
243
244
245
246
(163) (163)
T2B_24V EXPD T2B_N
247
C2 DO2 DO2
248
249
DO4 DO4
250
251
SVB-I SVB SVB-I
C3-4 DO3 DO3
252 163A 252A 1 2 163B
PTS-I
253 WHT MB.HB
PTS S X1
NB BLK 254A
254 - T4-M1
TB8 304 R-HP1
RED DO1
+ +5V / (259) DO1 255C
255 12 8 RED
DRN 301G 255 / (354)
PTD-I (303)
256 PTD BLK C1
- WHT
NB 256 / (354)
WHT
257 S X2 SRT
SRT-I
RED BLK
+ +5V / (259) X6
258 301G TB8
DRN 305 255A 259A TB2 NB
(255) BLK (222)
/ +5V +5VDC T5-M1
259 DRT1 (258) 236 236 236 (224)
DRT1-I
BLK DIP SWITCH (226)
X3
260 ON TB2_236 / (227)
MB.HB BLK OFF (229)
T4-M2 (232)
261 1 2 3 4 5 6
(233)
SW6 MUST
262 BE ON
WHEN LAST
263
264
Figure 32 continued: DPS005A, 208V with Gas Heat and Exhaust Fan
(160) (160)
301 120V_H 120V_N
HP1
PL4 PL4 R-HP1
NO NC
302 HP1-I NB HP1-I
160A 1 H C 2 303A 13 14 155A
(307)
(255)
303
MCB
(152)
304 R-CCH1
NO NC
T2-C1 DO1 T2-DO1B
160A 305A 13 14 155A
305
309
311
313
TB2 TB2 TB2
DO5 248 INV_COMP_RDY_STATUS 245C
314 245C 314A T4-C5-6 T4-D05 314B
TB2 TB2
318 DO8 LOCAL_REMOTE_STATUS
T4-D08 240 240C
319A
319
320
321
322
323
324
HEAT1
325
POAF(FIELD) TB2 AHL
1 2
326 W
226
GAS_HEAT_ENABLE(FIELD) TB2 NB
327
R HEAT1GM-CI
328 226C PL19
GRN
G
3
329 HEAT1GM-CI
RED 1 WHT
L1 L2
330 TB2 ALARM_RESET(FIELD) TB2 EXPD PL19 2
160A 331A
DI1
HEAT1GM-CI
331 235 231 TB2 3
WHT
+
332 PL18
GAS_HEAT_CAP(FIELD) 222
TB2
333 BLK 4
-
X8-AO 222C TB8 MOD GAS
334 0-10VDC DRN301G
HEATER
T5-M2
NB
335
336
T5-X5
337
155A
R1
338
339
340
341
342
343
344
345
CBL345-I WHT
346 A1+ / (212)
BLK
B1- / (213)
347 DRN
GND1 / (214)
A2+ / (360)
348 EVBJMP-I
B2- / (361)
349 SPL1
GND2 / (362)
EVI EVI-I
350 ORG 1 5 WHT A4P
1 + - GND
RED 2 4 BLK 1 3 EVB/88A-I (112)
2 MOD A4/4-I
351 YEL 3 3 BRN RED 351E
X86A
3 X89A 1 1 1 1
EVI BLK RED
4 2
ACS3
ACS1
X88A
X4A
NB 4
352 GRY 5 1 GRN BLK 352B
5 EVB 2 2 2 2
(108)
353 IFB 255 256 X6A-2I
NB IFBA-I (354)
354B 255D (255) (257) WHT
(363) CHK1_24V 3 1
24VAC
16V
354
TN2
DIP SWITCH
355A BLK
X6A
ON K SD 24
(363) CHK1_N 1 GND 2
355 1234 DIP SWITCH
RED
2
3
356 (163) (163) 1234
T2B_N T2B_24V
IFN_MOTOR
357
IFN-CI NB
WHT 1
163B
163A
(212) / A1+
358 IFB-I BLK 2
(213) / B1-
CHK1 DRN
359 (214) / GND1
1 3 EXH_MOTOR
360 EXH-CI
WHT 1 NB
(348) / A2+
BLK 2
361 3 1 (349) / B2-
DRN
(349) / GND2
362
CHK1_24V / (354)
363
CHK1_N / (355)
364
Figure 32 continued: DPS005A, 208V with Gas Heat and Exhaust Fan
TB2
NOTE:
Only wire to bottom of TB2,
top is for customer connection.
BUSBAR EXPD
MCB
PC5 GFR1
GND2
TB8 TB1
SPD1
CHK 1
PB1 GND51 GND10
R-HP1
R-CCH1 LOAD
IFB
ACS3
Modbus
LOAD
PVM1 ACS2
ACS1
LINE Top View Mounted on
the side of the
T2A LINE
24V transformer panel
T2B
DS1
H
F1A F1B F1C
TB6 T2C
GLG1
T1
REC1 DRT1,3
DS1
Discharge Refrigerant Temperature Sensor
Disconnect Switch, Unit Power
PVM1
R63
Phase Voltage Monitor
Relay, Duct High Limit Switch
DS2 Disconnect Switch, Supply Fan / Circuit 2 RAE Enthalpy Sensor, Return Air
DS6 Disconnect Switch, Powered GFCI Receptacle RAT Temperature Sensor, Return Air
ECB1 Ebtron Control Board R-CCH1 Crankcase Heater Relay
RECEPTACLE TO EVB Expansion Valve Board REC1 Receptacle, GFCI
BE SHIPPED LOOSE EVBF Expansion Valve Board Electrical Noise Filter RES3,4 Resistor
EVI Indoor Expansion Valve RHB1 Reheat Board, Hot Gas
EVO Outdoor Expansion Valve R-HP1 High Pressure Compressor 1 Relay
EXPB,D Expansion Control Board RHV1 Valve, Reheat Coil
F1A,B Fuse, Control Circuit Transformer (T1), Primary SD1/SD2 Smoke Detector, Supply Air/Return Air
F1C,D Fuse, Control Circuit Transformer (T1), Secondary SHS1 Space Humidity Sensor
F4A,B,C Fuse, 460V 3-Phase Transformer (T4), Primary SPD Surge Protective Device
F6C Fuse, Powered GFCI Transformer (T6), Secondary SPS1 Static Pressure Sensor, Duct
GFR1 Ground Fault Relay SPS2 Static Pressure Sensor, Building
HEAT1 Heater Module SRT Suction Refrigerant Temperature Sensor
HL Hi-Limit Switch, Gas Heat SVB Refrigerant Bypass Solenoid Valve
HP1,3 Hi-Pressure Switch, Refrigeration Circuits 1, 3 SVR Refrigerant Receiver Solenoid Valve
IFB Interface Board T1 Transformer, Main Control
IFBF Interface Board Electrical Noise Filter T12 575/460V Primary Power Transformer
IRT Indoor Refrigerant Temperature Sensor T1F Main Transformer Electrical Noise Filter
Field Wiring
LCT Temperature Sensor, Leaving Coil T2A,B Transformer, Control Input (115/24VAC)
LR1 Compressor Line Reactor T4 Transformer, 230V Single Phase (460/397VAC)
Factory Wiring M1F Compressor 1 Electrical Noise Filter T6 Transformer, Powered GFCI Receptacle (Line/115VAC)
M3 Contactor, Compressor 3 T7 Transformer, Reheat Control Board (115/24VAC)
Factory Terminal M60 Contactor, Constant Speed Recovery Wheel TB1 Terminal Block, Internal Power Distribution
MCB Main Control Board TB2 Terminal Block, Field -24V
Field Terminal MJ Mechanical Jumper TB8 Terminal Block, Internal Signal Distribution
MMP1 Manual Motor Protector, A4P Board VFD60 Variable Frequency Drive, Energy Recovery Wheel
MMP10 Manual Motor Protector, Supply Fan
Plug Connection MMP3 Manual Motor Protector, Compressor 3
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied Representative for warranty details. To find your
local Daikin Applied Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.