0% found this document useful (0 votes)
2K views114 pages

Microtech III Dps

Uploaded by

Lê Anh Tuấn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views114 pages

Microtech III Dps

Uploaded by

Lê Anh Tuấn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 114

Installation and Maintenance Manual OM 1263

Group: Applied Air Systems


Part Number: OM 1263
Date: June 2018

MicroTech® III Unit Controller for


Rebel® Refrigeration Only Controls
Model DPS
Table of Contents

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Trending . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Adjusting PI Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Trending Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Additional Instructions and Information . . . . . . . . . . . . . . . . 4 Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 About this Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
IFB Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Using the Keypad/Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Alarm Clearing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Navigation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Compressor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Edit Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Operator’s Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Service Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Determining Unit State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Keypad/Display Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Off Operating State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Quick Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Start Up Operating State . . . . . . . . . . . . . . . . . . . . . . . . . . 48
View/Set Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Mechanical Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Unit Status Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Off to Prestart Pressure Equalization . . . . . . . . . . . . . . . . . 48
Temperature Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Prestart Pressure Equalization to Off . . . . . . . . . . . . . . . . . 48
Flow Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Prestart Pressure Equalization to Initialization . . . . . . . . . . 48
RF/EF Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Initialization to Normal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SAF Spd Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Initialization to Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . 48
Time/Date Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Initialization to Standby for Restart . . . . . . . . . . . . . . . . . . 49
Commission Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Normal to Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Normal to Standby for Restart . . . . . . . . . . . . . . . . . . . . . . 49
Timer Settings Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pumpdown to Standby for Restart . . . . . . . . . . . . . . . . . . . 49
SAF Set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pumpdown to Initialization . . . . . . . . . . . . . . . . . . . . . . . . . 49
RF/EF Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Standby for Restart to Off . . . . . . . . . . . . . . . . . . . . . . . . . 49
Inverter Compressor Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Inverter Compressor Cooling Operation . . . . . . . . . . . . . . 49
Outdoor Air Fan Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Input Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Expansion Valve Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Defrost Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Compressor Control PI_Loop . . . . . . . . . . . . . . . . . . . . . . 50
Alarm Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Compressor Output Control . . . . . . . . . . . . . . . . . . . . . . . . 50
Alarm/Event Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Fixed Speed Compressor Step Transitions . . . . . . . . . . . . 50
Alarm Delays Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Inverter Compressor Cooling State Descriptions . . . . . . . . . . . . . . 51
Manual Control Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Cooling Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Manual Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Pre Start Pressure Equalization . . . . . . . . . . . . . . . . . . . . . 51
Service Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Save/Restore Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Normal Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Operating Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Active Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Standby for Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Alarm Log Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Determining Cooling Status . . . . . . . . . . . . . . . . . . . . . . . . 57
Alarm Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Determining Heat Status . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Analog Input Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Determining Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . 58
Universal I/O Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Determining Heat Capacity . . . . . . . . . . . . . . . . . . . . . . . . 58
Digital Input Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Determining Supply Air Fan Capacity . . . . . . . . . . . . . . . . 58
Digital Output Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Determining RF/EF Capacity . . . . . . . . . . . . . . . . . . . . . . . 58
Modbus Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Determining Outside Air Damper Position . . . . . . . . . . . . . 58
Sensor Offsets Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Determining System Mode . . . . . . . . . . . . . . . . . . . . . . . . . 58
OAT Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Unit Configuration Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Unit Configuration Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

OM 1263 • MICROTECH UNIT CONTROLLER 2 www.DaikinApplied.com


Table of Contents

Heat Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Appendix – General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100


Heat Pump Cooling Operation . . . . . . . . . . . . . . . . . . . . . . 59 Supply Fan Failure Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Pump Heating Operation . . . . . . . . . . . . . . . . . . . . . . 59 HLL = Hall Sensor Error . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Pump Defrost Operation . . . . . . . . . . . . . . . . . . . . . . 59 TFEI = Electronics Interior Overheated . . . . . . . . . . . . . . 100
Supplemental Heating/Compressor Heating Transitions . . . . . . . . 59 First occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Compressor Heating Operation State Machine – Repeated occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Pump Units Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
TFM = Motor Overheated . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 First occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heating Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Repeated occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 TFE = Power Mod Overheated . . . . . . . . . . . . . . . . . . . . 101
Normal Heat Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 First occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Normal Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Repeated occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Pumpdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 BLK = Locked Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Standby for Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 First occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Repeated occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Defrost Operation – Heat Pump Units Only . . . . . . . . . . . . 67 SKF = Communication Error . . . . . . . . . . . . . . . . . . . . . . 101
Defrost Operation State . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 First occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
4 Way Reversing Valve Control (4WV) – Repeated occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Heat Pump Units Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
PHA = Phase failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Receiver Solenoid Valve Control (SVR) . . . . . . . . . . . . . . . 68
Repeated occurrence: . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Bypass Solenoid Valve Control (SVB) . . . . . . . . . . . . . . . . 68
Appendix – Sample Wiring Diagrams: Rebel 3-15 Tons . . . . . . . 105
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix – Sample Wiring Diagrams: Rebel 16-28 Tons . . . . . . 109
Inverter Board Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
IFBCommStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
ACS1 DataRcvd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
ACS3 DataRcvd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
CHECK 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
CHECK 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
CHECK 3 – Power Resistor Check . . . . . . . . . . . . . . . 75
ERROR CODE: E5 – Inverter Compressor Motor Lock . . . . . . . . 76
ERROR CODE: E7 – Malfunction of Outdoor Unit Fan Motor . . . 78
ERROR CODE: H7 – Abnormal Outdoor Fan Motor Signal . . . . . 80
ERROR CODE: L1 – Defective Inverter PC Board . . . . . . . . . . . 81
ERROR CODE: L4 – Malfunction of Inverter Radiating
Fin Temperature Rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Thermistor Resistance/Temperature Characteristics . . . . . 85
ERROR CODE: L5 – Momentary Overcurrent of
Inverter Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ERROR CODE: L8 – Momentary Overcurrent of
Inverter Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
ERROR CODE: L9 – Inverter Compressor Starting Failure . . . . 90
ERROR CODE: P1 – Inverter Over-Ripple Protection . . . . . . . . . 92
ERROR CODE: P4 – Malfunction of Inverter Radiating
Fin Temperature Rise Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Thermistor Resistance/Temperature Characteristics . . . . . 96
ERROR CODE: PJ – Faulty Field Setting after Replacing
Main PC Board or Faulty Combination of PC Board . . . . . . . . . . . . 97
ERROR CODE: U2 – Power Supply Insufficient or
Instantaneous Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

www.DaikinApplied.com 3 OM 1263 • MICROTECH UNIT CONTROLLER


Introduction

Introduction

This manual provides information regarding the MicroTech® III Additional Instructions and Information
control system. It specifically describes the operation and
programmable options for units with refrigeration only controls For installation and startup instructions and general information
(ROC). regarding a Rebel™ rooftop unit, refer to the applicable model-
specific installation and maintenance manual (Table 1).
The ROC MicroTech III Controller is a device that is not
capable of complete, stand-alone operation. Information in the
controller can be displayed and modified by using the keypad/ Table 1: Installation and Maintenance Resources
display in the units main control panel. The ROC systems Unit Manual
require a third-party controller for the Rebel unit to function.
MicroTech III Remote Unit Interface IM 1005
DPS 03 – 28 IM 1125

Adjusting PI Control Parameters


The rooftop MicroTech III controller uses a “velocity” form of NOTICE
the traditional PI loop arranged such that the output is adjusted This equipment generates, uses, and can radiate radio frequency energy
based on a “gain” parameter multiplied by the “projected” error. and, if not installed and used in accordance with this instruction manual,
The projected error is determined based on the rate the error is may cause interference to radio communications. It has been tested and
changing as shown in Figure 1. found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC rules. These limits are designed to provide reasonable
Figure 1: Projected Error Timeline protection against harmful interference when the equipment is operated
in a commercial environment. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user is
required to correct the interference at his own expense. Daikin Applied
disclaims any liability resulting from any interference or
for the correction thereof.

WARNING
Electric shock hazard. Can cause personal injury or
equipment damage.
This equipment must be properly grounded. Connections and service to the
control panel must be performed only by personnel that are knowledgeable
in the operation of the equipment being controlled.

The change in output (Do) after each sample period (ST) is


given by the following equation:
Do= Gain X Projected Error.
Although it is generally recommended that they are left at the
factory settings there are four PI loop adjustment parameters
available via the MicroTech III HMI. These are Gain, Period
(ST), Project Ahead Time (PAT) and Max Change.
Generally speaking, the PAT should be set roughly equal to the
“time constant” of the system being controlled and the Period
(ST) one quarter to half the PAT. The Gain is then set to
achieve control stability. If the system is unstable (hunting) the
control is too fast and the Gain should be decreased to slow
the control response. If the system takes excessively long to
reach setpoint during transient conditions (sluggish) the Gain
can be increased to speed the control response. The goal is
an acceptable balance between these two conditions. When in
doubt these parameters should be set to the factory settings.

OM 1263 • MICROTECH UNIT CONTROLLER 4 www.DaikinApplied.com


Introduction

Introduction

CAUTION Getting Started


Extreme temperature hazard. Can cause damage to This manual contains information designed to assist the field
system components. technician with unit setup. The technician will need to be
The MicroTech III controller is designed to operate in ambient temperatures familiar with the following topics at a minimum to successfully
from -20°F to 125°F. It can be stored in ambient temperatures from -40°F set up unit operation.
to 140°F. It is designed to be stored and operated in relative humidity up to • Keypad Navigation/Editing/Passwords
95% (non-condensing).
• Control Mode
• Heat/Cool Changeover
WARNING • Compressor Capacity
Excessive moisture in the control panel can cause • Supply Fan Capacity
hazardous working conditions and improper equipment
• Exhaust Fan Capacity
operation.
When servicing this equipment during rainy weather, the electrical
components in the main control panel must be protected from the rain.

CAUTION
Static sensitive components. A static discharge while
handling electronic circuit boards can cause damage to
the components.
Discharge any static electrical charge by touching the bare metal inside the
main control panel before performing any service work. Never unplug any
cables, circuit board terminal blocks, relay modules, or power plugs while
power is applied to the panel.

Figure 2: Inter Component Communications Diagram

MicroTech® III Unit Controller

Modbus Communication

01 02 04 06 IFB
SAF ExFan OA Fan VarCmp
ACS1

ACS2

ACS3

ECM ECM VFD/ECM Drive


07 08 09

ACS Comm ACS Comm

NOTE: See “IFBCommStatus” on page 70 and “ACS1 INV


EVB
DataRcvd” on page 71 and the “Thermistor CMP
Resistance/Temperature Characteristics” on
page 85 Section of this manual if there are any
questions about the communications from component INV EVO
to component. OA Heat Pump Only
Fan1
ORT
Heat Pump Only
INV
OA EVI
Fan2

IRT
Heat Pump Only

www.DaikinApplied.com 5 OM 1263 • MICROTECH UNIT CONTROLLER


Introduction

IFB Board
The IFB board is used to translate between the MicroTech III interconnected forming the ACS1 communication loop. On
controller Modbus and the Daikin inverter compressor/outdoor 208/230V units the A4P board controls both INV and OF1. On
fan boards’ proprietary protocol. 460/575V units the A4P board controls only INV and there is
a separate A5P board that controls OF1. If a unit is equipped
There are three “ACS” communication current loop channels
with an OF2 it is controlled by a separate A5P control board.
available on the IFB board; ACS1, ACS2 and ACS3. ACS1 is
Figure 3 shows the three possible board/loop arrangements
use for control of the inverter compressor (INV) and one or two
that make up the ACS1 loop.
outdoor fans (OF1 and OF2). ACS3 is use for control of the
indoor expansion valve (EVI) and if the unit is a heat pump the Expansion valves EVI and if applicable EVO are controlled
outdoor expansion valve (EVO). ACS2 is not currently used. by an expansion valve driver board EVB. The EVB board is
connected to the IFB board forming the ACS3 communication
INV, OF1 and OF2 are controlled by a combination of
loop. Figure 3 shows the ACS3 communication loop.
circuit boards designated A4P and A5P. These boards are

Figure 3: ACS Communication Current Loop Arrangements

For Troubleshooting Module-to-Module Communication, See page 70.

OM 1263 • MICROTECH UNIT CONTROLLER 6 www.DaikinApplied.com


Using the Keypad/Display

Using the Keypad/Display

The keypad/display consists of a 5-line by 22 character display, The keypad/display Information is organized into Menu groups;
three keys and a “push and roll” navigation wheel. There is an Main Menu, Quick Menu, View/Set Unit Menu, Commission
Alarm Button, Menu (Home) Button, and a Back Button. The Unit Menu, Manual Control Menu, Service Menu, Unit
wheel is used to navigate between lines on a screen (page) Configuration Menu and Alarm list Menus.
and to increase and decrease changeable values when editing. NOTE: Only menus and items that are applicable to the
Pushing the wheel acts as an Enter Button. specific unit configuration are displayed.
The Main Menu allows the user to enter a password, access
Figure 4: Keypad Controls the Quick Menu pages, view the current unit state, access the
Alarm List Menu as well as access to information about this
unit. The Quick Menu provides access to status information
indicating the current operating condition of the unit. The View/
Set Unit Menus include basic menus and items required to
setup the unit for general operation. The Commission Unit
Menus include more advanced items for “tuning” unit operation
The first line on each page includes the page title and the line such as PI loop parameters and time delays. The Manual
number to which the cursor is currently “pointing”. The line Control Menu allows service personnel to test unit specific
numbers are X/Y to indicate line number X of a total of Y lines operation manually. The Unit Configuration Menu allows the
for that page. The left most position of the title line includes an user to access to the unit specific configuration information.
“up” arrow to indicate there are pages “above” the currently These generally do not needing changing or accessing unless
displayed items, a “down” arrow to indicate there are pages there is a fundamental change to or a problem with the unit
“below” the currently displayed items or an “up/down” arrow operation. The Alarm Lists Menu includes active alarm and
to indicate there are pages “above and below” the currently alarm log information.
displayed page.
Each line on a page can contain status only information or
include changeable data fields. When a line contains status
only information and the cursor is on that line all but the value
field of that line is highlighted meaning the text is white with
a black box around it. When the line contains a changeable
value and the cursor is at that line, the entire line is highlighted.
Each line on a page may also be defined as a “jump” line,
meaning pushing the navigation wheel will cause a “jump” to
a new page. An arrow is displayed to the far right of the line to
indicate it is a “jump” line and the entire line is highlighted when
the cursor is on that line.

www.DaikinApplied.com 7 OM 1263 • MICROTECH UNIT CONTROLLER


Using the Keypad/Display

Passwords
Various menu functions are accessible or inaccessible, Figure 5: Password Main Page
depending on the access level of the user, and the password
AHU 01 1/5
they enter, if any. There are four access levels, including no
password, Level 2, Level 4, and Level 6, with Level 2 having Enter Password
the highest level of access. Without entering a password, the Quick Menu
user has access only to basic status menu items. Entering Unit State=________
the Level 6 password (5321) allows access to the Alarm Lists Alarm Lists
Menu, Quick Menu, and the View/Set Unit Menus group. About This AHU
Entering the Level 4 password (2526) allows similar access The password field initially has a value **** where each *
as Level 6 with the addition of the Commission Unit Menu, represents an adjustable field. These values can be changed
Manual Control, and Service Menu groups. Entering the Level by entering the Edit Mode described below.
2 password (6363) allows similar access as Level 4 with the
addition of the Unit Configuration Menu.
Figure 6: Password Entry Page
NOTE: Alarms can be acknowledged without entering a
password. Enter Password 1/1
The main password page is displayed when the keypad/display Enter Password ****
is first accessed, the Home Key is pressed, the Back Key is
pressed multiple times, or if the keypad/display has been idle
Entering an invalid password has the same effect as continuing
longer than the Password Timeout (default 10 minutes). The
without entering a password. Once a valid password has been
main password page provides access to enter a password,
entered, the controller allows further changes and access
access the Quick Menu, view the current Unit State, access the
without requiring the user to enter a password until either the
alarm lists or view information about the unit.
password timer expires or a different password is entered.
The default value for this password timer is 10 minutes. It is
changeable from 3 to 30 minutes via the Timer Settings menu.

OM 1263 • MICROTECH UNIT CONTROLLER 8 www.DaikinApplied.com


Using the Keypad/Display

Navigation Mode Edit Mode


In the Navigation Mode, when a line on a page contains no The Editing Mode is entered by pressing the navigation wheel
editable fields all but the value field of that line is highlighted while the cursor is pointing to a line containing an editable field.
meaning the text is white with a black box around it. When the Once in the edit mode pressing the wheel again causes the
line contains an editable value field the entire line is inverted editable field to be highlighted. Turning the wheel clockwise
when the cursor is pointing to that line. while the editable field is highlighted causes the value to be
increased. Turning the wheel counter-clockwise while the
When the navigation wheel is turned clockwise, the cursor
editable field is highlighted causes the value to be decreased.
moves to the next line (down) on the page. When the wheel is
The faster the wheel is turned the faster the value is increased
turned counter-clockwise the cursor moves to the previous line
or decreased. Pressing the wheel again cause the new value
(up) on the page. The faster the wheel is turned the faster the
to be saved and the keypad/display to leave the edit mode and
cursor moves.
return to the navigation mode.
When the Back Button is pressed the display reverts back to
the previously displayed page. If the Back button is repeated
pressed the display continues to revert one page back along Service Timers
the current navigation path until the “main menu” is reached.
A user may override timers for a period of up to 240 minutes
When the Menu (Home) Button is pressed the display reverts by setting the Service Timer to a non-zero number. When the
to the “main page.” Service Timer is not zero, the times listed below are set to the
When the Alarm Button is depressed, the Alarm Lists menu is Service Time (Default = 20 seconds) instead of the normal
displayed. values. This allows the unit to be run through its operating
states without having to wait for the normal time delays to
expire. These times revert to the standard values when the
Service Time count down to zero or is set to zero by the user.
The affected times are:
• Cooling Stage Time
• Heating Stage Time
• Start Initial Time
• Recirculation
• ZeroOATime

www.DaikinApplied.com 9 OM 1263 • MICROTECH UNIT CONTROLLER


Keypad/Display Menu Structure

Keypad/Display Menu Structure

The following is a description of the MicroTech III menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit configuration.

Figure 7: Main Menu – Keypad/Display Menu Structure

See page 8 See page 17 — 17 See page 18 — 21 See page 22 — 30


Main Menu Enter Password Quick Menu View/Set Unit Commission Unit
Enter Password ► Enter Password ******* ► System Mode= Local Unit Status/Settings ► Unit Set-Up ►
Quick Menu ► Heat/Cool In= Heat/Cool Temperatures ► Timer Settings ►
View/Set Unit ► CmpIntrLock= Flow Status ► SAF Set-Up ►
System Mode= Local Dehum Status=________ SAF Spd Control ► RF/EF Set-Up ►
Heat/Cool In= Heat/Cool Clg Capacity= XXX% RF/EF Control ► INV Cmp Set-Up ►
CmpIntrLock= OAD/Econ Cap= XXX% Date/Time/Schedules ► OA Fan Set-Up ►
Dehum Status= Htg Capacity= XXX% Exp Valve Set-Up ►
Commission Unit ► Reheat Cap= XXX% For more detail go to: Defrost Set-Up ►
Manual Control ► SAF Speed= XXX% Figure 8, page 12 Alarm/Event Config ►
Service Menus ► RF/EF Cap= XXX%
For more detail go to:
Unit Maintenance ► OA Temp= XXX°F
Figure 5, page 8
Unit Configuration ►
Alarm Lists ►
About This Unit ►

See page 39
About This Unit
SO_Item= 123456_12345
Unit SN= FBOU123456789
App Version= 2506017xxx
Cf1-15= xxxxxxxxxxxxxxxx
Cf6-29= xxxxxxxxxxxxxxxx
HMI GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
OBH GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx

OM 1263 • MICROTECH UNIT CONTROLLER 10 www.DaikinApplied.com


Keypad/Display Menu Structure

See page 31 — 31 See page 32 — 35 See page 32 See page 36 See page 16
Manual Control Service Menus Unit Maintenance Unit Configuration Alarm Lists
Manual Control= Normal Timer Settings ► Operating Hours Apply Changes= No Active Alarms ►
Supply Fan= Off Operating Hours ► Unit Type= DPS/DAH(3) Alarm Log ►
SAF Spd Cmd= 0% Save/Restore Settings ► Control Type= RefOnly(3)
SAF Spd Cmd= 0% Active Alarms ► Clg Type= INV(4) For more detail go to:
INV/OF Ena= Off Alarm Log ► Comp Config= 1V1F1C(M) Figure 12, page 16
INV Cmp= Off Event Log ► Gen Clg Stgs= NA
INV Spd Cmd= 0% Alarm/Event Config ► Low Ambient= NA(0)
Comp 3= Off Analog Input Status ► Cond Ctrl= INV(8)
OA Fan= Off Universal I/O Status ► OA Dmpr/Econ= AirEc(3)
OA Fan Cmd= 0% Digital Input Status ► OA Flow Stn= None(0)
4 Way Valve= Off Digital Output Status ► Htg Type= None(0)
RcvSol Valve=Off Modbus Status ► Htg Stages= 1
BP Sol Valve= Off IP Set-up ► Max Heat Rise= 100
EVI Cmd= 0% HMI Set-up ► SAF Type= EBMVAV(F)
EVO Cmd= 0% Sensor Offsets ► RAF Type= None(0)
RF/EF Fan= Off RF/EF Ctrl= NA(0)
RF/EF Spd Cmd= 0% For more detail go to: 2ndDSPSnsr= NA(0)
OAD/Econo= 0% Figure 12, page 16 EFT/LCT Snsr= NA(0)
Reheat Valve= 0% Enrgy Rec= None(0)
RH Output= Off Clg Circ Type= 1Air(2)
Alm Output= Off Head P Ctrl= NA(0)
Bypass Ctrl= NA(0)
Unit Size= 012
Refrig Type= R410A(2)
Reheat Type= None(0)
Unit Voltage= 460V/60Hz(2)
EV Type= EVBSag(1)
Apply Changes= No

www.DaikinApplied.com 11 OM 1263 • MICROTECH UNIT CONTROLLER


Keypad/Display Menu Structure

Figure 8: View/Set Unit – Keypad/Display Menu Structure

See page 18 — 21
View/Set Unit
Unit Status/Settings ►
Temperatures ►
Flow Status ►
SAF Spd Control ►
RF/EF Control ►
Date/Time/Schedules ►

See page 18 — 19 See page 20 See page 20 See page 20 See page 20 See page 21
Unit Status/Settings Temperatures Flow Status SAF Speed Control RF/EF Control Date/Time/Schedules
System Mode= Local OA Temp= XXX°F Supply Fan= __________ SAF Speed= XXX% RF/EF Cap= XXX% Time= hh:mm:ss
Heat/Cool In= Heat/Cool DRT1= XXX°F Ret/Exh Fan= _________ Speed Cmd= XXX% RF/EF Spd Cmd= XXX% Date= MM/DD/YY
CmpIntrLock= _________ DRT3= XXX°F UTC Diff= -60min
CmpCapIn= ___________ SRT= XXX°F DAYLIGHT SAVINGS
SAFSSIn= ____________ DFT= XXX°F DLS Strt Mon= Mar
SAFCapIn= ___________ IRT= XXX°F DLS Strt Wk= 2nd Week
EAFSSIn= ____________ ORT= XXX°F DLS End Mon= Nov
EAFCapIn= ___________ INVCompTemp= XXX°F DLS End Wk= 1st Week
RhtVlvIn= ____________ DLS Enable= Auto
OADCapIn= ___________
AlmResetIn=__________
Dehum Status= ________
Clg Status= ___________
Htg Status= ___________
SuplHtgStatus= ________
Econo Status= _________
Clg Capacity= XXX%
Htg Capacity= XXX%
Supl Htg Cap= XXX%
Reheat Cap= XXX%
SAF Speed= XXX%
RF/EF Cap= XXX%
OAD/Econo Cap=XXX%

OM 1263 • MICROTECH UNIT CONTROLLER 12 www.DaikinApplied.com


Keypad/Display Menu Structure

Figure 9: Commission Unit – Keypad/Display Menu Structure

See page 22 — 30
Commission Unit
Unit Set-Up ►
Timer Settings ►
SAF Set-Up ►
RF/EF Set-Up ►
INV Cmp Set-Up ►
OA Fan Set-Up ►
Exp Valve Set-Up ►
Defrost Set-Up ►
Alarm/Event Config ►
See page 22 See page 22 See page 22 See page 23
Unit Set-Up Timer Settings SAF Set-Up RF/EF Set-Up
Eng Units= English Pwd Timeout= 10min Max Vent Speed= 100% Max Vent Spd= 100%
Unit Name= xxxxxxxxxxxx Clg Stg Time= 5min Max SAF RPM= 2600 Max RF/EF RPM= 2600
Max SAF Hz= 60.0Hz Max RF/EF Hz= 60Hz
CmpOp_MinSAF= 20% RF/EF Status= XXXXX
SAF Status= XXXXX

See page 24 — 25 See page 26 See page 27 — 28


INV Cmp Set-Up OA Fan Set-Up Exp Valve Set-Up
COMPRESSOR STATUS COMPRESSOR SETUP OA FAN STATUS EXP VALVE STATUS EXP VALVE SETUP
Clg State= ____________ Clg Stg Time= 5min OA Fan1 Spd= XXX% EVI Pos= XXX% SSH DB= 2.0ºF
Htg State= ____________ Clg Lo OAT Lk= 55ºF OA Fan1 Cmd= XXX% EVO Pos= XXX% ClgSH Lo Base= 5.0ºF
INV Cmp Spd= XXX.X% Clg OAT Diff= 2ºF OA Fan1Amps= XX.XA EVStatus=____________ HtgSH Lo Base= 5.0ºF
INV Spd Cmd= XXX.X% Htg Lo OAT Lk= 0.0ºF Fault Code Details ► 1 REFRIG CIRCUIT STATUS ClgSH Hi Base= 9.0ºF
VCmpOilStatus= XXXXX Htg Hi OAT Lk= 55.0ºF OA Fan2 Spd= XXX% PTD= XXX.Xpsi HtgSH Hi Base= 9.0ºF
Comp 3=_____________ EffHtgHiOATLk= _____ºF OA Fan2 Cmd= XXX% PTS= XXX.Xpsi Htg EVI Meth= SbC
Fault Code Details ► 1 Htg OAT Diff= 2ºF OA Fan2Amps= XX.XA Suction SH= XX.XºF IC SC Spt= 9.0ºF
INV Port Temp= XXX.XºF INV Period= 20s Fault Code Details ► 1 Discharge SH= XX.XºF IC SC DB= 2.0ºF
INV Fin Temp= XXX.XºF INV Gain= 2.5 REFRIG CIRCUIT STATUS Subcooling= XX.X°F HtgSC EVI Min= XXX%
INV Amps= XX.XA INV PAT= 10s PTS= XXX.Xpsi Eff SSH Spt= XX.X°F Clg EVO Meth= SbC
Ctrl Card Tmp= XXX.XºF INV Max Chg= 15% PTD= XXX.Xpsi Eff SH Base= XX.X°F OC SC Spt= 9.0ºF
Heatsink Tmp= XXX.XºF OilManagement= Off Disch Sat Tmp= XXX.X°F Eff SC Spt= XX.X°F OC SC DB= 2.0ºF
REFRIG CIRCUIT STATUS LowOilTime= 10min EffDshSatTSpt= XXX.X°F Eff SC Lo Lmt= XXX% ClgSC EVO Min= 12%
PTD= XXX.Xpsi OilBoostTime= 10min OA Temp= XXX°F SRT= XXX°F ManCtrl EV Op= Auto
PTS= XXX.Xpsi VFD Status= __________ INV Fin Temp= XXX°F Disch Sat Tmp= XXX.X°F IFB Comm Status ►
4 Way Valve=__________ VFD Alm/Wrn= ________ OA FAN SET UP Sucn Sat Tmp= XXX.X°F
RcvrSol Valve=_________ IFB COMM STATUS ► 2 OA Fan Period= 25s IRT= XXX°F
BP Sol Valve=_________ OA Fan Gain= 2.5 ORT= XXX°F
OA Fan PAT= 75s
OA Fan Max= 90%
IFB COMM STATUS ► 2
1, 2 See the expansion
information on page 16
See page 29 See page 30
Defrost Set-Up Alarm/Event Config
Defrost State= _________ ALARM DELAYS
Manual DF= No Sens Alm Dly= 30s
MinCmpOpTm= 10min Temp AlmDly= 30s
MinAccCmpTm= 40min Hi Return Temp= 120°F
MaxFrostTm= 120min ALARM CONFIG
Defrost Temp= XXºF AlmLogToSD= No
Tdef Adj= 0.0ºF Problems= Slow
CmpOpTm= XXXmin EVENT CONFIG
AccCmpOpTm= XXXmin Show Events= Yes
LoFrstAccTm= XXXmin EventLogToSD= No
HiFrstAccTm= XXXmin ALARM CONFIG
EnaSnapshots= Yes
Show Snapshots= Yes
SnapshotsTo SD= No

www.DaikinApplied.com 13 OM 1263 • MICROTECH UNIT CONTROLLER


Keypad/Display Menu Structure

Figure 10: Service Menu – Keypad/Display Menu Structure

See page 32 — 35
Service Menus
Timer Settings ►
Operating Hours ►
Save/Restore Settings ►
Active Alarms ►
Alarm Log ►
Event Log ►
Alarm/Event Config ►
Analog Input Status ►
Universal I/O Status ►
Digital Input Status ►
Digital Output Status ► See page 22 See page 32 See page 32 See page 33
Modbus Status ► Timer Settings Operating Hours Save/Restore Settings Active Alarms
IP Set-up ► Pwd Timeout= 10min Supply Fan= XXXXXh Save Params= No Alm Count: xx Clr Alms= No
HMI Set-up ► Clg Stg Time= 5min Ret/Exh Fan= XXXXXh Rstr Params= No +Alarm 1: Alarm Type ►
Sensor Offsets ► OffHtCIDelay= 120s INV Comp= XXXXXh Rstr Factory= No +Alarm 2: Alarm Type ►
Comp 3= XXXXXh SaveToCard= No ●
Cmp Cooling= XXXXXh LoadFromCard= No ●
Cmp Heating= XXXXXh CreateTrace= No ●
Trace To SD= No +Alarm 10: Alarm Type ►

3
3, 4 See connection on page 16

See page 33 See page 34 See page 34 See page 34


Analog Input Status Universal I/O Status Digital Input Status Digital Output Status
MCB Al1= XXXXXXXX MCB X1= XXXXXXXX MCB DI1= XXXXXXXX MCB DO1= XXXXXXXX
MCB Al2= XXXXXXXX MCB X2= XXXXXXXX MCB DI2= XXXXXXXX MCB DO2= XXXXXXXX
MCB Al3= XXXXXXXX MCB X3= XXXXXXXX MCB DI3= XXXXXXXX MCB DO3= XXXXXXXX
EMD Al1= XXXXXXXX MCB X4= XXXXXXXX MCB DI4= XXXXXXXX MCB DO4= XXXXXXXX
EMD Al2= XXXXXXXX MCB X5= XXXXXXXX MCB DI5= XXXXXXXX MCB DO5= XXXXXXXX
EMD Al3= XXXXXXXX MCB X6= XXXXXXXX MCB DI6= XXXXXXXX MCB DO6= XXXXXXXX
MCB X7= XXXXXXXX EMB DIA1= XXXXXXXX MCB DO7= XXXXXXXX
MCB X8= XXXXXXXX EMD DIA1= XXXXXXXX MCB DO8= XXXXXXXX
EMD X1= XXXXXXXX EMD DIA4= XXXXXXXX MCB DO9= XXXXXXXX
EMD X2= XXXXXXXX MCB DO10= XXXXXXXX
EMD X3= XXXXXXXX EMD DO1= XXXXXXXX
EMD X4= XXXXXXXX EMD DO2= XXXXXXXX
EMD X5= XXXXXXXX EMD DO3= XXXXXXXX
EMD X6= XXXXXXXX EMD DO4= XXXXXXXX
EMD X7= XXXXXXXX EMD DO5= XXXXXXXX
EMD X8= XXXXXXXX EMD DO6= XXXXXXXX

OM 1263 • MICROTECH UNIT CONTROLLER 14 www.DaikinApplied.com


Keypad/Display Menu Structure

See page 33 See page 33 See page 33


Alarm Log Event Log Alarm/Event Config
Log Count: xx Clr Log= No ► Log Count: xx Clr Log= No ► ALARM DELAYS
+/-Alarm 1: Alarm Type ► +/-Alarm 1: Alarm Type ► Sens Alm Dly= 30s
+/-Alarm 2: Alarm Type ► +/-Alarm 2: Alarm Type ► Temp AlmDly= 30s
● ● ALARM CONFIG
● ● AlmLogToSD= No
● ● EVENT CONFIG
+/-Alarm 10: Alarm Type ► +/-Alarm 10: Alarm Type ► Show Events= Yes
● ● EventLogToSD= No
● ● SNAPSHOT CONFIG
● ● EnaSnapshots= Yes
+/-Alarm 50: Alarm Type ► +/-Alarm 50: Alarm Type ► Show Snapshots= Yes
SnapshotsToSD= No

See page 35 See page 34 See page 39 See page 35


Modbus Status IP Set-Up HMI Set-Up Sensor Offsets
SF MB Status= XXXXXXX ApplyIPChgs= No Contrast= 0 OA Temp= 0.0ºF
RF/EF MB Status= XXXX DHCP= On BackLight Clr= White DRT1= 0.0ºF
OF MB Status= XXXXXX Act Ip= XXX.XXX.XXX.XXX PBusPwrSply= On DRT3= 0.0ºF
IFB MB Status= XXXXXX ActMsk= XXX.XXX.XXX.XXX SRT= 0.0ºF
VCmp MB Status= XXXX ActGwy= XXX.XXX.XXX.XXX DFT= 0.0ºF
MB Resistance= Yes Gvn IP= XXX.XXX.XXX.XXX IRT= 0.0ºF
ECM Config= Done GvnMsk= XXX.XXX.XXX.XXX ORT= 0.0ºF
GvnGwy= XXX.XXX.XXX.XXX

www.DaikinApplied.com 15 OM 1263 • MICROTECH UNIT CONTROLLER


Keypad/Display Menu Structure

Figure 11: Trending – Keypad/Display Menu Structure

See page 38
Trending
Trending Ena= No
Apply Chgs= No
Sample Time= 300s
TrendOnOff= Off
Export Data= No
Clear Trend= Done
TrendFull= Wrap
DefaultTrend= No
Points 1–8 ►
Points 9–24 ►
Points 25–30 ►
Points 1–8 Points 9–24 Points 25–30
Point 1= INV% Point 9= Clg St Point 25= SSH
Point 2= STDOut Point 10= Htg St Point 26= SSHSpt
Point 3= SAF% Point 11= Cap%In Point 27= HDRT1
Point 4= EF% Point 12= INVCmd Point 28= HDRT3
Point 5= OAD% Point 13= CmpInLk Point 29= OilSts
Point 6= RH% Point 14= PTD Point 30= OilMng
Point 7= H/C Out Point 15= PTS
Point 8= OAT Point 16= EVI%
Point 17= EVO%
Point 18= OAFCmd
Point 19= OF1Spd
Point 20= OF2Spd
Point 21= Tc
Point 22= TcSpt
Point 23= DSH
Point 24= Teg

Figure 12: Expansion Information – Keypad/Display Menu Structure

1 2
See page 100 See page 42
Fault Code Details IFB Comm Status
ACTIVE FAULT CODES IFB SW Vers= VP0329008
INVAlarmCode=______ IFBCommStatus=____
Code Text PrvCommStatus=_______
OF1AlarmCode=_______ MM/DD/YYYY HH:MM:SS
Code Text ACS1 DataRcvd=_______
OF2AlarmCode=_______ ACS3 DataRcvd=_______
Code Text
PREVIOUS FAULT CODES
PrvINVAlmCode=_______
Code Text 3 4
MM/DD/YYYY HH:MM:SS See page 33 See page 33 See page 33
PrvOF1AlmCode=______ Alarm Lists Active Alarms Alarm Log Alarm Details
Code Text Active Alarms ► Alm Count: xx Clr Alms= No Log Count: xx Clr Log= No ► +/-Alarm 1: Alarm Type
MM/DD/YYYY HH:MM:SS Alarm Log ► +Alarm 1: Alarm Type ► +/-Alarm 1: Alarm Type ► MM/DD/YYYY HH:MM:SS
PrvOF2AlmCode=______ Event Log ► +Alarm 2: Alarm Type ► +/-Alarm 2: Alarm Type ►
Code Text ● ●
LogCt:** Clr Log= -:No
MM/DD/YYYY HH:MM:SS
+Event 1 ► ● ●
+Event 2 ► ● ●
● +Alarm 10: Alarm Type ► +/-Alarm 10: Alarm Type ►
● ●
● ●

+Event 49 ►
+Event 50 ► +/-Alarm 50: Alarm Type ►
Event Details ►
+Alarm: Alarm Type ►
Alarm Date
Alarm Time

OM 1263 • MICROTECH UNIT CONTROLLER 16 www.DaikinApplied.com


Quick Menu

Quick Menu

Items in the Quick Menu (see Table 2) contain basic unit operating status and control set point parameters. The items shown in the
Quick Menu are Read Only if a valid password has not been entered. The following are brief descriptions of the Quick Menu items.
No password is required to view the Quick Menu.

Table 2: Quick Menu


Menu Display Name Default Setting Range Password Level
System Mode Local Local/Remote 6
Heat/Cool In Heat/Cool Heat/Cool 6
CmpIntrLock — Open/Closed 6
Dehum Status — Active/Inactive 6
Clg Capacity — 0 – 100% None
OAD/Econo Cap — 0 – 100% None
Htg Capacity — 0 – 100% None
Reheat Capacity — 0 – 100% None
SAF Speed — 0 – 100% None
RF/EF Cap — 0 – 100% None
OA Temp — -50.0 – 200.0°F None

System Mode is an adjustable item that sets the status for OAD/Econo Cap is a status only item which indicates the
the for the unit to run on local with field inputs are ignored or percentage that the outdoor damper or economizer valve is
remote where operation is based on field inputs currently open.
Heat/Cool In is an adjustable item that only applicable Htg Capacity is a status only item which indicates the
on heatpump units to determine DX cooling or heatpump percentage of the unit maximum heating capacity currently
operation operating.
CmpInterLock is an adjustable input safety that can be used Reheat Capacity is a status only item which indicates the
to prevent compressor operation based on external system percentage of the unit maximum reheat capacity currently
safeties operating.
Dehum Status is a status only item which indicates the status SAF Capacity is a status only item which indicates the
of operation of the dehumidifier. The dehumidifier can be active capacity of the supply air fan.
or inactive. RF/EF Capacity is a status only item indicating the capacity of
Clg Capacity is a status only item which indicates the the return fan/exhaust air fans.
percentage of the unit maximum cooling capacity currently OA Temp is a status only item which displays the current
operating. temperature reading from the unit mounted outdoor air
temperature sensor. This sensor is standard on all units.

www.DaikinApplied.com 17 OM 1263 • MICROTECH UNIT CONTROLLER


View/Set Menu

View/Set Menu

Unit Status Settings


The “Unit Status Settings” menu provides a summary of basic unit status and control items. This menu summarizes the current
operating state of the unit, giving the operating state the unit is in, along with the current capacity level of that operating state.

Table 3: Unit Status Settings


Item Display Name Default Setting Range Password Level
Local
System Mode= Local 6
Remote
Heat
Heat/Cool In= Heat/Cool 6
Cool
Open
CmpIntrLock= — 6
Closed
CmpCapIn= — 0-100% 6
Off
SAFSSIn= — 6
On
SAFCapIn= — 0-100% 6
Off
EAFSSIn= — 6
On
EAFCapIn= — 0-100% 6
RhtVlvIn= — 0-100% 6
OADCapIn= — 0-100% 6
Normal
AlmResetIn= — 6
Clear
Inactive
Dehum Status= — 6
Active
Enabled
NA
OffAmb
Clg Status= — 6
OffAlarm
NA
NA
Enabled
NAOffAmb
Htg Status= — 6
OffAlarm
NANA
Clg Capacity= — 0-100% 6
Htg Capacity= — 0-100% 6
Reheat Cap= — 0-100% 6
SAF Speed= — 0-100% 6
RF/EF Cap= — 0-100% 6
OAD/Econo Cap= — 0-100% 6

OM 1263 • MICROTECH UNIT CONTROLLER 18 www.DaikinApplied.com


View/Set Menu

System Mode is an adjustable item that sets the status for Clg Status is a status only item which indicates whether or not
the for the unit to run on local with field inputs are ignored or mechanical cooling is currently allowed. If cooling is disabled,
remote where operation is based on field inputs the reason is indicated.
Heat/Cool In is an adjustable item that only applicable Htg Status is a status only item which indicates whether or
on heatpump units to determine DX cooling or heatpump not heating is currently allowed. If heating is disabled, the
operation reason is indicated. If the unit is a heat pump, this applies to
compressor heat.
CmpInterLock is an adjustable input safety that can be used
to prevent compressor operation based on external system Clg Capacity is a status only item which indicates the
safeties percentage of the unit maximum cooling capacity currently
operating.
CmpCapln is the adjustable input for the amount of DX output
desired Htg Capacity is a status only item which indicates the
percentage of the unit maximum heating capacity currently
SAFSSIn is the adjustable input for the supply fan start/stop
operating. If the unit is a heat pump, this applies to the
input
compressor heat.
SAFCapIn is adjustable input for the supply fan capacity
Reheat Capacity is a status only item which indicates the
desired
percentage of the unit maximum reheat capacity currently
EAFSSIn is the adjustable input for the exhaust fan start/stop operating.
input
SAF Capacity is a status only item which indicates the
EAFCapIn is the adjustable input for the exhaust fan capacity capacity of the supply air fan.
desired
RF/EF Capacity is a status only item indicating the capacity of
RhtVlvIn is the adjustable input for the amount of hot gas the return fan/exhaust air fans.
reheat desired
OAD/EconoCap is a status item which indicates the
OADCapIn is the adjustable input for the amount open desired percentage that the outdoor damper is currently open.
of outdoor air damper
AlarmResetIn the adjustable point from the field that can reset
applicable refrigeration alarms
Dehum Status is a status only item which indicates the status
of operation of the dehumidifier. The dehumidifier can be active
or inactive.

www.DaikinApplied.com 19 OM 1263 • MICROTECH UNIT CONTROLLER


View/Set Menu

Temperature Menu
Menus in the Temperatures menu contain unit temperature status information.

Table 4: Temperature Menu


Item Display Name Default Setting Range Password Level
OA Temp= — -50.0 – 200.0°F 6
DRT1= — -50.0 – 392.0°F 6
DRT3= — -50.0 – 392.0°F 6
SRT= — -50.0 – 200.0°F 6
DFT= — -50.0 – 200.0°F 6
IRT= — -50.0 – 150.0°F 6
ORT= — -50.0 – 150.0°F 6
INVCompTemp= — -50.0 – 392.0°F 2

OA Temp is a status only item which displays the current DFT (Heat Pump only) is a status only item which displays the
temperature reading from the unit mounted outdoor air current defrost temperature sensor reading.
temperature sensor.
IRT (Heat Pump only) is a status only item which displays the
DRT1 is a status only item which displays the current inverter current indoor refrigerant temperature sensor reading.
compressor discharge refrigerant line temperature sensor ORT (Heat Pump only) is a status only item which displays the
reading. current outdoor refrigerant temperature sensor reading.
DRT3 is a status only item which displays the current fixed INVCompTemp (15 ton unit size only) is a status only
compressor (Comp 3) discharge refrigerant line temperature item which displays the current inverter compressor body
sensor reading. temperature sensor reading.
SRT is a status only item which displays the current suction
refrigerant line temperature sensor reading.

Flow Status Menu SAF Spd Control Menu


Table 5: Flow Status Menu Table 7: Supply Fan Speed Menu
Item Display Item Display
Default Setting Range Password Level Default Setting Range Password Level
Name Name
Off SAF Speed= — 0 – 100% 6
Supply Fan= — 6 SAF Spd Cmd= — 0 – 100% 6
On
Off
Ret/Exh Fan= —
On
6 SAF Speed is a status only item that indicates the current
supply fan speed.
Supply Fan is a status only item that indicates the current S/S Speed Cmd is a status only item that indicates the current
state of the supply fan. supply fan commanded speed.
Ret/Exh Fan is a status only item that indicates the current S/S
state of the exhaust or return fan.

RF/EF Control Menu


Table 6: Return/Exhaust Fan Speed Menu
Item Display
Default Setting Range Password Level
Name
RF/EF Cap= — 0 – 100% 6
RF/EF Spd Cmd= — 0 – 100% 6

RF/EF Cap is a status only item which indicates the current


exhaust fan capacity.
RF/EF Spd Cmd is an adjustable input to command the return/
exhaust fan speed.

OM 1263 • MICROTECH UNIT CONTROLLER 20 www.DaikinApplied.com


View/Set Menu

Time/Date Menu
Table 8: Time/Date
Item Display Name Default Setting Range Password Level
Time= — 0 – 23: 0 – 59: 0 – 59 6
Date= — 1 – 12/0 – 31/1970 – 9999 6
UTC Diff= -60 — 4
NA
Jan
Feb
Mar
Apr
May
DLS Strt Mon= Mar Jun 2
Jul
Aug
Sep
Oct
Nov
Dec
1stSun
2ndSun
DLS Strt Wk= 2ndWeek 3rdSun 2
4thSun
5thSun
NA
Jan
Feb
Mar
Apr
May
DLS End Month= Nov Jun 2
Jul
Aug
Sep
Oct
Nov
Dec
1stSun
2ndSun
DLS End Week= 1stWeek 3rdSun 2
4thSun
5thSun
DLS Enable= Auto Off/Auto 2

Time is an adjustable item that sets the current time. DLS End Month is the adjustable item to select the month that
daylight savings locally ends
Date is an adjustable item that sets the current date.
DLS End Week is the adjustable item to select the week that
UTC Diff It is an adjustable parameter that can be set to
daylight savings locally ends
indicate how the local time where the unit is situated differs
from the Coordinated Universal Time (UTC). DLS Enable is an adjustable item that sets whether or not
daylight savings time is enabled
DLS Strt Mon is the adjustable item to select the month that
daylight savings locally begins
DLS Strt Wk is the adjustable item to select the week that
daylight savings locally begins

www.DaikinApplied.com 21 OM 1263 • MICROTECH UNIT CONTROLLER


Commission Unit

Commission Unit

Unit Setup SAF Set-up


Table 9: Unit Setup Menu (See page 22 for more information)
Default Password
Item Display Name
Setting
Range
Level Table 11: Supply Fan Speed Menu
Eng Units= English English, SI 4 Item Display
Default Setting Range Password Level
Unit Name= — — 4 Name
MaxVentSpd= 100% 0 – 100% N/A
Eng Units is an adjustable item to indicate if the unit is to Max SAF RPM= 2600 0 – 5000 2
display English or Metric units of measure. Max SAF Hz= 60.0Hz 0 – 100Hz 2
Unit Name is an adjustable item that allows each controller CompOp_
20% 10 – 100% 2
MinSAF=
to be given a unique name. This may be useful when multiple
OK
units are connected to a single remote HMI.
HLL
TFEI

Timer Settings Menu TFM


TFE
BLK
Table 10: Timer Settings Menu “SAF Status=
— SKF 2
(EBM Fan)*”
PHA
Password
Item Display Name Default Setting Range UzLow
Level
Pwd Timeout 10 min 3 – 30min 4 UzHigh
Clg Stg Time 5 min 5 – 60min 4 UeLow
Off HtCl Delay 120s 0 – 999s 2 UeHigh
NoComm
Pwd Timeout is an adjustable item that sets the amount OK
of time in minutes that the controller will allow access to “SAF Status=
— Fault 2
(ABB Drive)”
applicable menus without re-entering the necessary password. No Comm
If the keypad display remains idle for this time period, the *See supply fan failure codes on page 98
display will revert to the “main menu” requiring a re-enter of the
password. Max Vent Speed is an adjustable item that sets the supply fan
speed when an external ventilation override input to the supply
Clg Stg Time is an adjustable item used to set a minimum time fan is present.
period between compressor stage changes.
Max SAF RPM is an adjustable item that sets the maximum
OffHtClDelay is an adjustable item that sets a delay in turning RPM value for the supply air fan. Note this is set based on the
OFF the supply air fan when the unit is shut OFF while cooling supply fan model size and the system specifications.
or heating operation is active.
Max SAF Hz is an adjustable item to allow the maximum fan
speed based on space design conditions
CompOp_MinSAF is an adjustable minimum speed for the fan
to be running and allow for compressor operation
SAF Status is a status only item that the fan motor or VFD
output on the status of the supply fan motor

OM 1263 • MICROTECH UNIT CONTROLLER 22 www.DaikinApplied.com


Commission Unit

RF/EF Set-Up
(See page 23 for more information)
Table 12: Return Fan/Exhaust Fan Set-up Menu
Item Display
Default Setting Range Password Level
Name
MaxVentSpd= 100% 0 – 100% N/A
Max RFEF RPM= 2600 0 – 5000 2
Max RF/EF Hz= 60.0Hz 0 – 100Hz 2
CompOp_
20% 10 – 100% 2
MinSAF=
OK
HLL
TFEI
TFM
TFE
BLK
“RF/EF Status=
— SKF 2
(EBM Fan)*”
PHA
UzLow
UzHigh
UeLow
UeHigh
NoComm
*See exhaust fan failure codes on page 98

MaxVentSpd is an adjustable item that sets the exhaust


fan speed when an external ventilation override input to the
exhaust fan is present.
Max RFEF RPM= is an adjustable item that sets the maximum
RPM value for the exhaust air fan.
NOTE: This is set based on the exhaust fan model size.
Max RF/EF Hz is an adjustable item to allow the maximum fan
speed based on space design conditions
CompOp_MinSAF is an adjustable minimum speed for the fan
to be running and allow for compressor operation
RF/EF Status is a status only item that the fan motor or VFD
output on the status of the exhaust or return fan motor

www.DaikinApplied.com 23 OM 1263 • MICROTECH UNIT CONTROLLER


Commission Unit

Inverter Compressor Set-Up


(See page 51 — 56 for more information)

Table 13: Inverter Compressor Set Up Menu


Item Display
Item Display Default Setting Range Password Level
Default Setting Range Password Level Name
Name
Compressor Setup
Compressor Status
Clg Stg Time= 5min 3 – 60min 4
Off
55°F (RTU/SCU)
Start
Clg Lo OAT Lk= 0°F (MPS) 0 – 100°F 4
Init
Clg State= — 4 25°F (DPS)
Normal
Clg OAT Diff= 2°F 0 – 10°F 4
Pumpdn
0°F
Standby
Htg Lo OAT Lk= 45°F (100% OA -20 – 50°F 4
Off
w/o ER)
Start
Htg Hi OAT Lk= 55°F 0 – 100°F 4
Init
Htg State= — 4 EffHtgHiOATLk= — 0 – 100°F 4
Normal
Htg OAT Diff= 2°F 0 – 10°F 4
Pumpdn
INV Period= 20s 1 – 300s 4
Standby
INV Gain= 2 0.0 – 100.0 4
INV Cmp Spd= — 0 – 100% 4
INV PAT= 60s 0 – 999s 4
INV Spd Cmd= — 0 – 100% 4
INV Max Chg= 15% 0 – 50% 4
Open
VCmpOilStatus= — 2 Off
Closed
Balance
Off
Comp 3= — 4 OilManagement= Off LoBoost 2
On
HiBoost
Fault Code Details
Boost
INV Port Temp= — -50.0 – 200.0°F 2
LowOilTime= 10m 1 – 30m 2
INV Fin Temp= — -50.0 – 200.0°F 2
OilBoostTime= 10m 1 – 15m 2
INV Amps= — 0 – 50A 4
OK
Ctrl Card Tmp= — -50.0 – 200.0°F 2
OvrTActv
Heatsink Tmp= — -50.0 – 200.0°F 2
WrnActv
Refrig Circuit Status
VFD Status= — AlmNoTrp 2
PTD= — 0 – 5000kPa 4
AlmTrp
PTS= — 0 – 5000kPa 4
TripLck
Cool
4 WayValve= — 2 NoComm
Heat
None
Closed VFD Alm/Wrn= — 2
RcvrSol Valve= — 2 A** – W**
Open
IFB Comm Status (10010)
Closed
BP Sol Valve= — 2
Open

OM 1263 • MICROTECH UNIT CONTROLLER 24 www.DaikinApplied.com


Commission Unit

Clg State is a status only item which displays the current Mechanical cooling operation is disabled when the outdoor air
compressor operating state when the unit is in the Cooling temperature sensor input falls below this set point.
operating state or when dehumidification operation is active. Clg OAT Diff is a status only item which indicates if the unit is in
See page 55 for compressor cooling operating state details. the deadband for the low ambient cooling lockout and will indicate
Htg State (Heat Pump only) is a status only item which when the unit is no longer in that lockout condition.
displays the current compressor operating state when the unit Htg Lo OAT Lk is an adjustable item that sets a low outdoor
is in the Heating or Min DAT operating state. See page 65 ambient temperature value below which compressor heating is
for compressor heating operation state details. locked out.
INV Cmp Spd is a status only item which displays the current Htg Hi OAT Lk is an adjustable item that sets a high outdoor
inverter compressor speed in percent of the maximum. ambient temperature value above which compressor heating is
INV Spd Cmd is a status only item that indicates the current locked out.
commanded speed of the inverter compressor. EffHtgOATLk is a status only item that displays the current
VCmpOilStatus is a status only item which displays if the unit is value that is being used for high outdoor ambient compressor
in oil boost mode or standard operation. Open indicates a low oil heating lock out. Normally this value reads the same as the Htg
reading Hi OAT Lk but can be lower due to the low differential pressure
limiting function while the unit is operating in the Heating or
Comp 3 is a status only item which displays the current on/off
MinDAT states.
status of the fixe compressor.
Htg OAT Diff is a status only item which indicates if the unit is the
INV Port Temp is a status only item which displays the current
deadband for the high ambient compressor heating lockout and
value of the calculated temperature (based on the current
will indicate when the unit is no longer in that lockout condition
suction pressure reading) at the inverter compressors inlet
port. This value is used in the inverter compressor discharge INV Period is an adjustable item that sets the sample period
line higher temperature limiting protection function. for the PI loop used to control the compressor capacity to
maintain the effective discharge air temperature set point.
INV Fin Temp is a status only item which displays the current
inverter compressor control board cooling fin temperature. INV Gain is an adjustable item that sets the Gain for the PI
This value is used in the inverter compressor fin temperature loop used for the PI loop used to control the compressor
limiting protection function. capacity to maintain the effective discharge air temperature set
point.
INV Amps is a status only item which displays the amps used by
the inverter compressor (3-15Ts only). This can indicate a high INV PAT is an adjustable item that sets the project ahead
amp unloading occurance. time for the PI loop used for the PI loop used to control the
compressor capacity to maintain the effective discharge air
Ctrl Card Tmp is a status only item which displays the drive
temperature set point.
temperature (16-28Ts only). This can indicate a high temp
unloading occurance. INV Max Chg is an adjustable item that sets the maximum
change value for the PI loop used for the PI loop used to
Heatsink Tmp is a status only item which displays the board
control the compressor capacity to maintain the effective
heat temperature (16-28Ts only). This can indicate a high temp
discharge air temperature set point.
unloading occurance.
OilManagement is a status only point that indicates if the unit
PTD is a status only item which displays the current value of
(16–28 Ton only) is in a oil boost mode or not.
the discharge line refrigerant pressure.
LowOilTime is an adjustable point to set the length of time,
PTS is a status only item which displays the current value of
while in oil return mode, the unit will verify oil level as adequitely
the suction line refrigerant pressure.
maintained.
4 Way Valve (Heat Pump only) is a status only item which
OilBoostTime is an adjustable point to set the length of time,
displays the current Heat/Cool (Closed/Open) status of the
while in oil return mode, the unit will actively accellerate the
heat pump four way reversing valve.
compressor speed to return oil to the compressor.
RcvrSol Valve (Heat Pump only) is a status only item which
VFD Status is a status only point from the inverter compressor
displays the current Open/Closed status of the heat pump
VFD (16–28 Ton only) indicating the current state of the drive.
receiver solenoid valve.
VFD Alm/Wrn is a status only point from the inverter
BP Sol Valve is a status only item which displays the current
compressor VFD (16–28 Ton only) indicating the drive fault
Open/Closed status of the refrigerant circuit bypass solenoid
codes.
valve. This valve is normally closed but opens when needed to
equalize the low and high side refrigerant pressures.
Clg Stg Time is an adjustable item used to set a minimum time
period between compressor stage changes
Clg Lo OAT Lk is an adjustable item which sets the low
outdoor air temperature mechanical cooling lockout point.

www.DaikinApplied.com 25 OM 1263 • MICROTECH UNIT CONTROLLER


Commission Unit

Outdoor Air Fan Set-Up


Table 14: Outdoor Air Fan Set Up Menu OA Fan1 Spd is a status only item that displays the current
speed of outdoor fan 1 in percent of maximum speed.
Item Display
Default Setting Range Password Level
Name OA Fan1 Cmd= is is a status only item that indicates the
OAFan Set-Up (347) current command speed of outdoor fan 1.
OA Fan Status
OA Fan1 Amps is a status only item which displays the current
OA Fan1 Spd= — 0 – 100% 4
amperage being drawn by outdoor fan 1.
OA Fan1 Cmd= — 0 – 100% 4
OA Fan1Amps= — 0 – 50A 4 OA Fan2 Spd is a status only item that displays the current
Fault Code Details (10000) speed of outdoor fan 2 in percent of maximum speed.
OA Fan2 Spd= — 0 – 100% 4
OA Fan2 Cmd= is is a status only item that indicates the
OA Fan2 Cmd= — 0 – 100% 4
current command speed of outdoor fan 2.
OA Fan2Amps= — 0 – 50A 4
Fault Code Details (10000) OA Fan2 Amps is a status only item which displays the current
Refrig Circuit Status amperage being drawn by outdoor fan 2.
PTD= — 0 – 5000kPa 4 PTD is a status only item which displays the current discharge
PTS= — 0 – 5000kPa 4 refrigerant line pressure sensor reading.
Disch Sat Tmp= — -50.0 – 212.0°F 4
EffDshSatTSpt= — -50.0 – 212.0°F 2 PTS is a status only item which displays the current suction
OA Temp= — -50.0 – 200.0°F 4 refrigerant line pressure sensor reading.
INV Fin Temp= — -50.0 – 200.0°F 2 Disch Sat Tmp is a status only item which displays the current
OA Fan Setup discharge pressure equivalent saturation temperature.
DischSatTDiff= 15°F 10.0 – 20.0°F 2
Disch SatTDB= 2.0°F 2 – 10.0°F 2
EffDshSatTSpt is a status only item which displays the
OA Fan period= 25s 0 – 999s 4
effective discharge saturation temperature set point used to
OA Fan Gain= 2.5 0 – 100 4
control the outdoor air fans in the cooling mode of operation.
OA Fan PAT= 75s 0 – 999s 4 OA Temp is a status only item which displays the current
OA Fan Max= 20% 0 – 100% 2 temperature reading from the unit mounted outdoor air
OK temperature sensor.
HLL
INV Fin Temp is a status only item which displays the current
TFEI
inverter compressor control board cooling fin temperature.
TFM
This value is used in the inverter compressor fin temperature
TFE
limiting protection function.
BLK
OF Status= — SKF 2 DischSatTDiff is an adjustable item which sets a differential
PHA above the current outdoor air temperature reading which is
UzLow used to establish the EffDshSatTSpt.
UzHigh
DischSatTDB is an adjustable item which sets a control
UeLow
deadband around the EffDshSatTSpt.
UeHigh
NoComm OA Fan Period is an adjustable item that sets the sample
IFB Comm Status (10010) period for the PI loop used to control the outdoor fans in the
cooling mode of operation to maintain the EffDshSatTSpt.
OA Fan Gain is an adjustable item that sets the Gain for the PI
loop used for the PI loop used to control the outdoor fans in the
cooling mode of operation to maintain the EffDshSatTSpt.
OA Fan PAT is an adjustable item that sets the project ahead
time for the PI loop used for the PI loop used to control the
outdoor fans in the cooling mode of operation to maintain the
EffDshSatTSpt.
OF Status is a status only item that the fan motor on the status
of the outdoor fan motor

OM 1263 • MICROTECH UNIT CONTROLLER 26 www.DaikinApplied.com


Commission Unit

Expansion Valve Set-Up


Table 15: Expansion Valve Set Up Menu EVO Pos (Heat Pump only) is a status only item which
displays the current position of the outdoor expansion valve.
Item Display Default Range Password
Name Setting Level EVI Pos is a status only item which displays the current
Expansion Valve Status position of the indoor expansion valve.
EVI Pos= — 0–100% 4
EVI Status is a status only item which displays the current
EVO Pos= — 0–100% 4
OK status of the connection between the IFB communication board
EVIErr and the expansion valve control board (EVB).
EVOErr
EV Status= — 4 PTS is a status only item which displays the current suction
EVI&OErr
InitErr refrigerant line pressure sensor reading.
MBErr PTD is a status only item which displays the current discharge
Refrigerant Circuit Status refrigerant line pressure sensor reading.
PTS= — 0–5000kPa 4
PTD= — 0–5000kPa 4 Suction SH is a status only item which displays the current
Suction SH= — -100.0–100.0°F 4 suction superheat value based on suction temperature minus
Discharge SH= — -100.0–100.0°F 4 saturated suction pressure.
Subcooling= — -100.0–100.0°F 4
Eff SSH Spt= — 3.0–22.0°F 2 Discharge SH= is a status only item that indicates the current
EffSH Base= — 5.0–9.0°F 2 discharge superheat value based on discharge refrigerant
Eff SC Spt= — 0.0–15.0°F 2 temperature minus the discharge saturation temperature.
Eff SC Lo Lmt= — 0–100% 2
SRT= — -50.0–200.0°F 2 Subcooling (Heat Pump only) is a status only item which
Disch Sat Tmp= — -50.0–212.0°F 2 displays the current discharge subcooling value.
Sucn Sat Tmp= — -50.0–212.0°F 2
IRT= — -50.0–200.0°F 2
Eff SSH Spt is a status only item which displays the effective
ORT= — -50.0–200.0°F 2 suction superheat set point. This value varies depending on
Expansion Valve Set Up suction and discharge superheat conditions.
SSH DB= 0.5°F 0–10.0°F 2
Eff SH Base is a status only item which displays the effective
SSHLoBase= 5.0°F 0–10.0°F 2
SSHHiBase= 8.0°F 0–10.0°F 2
suction superheat base set point value. This value is normally
STD set equal to the SH Hi Base value but can be lowered toward
Htg EVI Meth= STD 2
Sbc the SH Lo Base value during steady state supply fan and
IC SC Spt= — 0–15.0°F 2 compressor operation.
IC SC DB= — 0.0–10.0°F 2
HtgSC EVI Min= 0% 0–100% 4 Eff SC Spt (Heat Pump only) is a status only item which
STD displays the effective subcooling set point. This value is
Clg EVO Meth= STD 2
ALT normally set equal to the IC SC Spt (or OC SC Spt) value but
OC SC Spt= — 0–15.0°F 2 can be raised toward 15°F during steady state supply fan and
OC SC DB= — 0.0–10.0°F 2
compressor operation.
ClgSC EVI Min= 0% 0–100% 4

ManCtrl EV Op= Auto


Man
2
Eff SC Lo Lmt (Heat Pump only) is a status only item which
Auto displays the effective subcooling expansion valve position low
limit. This value is normally set to the 50% but can be lowered
during steady state supply fan and compressor operation.
SRT is a status only item which displays the current suction
refrigerant line temperature sensor reading. This value is used
to calculate suction superheat.
Disch Sat Tmp is a status only item which displays the current
discharge pressure equivalent saturation temperature.
Sucn Sat Tmp is a status only item which displays the current
suction pressure equivalent saturation temperature.

www.DaikinApplied.com 27 OM 1263 • MICROTECH UNIT CONTROLLER


Commission Unit

IRT (Heat Pump only) is a status only item which displays the OC SC Spt is an adjustable item that sets a base value for the
current indoor refrigerant temperature sensor reading. Eff SC Spt during cooling operation.
ORT (Heat Pump only) is a status only item which displays the OC SC DB is an adjustable item that sets a deadband around
current outdoor refrigerant temperature sensor reading. the Eff SC Spt during cooling operation.
SSH DB is an adjustable item that sets deadband around ClgSC EVO Min= is an adjustable item which sets a minimum
the Eff SSH Spt for superheat control of either the indoor outdoor expansion valve position for steady-state sub cooling
expansion valve (cooling operation) or outdoor expansion valve reset control during heat pump cooling operation.
(EVO). ManCtrl EV Op is an adjustable item that sets the mode of
SSH Lo Base is an adjustable item that sets a low limit for expansion valve control during Manual Control operation.
the EffSH Base value. This parameter is for test purposes and If set to “Auto” the expansion values are automatically
should not generally be changed in the field. controlled during Manual Control operation. If set to “Man”
the expansion valves are manually controlled during Manual
SSH Hi Base is an adjustable item that sets a high limit for
Control operation.
the EffSH Base value. This parameter is for test purposes and
should not generally be changed in the field. Expansion Valve Control (EVI or EVO, EVO supplied only
on heat pumps)
Htg EVI Method (Heat Pump only) is an adjustable item
that sets the method of control of the indoor expansion valve The EVI valve is modulated use a PI Loop during cooling
(EVI) during heating operation. If set to “STD” EVI is driven operation to maintain the effective suction superheat set point.
continuously to 100% open during heating operation. If set to On heat pump units EVI is either driven to the 100% open
subcooling “Sbc” then EVI is control to maintain the Eff SC Spt position or modulated to maintain the effective subcooling set
during heating operation. point during heating operation.
IC SC Spt is an adjustable item that sets a base value for the The EVO valve is modulated use a PI Loop during heating
Eff SC Spt during heating operation. operation to maintain the effective suction superheat set
point. EVO is either driven to the 100% open position or
IC SC DB is an adjustable item that sets a deadband around modulated to maintain the effective subcooling set point
the Eff SC Spt during heating operation. during cooling operation.
HtgSC EVI Min= is an adjustable item which sets a minimum
indoor expansion valve position for steady-state sub cooling
reset control during heat pump heating operation.
Clg EVO Method (Heat Pump only) is an adjustable item that
sets the method of control of the outdoor expansion valve
(EVO) during cooling operation. If set to “STD” EVO is driven
continuously to 100% open during cooling operation. If set to
“Sbc” then EVO is control to maintain the Eff SC Spt during
cooling operation.

OM 1263 • MICROTECH UNIT CONTROLLER 28 www.DaikinApplied.com


Commission Unit

Defrost Set-Up
(See page 67 for more information) Defrost State (Heat Pump only) is a status only item which
displays the current state of defrost operation. The states are
Off, Initialization, Execute and Terminate.
Table 16: Defrost Set Up Menu
Manual DF (Heat Pump only) is an adjustable item that allows
Item Display Default Range Password for manual initiation of defrost operation.
Name Setting Level
Off MinCmpOpTm (Heat Pump only) is an adjustable item that
Init sets minimum time that compressor heating operation must
Defrost State= — 4 active in the current run cycle before defrost operation can be
Exec
Term initiated.
No MinAccCmpTm (Heat Pump only) is an adjustable item that
Manual DF= No 4
Yes sets minimum accumulated compressor heating run time since
MinCmpOpTm= 10min 0 – 60min 2 the last defrost cycle before defrost operation can be initiated.
MinAccCmpTm= 40min 0 – 300min 2 MaxFrostTm (Heat Pump only) is an adjustable item that
MaxFrostTm= 120min 40 – 360min 2 defines the maximum time during periods of potential coil
Defrost Temp= — -64 – 64°F 2 frosting that can accumulated without initiating a defrost cycle.
Tdef Adj= 0°F -4.0 – 4.0°F 2 Defrost Temp (Heat Pump only) is a status only item
CmpOpTm= — 0 – 50000.0min 2 which displays the effective temperature value the defrost
AccCmpOpTm= — 0 – 50000.0min 2 temperature input must fall below before defrost operation is
LoFrstAccTm= — 0 – 50000.0min 2 initiated base on temperature.
HiFrstAccTm= — 0 – 50000.0min 2
Tdef Adj (Heat Pump only) is an adjustable item that allows a
manual bias adjustment to be used in the internal calculation
of the Defrost Temp. Increasing this value would cause defrost
to be initiated at a warmer defrost temperature value and vise
versa.
CmpOpTime (Heat Pump only) is a status only item which
displays the time that compressor heating operation has been
active in the current run cycle.
AccCmpOpTm (Heat Pump only) is a status only item which
displays the accumulated time of compressor heating operation
since the last defrost cycle.
LoFrstAccTm (Heat Pump only) is a status only item which
displays the accumulated time since the last defrost cycle of
low frost potential.
HiFrstAccTm (Heat Pump only) is a status only item which
displays the accumulated time since the last defrost cycle of
high frost potential.

www.DaikinApplied.com 29 OM 1263 • MICROTECH UNIT CONTROLLER


Alarm Menus

Alarm Menus

Alarm/Event Configuration Menu


Alarm Delays Menu
The Alarm Delays Setup Menu can be accessed when a level 2
password has been entered. The default settings are the result
of many years of testing and should not be changed.

Table 17: Alarm Delays Setup Menu


Item Display Sens Alm Dly is an adjustable item used to set the sensor
Default Setting Range Password Level
Name alarm delay time.
Alarm Delays
Sens Alm Dly= 30s 0 – 300s 2
Temp Alm Dly is an adjustable item used to set the
Temp Alm Dly= 30s 0 – 300s 2
temperature alarm delay time
Alarm Configuration AlmLogToSD is a cselectable option to determine if alarms are
No to be stored on the local SD card.
AlmLogToSD= No SI 2
Show Events is a location to see the events that have
English
occurred on the unit
Event Config
No EventLogToSD is a selectable option to determin if events are
Show Events= Yes 2
Yes to be stored on the local SD card.
No
EnaSnapshots are points and values determined to be
EventLogToSD= No SI 2
captured for review at a later time.
English
Snapshot Config Show Snapshots is a location to see the snapshots that have
No occurred on the unit
EnaSnapshots= Yes 2
Yes SnapshotsToSD is a selectable option to determine if
No snapshots are to be stored on the local SD card.
Show Snapshots= Yes 2
Yes
No
SnapshotsToSD= No SI 2
English

OM 1263 • MICROTECH UNIT CONTROLLER 30 www.DaikinApplied.com


Manual Control Menu

Manual Control Menu

Manual Control
The manual control of operation is a function that is used for INV Spd Cmd is an adjustable item that sets the speed of the
operating the unit during a service call only. The unit must not inverter compressor. Note that the inverter compressor speed
be operated in this mode for any extended period of time. cannot be manually adjusted until the compressor operating
state reaches Normal after the INV Comp output is turned ON.
Table 18: Manual Control Menu
Comp3 is an adjustable item used to turn the fixed speed
Item Display
Default Setting Range Password Level
compressor ON and OFF. Note that the fixed speed
Name compressor cannot be manually turned on unless the SAF Spd
Normal Cmd is first set to at least 33%.
Manual Ctrl= Normal 4
ManCtrl
Off OA Fan is an adjustable item used to turn the outdoor fan(s)
Supply Fan= Off 4 ON and OFF.
On
SAF Spd Cmd= 0% 0 – 100% 4 OA Fan Cmd is an adjustable item that sets the speed of
INV/OF Ena= Off
Off
4
the outdoor fan(s). Note that once the INV Comp or Comp3
On output is turned ON the outdoor fan speed cannot be manually
INV Cmp= Off
Off
4
adjusted until the compressor operating state reaches Normal.
On
INV Spd Cmd= 0% 0 – 100% 4
4 Way Valve (Heat Pump only) is an adjustable item used
Off
to change the 4 way reversing valve from the Cool to Heat
Comp 3= Off
On
4 position. Note that this setting determines whether the
Off
compressors operate in the cooling or heating mode when they
OA Fan= Off
On
4 are manually started.
OA Fan Cmd= 0% 0 – 100% 4 RcvrSol Valve (Heat Pump only) is an adjustable item used to
4 Way Valve= Off
Off
4
open and close the receiver solenoid valve.
On
BP Sol Valve is an adjustable item used to open and close the
Off
RcvrSol Valve= Off 4 bypass solenoid valve.
On
Off EVI Cmd is an adjustable item used to set the position of the
BP Sol Valve= Off 4
On indoor expansion valve. Note that this can only be manually
EVI Cmd= 0% 0 – 100% 4 adjusted when the ManCtrl EV Op parameter is set to “Man”.
EVO Cmd= 0% 0 – 100% 4
EVO Cmd (Heat Pump only) is an adjustable item used to set
Off
RF/EF= Off 4 the position of the outdoor expansion valve. Note that this can
On
only be manually adjusted when the ManCtrl EV Op parameter
RF/EF Spd Cmd= 0% 0 – 100% 4
is set to “Man”.
OAD/Econo= 0% 0 – 100% 4
Reheat Valve= 0% 0 – 100% 4 RF/EF is an adjustable item that turns ON the return/exhaust fan.
Off RF/EF Spd Cmd is an adjustable item for units with variable
RH Output= Off 4
On
speed supply air fan on the return/exhaust fans that sets the
Off
Alm Output= Off 4 speed of the return/exhaust fan.
On
OAD/Econo is an adjustable item which is used to set the
Manual Ctrl is an adjustable item that puts the unit into manual economizer damper position.
control. Major components of the unit are turned ON and OFF by
Reheat Valve is an adjustable item used to manually drive the
this control. The units normal control sequences are overridden
reheat valve open and closed.
in this state with the exception of all the “fault” alarms and the
cooling circuit high pressure and low pressure alarms. RHOutput a status point for if the unit is in reheat mode or not.
Supply Fan is an adjustable item that turns on the supply fan. Alm Output is an adjustable item which is used to turn ON/
OFF the alarm output.
SAF Spd Cmd is an adjustable item only on VAV units that
sets the speed of the supply air fan. When Manual Control is set to ManCtrl, the Control Mode is
set to OFF so that the unit will not restart automatically. When
INV/OF Ena is an adjustable item used to turn the inverter Manual Control is set to Normal all digital outputs in the Manual
compressor/outdoor fan enable output ON and OFF. Inverter Control menu are set to OFF and all the analog outputs are set
compressor or outdoor fans cannot be manually controlled to 0.0% so that all outputs are in the OFF or minimum position
without first turning this output ON. when Manual Control is set to ManCtrl
INV Comp is an adjustable item used to turn the inverter
compressor ON and OFF. Note that the inverter compressor
cannot be manually turned on unless the SAF Spd Cmd is first
set to at least 33% and the INV/OF Ena output is turned ON.

www.DaikinApplied.com 31 OM 1263 • MICROTECH UNIT CONTROLLER


Service Menus

Service Menus

Save/Restore Menu Operating Hours


The Save/Restore menu can be used to save or restore the The Operating Hours menu gives a summary of the hours of
user configured parameters as well as reset the controller back operation for each of the supply fans, return/exhaust fans,
to the factory default parameters. compressors, heating and economizer operation.

Table 19: Save/Restore Menu Table 20: Operating Hours Menu


Item Display Item Display
Default Setting Range Password Level Default Setting Range Password Level
Name Name
No Supply Fan= — 0 – 50000H 4
Save Params= No 2
Yes Ret/Exh Fan= — 0 – 50000H 4
No Cmp Cooling= — 0 – 50000H 4
Rstr Params= No 2
Yes INV Comp= — 0 – 50000H 4
No Comp 3= — 0 – 50000H 4
Rstr Factory= No 2
Yes Cmp Heating= — 0 – 50000H 4
No
SaveToCard= No 2 Supply Fan is a status item which gives the number of hours
Yes
No the supply fan has operated.
LoadFromCard= No 2
Yes Return/Exhaust Fan is a status item which gives the number
No of hours the return/exhaust fans have operated.
CreateTrace= No 2
Yes
No
Cmp Cooling is a status item which indicates the number of
TraceToSD= No
Yes
2 hours compressor cooling has operated.
INV Comp is a status item which indicates the number of hours
Save Params is an adjustable item used to save the current the inverter compressor has operated.
parameters and configuration.
Comp 3 is a status item which indicates the number of hours
Rstr Params is an adjustable item used to restore the current the fixed speed compressor has operated.
parameters and configuration.
Cmp Heating is a status item which indicates the number of
Rstr Factory is an adjustable item used to restore the factory hours compressor heating has operated.
parameters and configuration.
SaveToCard is an adjustable item used to save the current
parameters and configuration to an SD card.
LoadFromCard is an adjustable item used to restore the
current parameters and configuration from an SD card.
NOTE: The controller will automatically perform a reset when
the value of Load From Card is changed from No to
Yes and the enter button is pushed.

OM 1263 • MICROTECH UNIT CONTROLLER 32 www.DaikinApplied.com


Service Menus

Active Alarms Menu Alarm Configuration Menu


All active alarms as well as the date and time that they were The Alarm Configuration menu is also available under the
detected are displayed on the Active Alarm menu. These Commission Unit menu. Refer to page 30.
alarms are displayed in order of group priority: Faults first,
Problems second, and Warnings last. Within each group,
alarms are displayed in the order that they were detected. Analog Input Status Menu
The Analog Input Status Menu provides diagnostic information
Table 21: Active Alarm Menu to qualified service personnel. The items listed in this menu will
provide current status information of the unit’s analog inputs.
Item Display Name Default Range Password
Setting Level The value shown is the input resistance shown in 1/10th of an
Active Alm Count= — 0-10 None ohm scale. Example: MCB-AI1 (DAT sensor) shows a value
No of 181380, the actual resistance would be 18,138 ohms. This
ClrFlts would translate to a temperature of 53.5 ºF.
ClrAlms= No ClrPrblms None
ClrWrngs Table 23: Analog Input Status Menu
ClrAllAlms
+Alarm 1: Alarm Type — — None Item Display
Default Setting Range Password Level
Name
+Alarm 2: Alarm Type — — None
MCB AI1= — 0 – 9999999 2
MCB AI2= — 0 – 9999999 2

Alarm Log Menu MCB AI3=


EMD AI1=


0 – 9999999
0 – 9999999
2
2
The last fifty alarm events (alarm detection and return to EMD AI2= — 0 – 9999999 2
normal) as well as the date and times that they were detected EMD AI3= — 0 – 9999999 2
are displayed on the Alarm Log menu. These alarm events are
displayed in the order that they were detected. The alarm event
that was detected most recently is displayed first. Multiple
occurrences of the same alarm may appear.

Table 22: Alarm Log Menu

Item Display Name Default Range Password


Setting Level
Log Alm Count= — 0-50 None
No
ClrLog= No None
Yes
+Alarm 1: Alarm Type — — None
+Alarm 2: Alarm Type — — None

Once an alarm is cleared there will be two entries in the Alarm


Log. A (+) sign will be shown next to the entry added when the
alarm became active and a (-) sign will be shown next to the
entry added when the alarm has been cleared.

www.DaikinApplied.com 33 OM 1263 • MICROTECH UNIT CONTROLLER


Service Menus

Universal I/O Status Menu Digital Input Status Menu


The Universal I/O Status Menu provides diagnostic information The Digital Input Status Menu provides diagnostic information
to qualified service personnel. The items listed in this menu to qualified service personnel. The items listed in this menu
will provide current status information of the Universal inputs will provide current status information of the controller’s digital
& outputs. If the universal I/O is configured for resistance, inputs.
the value will be displayed in 1/10th ohm scale. If the I/O is
configured for mA, the value will be displayed in micro amps Table 25: Digital Input Status Menu
(1 mA = 1000 micro amps). If I/O is configured for voltage, the
value is displayed in 1/1000th volt scale. Example: MCB-X7 Item Display
Default Setting Range Password Level
Name
(OA Damper analog output) shows a value of 3000, this would
MCB DI1= Off Off/On 2
translate into 3 VDC.
MCB DI2= Off Off/On 2
MCB DI3= Off Off/On 2
Table 24: Universal I/O Status Menu MCB DI4= Off Off/On 2
MCB DI5= Off Off/On 2
Item Display Default Range Password
Name Setting Level MCB DI6= Off Off/On 2
MCB X1= — 0 – 9999999 2 EMB DI1= Off Off/On 2
MCB X2= — 0 – 9999999 2 EMB DI1= Off Off/On 2
MCB X3= — 0 – 9999999 2 EMD DI4= Off Off/On 2
MCB X4= — 0 – 9999999 2
MCB X5= — 0 – 9999999 2
MCB X6= — 0 – 9999999 2
MCB X7= — 0 – 9999999 2 Digital Output Status Menu
MCB X8= — 0 – 9999999 2
EMD X1= — 0 – 9999999 2 The Digital Output Status Menu provides diagnostic
EMD X2= — 0 – 9999999 2 information to qualified service personnel. The items listed
EMD X3= — 0 – 9999999 2 in this menu will provide current status information of the
EMD X4= — 0 – 9999999 2 controller’s digital outputs.
EMD X5= — 0 – 9999999 2
EMD X6= — 0 – 9999999 2
EMD X7= — 0 – 9999999 2
Table 26: Digital Output Status Menu
EMD X8= — 0 – 9999999 2 Item Display Default Password
Name Setting Range Level
MCB DO1= Off Off/On 2
MCB DO2= Off Off/On 2
MCB DO3= Off Off/On 2
MCB DO4= Off Off/On 2
MCB DO5= Off Off/On 2
MCB DO6= Off Off/On 2
MCB DO7= Off Off/On 2
MCB DO8= Off Off/On 2
MCB DO9= Off Off/On 2
MCB DO10= Off Off/On 2
EMD DO1= Off Off/On 2
EMD DO2= Off Off/On 2
EMD-DO3= Off Off/On 2
EMD-DO4= Off Off/On 2
EMD DO5= Off Off/On 2
EMD DO6= Off Off/On 2

OM 1263 • MICROTECH UNIT CONTROLLER 34 www.DaikinApplied.com


Service Menus

Modbus Status Menu Sensor Offsets Menu


The Modbus Status Menu provides diagnostic information The Sensor Offsets Menu provides a means of calibrating the
to qualified service personnel. The items listed provide the various temperature sensor inputs to the unit. Each sensor
status of the Modbus communications with the various devices can be “biased” by as much as +/- 10.0°F.
controlled by the internal Modbus network
Table 28: Sensor Offset Menu
Table 27: Modbus Status Menu
Item Display
Default Setting Range Password Level
Item Display Name
Default Setting Range Password Level
Name OA Temp= 0.0°F 0.0 – 10.0°F 2
SF MB Status= — Fault/OK 2 DRT1= 0.0°F 0.0 – 10.0°F 2
RFEF MB Status= — Fault/OK 2 DRT3= 0.0°F 0.0 – 10.0°F 2
OF MB Status= — Fault/OK 2 SRT= 0.0°F 0.0 – 10.0°F 2
IFB MB Status= — Fault/OK 2 DFT= 0.0°F 0.0 – 10.0°F 2
VCmp MB IRT= 0.0°F 0.0 – 10.0°F 2
— Fault/OK 2
Status= ORT= 0.0°F 0.0 – 10.0°F 2
MBResistance= Yes No/Yess 2
Done
SetAdd1
ECM Config= Done SetAdd2 2
SetAdd4
SetAddCtl

SF MB Status is a status only item which indicates the status


of the Modbus communications between the main controller
and the supply fan motor.
RFEF MB Status is a status only item which indicates the
status of the Modbus communications between the main
controller and the return/exhaust fan motor.
OF MB Status is a status only point to indicate if the
compressor is properly communicating with the controller via
Modbus.
IFB MB Status ...
VCmp MB Status is a status only point to indicate if the
compressor is properly communicating with the controller via
Modbus.
MB Resistance is an adjustable item used turn the main
controller’s internal Modbus termination resistor.
ECM Config is an adjustable item used to set or change the
internal Modbus address in the supply and exhaust fan motors

www.DaikinApplied.com 35 OM 1263 • MICROTECH UNIT CONTROLLER


Unit Configuration Setup

Unit Configuration Setup

Unit Configuration Setup Menu


After the main control board application software is loaded Table 29 lists the configuration code variables including the
into the MCB, it must be “configured” for the specific position within the code, description of the parameter, and the
control application. This consists of setting the value of 25 applicable settings for each. The default values are shown
configuration variables within the MCB. These variables define in bold font. The unit is configured at the factory however
things such as the type of cooling, number of compressors and may also be configured in the field by accessing the Unit
cooling stages and the type of heat. If all of these items are not Configuration Menu. Once changes have been made to the
set appropriately for the specific unit, the unit will not function Unit Configuration Menu, the Apply Changes flag must be
properly. The correct settings for these parameters are defined changed from no to yes in order for the controller to recognize
for a given unit by the unit “Software Configuration Code.” the changes. Setting the Apply Changes flag to yes will
automatically rest the controller.
The “Software Configuration Code” consists of a 29-character
string of numbers and letters. The code can be found on the
Unit Software Identification Label located on the back side of
the control panel door.

Table 29: Unit Configuration Menu


“ROC
Configuration Code Position Description Values (Default in Bold)
Applicability”
3=Rebel Cool Only
1 Unit Type ●
4=Rebel Heat Pump
0=Zone Control NA
1=DAT Control NA
2 Control Type
2=1ZoneVAV NA
3=RefOnly ●
0=None NA
3 Cooling Type
4=Inverter Compressorized Clg ●
0=None ●
1=Generic Condenser NA
4 Compressorized Cooling Configuration
L=1INV/1Circ ●
M=1INV/1STD/1Circ ●
5 Generic Condenser Stages 1-8 Stages (Default 8) NA
0=None
6 Low Ambient NA
1=Yes
7=EBM
7 Condenser Control 8=INV ●
9=INVMC
0=None ●
1=Single Position 30% ●
2=Single Position 100% ●
8 Damper Type 3=Economizer Airside ●
5=100%OA_DOAS NA
6=AirEcon_DOAS NA
7=3-% DOAS NA
0=None ●
9 OA Flow Station 5=Generic Flow Station ●
6=Generic Flow Station w/CO2 NA
0=None ●
1=F&BP Control NA
2=Staged ●
10 Heating Type 5=Steam or Hot Water ●
6=SCR Electric ●
7=MOSLoGas ●
8=MOSHiGas ●
11 Max Heating Stages 1-8 Stages (Default =1) ●
12,13,14 Max Heat Rise Three Digits (Default = 100) ●
6=EBMVAV
15 Supply Fan Type ●
7=EBMCAV

OM 1263 • MICROTECH UNIT CONTROLLER 36 www.DaikinApplied.com


Unit Configuration Setup

“ROC
Configuration Code Position Description Values (Default in Bold)
Applicability”
0=None ●
16 Return Fan Type 6=EBMVAV
7=EBMCAV
0=None ●
1=Tracking NA
Return/Exhaust Fan Capacity Control
17 2=Building Pressure NA
Method
3=Speed/Network NA
4=OADamper NA
0=No
18 Second Duct Pressure Sensor NA
1=Yes
0=No
19 Entering Fan Temp Sensor NA
1=Yes
0=None ●
1=ConstSpdWh/NoRH ●
2=VarSpdWhl/Danfoss ●
20 Energy Recovery 3=VarSpdWhl/MD2 NA
4=VarSpdWhl/MD3 NA
5=VarSpdWhl/ABB ●
6=ConstSpdWhl/wRH ●
0=Individual NA
21 Cooling Circuit Type 1=2,3 or 4 Circ. Water Condenser NA
2=2 Circ Air Condesner ●
0=No ●
22 Head Pressure Control
1=Yes NA
0=Slave ●
23 Bypass Valve Control
1=Bypass NA
24,25,26 Unit Size Three Digits (Default = 050) ●
0=R22 NA
27 Refrigerant Type 1=R407C NA
2=R410A ●
0=None ●
28 Reheat Type 2=ModHG ●
3=StdHtRht NA
0=208/60Hz ●
1=230/60Hz ●
2=460/60Hz ●
3=575/60Hz ●
29 Unit Voltage
4=208/50Hz ●
5=230/50Hz ●
6=460/50Hz ●
7=575/50Hz ●
0=None ●
30 Expansion Valve Type 1=EVBSag ●
4=MTIIIDF ●

www.DaikinApplied.com 37 OM 1263 • MICROTECH UNIT CONTROLLER


Trending

Trending

Trending Menus
The Trending Menus allow for setting up and managing onboard Default
trending of up to 30 data points within the controller. This data
can then be exported to an SD card. The trending memory will There are thirty default trend points for ROC. They will only not
begin over-writing the oldest existing data in the controller’s be recorded if manually programmed not to record.
memory when the allocated trending memory fills up. If an
SD card is installed in the controllers SD card reader slot, an Table 31: Default Trends Menu
automatic export of the data will occur every night at midnight.
Item Display
Default Setting Range Password Level
Name
Table 30: Trending Menu Point 1= INV% INV% 2
Point 2= STDOut STDOut 2
Item Display
Default Setting Range Password Level Point 3= SAF% SAF% 2
Name
Trending Ena= No No/Yes 2 Point 4= EF% EF% 2
Apply Chgs= No No/Yes 2 Point 5= OAD% OAD% 2
Sample Time= 300s 1-3600s 2 Point 6= RH% RH% 2
TrendOnOff= Off Off/On 2 Point 7= H/COut H/COut 2
AutoExpTime= 1440m 0-1440m 2 Point 8= OAT OAT 2
Export Data= No No/Yes 2 Point 9= ClgSt ClgSt 2
Done 2 Point 10= HtgSt HtgSt 2
Clear Trend= Done ClrData 2 Point 11= Cap%In Cap%In 2
ClrCfg 2 Point 12= INVCmd INVCmd 2
TrendFull= Wrap Wrap/Stop 2 Point 13= CmpInLk CmpInLk 2
DefaultTrend= No No/Yes 2 Point 14= PTD PTD 2
Point 15= PTS PTS 2
Trending Ena is an adjustable item which enables and Point 16= EVI% EVI% 2
disables the on board trending function. Point 17= EVO% EVO% 2
Point 18= OAFCmd OAFCmd 2
Apply Changes is an adjustable item which must be set to
Point 19= OF1Spd OF1Spd 2
make changes to trending point definitions and sampling rate
Point 20= OF2Spd OF2Spd 2
take effect.
Point 21= Tc Tc 2
Sample Time is an adjustable item used to the sampling rate Point 22= TcSpt TcSpt 2
for trending data points. Point 23= DSH DSH 2
Point 24= Teg Teg 2
TrendOnOff is an adjustable item which starts and stops the
Point 25= SSH SSH 2
on board trending function.
Point 26= SSHSpt SSHSpt 2
AutoExpTime is the length of time a trend is to be captured Point 27= HDRT1 HDRT1 2
Export Data is an adjustable item which initiates a manual Point 28= HDRT3 HDRT3 2
export of the current on board trend data to an SD card. Point 29= OilSts OilSts 2
Point 30= OilMng OilMng 2
Clear Trend is an adjustable item used to either clear only the
current trend data or the entire trend configuration.
TrendFull is a writable input that allows the user to define
once the trend is recorded to either stop recording or begin to
overwright the beginning of the trend
DefaultTrend is a status to reset all trend reading back to the
unit default settings or not.

OM 1263 • MICROTECH UNIT CONTROLLER 38 www.DaikinApplied.com


Alarms

Alarms

About this Unit Alarms


Alarms provide the user with information about abnormal
Table 32: About this Unit Menu conditions that affect unit operation. The cause of the alarm
should be investigated and eliminated before the unit or any
Menu Display Name Item Display Name
SO_Item=
disabled equipment in it is placed back into service.
Unit SN= Problems are conditions that result in the limitation of unit
App Version=
operation or shut down of the DX circuit. Some of these alarms
Cf1-15=
Cf16-29=
must be cleared manually, but others clear automatically.

About this Unit


Main BSP= Refrigeration and compressor alarms are generally a
LON BSP=
combination problem and fault alarm. The unit will first unload
LON App Ver=
BACnet BSP=
to try and stay online, then turn off if unsuccessful.
D-Net BSP= All active alarms as well as the date and time that they were
HMI GIUD= detected are displayed on the Active Alarm menu. These alarms
OBH GIUD=
are displayed in order of priority. Higher priority alarms are
displayed first. The last fifty alarm “events” detected as well as
SO_Item is an adjustable item which can be used to store the the date and times that they were detected are displayed on the
sales order number of the unit for reference purposes. Alarm Log menu. An alarm “event” is either an alarm becoming
Unit SN is an adjustable item which can be used to store the active or being cleared. A “+” symbol precedes the active alarm
serial number of the unit for reference purposes. event and a “-” symbol precedes the cleared alarm event. These
alarms are displayed in the order that they were detected. The
App Version is the version of application code loaded into the
alarm that was detected most recently is displayed first. Multiple
controller
occurrences of the same alarm may appear.
Cf1-15 describe positions 1-15 of the unit configuration string
Cf16-29 describe positions 16-29 of the unit configuration string
Main BSP is the current version of firmware in the main
controller
LON BSP is a status only item which indicates the current
version of firmware in the LON communication module
connected to the main controller.
LON App Ver is a status only item which indicates the current
version of application code in the LON communication module
connected to the main controller.
BACnet BSP is a status only item which indicates the current
version of firmware in the BACnet communication module
connected to the main controller.
D-Net BSP is a status only item which indicates the current
version of firmware in the D-Net communication module
connected to the main controller.
HMI GUID is the HMI software identifier number unique to each
application code version
OBH GUID is the OBH software identifier number unique to
each application code version

www.DaikinApplied.com 39 OM 1263 • MICROTECH UNIT CONTROLLER


Alarms

Alarm Clearing
Active alarms can be cleared through the keypad/display. Outdoor Refrigerant Temperature Sensor
Alarms are automatically cleared when power is cycled. Alarms Problem (Heat Pump only) – (ORT Sensor:
are cleared only if the conditions required to initiate the alarm
do not exist. All alarms and groups of alarms can be cleared
Problem)
via the network or keypad by setting the ClearAlms variable to This alarm occurs when the ORT sensor input is outside the
a non-zero value as indicated in the table below. Emergency range of -4 to 150°F continuously for the Sensor Alarm Delay
Off Faults can be set to automatically clear once the condition (default 30 seconds).
that caused the alarm is corrected. This can be accomplished When this alarm is active compressor cooling operation is
by navigating to Commission Unit/Alarm Configuration/Emerg disabled if ClgEVOMethod is set to “Sbc”. Otherwise not action
Stop and changing the default ManClr value to AutoClr. is taken.
NOTE: The enumeration text is what shows up on the
The alarm must be manually cleared once corrective action is
keypad/display not the number. The value of this
variable automatically reverts to zero when the taken.
alarms are cleared. This variable may be set through
the keypad in the Active Alarm menu. It may be set Fixed Speed Compressor Discharge Line
via LON using nviClearAlarms and via BACnet using Refrigerant Temperature Sensor Problem –
the ClearAlarms object. (DRT3 Sensor: Problem)
Alarm List Menu – see page 33. This alarm occurs when the DRT3 sensor input is shorted or open
circuited for the Sensor Alarm Delay (default 30 seconds). It can
Table 33: Alarm Clearing also occur when the fixed speed compressor is off and the input is
Value Action above 329°F or the compressor has been off for 20 minutes and
0 None
the input is below -4°F.
1 Clear All Faults
2 Clear All Problems When this alarm is active the fixed speed compressor is disabled.
3 Clear All Warnings
4 Clear All Alarms The alarm must be manually cleared once corrective action is
taken.
Problems
Inverter Compressor Discharge Line
OAT Temperature Sensor Problem - (OAT Refrigerant Temperature Sensor Problem –
Sensor: Problem) (DRT1 Sensor: Problem)
If the outside air temperature sensor (OAT) is present, a valid This alarm occurs when the DRT1 sensor input is shorted or open
OAT value is not provided via the network and the local OAT circuited for the Sensor Alarm Delay (default 30 seconds). It can
sensor is either shorted or open circuited for longer than the also occur when the inverter compressor is off and the input is
Sensor Alarm Delay (default is 30 seconds), the Outside above 329°F or the compressor has been off for 20 minutes and
Air Sensor problem occurs. When the OAT Sensor problem the input is below -4°F.
occurs, the unit continues to operate with the following When this alarm is active compressor cooling and heating
modifications: operation are disabled.
• Compressor heating and cooling operations are locked out. The alarm must be manually cleared once corrective action is
• Cooling Reset and Heating Reset revert to none if they taken.
are set to OAT
• Economizer is locked out due to high OAT Inverter Compressor Problem – (INV Comp:
When the alarm condition is no longer present, the OAT Sensor Problem)
problem automatically clears. This alarm occurs whenever the inverter compressor board
generates an internal fault code. Refer to the troubleshooting
Indoor Refrigerant Temperature Sensor section of this document for fault code details.
Problem (Heat Pump only) – (IRT Sensor: When this alarm is active compressor cooling and heating
Problem) operation are disabled.
This alarm occurs when the IRT sensor input is outside the range The alarm must be manually cleared once corrective action is
of -4°F to 150°F continuously for the Sensor Alarm Delay (default taken.
30 seconds). When this alarm is active compressor heating
operation is disabled if HtgEVIMethod is set to “Sbc”. Otherwise
not action is taken. The alarm must be manually cleared once
corrective action is taken.

OM 1263 • MICROTECH UNIT CONTROLLER 40 www.DaikinApplied.com


Alarms

Defrost Temperature Sensor Problem (Heat Outdoor Fan Problem – (OA Fan: Problem)
Pump only) – (DFT Sensor: Problem) On a single outdoor fan unit this alarm occurs when compressor
This alarm occurs when the DFT sensor input is shorted or open operation is forced to the Standby state due to an outdoor fan
circuited for the Sensor Alarm Delay (default 30 seconds). It can internal fault for a third time in a 30 minute period.
also occur if the input is outside the range of -47°F to 194°F. On a two outdoor fan unit this alarm occurs when compressor
When this alarm is active compressor cooling and heating operation is forced to the Standby state due an outdoor fan 2
operation are disabled. internal fault for a third time in a 30 minute period. Note that
outdoor fan 2 in this configuration provides critical cooling for the
The alarm must be manually cleared once corrective action is inverter/outdoor fan control boards.
taken.
When this alarm is active compressor cooling and heating
Suction Line Refrigerant Temperature Sensor operation are disabled.
Problem – (SRT Sensor: Problem) The alarm must be manually cleared once corrective action is
This alarm occurs when the SRT sensor input is shorted or open taken.
circuited for the Sensor Alarm Delay (default 30 seconds). It can
also occur if the input is outside the range of -47°F to 194°F. Low Refrigerant Charge Problem – (Lo Charge:
Problem)
When this alarm is active compressor cooling and heating
operation are disabled. During compressor cooling operation this alarm occurs when the
indoor expansion valve (EVI) is fully open (greater that 95%),
The alarm must be manually cleared once corrective action is the super heat is well above set point (greater than 20°F) and
taken. the lower of the two discharge line temperature inputs (DRT1
and DRT3) is hot (greater than 150°F) for more than 30 minutes
High Inverter Compressor Discharge Line continuously.
Temperature Problem – (Hi DL Temp: Problem)
During compressor heating operation this alarm occurs when the
This alarm occurs when the High Discharge Line Temperature outdoor expansion valve (EVO) is fully open (greater that 95%)
Unloading function has forced compressor operation to the and the super heat is well above set point (greater than 20°F) for
Standby state for a third time in a 100 minute period. more than 60 minutes continuously.
When this alarm is active compressor cooling and heating When this alarm is active compressor cooling and heating
operation are disabled. operation are disabled.
The alarm must be manually cleared once corrective action is The alarm must be manually cleared once corrective action is
taken. taken.

Expansion Valve Problem – (Exp Valve: Refrigerant Charge Loss Problem –


Problem) (ChargeLoss: Problem)
This alarm occurs when the IFB communication board detects This alarm occurs when both the suction and discharge
a faulty or disconnection between an expansion valve (EVI or line pressure inputs (PTS and PTD) remain below 10 psi
EVO) and the expansion valve control board (EVB). continuously for 5 seconds.
When this alarm is active compressor cooling and heating When this alarm is active compressor cooling and heating
operation are disabled. operation are disabled.
The alarm must be manually cleared once corrective action is The alarm must be manually cleared once corrective action is
taken. taken.
NOTE: The EVB only detects a change in the EVI or EVO
condition upon power up of the EVB. Suction Line Refrigerant Pressure Sensor
Problem – (PTS Sensor: Problem)
This alarm occurs when the suction line pressure inputs (PTS)
remains above 256 psi continuously for 12 minutes or below -15
psi continuously for 10 seconds.
When this alarm is active compressor cooling and heating
operation are disabled.
The alarm must be manually cleared once corrective action is
taken.

www.DaikinApplied.com 41 OM 1263 • MICROTECH UNIT CONTROLLER


Alarms

Discharge Line Refrigerant Pressure Sensor High Refrigerant Pressure Problem –


Problem – (PTD Sensor: Problem) (Hi Press 1: Problem)
This alarm occurs when the suction line pressure inputs (PTD) This alarm occurs when either the Cooling High Pressure
remains above 611.6 psi or below 1.42 psi continuously for 10 Unloading or the Heating High Pressure unloading function has
seconds. forced compressor operation to the Standby state for a third
time in a 30 minute period. This alarm also occurs if either of
When this alarm is active compressor cooling and heating
the mechanical high pressure switches (HP1 or HP3) open.
operation are disabled.
When this alarm is active compressor cooling and heating
The alarm must be manually cleared once corrective action is
operation are disabled.
taken.
The alarm must be manually cleared once corrective action is
Interface Board Communication Problem – (IFB taken
Comm: Problem)
High Inverter Compressor Body Temperature –
This alarm occurs when a communication problem is detected
at any of the communication connections to the IFB board. (HiINVCmpT: Problem)
If the inverter compressor body temperature rises above
When this alarm is active compressor cooling and heating
245°F continuously for 5 seconds or 230°F for 10 minutes,
operation are generally disabled.
the inverter compressor is shut down. After remaining in the
The alarm normally is cleared automatically when the standby for restart state for one cooling stage time period the
communication problem is corrected. If the alarm occurs for a compressor is allow to restart. If this occurs three times in a
fifth time in a 24 hour period it must be manually cleared once 100 minute time period, the High Inverter Compressor Body
corrective action is taken. Temperature problem occurs. The cooling will then remain off
until this alarm is manually cleared through the unit keypad or
Low Refrigerant Pressure Differential Problem – via a network signal.
(Lo Press Diff: Problem)
This alarm occurs when the Low Differential Pressure Inverter Compressor Body Temperature Sensor
Unloading function has forced compressor operation to the Problem – (INVCmpTSnsr: Problem)
Standby state for a third time in a 30 minute period. If the inverter compressor body temperature sensor becomes
When this alarm is active compressor cooling and heating shorted or open circuited or out of range for longer than
operation are disabled. the Sensor Alarm Delay (Default= 30 seconds). When this
alarm is active compressor cooling and heating operation
The alarm must be manually cleared once corrective action is are disabled. The alarm must be manually cleared once
taken. corrective action is taken.

Low Refrigerant Pressure Problem – Variable Compressor Oil Problem - (Var Comp
(Lo Press 1: Problem) Oil Problem)
This alarm occurs when either the Cooling Low Pressure This alarm occures when either the variable compressor
Unloading or the Heating Low Pressure unloading function has has been operating at the max speed or for the oil boost
forced compressor operation to the Standby state for a third time period and the low oil flag is still active or the maximum
time in a 30 minute period. number of oil boost cycles within a 24hr period have occurred.
When this alarm is active compressor cooling and heating When this alarm is active compressor cooling and heating
operation are disabled. operation is disabled.
The alarm must be manually cleared once corrective action is The alarm must be manually cleared once corrective action is
taken. taken.

OM 1263 • MICROTECH UNIT CONTROLLER 42 www.DaikinApplied.com


Alarms

4 Way Valve Problem - (4WayValve: Problem)


This alarm occures only on heat pump units when any of
the following conditions are true. When compressor heating
state is normal yet the DFT-Teg > 10°F for 15 minutes. When
compressor cooling state is normal yet the DFT-Teg < or equal
to 15°F for 15 mintues. When cooling or heating state is
normal, defrost cycle is inactive, and 4 way valve flag is false
for 15 minutes. Or when compressor state transisitons from
alternate initialization to normal and 4 way valve flag is false.
When this alarm is active compressor cooling and heating
operaiton is disabled.
The alarm must be manually cleared once corrective action is
taken.

Protection Interlock Problem - (Protection


Interlock Problem)
This alarm occures when the following are true for 90 seconds:
system mode is remote, inverter compressor start/stop
command is on, and compressor interlock is off.
When this alarm is active compressor cooling and heating
operation is disabled.
The alarm must be manually cleared once corrective action is
taken.

www.DaikinApplied.com 43 OM 1263 • MICROTECH UNIT CONTROLLER


Compressor Protection

Compressor Protection

Compressor Protection Unloading Control Cooling Low Pressure Unloading Control


There are a number unloading control functions that limit Normal compressor operation is limited during cooling
the staging and speed control of the compressors to protect operation when low suction pressure conditions occur. When
them from damage under abnormal operating conditions. The the suction pressure falls below 50 psi the inverter compressor
following unload functions are provided: capacity is held at its current valve and the bypass solenoid
valve (SVB) is opened in an attempt to keep the pressure from
• Cooling High Pressure Unloading Control
falling below 36 psi. If the pressure continues to fall below 36
• Cooling Low Pressure Unloading Control psi the inverter compressor is slowed to minimum speed and
• Heating High Pressure Unloading Control any fixed speed compressor running is stopped. If the pressure
• Heating High Protection Control [anticipating high continues to fall below 10 psi, compressor operation is forced
pressure] to the Standby state where it remains for a cooling stage time
• Heating Low Pressure Unloading Control period before being allowed to restart. If the unit is forced to
Standby in this manner 3 times in a 30 minute period, a low
• Inverter Compressor High Discharge Line Temperature
pressure alarm is generated requiring manual reset.
Unloading Control
• Standard Compressor High Discharge Line Temperature Once active this limiting function remains active until the
Unloading Control suction pressure rises back above 57 psi.
• Inverter Compressor High Current Unloading Control Heating High Pressure Unloading Control
• Inverter Compressor Request for Unloading Control
Normal compressor operation is limited during heating
• Compression Ratio Unloading Control operation when high discharge pressure conditions occur.
• Inverter Compressor Board Temperature Unloading When the discharge pressure rises above 481 psi the inverter
Control compressor capacity is immediately reduced by seven steps
• Low Differential Pressure Protection Control and then reduced a further step every 10 seconds in an
attempt to keep the pressure from rising above 497 psi. If
Cooling High Pressure Unloading Control the pressure continues to rise above 497 psi the inverter
Normal compressor operation is limited during cooling operation compressor is slowed to minimum speed and any fixed speed
when high discharge pressure conditions occur. When the compressor running is stopped. If the pressure continues to
discharge pressure rises above 503 psi the inverter compressor rise above 527 psi, compressor operation is forced to the
is immediately reduced by three steps* and then reduced a Standby state where it remains for a heating stage time period
further step every 10 seconds in an attempt to keep the pressure before being allowed to restart. If the unit is forced to Standby
from rising above 515 psi. If reducing the compressor capacity in this manner 3 times in a 30 minute period, a high pressure
fails to keep the pressure below 515 psi the inverter compressor alarm is generated requiring manual reset.
is reduced to minimum and any fixed speed compressor running Once active this limiting function remains active until the
is stopped. If the discharge pressure continues to rise above 527 discharge pressure falls back below 427 psi.
psi, compressor operation is forced to the Standby state where it
* See page 50 for more information about what is a
remains for a cooling stage time period before being allowed to
compressor “step”.
restart. If the unit is forced to Standby in this manner 3 times in
a 30 minute period, a high pressure alarm is generated requiring
manual reset.
Once active this limiting function remains active until the
discharge pressure falls back below 469 psi.

OM 1263 • MICROTECH UNIT CONTROLLER 44 www.DaikinApplied.com


Compressor Protection

Heating High Pressure Protection Control Fixed Speed Compressor High Discharge Line
Normal compressor operation is limited during heating operation Temperature Unloading Control
when high discharge pressure or high inverter compressor Normal fixed speed compressor operation is limited when high
discharge line temperature conditions occur while the inverter discharge line temperature (DRT3) conditions occur. When
compressor is operating alone (fixed speed compressor off or DRT3 rises above 275°F or above 248°F continuously for 5
not present) at low speed. This is an indication that too much minutes or when a calculated inverter compressor suction port
liquid is backing up in the condenser causing hot high pressure temperature (Tp) value rises above 293°F or above 275°F
conditions. When the DRT1 sensor input rises above 234°F or continuously for 10 minutes, the fixed is stopped.
the discharge pressure rises above 455 psi while the inverter Once active this limiting function remains active for 10 minutes.
compressor is operating alone at low speed, the inverter
compressor capacity is immediately reduced to minimum speed Inverter Compressor High Current Unloading
and the indoor expansion valve (EVI) is driven fully open. Note Control
the bypass solenoid valve is also opened if DRT1 is above
Normal compressor operation is limited when high inverter
234°F or if the pressure is above 469 psi.
compressor current conditions occur. When the internal inverter
Once active this limiting function remains active until the discharge compressor amp draw exceeds 14.7A (460/575V unit) or 26.5A
pressure falls back below 427 psi, DRT1 is below 225°F and (208/230V unit) the inverter compressor capacity is immediately
Heating High Pressure Unloading is inactive. reduced by one step and then reduced a further step every 15
seconds in an attempt to keep the amps below these values.
Heating Low Pressure Unloading Control Once active this limiting function remains active until the amps
Normal compressor operation is limited during heating operation are above these values and the inverter capacity is back to the
when low suction pressure conditions occur. When the suction normal unlimited value.
pressure falls below 24 psi the inverter compressor is reduced
by three steps then reduced a further step every 10 seconds in Inverter Compressor Request for Unloading
order to keep the pressure from falling below 19 psi. If reducing Control
the compressor capacity fails to keep the pressure above 19 psi, Normal compressor operation is limited when inverter
the inverter compressor is reduced to minimum and any fixed compressor control board provides a request to unload. This
speed compressor running is stopped. If the suction pressure can occur for a number of internal compressor board built-in
continues to fall below 10 psi, compressor operation is forced protection reasons (high amp draw for example). When the
to the Standby state where it remains for a heating stage time inverter unload request is active, the inverter compressor
period before being allowed to restart. If the unit is forced to capacity is immediately reduced by one step and then reduced
Standby in this manner 3 times in a 30 minute period, a low a further step every 15 seconds as long as the request remains
pressure alarm is generated requiring manual reset. active.
Once active this limiting function remains active until the suction Once active this limiting function remains active until the request
pressure rises back above 33 psi. becomes inactive and the inverter capacity is back to the normal
unlimited value.
Inverter Compressor High Discharge Line
Temperature Unloading Control High Compression Ratio Unloading Control
Normal compressor operation is limited when high inverter Normal compressor operation is limited when the ratio between
compressor discharge line temperature (DRT1) conditions the compression ratio between the discharge and suction
occur. When DRT1 rises above 239°F or a calculated suction pressure becomes too high. CmpRatio=(PTD + 14.7)/(PTS +
port temperature (Tp) value rises above 275°F, the inverter 14.7). Note: in this equation PTD and PTS are in PSI. When
compressor capacity is immediately reduced by one step and the compression ratio exceeds 8.5 the inverter compressor is
then reduced a further step every 30 seconds in an attempt to immediately reduced by three steps then reduced a further step
keep the temperatures from rising further. If DRT1 continues to every 10 seconds in an attempt to keep the compression ration
rise above 266°F or above 248°F continuously for 90 seconds, from continuing to increase. If the compression ratio continues to
the inverter compressor is reduced to minimum and any rise above 8.9, the inverter compressor is reduced to minimum
operating fixed speed compressor is stopped. If DRT1 continues and any operating fixed speed compressor is stopped.
to rise above 275°F or above 248°F continuously for 10 minutes
or Tp rises above 302°F, compressor operation is forced to the Once active this limiting function remains active until the
Standby state where it remains for a stage time period before compression ratio falls back below 8.0.
being allowed to restart. If the unit is forced to Standby in this
manner 3 times in a 100 minute period, a high inverter discharge
line temperature alarm is generated requiring manual reset.
Once active this limiting function remains active until DRT1 falls
back below 212°F and Tp is below 230°F.

www.DaikinApplied.com 45 OM 1263 • MICROTECH UNIT CONTROLLER


Compressor Protection

Inverter Compressor High Board Temperature Low Differential Pressure Protection Control
Unloading Control Normal compressor operation is overridden when the
Normal compressor operation is limited when inverter differential pressure between the high and low side of the
compressor control board indicates an abnormally high board refrigeration circuit (PTD-PTS) is abnormally low. This
(fin) temperature value. This indicates the inverter compressor condition can inhibit proper oil return for lubricating the
board is not receiving problem ventilation. When the inverter inverter compressor. When the differential pressure falls
board temperature exceeds 183°F (460/575V unit) or 178°F below 85 psi continuously for 40 seconds, the inverter
(208/230V unit), the inverter compressor is immediately compressor capacity is increased by one step then increased
reduced by one step then reduced a further step every 15 a further step every 40 seconds in an attempt to increase
seconds in an attempt to keep the board temperature from the differential pressure. If the inverter compressor is at
continuing to increase. The outdoor fan(s) are increased to maximum speed for 40 seconds and the differential pressure
maximum speed. is still below 85 psi, compressor operation is forced to the
Standby state where it remains for a stage time period before
Once active this limiting function remains active until the being allowed to restart. If the unit is forced to Standby in
inverter board temperature falls 5.4°F below the high limit. this manner 3 times in a 30 minute period, a low differential
pressure alarm is generated requiring manual reset.
Once active this limiting function remains active until the
differential pressure rises back above 171 psi.
To prevent excessive cycling of the compressor heating on an
off during moderate heating load conditions, special steps are
taken if this protection function causes the unit to cycle out of
heating while it is active. If this occurs, the current effective
compressor heating ambient lock out setting is reduced 10°F
below the current outdoor air temperature which will lock out
compressor heating operation. The effective compressor
heating ambient lock out setting remains at this lower value
until any of the following occur:
• 120 minutes elapses
• The effective minimum outdoor damper position changes
by more that 10%.
• The effective discharge air heating set point changes by
more than 5°F.
• The outdoor air temperature falls below this lower
effective compressor heating ambient lock out setting.

OM 1263 • MICROTECH UNIT CONTROLLER 46 www.DaikinApplied.com


Operator’s Guide

Operator’s Guide

The following “Operator’s Guide” sections provide information


regarding the day-to-day operation of the MicroTech III Determining Unit State
Unit Controller. Topics covered are such common tasks as
scheduling, displaying and clearing alarms, and setting the (See page 58 for more information)
controller for manual operation. The unit will operate in one of eight operating states. The
current state will be displayed by the Unit State parameter in
Figure 13: State Diagram the system summary menu.
In the OFF state, all heating, cooling, and fans are OFF. The
alarm output indicates the type of alarm, if any, that is active.
In the start up state, the Fan Operation output is turned ON to
allow shut off dampers to be opened before any the supply fan
is turned ON. The outdoor air dampers remain closed.
The supply fan is turned ON when the unit enters the
Recirculation state. The supply fan in VAV units is controlled
as described in the Supply Fan Capacity Control section, page
20. The outdoor dampers remain closed.
A separate morning warm-up state is not provided, but an
edited ZeroOATime is used to keep the outside air damper
closed when the unit first starts. The Minimum OA Position is
set to zero as long as the as the fan has been on for less than
the ZeroOATime.
DAT Control units have a MWU set point available.
The Minimum OA Position is set to zero as long as the as the
fan has been on for less than the ZeroOATime. This allows the
Return Air type units to cool down the space with mechanical
cooling or to warm up the space with the dampers closed. If the
ZeroOATime is set correctly, the OA dampers will be open only
during occupied periods. When Optimum Start is used Zero OA
Time is set equal to the time to occupancy when the unit starts
so that the OA dampers will open at occupancy time.
Neither heating nor cooling is provided when the unit is in the
fan only state, with the exception of when dehumidification
is active. The outdoor dampers are opened to the minimum
The transition from any operating state to another is graphically position in this state when the fan on time exceeds the Zero
represented in this figure. With a “start up” command from OA Time.
an Off State the unit will always go into the “Start Up” state of
operation for 3 minutes (adjustable). Next, it will transition into In the other four states, temperature is controlled as describe
the “Recirculation” state of operation for another 3 minutes in the appropriate sections of this document. These states are
(adjustable) before finally going into the Fan Only state of Minimum DAT, Heating, Economizer, and Cooling. The outdoor
operation. Then, based on sensor inputs it will go into any dampers are opened to at least the minimum position in these
of the 4 remaining states of operation - heating, cooling, states when the fan on time exceeds the Zero OA Time.
economizer, or minimum discharge air heating.
Off Operating State
In the OFF operating state the fans are OFF, the outside air
dampers are closed and any variable speed supply air fan’s
are driven to 0%. Cooling and heating are disabled. The unit
is in the OFF state when it is not enabled, or when it is in the
unoccupied mode with no call for unoccupied operation. refer
to “Determining Unit Status” on page 57 for reasons the unit
can be disabled.

www.DaikinApplied.com 47 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Start Up Operating State Off to Prestart Pressure Equalization


When a unit is commanded to start it will always enter the The Compressor Cooling State transitions from OFF to Prestart
Startup operating state from the Off operating state. The unit Pressure Equalization when the unit enters the Cooling
remains in the Startup operating state for an adjustable time operating state becomes active.
period (default 180 seconds) before entering the Recirculating
operating state. Prestart Pressure Equalization to Off
During the Start up operating state the fans remain off, the The Compressor Cooling State transitions from Prestart
outdoor air dampers are driven closed, and variable speed Pressure Equalization to OFF if there is no longer a call for
supply air fan’s remain at 0%. Cooling and heating are cooling operation.
disabled, except for 100% OA heating start sequences.
Prestart Pressure Equalization to
Heating Initialization
The unit enters the Heating operating state when the control The Compressor Cooling State transitions from Prestart
calls for heat. This is for heat pumps only. Pressure Equalization to initialization after thirty seconds.

Initialization to Normal
Mechanical Cooling
The Compressor Cooling State transitions from Initialization
The unit enters the mechanical cooling operating state when to Normal when the initialization sequence is complete. See
cooling is called for by the third-party controller. Initialization state description in the Inverter Compressor
Cooling State Descriptions section, page 51.
Figure 14: Cooling State Diagram
Initialization to Pumpdown
The Compressor Cooling State transitions from Initialization to
Pumpdown if there is no longer a call for cooling operation.

OM 1263 • MICROTECH UNIT CONTROLLER 48 www.DaikinApplied.com


Operator’s Guide

Initialization to Standby for Restart Input Devices


The Compressor Cooling State transitions from Initialization PTS (suction refrigerant pressure) – MicroTech III AI
to Standby for Restart if one of the Compressor Protection PTD (discharge refrigerant pressure) – MicroTech III AI
functions force a transition to Standby for Restart, the inverter
compressor or outdoor fan board requests a transition to DRT1 (INV compressor discharge refrigerant line temperature)
Standby for Restart or if all compressor operation becomes – MicroTech III AI
disabled for any reason. DRT3 (compressor discharge refrigerant line temperature) –
MicroTech III AI
Normal to Pumpdown
SRT (suction refrigerant temperature) – MicroTech III AI
The Compressor Cooling State transitions from Normal to
Pumpdown if there is no longer a call for cooling operation. DFT (defrost temperature) – MicroTech III AI
IRT (indoor refrigerant temperature) – IFB (heat pump)
Normal to Standby for Restart
ORT (outdoor refrigerant temperature) – IFB (heat pump)
The Compressor Cooling State transitions from Normal to
Standby for Restart if one of the Compressor Protection
functions force a transition to Standby for Restart, the inverter Compressor Control
compressor or outdoor fan board requests a transition to DPS units will utilize one of the following Compressor Cooling
Standby for Restart or if all compressor operation becomes Configurations:
disabled for any reason.
• Single inverter compressor (INV) on sizes 3–6 tons,
Pumpdown to Standby for Restart 16–20 tons
• Single inverter compressor (INV) and a standard
The Compressor Cooling State transitions from Pumpdown
compressor on all other sizes
to Standby for Restart if one of the Compressor Protection
functions force a transition to Standby for Restart, the inverter When compressor operation is active the combination of
compressor or outdoor fan board requests a transition to inverter and standard compressors is controlled to maintain the
Standby for Restart or if all compressor operation becomes applicable cooling capacity input of the manual control.
disabled for any reason. The control of the inverter compressor is accomplished by
sending the analog output of a PI_Loop via Modbus to the
Pumpdown to Initialization inverter compressor control board. As the PI_Loop output
The Compressor Cooling State transitions from Pumpdown varies from 0-100% the speed of the inverter compressor
to initialization if there is a call for cooling or dehumidification increases from 0 to maximum. In the case where the unit is
operation. also equipped with standard (fixed) compressor, the fixed
compressor is started and stopped via a digital output.
Standby for Restart to Off
Upon an increasing call for cooling the inverter compressor
The Compressor Cooling State transitions from Standby for is modulated to its maximum capacity before the fixed
Restart to OFF after the cooling stage timer expires. compressor is turned ON. When the load is such that the fixed
compressor is required, the inverter compressor is slowed to
Inverter Compressor Cooling Operation its minimum speed before turning on the fixed compressor. The
Rebel units are always equipped with an inverter compressor. inverter compressor is then modulated to maintain the load.
A fixed speed compressor is also provided on sizes 7.5–12, Upon a decreasing call for cooling the inverter compressor is
25–28 tons. modulated to its minimum speed before the fixed compressor
The primary control devices related to inverter compressor is turned OFF. Once the fixed compressor is turned off the
operation are the following: inverter compressor is modulated maintain the load.

• Inverter and Fixed Speed Compressors (INV, Comp3 )


• 1 or 2 Outdoor Fan(s)
• 4 Way Reversing Valve (4WV) – Heat Pump Units Only
• Refrigerant Receiver Solenoid Valve (SVR) – Heat Pump
Units Only
• Refrigerant Discharge to Suction Bypass Solenoid Valve
(SVB)
• Indoor Coil Expansion Valve (EVI)
• Outdoor Coil Expansion Valve (EVO) – Heat Pump Units
Only
Control of these devices is described in the following sections.

www.DaikinApplied.com 49 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Compressor Control PI_Loop Fixed Speed Compressor Step


When normal inverter compressor operation is active, the Transitions
inverter compressor is controlled via a PI_Loop to maintain the Under normal compressor control, when the unit is equipped
remote of the manual point. with a fixed speed compressor, special transition steps are
The compressor control PI_Loop is active when inverter taken when starting and stopping the fixed speed compressor.
operation is in either the Normal Cooling or, in the case of These steps are as follows:
a heat pump configuration, the Normal Heating state. The
PI_Loop is over-ridden when not in these states or when in Starting the Fixed Speed Compressor
these states and any of the Compressor Protection Unloading Whenever the inverter compressor can not maintain sufficiently
Control functions or Fixed Speed Compressor Step Transitions cold discharge air temperature at maximum speed, and timers
are active. are satisfied, the following fixed speed compressor stage up
sequence occurs:
Compressor Output Control • Inverter Compressor speed is set to the minimum
value. When the inverter compressor speed reaches
Inverter Compressor (INV)
the minimum value then the fixed speed compressor is
ON/OFF and speed commands are communicated to the turned ON.
inverter compressor control board via Modbus through the IFB
• Inverter Compressor speed is held constant for 30
Communication board.
seconds
Fixed Speed Compressor (Comp3) • Displayed compressor cooling/heating capacity is
released to normal operation.
A digital output is energized on the main control board controls
the fixed speed compressor (Comp3). Stopping the Fixed Speed Compressor
Whenever the two compressors provide excessively cold
discharge air temperature at minimum speed, and timers are
satisfied, the following fixed speed compressor stage down
sequence occurs:
• SVB bypass solenoid is opened
• Fixed speed compressor is turned OFF one second after
SVB is opened
• SVB remains open for one second and then is turned OFF
• Inverter Compressor speed is set to maximum.
• When the inverter compressor speed reaches the
maximum speed value, compressor cooling/heating
control is released to normal operation.

OM 1263 • MICROTECH UNIT CONTROLLER 50 www.DaikinApplied.com


Operator’s Guide

Inverter Compressor Cooling State Descriptions


The Inverter Compressor Cooling State determines the Pre Start Pressure Equalization
operation of the following devices:
In the Pre Start Pressure Equalization state the SVB valve
• Inverter Compressor is opened to divert hot gas leaving the compressor directly
• Fixed Speed Compressor (if present) to the suction line to equalize the pressures in the system
• Outdoor Fan(s) before beginning compressor operation. Operation remains in
• 4 Way Reversing Valve (4WV) (Heat Pump only) this state for 30 seconds [adjustable.] When in the Pre Start
Pressure Equalization state, all devices are off or closed,
• Outdoor Expansion Valve (EVO) (Heat Pump only)
except the Outdoor Fan and SVB. The Outdoor fan speed is
• Indoor Expansion Valve (EVI) set to 50%.
• Receiver Solenoid Valve (SVR) (Heat Pump only)
• Bypass Solenoid Valve (SVB) Initialization
In the Initialization state either the Standard Initialization
Cooling Off or Alternate Initialization sequence is used in order to
manage refrigerant and to assure a 4-way valve is switched.
Compressor cooling operation begins in the Cooling Off state.
The Alternate Initialization sequence is used on inverter
All devices are OFF or closed. The state remains OFF until
compressor units the first time the unit enters cooling after unit
there is a call for cooling or dehumidification
power up, the compressors had last operated in heating, or if it
has been a long time since cooling has operated and it is cold
outdoors.
Otherwise the Standard Initialization Sequence is normally used.
Table 34: Standard Initialization Sequence, 3–15 Tons
Device Step 1 Step 2 Step 3 Step 4
“Inverter Compressor Speed = “Inverter Compressor Speed =
Inverter Compressor & Comp3 Minimum Smaller of Step 12 or Maximum ← A
Comp3 = Off Comp3 = Off
“If OAT ≥50°F or RAT ≥73°F,
Inverter Compressor Speed =
Inverter Compressor Speed = Smaller of Step 12 or Maximum
Inverter Compressor Only ← A
Minimum If OAT <50°F or RAT <73°F,
Inverter Compressor Speed =
Minimum
“Outdoor Fan = 0% if OAT <
68°F
Outdoor Fan B ← ←
Outdoor Fan = 5% if OAT ≥
68°F
4 Way Valve (Heat Pump) OFF ← ← ←
Outdoor Coil
Expansion Valve (EVO) EVO = 100% ← ← ←
(Heat Pump only)
SVR (Heat Pump only) Closed ← ← ←
“Close if either of the following
is true:
SVB Normally Open ← 60 seconds elapses from the ←
beginning of Step 1
Discharge superhead>9°F”
Indoor Coil
EVI = 0% C ← ←
Expansion Valve (EVI)
5 Seconds = 15 Ton size E = 15 Ton size
Time Duration 5 Seconds D
10 Seconds ≠ 15 Ton size 5 Seconds ≠ 15 Ton size
A. Inverter compressor speed is increased until the 4-way valve is seated (discharge minus suction pressure >57 psi) and as
long as the suction pressure is above 43 psi. Comp 3 remains OFF
B. Outdoor fan capacity is controlled to maintain the discharge pressure between 256 psi and 313 psi. Outdoor fan capacity is
set to 100% if discharge pressure is above 384 psi. Outdoor fan capacity runs at least at minimum capacity if inverter board
(fin) temperature >167°F
C. The indoor expansion valve is controlled to keep the suction superheat between 3.6°F and 9.0°F.
D. Standard Initialization lasts a maximum 140 seconds. It is completed early anywhere between 20 seconds and 140 seconds
if the saturated suction temperature is high (above 118°F), the suction pressure is low (below 79 psi) or once the 4-way
valve is seated (differential pressure above 57 psi, suction pressure below 142 psi and suction or discharge superheat
above 27°F).

www.DaikinApplied.com 51 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Table 35: Standard Initialization Sequence, 16–28 Tons


Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed
Inverter Compressor Speed
Inverter Compressor Speed = Inverter Compressor Speed = = Increasing 1 step every 20
= Increasing 2 steps every 5
Inverter Compressor & Comp3 Minimum Step 2 seconds if there is no change
seconds if PTD-PTD < 26 PSI
Comp3 = Off Comp3 = Off of 4 Way Valve call
Comp3 = Off
Comp3 = Off
If OAT ≥50°F or RAT ≥73°F,
Inverter Compressor Speed =
Inverter Compressor Speed = Smaller of Step 12 or Maximum
Inverter Compressor Only ← A
Minimum If OAT <50°F or RAT <73°F,
Inverter Compressor Speed =
Minimum
Outdoor Fan = 0% if OAT <
68°F
Outdoor Fan B ← ←
Outdoor Fan = 5% if OAT ≥
68°F
4 Way Valve (Heat Pump) OFF ← ← ←
Indoor Coil
C ← ← ←
Expansion Valve (EVI)
E = 25/28 Ton size
Time Duration 5 Seconds 5 Seconds D
5 Seconds ≠ 25/28 Ton size
A. Inverter compressor speed is increasing until the 4-way valve is seated (discharge minus suction pressure is >57 psi) and
as long as the suction pressure is above 43 psi. Comp3 remains OFF
B. Outdoor fan capacity is controlled to maintain the discharge pressure between 256 psi and 313 psi. Outdoor fan capacity
is set to 100% if discharge pressure is above 384 psi. Outdoor fan capacity runs at least at minimum capcity if heat sink
temperature is > 167°F
C. The indoor expansion vavle is to keep the suction superheat between 7.2°F and 12.0 °F
D. The standard initialization lasts a max of 120 seconds. It is completed early anywhere between 20 and 120 seconds if the
saturation suction temperature is high (above 118°F), the suction pressure is low (below 79 psi) or once the 4-way valve is
seated (differential pressure above 57 psi, suction below 142 psi, suction superheat above 27°F, and discharge superheat
above 34°F)

OM 1263 • MICROTECH UNIT CONTROLLER 52 www.DaikinApplied.com


Operator’s Guide

Table 36: Alternate Initialization Sequence, 3–15 Tons


Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed =
Inverter Compressor Speed =
Inverter Compressor & Comp3 Smaller of Step 12 or Maximum ← A
Minimum Comp3 = Off
Comp3 = Off
If OAT ≥50°F or RAT ≥73°F,
Inverter Compressor Speed =
Inverter Compressor Speed = Smaller of Step 12 or Maximum
Inverter Compressor Only ← A
Minimum If OAT <50°F or RAT <73°F,
Inverter Compressor Speed =
Minimum“
Outdoor Fan = 0% if OAT <
68°F
Outdoor Fan B ← ←
Outdoor Fan = 5% if OAT ≥
68°F
4 Way Valve (Heat Pump) OFF ← ← ←
Outdoor Coil
Expansion Valve (EVO) EVO = 100% ← ← ←
(Heat Pump only)
SVR (Heat Pump only) Closed ← ← ←
Normally Open
SVB Close if Discharge superheat ← ← NA
>9°F
Indoor Coil
EVI = 0% C ← ←
Expansion Valve (EVI)
E = 15 Ton size F= 15 Ton size
Time Duration 5 Seconds 5 Seconds
D ≠ 15 Ton size NA
A. Inverter compressor speed is increased until the 4-way valve is seated (discharge minus suction pressure >57 psi) and as
long as the suction pressure is above 43 psi. inverter compressor speed is also increased if the suction pressure remains
above 71 psi. Comp 3 turns on if the inverter compressor speed is at maximum and these conditions are not met. Comp 3
is turned back OFF after 20 seconds if the suction pressure drops below 43 psi.
B. Outdoor fan capacity is controlled to maintain the discharge pressure between 171 psi and 221 psi. Outdoor fan capacity
is set to 100% if discharge pressure is above 427 psi. Outdoor fan capacity runs at least at minimum capacity if inverter
board (fin) temperature >167°F.
C. EVI is controlled to keep the suction superheat between 3.6°F and 14.4°F.
D. Alternate Initialization lasts a maximum 15 minutes. It is completed early anywhere between 10 seconds and 15 minutes if
once the 4-way valve is seated (differential pressure above 57 psi and the discharge superheat above 9.0°F).
E. Step 3 ends when the compressor has reached 65% full speed, differential pressure is >26 psi for 3 seconds, the stage
has been active for 3 minutes, or Comp3 is active
F. Step 4 (initializaiton) is complete when the stage has been active for 15 minutes, or 4 way valve has set and discharge
superheat is above 9°F

www.DaikinApplied.com 53 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Table 37: Alternate Initialization Sequence, 16–28 Tons


Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed
Inverter Compressor Speed = Inverter Compressor Speed =
= Increasing 1 step every 5
Inverter Compressor & Comp3 Minimum Step 2 A
seconds if PTD-PTD < 26 PSI
Comp3 = Off Comp3 = Off
Comp3 = Off
If OAT ≥50°F or RAT ≥73°F,
Inverter Compressor Speed =
Inverter Compressor Speed = Smaller of Step 12 or Maximum
Inverter Compressor Only A N/A
Minimum If OAT <50°F or RAT <73°F,
Inverter Compressor Speed =
Minimum
Outdoor Fan = 0% if OAT < 68°F
Outdoor Fan B ← ←
Outdoor Fan = 5% if OAT ≥ 68°F
4 Way Valve (Heat Pump) OFF ← ← ←
Indoor Coil
EVI = 0% C ← ←
Expansion Valve (EVI)
E = 25/28 Ton size
Time Duration 5 Seconds 5 Seconds F
D ≠ 15 Ton size
A. Inverter compressor speed is increasing until the 4-way valve is seated (discharge minus suction pressure is >57 psi) and
as long as the suction pressure is above 43 psi. Inverter compressor speed is increased if the suction pressure remains
above 71 psi. Comp3 turns ON if the inverter compressor speed is at maximum and these conditions are not met. Comp3 is
turned back OFF afer 20 seconds if the suction pressure is below 43 psi
B. Outdoor fan capacity is controlled to maintain the discharge pressure between 171 psi and 221 psi. Outdoor fan capacity
is set to 100% if discharge pressure is above 427 psi. Outdoor fan capacity runs at least at minimum capcity if heat sink
temperature is >167°F
C. The indoor expansion valve is to keep the suction superheat between 7.2°F and 20°F
D. The standard initialization lasts a max of 15 minutes. It is completed early anywhere between 20 and 15 minutes if the
4-way valve is seated (differential pressure above 57 psi and discharge superheat above 34°F)
E. Step 3 ends when the compressor has reached 65% full speed, differential pressure is >26 psi for 3 seconds, the stage has
been active for 3 minutes, or Comp3 is active
F. Step 4 (initializaiton) is complete when the stage has been active for 15 minutes, or 4-way valve has set and discharge
superheat is above 34°F

OM 1263 • MICROTECH UNIT CONTROLLER 54 www.DaikinApplied.com


Operator’s Guide

Normal Cooling
In the Normal Cooling state the following are accomplished:
• Indoor coil expansion value is modulated to maintain the suction superheat at the suction superheat set point
• Outdoor coil expansion valve is controlled to maintain outdoor coil subcooling at the outdoor coil subcooling set point (heat
pump)
• Outdoor fan(s) are modulated to maintain the discharge saturation temperature at the discharge saturation temperature set
point
When in the Normal Cooling state the action of the cooling control devices is as follows:

Table 38: Normal Cooling State


Device Action
Inverter Compressor Speed Controlled with PI Loop to Maintain DAT Setpoint
Compressors Comp 3: Turned On when inverter speed is at Maximum
Comp 3: Turned Off when inverter speed is at Minimum
Outdoor Fan Capacity Controlled With PI Loop to Maintain condensing
Outdoor Fan
temperature setpoint
4 Way Valve
OFF
(Heat Pump)
Outdoor Coil Expansion Valve (EVO) (Heat Pump only) A
SVR (Heat Pump only) Closed
SVB is normally closed during the Normal Cooling state
except in the following cases:
SVB SVB is opened for one second before and after Comp 3 is stopped.
During Low Pressure Unloading Control SVB is opened if PTS< 21 psi.
It is closed again when PTS> 43 psi.
Indoor Coil Expansion Valve (EVI) EVI Controlled With PI Loop to Maintain Suction Superheat Setpoint
Time Duration While in Normal Cooling state

A. The outdoor expansion valve position is either driven fully open (100%) or varied based on outdoor coil subcooling as follows:
• When the outdoor expansion valve Method is set to 100%, the outdoor expansion valve is driven to the 100% open
position.
• When the outdoor expansion valve Method is set to subcooling, the outdoor expansion valve is controlled to maintain
the outdoor coil subcooling temperature set point.

Normal Cooling Outdoor Fan (OA Fan PI_Loop) • If discharge pressure is high (above 162 psi) or the INV
Control Board (fin) Temp is low [below 172°F (169°F for 208/230
volt units) continuously for 15 seconds] the outdoor fan
One or two outdoor fans are controlled via Modbus speed is decreased by 2%. No further changes are made
connections to the Inverter Compressor Board via the IFB for 30 seconds.
communication board.
Outdoor Fan Fault Protection
The outdoor fan control PI_Loop is active only during the
Normal Cooling and Cooling Pumpdown operating states and If a unit is equipped with only one outdoor fan and it is shut off
the loop maintains the discharge saturation temperature at the on one of its internal faults, compressor operation enters the
set point between a minimum value of 86°F and a maximum Standby for Restart state.
value of 131°F. EER values will be improved by allowing the If a unit is equipped with two outdoor fans and either outdoor
lower set points when appropriate. fan 2 or both outdoor fans shut off on one of their internal
faults, compressor operation enters the Standby for Restart
Normal Heating OA Fan Control state. Note: In the case of two fans outdoor fan 2 provides
During the Normal Heating state the outdoor fan speed is first critical cooling for the inverter compressor/outdoor fan control
set at the maximum value and is then controlled as follows: boards.
• If discharge pressure is low (below 107 psi) or the INV Once compressor operation finishes the Standby for Restart
Board (fin) Temp is high [above 176°F (172°F for 208/230 state and if there is a call for cooling, compressor operation
volt units) continuously for 15 seconds] the outdoor fan is allowed to sequence to the Normal operating state in the
speed is increased by 2%. No further changes are made normal manner. If this cycle is repeated three times in a thirty
for 15 seconds. minute period an OA Fan: Problem alarm is generated, locking
out compressor operation, requiring a manual reset.

www.DaikinApplied.com 55 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Pumpdown
When compressor operation is no longer needed, the compressor enters the Pumpdown state before entering the Standby for
Restart state from either the Initialization or Normal Cooling state.
The following describes the operation of the cooling control devices in the Pumpdown state:

Table 39: Pumpdown State


Step 1 Step 2
Inverter Compressor speed = maximum Inverter Compressor speed = minimum
Compressors
Comp3= OFF Comp3= OFF
Outdoor fan Normal control ←
4 way valve Off ←
Outdoor Expansion Valve (EVO) (Heat Pump only) Outdoor Expansion Valve position = 100% Outdoor Expansion Valve position = 50%
Open except Closed after 10 seconds
SVR (Heat Pump only) Closed
if suction super heat < 41°F
SVB Open Closed
Indoor Expansion Valve (EVI) Closed Closed
Time Duration A B

A. The inverter compressor speed is at maximum with the outdoor expansion valve open, SVR closed, SVB open and the
indoor expansion valve closed for a maximum of 5 minutes. Step 1 is normally finished before 5 minutes when the suction
pressure drops below 72 psi. Step 1 is terminated if the inverter compressor discharge line temperature is above 230°F, the
inverter compressor port temperature is above 257°F or the discharge pressure is above 427 psi.
B. The inverter compressor speed is at minimum, the outdoor expansion valve is open 50% open, SVR closed, SVB open and
indoor expansion valve closed. Pumpdown is normally complete when the suction pressure drops below 36 psi. Pumpdown
is terminated if the inverter compressor port temperature rises above 320°F

Standby for Restart


The Standby for Restart state guarantees at least one Clg Stg Time period elapses before re-entering the Intialization and Normal
Cooling states. The following describes the Standby for Restart state sequence:

Table 40: Standby for Restart State


Stage 1 Stage 2
Compressors Inverter Compressor speed = 0% and Comp3 OFF ←
Outdoor Fan position = 50% if OAT > 86°F when
entering Standby for Restart state
Outdoor Fan ←
Outdoor Fan position = 0% if OAT ≤ 86°F when
entering Standby for Restart state
4 way valve, outdoor expansion valve (EVO) (Heat
Off or closed Off or closed
Pump only) and SVB
Open if saturated discharge pressure > 427 psi when
SVR (HeatPump only) entering Standby for Restart state Closed
Closed otherwise
Indoor expansion valve (EVI) Closed Closed
5 seconds Remainder of Clg Stg Time
Time Duration
Clg Stg Time (default=5 minutes)

OM 1263 • MICROTECH UNIT CONTROLLER 56 www.DaikinApplied.com


Operator’s Guide

Determining Cooling Status Determining Heat Status


Clg Status is a status item which indicates whether or not Htg Status is a status item which indicates whether or not the
mechanical cooling is currently allowed. If cooling is disabled, primary source of heating in the unit is currently allowed. On
the reason is indicated. heat pump units this is the compressor heating.
The following are descriptions of cooling status states. The following are descriptions of the heating status states:

Enabled Enabled
Mechanical cooling is enabled if all the following are true: In the heat pump, compressor heating is enabled if all of the
following are true:
• Control mode is not set via the keypad to fan only or heat
only • Control Mode is not set via the keypad to fan only or cool
• Control mode is set via the keypad to auto and not only
disabled via a third-party signal • Control Mode is set via the keypad to auto and heating is
• The outdoor air temperature (OAT) is high enough for not disabled via a network command
operation • The outdoor air temperature (OAT) is warm enough
• Compressor operation is not disabled by an alarm (above 0°F default) and cool enough (below 55°F default)
condition for compressor heating operation.

None None
Cooling capability is not provided. Unit is not a heat pump and heating capability is not provided

Off Ambient Off Ambient


The outdoor air temperature (OAT) is too low for operation. In a heat pump, the OAT is too high or too low for compressor
heating operation. OAT becomes too high for compressor heat
The OAT becomes too low for operation when it drops below operation when it rises above the high OAT heating lock out
the OAT cooling lockout setting. OAT becomes high enough for set point. The OAT becomes low enough for compressor heat
operation when it rises above the OAT cooling lockout setting operation when it drops below the high OAT heating lock out
by more than 2°F (adjustable - OAT Diff). set point by more than the heating lockout differential. The The
OAT becomes too low for compressor heat operation when it
Off Alarm falls below the low OAT heating lock out set point. The OAT
Compressor operation is disabled by an alarm condition. becomes high enough for compressor heat operation when
it rises above the low OAT heating lock out set point by more
Off Network than the heating lockout differential.
Control mode is set via the keypad to auto and cooling is
disabled via a network command.
Off Network
Control Mode is set via the keypad to auto and heating is
Off Manual disabled via a network command.
Control mode is set to Fan Only or Heat Only via the keypad
display.
Off Manual
Control Mode is set via the keypad to fan only or cool only..

www.DaikinApplied.com 57 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Determining Cooling Capacity Auto


Clg Capacity is a status item which indicates the percentage of When the Net App Mode is set to “Auto” heating and cooling
the unit maximum cooling capacity currently operating. operation are allowed to operate as required to maintain the
heating and cooling set points.
Determining Heat Capacity
Htg Capacity is a status item which indicates the percentage OAT Lockout
of the unit maximum primary heating source that is currently On heat pump units, compressor heating (primary heat) is
operating. On heat pump units this is the compressor heating disabled whenever the outdoor air temperature is below the
capacity. Low Outdoor Air Ambient Heating Lockout set point or above
the High Outdoor Air Ambient Heating Lockout set point.
Determining Supply Air Fan Capacity Whenever the outdoor air temperature rises above the Low
SAF Speed is a status only item which indicates the supply Outdoor Air Ambient Heating Lockout set point or falls below
air fan capacity. 0-100% of maximum speed is indicated if the the High Outdoor Air Ambient Heating Lockout set point
unit is equipped with a variable volume supply air fan. 100% is by more than the Heating Lockout Differential, compressor
indicated if the supply fan is constant volume and is running. heating operation is re-enabled.
Supplemental heating (secondary heat) is disabled whenever
Determining RF/EF Capacity the outdoor air temperature is above the High Outdoor Air
Ambient Supplemental Heating Lockout Set Point. Whenever
RF/EF capacity is a status only item which indicates the current
the outdoor air temperature falls below the High Outdoor Air
exhaust fan capacity. 0-100% of maximum speed is indicated if
Ambient Supplemental Heating Lockout Set Point by more
the unit is equipped with a variable volume exhaust fan. 100% is
than the Heating Lockout Differential, supplemental heating
indicated if the exhaust fan is constant volume and is running.
operation is re-enabled.

Determining Outside Air Damper Compressor cooling operation is disabled whenever the
outdoor air temperature falls below the Low Outdoor Air
Position Ambient Cooling Lockout Set Point. Whenever the outdoor
OAD/Econo Cap is a status only item which indicates the air temperature rises above the Low Outdoor Air Ambient
current outdoor air damper or economizer valve position. Cooling Lockout Set Point by more than the Cooling Lockout
Differential, compressor cooling operation is re-enabled.
Determining System Mode On non-heat pump units, heating is disabled whenever
The system can be set up for local or remote modes. the outdoor air temperature is above the High Outdoor Air
Ambient Heating Lockout Set Point. Whenever the outdoor
Off air temperature falls below the High Outdoor Air Ambient
Heating Lockout Set Point by more than the Heating Lockout
When the Net App Mode is set to “OFF,” the Unit Status is “Off Differential, heating operation is re-enabled.
Net” and the unit is completely disabled, including unoccupied
heating (night set back) and unoccupied cooling (night set up) Compressor cooling operation is disabled whenever the
operation. outdoor air temperature falls below the Low Outdoor Air
Ambient Cooling Lockout Set Point. Whenever the outdoor
Heat Only air temperature rises above the Low Outdoor Air Ambient
Cooling Lockout Set Point by more than the Cooling Lockout
When the Net App Mode is set to “Heat Only,” heating Differential, compressor cooling operation is re-enabled.
operation is allowed to operate as required to maintain the
heating set points. Cooling operation is disabled (Cooling
Status is “Off Net”).

Cool Only
When the Net App Mode is set to “Cool Only,” cooling
operation is allowed to operate as required to maintain the
cooling set points. Heating operation is disabled (Heating
Status is “Off Net”).

Fan Only
When the Net App Mode is set to “Fan Only,” the fans are
allowed to operate but cooling and heating operation is
disabled (Cooling Status and Heating Status are “Off Net”).

OM 1263 • MICROTECH UNIT CONTROLLER 58 www.DaikinApplied.com


Operator’s Guide

Heat Pump Control Supplemental Heating/Compressor


A heat pump unit transitions between the Cooling and Heating
operating states as described above. If compressor heating is
Heating Transitions
available it is used first to provide the heating source during Special action is required when the unit transitions from using
the Heating states. If compressor heating is unavailable (as compressor (heat pump) heating to supplemental heating and
during defrost operation for example) or inadequate to meet vise versa. Normal operation is for the compressor heating to
the heating requirements during these states, supplemental turn ON first and ramp to full capacity before turning on any
heating will be used to add to or in lieu of the compressor supplemental heating. Once the compressor heating is at
heating. full capacity, the supplemental heating will then ramp up and
down as necessary to satisfy the load. There will however be
Heat Pump Cooling Operation instances when heating is required and compressor heating is
unavailable in which case the supplemental heating must turn
When the unit transitions from the Fan Only to Cooling ON first. These include the following cases:
operating state or if dehumidification operation becomes
active while in the Fan Only state, compressor cooling • Compressor heating operation is disabled
operation begins. Refer to “Inverter Compressor Cooling State • Heat pump defrost operation is active
Descriptions” on page 51 for a detail description of the • Dehumidification is active
cooling compressor operating sequence. • Unit is 100% OA and the OAT is below the low limit set
point of about 0° F [adjustable.] This is adjustable such
Heat Pump Heating Operation that heat pump operation can be locked out at ambients
When the unit transitions from the Fan Only to Heating where gas heat is more economical.
operating state, compressor heating operation begins. Refer In the cases where compressor heating becomes available
to “Inverter Compressor Heating State Descriptions” on while the supplemental heating is operating it is desirable
page 61 for a detail description of the heating compressor to shift as much of the load as possible to the compressor
operating sequence. heating. This is accomplished with the following sequence
which occurs whenever compressor heating enters the Normal
Heat Pump Defrost Operation Heating state or leaves defrost operation while supplemental
Defrost operation is required when compressor operation is in heating is active:
the Normal Heating state when frost build up on the outdoor • Inverter compressor speed is increased 5% every 15
coil interferes with the normal heat transfer from the outdoor seconds up to maximum speed.
coil to the ambient air. Refer to “Defrost Operation – Heat
• Fixed speed compressor is turned ON when the inverter
Pump Units Only” on page 67 for a detailed description.
compressor reaches maximum speed.

Supplemental heating is allowed to cycle OFF normally while


the compressor heating is ramping up. When the supplemental
heating has been OFF for one stage time period, normal
modulating compressor control begins from the current
capacity.
When compressor heating is operating while supplemental
heating is inactive, the supplemental heating is held inactive
until then compressor capacity has been operating at its
maximum capacity and the fixed compressor is ON for one
stage time period. At this point the supplemental heating is
enabled to start cycling to meet the load.

www.DaikinApplied.com 59 OM 1263 • MICROTECH UNIT CONTROLLER


Operator’s Guide

Heat Pump Operating State


Compressor Heating Operation State Prestart Pressure Equalization to Initialization
Machine – Heat Pump Units Only The Compressor Heating State transitions from Prestart
Pressure Equalization to initialization after ninety seconds.
This section applies to heat pump units only. When a unit is
configured for heat pump operation the primary source of
Initialization to Normal
heating is provided by operating the compressors in a heating
mode of operation. When this primary heat is unavailable or The Compressor Heating State transitions from Initialization
at is maximum capacity and more heating is required, any to Normal when the initialization sequence is complete. See
available supplemental heating is controlled as described Initialization state description in the “Inverter Compressor
in that section. When this primary heating is enabled the Heating State Descriptions” on page 61.
compressor transitions through the heating states shown in
the following state diagram. Control based on discharge air Initialization to Pumpdown
temperature (DAT) occurs in the Normal Heating state. The Compressor Heating State transitions from Initialization to
Pumpdown if there is no longer a call for MinDAT or Heating
Figure 15: Heating State Diagram operation.

Initialization to Standby for Restart


The Compressor Heating State transitions from Initialization
to Standby for Restart if one of the Compressor Protection
functions force a transition to Standby for Restart, the inverter
compressor or outdoor fan board requests a transition to
Standby for Restart or if all compressor operation becomes
disabled for any reason.

Normal to Pumpdown
The Compressor Heating State transitions from Normal to
Pumpdown if there is no longer a call for MinDAT or Heating
operation.

Normal to Standby for Restart


The Compressor Heating State transitions from Normal to
Standby for Restart if one of the Compressor Protection
functions force a transition to Standby for Restart, the inverter
compressor or outdoor fan board requests a transition to
Standby for Restart or if all compressor operation becomes
disabled for any reason.

Pumpdown to Standby for Restart


The Compressor Heating State transitions from Pumpdown
to Standby for Restart if one of the Compressor Protection
functions force a transition to Standby for Restart, the inverter
compressor or outdoor fan board requests a transition to
Standby for Restart or if all compressor operation becomes
disabled for any reason.
Off to Prestart Pressure Equalization
The Compressor Heating State transitions from OFF to Pumpdown to Initialization
Prestart Pressure Equalization when the unit enters the The Compressor Heating State transitions from Pumpdown
MinDAT or Heating operating state. to initialization if there is a call for cooling MinDAT or Heating
operation.
Prestart Pressure Equalization to Off
The Compressor Heating State transitions from Prestart Standby for Restart to Off
Pressure Equalization to OFF if there is no longer a call for The Compressor Heating State transitions from Standby for
MinDAT or Heating operation. Restart to OFF after the heating stage timer expires.

OM 1263 • MICROTECH UNIT CONTROLLER 60 www.DaikinApplied.com


Heat Pump

Heat Pump

Inverter Compressor Heating State Descriptions


The Inverter Compressor Heating State determines the Pre Start Pressure Equalization
operation of the following devices: In the Pre Start Pressure Equalization state the SVB valve is
• Inverter Compressor opened to divert hot gas leaving the compressor directly to
• Fixed Speed Compressor (if present) the suction line to equalize the pressures in the system before
beginning compressor operation. The outdoor fan is set at 50%
• Outdoor Fan(s)
speed. Operation remains in this state for 90 seconds. When
• 4 Way Reversing Valve (4WV) in the Pre Start Pressure Equalization state, all devices are
• Outdoor Expansion Valve (EVO) OFF or closed except the outdoor fan(s) and SVB. The outdoor
• Indoor Expansion Valve (EVI) fan(s) speed is set to 50%.
• Receiver Solenoid Valve (SVR)
• Bypass Solenoid Valve (SVB)
Initialization
In the Initialization state either the Standard Initialization or
Alternate Initialization sequence is used in order to manage
Heating Off refrigerant and assure the 4-way valve is switched. The
Compressor heating operation begins in the OFF state. When Alternate Initialization sequence is used the first time the unit
in the OFF state, all devices are off or closed. The state enters heating after unit power up, or when the compressors
remains here until there is a call for heating. had last operated in cooling, or if it has been a long time since
heating has operated and it is cold outdoors. Otherwise the
Standard Initialization Sequence is used.
Table 41: Standard Initialization Sequence, 3–15 Tons
Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed = Inverter Compressor Speed =
Inverter Compressor & Comp3 Minimum Smaller of Step 12 or Maximum ← A
Comp3 = Off Comp3 = Off
If OAT ≤59°F, Inverter
Compressor Speed = Smaller
Inverter Compressor Speed =
Inverter Compressor Only of Step 12 or Maximum ← A
Minimum
If OAT >59°F, Inverter
Compressor Speed = Minimum
Outdoor Fan Outdoor Fan = 100% ← ← ←
4 Way Valve (Heat Pump) ON ← ← ←
Outdoor Coil
Expansion Valve (EVO) EVO = 0% ← ← ←
(Heat Pump only)
SVR (Heat Pump only) Closed ← ← ←
Size ≠ 15 tons: Size = 15 Tons
Normallly Open Normallly Open
Close if either of the following is true: Close if either of the following is true:
SVB ← ←
60 seconds elapses from the 60 seconds elapses from the
beginning of Step 1 beginning of Step 1
Discharge superheat > 18°F Discharge superheat > 18°F
Indoor Coil
EVI = 100% C ← ←
Expansion Valve (EVI)
D = 15 Ton size
Time Duration 10 Seconds 5 Seconds C
5 Seconds ≠ 15 Ton size
A. Inverter compressor speed is increaded until the 4-way valve is seated (discharge minus suciton pressure >57 psi) and as
long as the discharge pressure is less than 221 psi. Comp3 is always OFF.
B. Outdoor fan capacity is controlled to maintain the discharge pressure between 256 psi and 313 psi. Outdoor fan capacity
is set to 100% if discharge pressure is above 384 psi. Outdoor fan capacity runs at least at minimum capacity if inverter
board (fin) temperature >167°F.
C. The indoor expansion valve is controlled to keep the suction superheat between 3.6°F and 9.0°F.
D. Step 3 ends when either minimum Step 16 reached, differential pressure is greater than 26 psi for 3 seconds, or the stage
has been active for 3 minutes.

See page 50 for more information about what is a compressor “step”.

www.DaikinApplied.com 61 OM 1263 • MICROTECH UNIT CONTROLLER


Heat Pump

Table 42: Standard Initialization Sequence, 16–28 Tons


Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed
Inverter Compressor Speed = Inverter Compressor Speed =
= Increasing 1 step every 5
Inverter Compressor & Comp3 Minimum Step 2 D
seconds if PTD-PTD < 26 PSI
Comp3 = Off Comp3 = Off
Comp3 = Off
If OAT ≤59°F, Inverter
Compressor Speed = Smaller
Inverter Compressor Speed =
Inverter Compressor Only of Step 12 or Maximum ← D
Minimum
If OAT >59°F, Inverter
Compressor Speed = Minimum
Outdoor Fan Outdoor Fan = 100% ← ← ←
4-Way Valve (Heat Pump) ON ← ← ←
Outdoor Coil
Expansion Valve (EVO) EVO = 0% A ← ←
(Heat Pump only)
Time Duration 10 Seconds 5 Seconds C B
A. The outdoor expansion valve is to keep the suction superheat between 3.6°F and 12°F.
B. Standard initialization lasts a maximum of 600 seconds. It is completed early anywhere between 10 and 600 seconds if
discharge pressure is high (above 384 psi) or the 4-way valve has been seated for 60 seconds (differential pressure above
57 psi).
C. Step 3 ends when the minimum Step 16 is reached, differential pressure is greater than 26 psi for 3 seconds, or 3 minutes
have elapsed since the start of step 3.
D. Inverter compressor speed is increaded until the 4-way valve is seated (discharge minus suciton pressure > 57 psi).
Comp3 is always OFF.
See page 50 for more information about what is a compressor “step”.

OM 1263 • MICROTECH UNIT CONTROLLER 62 www.DaikinApplied.com


Heat Pump

Table 43: Alternate Initialization Sequence, 3–15 Tons


Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed =
Inverter Compressor Speed =
Inverter Compressor & Comp3 Smaller of Step 12 or Maximum ← A
Minimum Comp3 = Off
Comp3 = Off
If OAT ≥50°F or RAT ≥73°F,
Inverter Compressor Speed =
Inverter Compressor Speed = Smaller of Step 12 or Maximum
Inverter Compressor Only ← A
Minimum If OAT <50°F or RAT <73°F,
Inverter Compressor Speed =
Minimum“
Outdoor Fan = 0% if OAT <
68°F
Outdoor Fan B ← ←
Outdoor Fan = 5% if OAT ≥
68°F
4 Way Valve (Heat Pump) OFF ← ← ←
Outdoor Coil
Expansion Valve (EVO) EVO = 100% ← ← ←
(Heat Pump only)
SVR (Heat Pump only) Closed ← ← ←
Normally Open
SVB Close if Discharge superheat ← ← NA
>9°F
Indoor Coil
EVI = 0% C ← ←
Expansion Valve (EVI)
E = 15 Ton size F= 15 Ton size
Time Duration 5 Seconds 5 Seconds
D ≠ 15 Ton size NA
A. Inverter compressor speed is increased until the 4-way valve is seated (discharge minus suction pressure >57 psi) and as
long as the suction pressure is above 43 psi. inverter compressor speed is also increased if the suction pressure remains
above 71 psi. Comp 3 turns on if the inverter compressor speed is at maximum and these conditions are not met. Comp 3
is turned back OFF after 20 seconds if the suction pressure drops below 43 psi.
B. Outdoor fan capacity is controlled to maintain the discharge pressure between 171 psi and 221 psi. Outdoor fan capacity
is set to 100% if discharge pressure is above 427 psi. Outdoor fan capacity runs at least at minimum capacity if inverter
board (fin) temperature >167°F.
C. EVI is controlled to keep the suction superheat between 3.6°F and 14.4°F.
D. Alternate Initialization lasts a maximum 15 minutes. It is completed early anywhere between 10 seconds and 15 minutes if
once the 4-way valve is seated (differential pressure above 57 psi and the discharge superheat above 9.0°F).
E. Step 3 ends when the compressor has reached 65% full speed, differential pressure is >26 psi for 3 seconds, the stage
has been active for 3 minutes, or Comp3 is active
F. Step 4 (initializaiton) is complete when the stage has been active for 15 minutes, or 4 way valve has set and discharge
superheat is above 9°F

www.DaikinApplied.com 63 OM 1263 • MICROTECH UNIT CONTROLLER


Heat Pump

Table 44: Alternate Initialization Sequence, 16–28 Tons


Device Step 1 Step 2 Step 3 Step 4
Inverter Compressor Speed
Inverter Compressor Speed = Inverter Compressor Speed = = Increasing 1 step every 5
Inverter Compressor & Comp3 A
Minimum Comp3 = Off Step 2 Comp3 = Off seconds if PTD-PTD < 26 PSI
Comp3 = Off
If OAT ≤59°F, Inverter
Compressor Speed = Smaller
Inverter Compressor Speed =
Inverter Compressor Only of Step 12 or Maximum A NA
Minimum
If OAT >59°F, Inverter
Compressor Speed = Minimum
Outdoor Fan Outdoor Fan = 100% ← ← ←
4 Way Valve (Heat Pump) ON ← ← ←
Outdoor Coil
Expansion Valve (EVO) B ← ← ←
(Heat Pump only)
Time Duration 5 Seconds 5 Seconds C ←
A. Inverter compressor speed is increased until the 4-way valve is seated (discharge minus suction pressure > 57 psi) and as
long as discharge presure is below 221 psi. Inverter compressor speed is also increased if the discharge pressure remains
below 171 psi. Comp3 turns on if the inverter compresor speed is at maximum and those conditions are not met. Comp3
turns back off after 20 seconds if the discharge pressure rised above 221 psi.
B. The outdoor expansion vavle is to keep the suction superheat between 3.6°F and 5.4 °F
C. Alternate initializaiton lasts a maximum 15 minutes. It is completed early anywhere between 10 seconds and 15 minutes if
once the 4-way valve is seated (differential pressure above 57 psi) and superheat is above 18°F or discharge pressure is
above 384 psi.

OM 1263 • MICROTECH UNIT CONTROLLER 64 www.DaikinApplied.com


Heat Pump

Normal Heat Pump Control


Normal Heating
In the Normal Heating state the following are accomplished:
• Compressor capacity (INV and Comp 3) is regulated to maintain the DAT at either the Discharge Air Temperature Heating
Setpoint (Unit State=Heating) or the Minimum Discharge Air Temperature Spt (Unit State=MinDAT)
• Outdoor coil expansion value (EVO) is modulated to maintain the suction superheat at the suction superheat setpoint
• Indoor coil expansion valve (EVI) is controlled to maintain indoor coil subcooling at the indoor coil subcooling setpoint (heat
pump)
• Outdoor fan(s) are set to maximum and then decreased if the suction pressure is high (above 162.2 psi) or increased back
toward the maximum if the suction pressure is low (below 106.7 psi).
When in the Normal Heating state the action of the heating control devices is as follows:

Table 45: Normal Heating State


Device Action
Inverter Compressor Speed Controlled with PI Loop to maintain DAT Setpoint
Compressors Comp 3: Turned On when Inverter Compressor at Maximum
Comp 3: Turned Off when Inverter Compressor at Minimum
Outdoor Fan A
4 Way Valve
ON
(HeatPump)
Outdoor Coil Expansion Valve (EVO)
EVO Controlled With PI Loop to maintain Suction Superheat Setpoint
(HeatPump)
SVR
Closed
(HeatPump)
SVB is normally closed during the Normal Heating state
except in the following cases:
SVB SVB is opened for one second before and after Comp 3 is stopped.
During Low Pressure Unloading Control SVB is opened if PTS <147.1 kPa
(21.34 psi). It is closed again when PTS>294.2 kPa (42.67 psi).
Indoor Coil Expansion Valve (EVI) B
Time Duration While in Normal Heating state

A. Outdoor fan(s) are set to maximum and then decreased if the suction pressure is high (above 162.2 psi) or increased back
toward the maximum if the suction pressure is low (below 106.7 psi).
B. The indoor expansion valve is either driven fully open or varied based on indoor coil subcooling as follows:
When the Htg EVI Method is set to 100%, the indoor expansion valve is driven to the 100% open position.
When the Htg EVI Method is set to SbC, the indoor expansion valve is controlled to maintain the indoor coil subcooling at
the indoor coil subcooling temperature setpoint.

www.DaikinApplied.com 65 OM 1263 • MICROTECH UNIT CONTROLLER


Heat Pump

Pumpdown
Compressor heating operation enters the Pumpdown state before entering the Standby for Restart state from either the
Initialization or Normal Heating state.
The following describes the operation of the compressor heating control devices in the Pumpdown state:

Table 46: Pumpdown State


Step 1
Inverter Compressor Speed = Smaller of Step 12 or maximum
Compressors
Comp3=OFF
Outdoor Fan Outdoor Fan speed = maximum
4 Way Valve (4WV) ON
Outdoor Expansion Valve (EVO) Outdoor Expansion Valve position = 0%
SVR Closed
SVB Open
Indoor Expansion Valve (EVI) Indoor Expansion Valve Control position = 50%
Time Duration See A below

A. Pumpdown is complete after 3 minutes or when the suction pressure drops below 34 psi. Pumpdown is terminated if either
the discharge superheat rises above 230°F or if the Inverter Compressor port temperature rises above 284°F.

Standby for Restart


The Standby for Restart state guarantees at least one Htg Stg Time period elapses before re-entering the Intializaton and Normal
Heating states. The following describes the Standby for Restart state sequence:

Table 47: Standby for Restart State


Step 1 Step 2
Inverter Compressor speed = 0%
Compressors ←
Comp3=OFF
Outdoor Fan speed = 50% if OAT > 86°F when
entering Standby for Restart state
Outdoor Fan ←
Outdoor Fan speed = 0% if OAT ≤ 86°F when entering
Standby for Restart state
4 Way Valve (4WV) ON ←
Outdoor Expansion Valve (EVO) Outdoor Expansion Valve position = 0% ←
SVR Closed Closed
SVB Closed ←
Indoor Expansion Valve (EVI) Indoor Expansion Valve position = 0% ←
5 seconds Remainder of Htg Stg Time
Time Duration
Htg Stg Time (default = 5 minutes)

OM 1263 • MICROTECH UNIT CONTROLLER 66 www.DaikinApplied.com


Heat Pump

Defrost Control
(See page 29 for more information) When a compressor is operating under these potential frosting
conditions for at least the MinCmpOpTm= period (Default=10
Defrost Operation – Heat Pump Units minutes) and the accumulated compressor operation time
since the last defrost cycle exceeds the MinAccCmpTm=
Only value (Default=40 minutes), the controller can initiate a defrost
This section applies to heat pump units only. Defrost cycle base on temperature, time or on a manual request as
operation is required when compressor operation is in the described in the following sections.
Normal Heating state when frost build up on the outdoor
coil interferes with the normal heat transfer from the outdoor Temperature Defrost
coil to the ambient air. When defrost operation is active, A defrost cycle is initiated based on temperature when the
compressor operation remains in the Normal Heating state Defrost Temperature (DFT) drops below a defrost temperature
but the device control is overridden until the defrost operation value (Tdef) and the saturated discharge temperature is below
is complete. While defrost operation is active, the auxiliary 109°F continuously for 3 minutes. The Tdef value is adjusted
supplemental heat source in the unit is required to maintain automatically between (+) 14°F and (-) 13.0°F based on
comfort conditions. outdoor air temperature. This value is not directly adjustable
but can be “biased” by setting the Tdef Adj= parameter
Defrost Operation State (Default=0°F) between -3.6°F and +3.6°F. Note: To improve
performance the Tdef value is also automatically adjusted after
When outdoor coil defrosting is required defrost operation
each defrost cycle depending on the length of the cycle.
transitions through the defrost states shown in the following
state diagram:
Timed Defrost
A defrost cycle is initiated based on time when the compressors
Figure 16: Defrost Operating States have accumulated enough time operating in potential frosting
conditions. The controller accumulates minutes of operation
in low frost potential (LoFrstAccTm=) and high frost potential
(HiFrstAccTm=) conditions. Whenever the HiFrstAccTm= time
plus ½ the LoFrstAccTm= time exceed the MaxFrostTm= setting
(Default=120minutes) a defrost cycle is initiated.

Manual Defrost
A defrost cycle is manually initiated when the Manual DF=
parameter is set from No to Yes. Note: Once the defrost cycle
begins the Manual DF= parameter automatically reverts to No.

Defrost Initialization
This state prepares the system for switching the 4-way valve to
the cooling position

Execute Defrost
The 4-way valve is switched to the cooling position to defrost
the coil. This state manages the refrigerant in the system and
assures the 4-way valve is seated before defrosting the coil.
Execute Defrost continues for 10 minutes or until the Defrost
Temperature (DFT) exceeds 51.8ºF or the discharge pressure
Defrost Initiation (Heat Pump) exceeds 426.7 psi.
DPS heat pump units require a defrost cycle to remove frost
Terminate Defrost
build-up that can accumulate on the outdoor coil during certain
heating operating conditions. The controller assumes there After the defrost operation is complete, the 4-way valve is
is a potential for frost build-up on the coil when the Defrost switched to the heating position. Terminate Defrost manages
Temperature (DFT) is less than 14.0°F and the saturated the system refrigerant and assures the 4-way valve is seated
suction temperature is below 32°F. before returning to normal heating compressor operation.

Defrost Inactive
When defrost operation is in the inactive state, action of the
compressor devices is a dictated by the applicable heating or
cooling compressor state.

www.DaikinApplied.com 67 OM 1263 • MICROTECH UNIT CONTROLLER


Heat Pump

4 Way Reversing Valve Control (4WV) – Bypass Solenoid Valve Control (SVB)
Heat Pump Units Only DPS units include a bypass solenoid valve that opens when
4WV is energized (On) when the unit is in the MinDAT or necessary to bypass refrigerant from the high to the low
Heating operating state. 4WVG is de-energized (OFF) when side of the inverter compressor to reduce the load on the
the unit is in the Cooling operating state. compressor. The bypass solenoid is closed most of the time.
Refer to the descriptions of the compressor operating states
NOTE: Once switched, the 4WV remains in the new position and protection control functions for details regarding when the
until the unit’s state changes from Cooling to MinDAT bypass valve is opened.
or Heating or viceversa.

Receiver Solenoid Valve Control (SVR)


DPS heat pump units include a receiver solenoid valve that is
used to direct the refrigerant to the receiver while switching the
valve during the defrost cycle. The SVR valve is closed most
of the time but is opened at certain points in the defrost cycle
and in the Pumpdown and Standby for Restart compressor
operating states.

OM 1263 • MICROTECH UNIT CONTROLLER 68 www.DaikinApplied.com


Troubleshooting

Troubleshooting

Inverter Board Fault Codes


MicroTech III communicates with the fan and compressor Detailed description and diagnostic instructions are shown on
inverter boards via Modbus. If the inverter boards detect the following pages.
an unsafe condition they issue the appropriate control
commands and an error code can be read at the MicroTech III Figure 17: Inverter Board Fault Codes
display as follows:
• Go to Main menu – Alarm lists – Active alarms – Alarm Fault Code Details
ACTIVE FAULT CODES
details - INV/OF Flt Code Details INVAlarmCode=______
• The error code is shown at “INVAlarmCode” and the error Code Text
description is shown at “Code text” as shown in Figure OF1AlarmCode=_______
Code Text
17. OF2AlarmCode=_______
Code Text
Possible Inverter Compressor fault codes are listed in Table 71 PREVIOUS FAULT CODES
below: PrvINVAlmCode=_______
Code Text
MM/DD/YYYY HH:MM:SS
Table 71: Rebel Inverter Compressor Fault Codes PrvOF1AlmCode=______
Code Text
Fault MM/DD/YYYY HH:MM:SS
HMI Code Text Extended Text
Code PrvOF2AlmCode=______
E5 Compressor Lock Compressor Locked Code Text
L1 Current Sensor Alm Current Sensor Alarm MM/DD/YYYY HH:MM:SS

L1 DC Cur Sensor Alm DC Current Sensor Alarm


L1 EEPROM Setup Problem EEPROM Setup Problem
L1 IGBT Problem Insulated Gate Bipolar Transistor Problem
L1 JP Setup Problem LP Setup Problem
L1 Momntry Ovrcurrent Momentary Over Current
L4 Fin Temp Rise Fin Temperature Rise
L5 Momntry Ovrcur (DC) Momentary DC Over Current
L8 Elec Therm (Cur1) Electrical Thermal (Current 1)
L8 Elec Therm (Cur2) Electrical Thermal (Current 2)
L8 Elec Therm (Step) Electrical Thermal (Out of Step)
L8 Elec Therm (Surge) Electrical Thermal (Surge)
L8 Time Lag Ovr Current Time Lag Over Current
L9 Stall Prevent (Strt) Startup Prevention (Startup)
P1 Pwr Sup Imbalance Power Supply Imbalance
P4 Fin Temp Sensor Alm Fin Temperature Sensor Alarm
PJ Model Setup Problem Model Setup Problem
U2 Phase Pwr Loss Phase Power Loss
U2 PN Short Circuit Alm PN Electrical Short Circuit Alarm
U2 Pwr Sup Insufficient Power Supply Insufficient

Possible outdoor fan fault codes are listed in Table 72 below.

Table 72: Rebel Outdoor Fan Fault Codes


Fault
HMI Code Text Extended Text
Code
E7 IPM Prot Active IPM Protection Active
E7 Momntry Ovrcurrent Momentary Over Current
E7 Motor Lock Motor Locked
H7 Motor Alarm Motor Alarm
L1 EEPROM Problem EEPROM Problem
L1 EEPROM Setup Problem EEPROM Setup Problem
L1 JP Setup Problem JP Setup Problem
L4 Fin Temp Rise Fin Temperature Rise
P4 Fin Temp Sensor Alm Fin Temperature Sensor Alarm
PJ Model Setup Problem Model Setup Problem
U2 Pwr Sup Voltage Alm Power Supply Voltage Alarm

www.DaikinApplied.com 69 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

Troubleshooting Module-to-Module Communication


There are three status parameters on the HMI that are INVErr: Communication between the A4P board controlling
designed to aid in diagnosing communication problems inverter compressor (INV) and the ACS1 communication loop
related to the IFB board. These are IFBCommStatus=, ACS1 has been interrupted for 20 seconds after communication had
DataRcvd= and ACS3 DataRcvd= and are described below. initially been established. If this indicator remains active more
Also refer to Figure 3 on page 6. than 120 seconds it generally suggests a defect in the A4P
board.
IFBCommStatus NOTE: A break anywhere in the communication current loop
The IFB communication status parameter indicates problems will result in an ACS1Err (described below).
with the communication between the MicroTech III controller ACS3Err: The ACS3 communication loop between the
and the INV, OF1, OF2 and the EVB devices via the IFB board. IFB board ACS3 connector and the EVB board has been
There are 13 possible conditions indicated by this parameter. interrupted for 65 seconds after communication had initially
These are described as follows: been established. This generally indicates a physical break in
OK: All communications related to IFB Board is OK the communication current loop wiring between the IFB board
and the EVB board, lack of power to the EVB board or a defect
OF2Err: Communication between the A5P board controlling in the EVB board.
OF2 and the ACS1 communication loop has been interrupted
for 65 seconds after communication had initially been ACS1Err: The ASC1 communication loop between the IFB
established. Since a break anywhere in the communication board ASC1 connector and the A4P and A5P boards has been
current loop will result in an ACS1Err (described below) this interrupted for 65 seconds after communication had initially been
indicator generally suggests a defect in the A5P board. established. This indicator generally suggests a physical break
or interruption somewhere in the communication current loop
OF1Err: wiring or possibly lack of power to both A4P and A5P.
460/575V Unit—Communication between the A5P board
controlling OF1 and the ACS1 communication loop has ACS13Err: The ASC1 and ACC3 communication loops
been interrupted for 65 seconds after communication between the IFB board ACS1 connector and the A4P and
had initially been established. Since a break anywhere in A5P boards and between the IFB board ACS3 connector and
the communication current loop will result in an ACS1Err the EVB board have been interrupted for 65 seconds after
(described below) this indicator generally suggests a defect in communication had initially been established. This indicates
the A5P board. that both of the conditions described above for ACS1Err and
ACS3Err exist.
208/230V Unit—Communication between the A4P board
controlling OF1 and the ACS1 communication loop has Init3Err: Proper communication was not established within
been interrupted for 65 seconds after communication 65 seconds of power up between the EVB board and the IFB
had initially been established. Since a break anywhere in board ACS3 connector. Refer also to ACS3 DataRcvd below.
the communication current loop will result in an ACS1Err Init1Err: Proper communication was not established within 65
(described below) this indicator generally suggests a defect in seconds of power up between the A4P and A5P boards and the
the A4P board. IFB board ACS1 connector. Refer also to ACS1 DataRcvd below.
OF12Err: Init13Err: Proper communication was not established within 65
460/575V Unit—Communication between both of the A5P seconds of power up between neither the EVB board and the
boards controlling OF1 and OF2 and the ACS1 communication IFB board ACS3 connector nor the A4P and A5P boards and
loop has been interrupted for 65 seconds after communication the IFB board ACS1 connector. Refer also to ACS1 DataRcvd
had initially been established. Since a break anywhere in and ACS3 DataRcvd below.
the communication current loop will result in an ACS1Err
IFBRst: 24 VAC power to the IFB was interrupted and
(described below) this indicator generally suggests a defect in
then re-established causing a reset of the ACS1 and ACS3
both the A5P boards.
communication loops.
208/230V Unit—Communication between the A4P board
MBErr: Communication between the MicroTech III controller
controlling OF1 and the A5P board controlling OF2 and
and the IFB board has been interrupted for 30 seconds.
the ACS1 communication loop has been interrupted for 65
seconds after communication had initially been established.
Since a break anywhere in the communication current loop will
result in an ACS1Err (described below) this indicator generally
suggests a defect in both the A4P and A5P boards.

OM 1263 • MICROTECH UNIT CONTROLLER 70 www.DaikinApplied.com


Troubleshooting

ACS1 DataRcvd ACS3 DataRcvd


Upon power up the IFB board receives initial confirmation Upon power up the IFB board receives confirmation data
data from all the devices that are connected to the ACS1 from all the devices that are connected to the ACS3 channel.
channel. Problems with this confirmation are indicated with this Problems with this confirmation are indicated with this
parameter. There are 8 possible conditions indicated. These parameter. There are 2 possible conditions indicated. These
are described as follows: are described as follows:
ErrAll: IFB did not receive initial confirmation data from Error: IFB did not receive initial confirmation data from
any of the devices on the ACS1 communication channel. the EVB board on the ACS3 communication channel.
This generally indicates a physical break in the ACS1 This generally indicates a physical break in the ACS3
communication loop wiring between the IFB board and the communication loop wiring between the IFB board and the
A4P and A5P boards or lack of power to both the A4P and A5P EVB board, lack of power to the EVB board or a defect in the
boards. EVB board.
F1F2Err: IFB did not receive initial confirmation data from OK: All initial confirmation data has been received from all the
the OF2 nor OF1 on the ACS1 communication channel. This EVB board on the ACS3 communication channel.
generally indicates a defect in both the boards controlling OF1
(A4P or A5P) and OF2 (A5P). Fig 1 note
INVF2Err: IFB did not receive initial confirmation data from
the INV nor OF2 on the ACS1 communication channel. This
generally indicates a defect in both the boards controlling INV
(A4P) and OF2 (A5P).
F2Err: IFB did not receive initial confirmation data from the
OF2 on the ACS1 communication channel. This generally
indicates a defect in the board controlling OF2 (A5P).
INVF1Err: IFB did not receive initial confirmation data from
the INV or OF1 on the ACS1 communication channel. This
generally indicates a defect in both the boards controlling INV
(A4P) and OF1 (A4P or A5P).
F1Err: IFB did not receive initial confirmation data from the
OF1 on the ACS1 communication channel. This generally
indicates a defect in the board controlling OF1 (A4P or A5P).
INVErr: IFB did not receive initial confirmation data from the
INV on the ACS1 communication channel. This generally
indicates a defect in the board controlling INV (A4P).
AllOK: All initial confirmation data has been received from all
the devices on the ACS1 communication loop.

www.DaikinApplied.com 71 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

Figure 18: Unit will not Start with Compressor Cooling



 
    
  
 

  


   



 
 
 

  


     
 

 
 

 
 

  
  



 

 
 


 
    

 

  


   





 
  

 

 

  
 



  

  

 
 
 
  
 




OM 1263 • MICROTECH UNIT CONTROLLER 72 www.DaikinApplied.com


Troubleshooting

Figure 19: Unit will not Heat with Compressor Heating




  






 
  
 

 

 

   





 
  
 
 


  
 


  


 


  


  



  
 


 
 
 

 
 
  

 


   
 
 

 

 


 


 
 
  








www.DaikinApplied.com 73 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

The Check 1, Check 2 and Check 3 procedures on page 74 and 75 are used to troubleshoot many error codes.

CHECK 1
Check on connector of fan motor (Power supply cable)
1. Turn OFF the power supply.
Measure the resistance between phases of U,V,W at the
motor side connectors (three-core wire) to check that
the values are balanced and there is no short circuiting,
while connector or relay connector is disconnected.

CHECK 2
1. Turn OFF the power supply.
2. Measure the resistance between Vcc and each phase
of U, V, W, and GND and each phase at the motor side
connectors (five-core wire) to check that the values are
balanced within the range of ± 20 %, while connector or
relay connector is disconnected. Furthermore, to use a
multiple meter for measurement, connect the probe of
negative pole to Vcc and that of positive pole to GND.

OM 1263 • MICROTECH UNIT CONTROLLER 74 www.DaikinApplied.com


Troubleshooting

CHECK 3 – Power Resistor Check

www.DaikinApplied.com 75 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: E5 – Inverter Compressor Motor Lock

Remote
Controller
Display E5
Method of Inverter PC board takes the position signal from UVW line connected between the inverter
Malfunction and compressor, and the malfunction is detected when any abnormality is observed in the
Detection
phase-current waveform.
Malfunction This malfunction will be output when the inverter compressor motor does not start up even
Decision
Condition in forced startup mode.
●●Inverter compressor lock
Supposed ●●High differential pressure (72.5psi or more)
Causes ●●Incorrect UVW wiring
●●Faulty inverter PC board

OM 1263 • MICROTECH UNIT CONTROLLER 76 www.DaikinApplied.com


Troubleshooting

Figure 20: E5 – Inverter Compressor Motor Lock

Check 3 See page 75

www.DaikinApplied.com 77 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: E7 – Malfunction of Outdoor Unit Fan Motor

Remote
Controller
Display E7
Detect a malfunction based on the current value in the INVERTER PC board (as for motor
Method of 2 current value in the fan PC board).
Malfunction
Detection Detect a malfunction for the fan motor circuit based on the number of rotation detected by
hole IC during the fan motor operation.
●●Overcurrent is detected for INVERTER PC board (A2P) or fan INVERTER PC board
Malfunction (A5P) (System down is caused by 4 times of detection.)
Decision
Condition ●●In the condition of fan motor rotation, the number of rotation is below the fixed number
for more than 6 seconds. (System down is caused by 4 times of detection.)
●●Failure of fan motor
●●Defect or connection error of the connectors/ harness between the fan motor and PC
Supposed board
Causes
●●The fan can not rotate due to any foreign substances entangled.
●●Clear condition: Continue normal operation for 5 minutes

OM 1263 • MICROTECH UNIT CONTROLLER 78 www.DaikinApplied.com


Troubleshooting

Figure 21: E7 – Malfunction of Outdoor Unit Fan Motor

(Referring to the information on page 74)

(Referring to the information on page 74)

www.DaikinApplied.com 79 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: H7 – Abnormal Outdoor Fan Motor Signal

Remote
Controller
Display H7
Method of
Malfunction Detection of abnormal signal from fan motor.
Detection
Malfunction
Decision In case of detection of abnormal signal at starting fan motor.
Condition
●●Abnormal fan motor signal (circuit malfunction)
Supposed
Causes ●●Broken, short or disconnection connector of fan motor connection cable
●●Fan Inverter PC board malfunction (A2P)
Perform ●●Check 1 and Check 2 on page 74

OM 1263 • MICROTECH UNIT CONTROLLER 80 www.DaikinApplied.com


Troubleshooting

ERROR CODE: L1 – Defective Inverter PC Board

Remote
Controller
Display L1
Malfunction is detected based on the current value during waveform output before starting
Method of compressor.
Malfunction
Detection Malfunction is detected based on the value from current sensor during synchronous
operation when starting the unit..
Overcurrent (OCP) flows during waveform output.
Malfunction
Decision Malfunction of current sensor during synchronous operation.
Condition
IPM failure.
●●Inverter PC board (A2P)
Supposed –– IPM failure
Causes –– Current sensor failure
–– Drive circuit failure

www.DaikinApplied.com 81 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

Figure 22: L1 – Defective Inverter PC Board

Check 3

Check 3

Check 3 See page 75 for Check 3 information

OM 1263 • MICROTECH UNIT CONTROLLER 82 www.DaikinApplied.com


Troubleshooting

ERROR CODE: L4 – Malfunction of Inverter Radiating Fin Temperature Rise

Remote
Controller
Display L4
Method of
Malfunction Fin temperature is detected by the thermistor of the radiation fin.
Detection
Malfunction
Decision When the temperature of the inverter radiation fin increases above 188.6°F.
Condition
●●Actuation of fin thermal (Actuates above 188.6°F)
Supposed
Causes ●●Defect of inverter PC board
●●Defect of fin thermistor

www.DaikinApplied.com 83 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

Figure 23: L4 – Malfunction of Inverter Radiating Fin Temperature Rise

OM 1263 • MICROTECH UNIT CONTROLLER 84 www.DaikinApplied.com


Troubleshooting

Figure 24: L4 – Malfunction of Inverter Radiating Fin Temperature Rise

Thermistor Resistance/Temperature
Characteristics

www.DaikinApplied.com 85 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: L5 – Momentary Overcurrent of Inverter Compressor

Remote
Controller
Display L5
Method of
Malfunction Malfunction is detected from current flowing in the power transistor.
Detection
Malfunction When an excessive current flows in the power transistor.
Decision
Condition (Instantaneous overcurrent also causes activation.)
●●Defect of compressor coil (disconnected, defective insulation)
Supposed
Causes ●●Compressor start-up malfunction (mechanical lock)
●●Defect of inverter PC board

OM 1263 • MICROTECH UNIT CONTROLLER 86 www.DaikinApplied.com


Troubleshooting

Figure 25: L5 – Momentary Overcurrent of Inverter Compressor

Check 3

Check 3 See page 75

www.DaikinApplied.com 87 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: L8 – Momentary Overcurrent of Inverter Compressor

Remote
Controller
Display L8
Method of
Malfunction Malfunction is detected from current flowing in the power transistor.
Detection
When overload in the compressor is detected. (Inverter secondary current 16.1A)
For 460V units
(1) 19.0A and over continues for 5 seconds.
Malfunction
Decision (2) 16.1A and over continues for 260 seconds.
Condition
For 230V units
(1) A current of 33.5A or more continues for a period of consecutive 5 sec.
(2) A current of 27.6A or more continues for a period of consecutive 260 sec.
●●Compressor overload
Supposed ●●Compressor coil disconnected
Causes ●●Defect of inverter PC board
●●Faulty compressor

OM 1263 • MICROTECH UNIT CONTROLLER 88 www.DaikinApplied.com


Troubleshooting

Figure 26: L8 – Momentary Overcurrent of Inverter Compressor

Check 3

Check 3 See page 75

www.DaikinApplied.com 89 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: L9 – Inverter Compressor Starting Failure

Remote
Controller
Display L9
Method of
Malfunction Detect the failure based on the signal waveform of the compressor.
Detection
Malfunction
Decision Starting the compressor does not complete.
Condition
●●Defective compressor
Supposed ●●Wiring connection error to the compressor
Causes ●●Large pressure difference before starting the compressor
●●Defective inverter PC board

OM 1263 • MICROTECH UNIT CONTROLLER 90 www.DaikinApplied.com


Troubleshooting

Figure 27: L9 – Inverter Compressor Starting Failure

Caution: Be sure to turn off power switch before connecting or


disconnecting connectors to prevent parts damage .

Check if the YES


compressor lead wires are Fix the compressor lead wire
disconnected

NO
Correct the wiring; then restart

YES

Check if the NO
insulation resistance of the Replace the inverter compressor
compressor is 100kΩ
or over

NO

Check 3 *
NO
Check if the Replace the compressor inverter PC board
power transistor is
normal

YES
Recheck the compressor/refrigeration circuit

YES

Unusual YES
compressor Replace the inverter compressor
noise?

* Check 3 See page 75

www.DaikinApplied.com 91 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: P1 – Inverter Over-Ripple Protection

Remote
Controller
Display P1
Imbalance in supply voltage is detected in PC board.
Method of
Malfunction Imbalance in the power supply voltage causes increased ripple of voltage of the main
Detection
circuit capacitor in the inverter. Consequently, the increased ripple is detected.
“P1” will be displayed by pressing the inspection button.
Malfunction
Decision When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
Condition
minutes.
●●Open phase
●●Voltage imbalance between phases
Supposed ●●Defect of main circuit capacitor
Causes ●●Defect of inverter PC board
●●Defect of K2 relay in inverter PC board
●●Improper main circuit wiring

OM 1263 • MICROTECH UNIT CONTROLLER 92 www.DaikinApplied.com


Troubleshooting

Figure 28: P1 – Inverter Over-Ripple Protection

www.DaikinApplied.com 93 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: P4 – Malfunction of Inverter Radiating Fin Temperature Rise Sensor

Remote
Controller
Display P4
Method of Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Detection “P4” will be displayed by pressing the inspection button.

●●Defect of radiator fin temperature sensor


Supposed ●●Defect of inverter PC board
Causes ●●Faulty inverter compressor
●●Faulty fan motor

OM 1263 • MICROTECH UNIT CONTROLLER 94 www.DaikinApplied.com


Troubleshooting

Figure 29: P4 – Malfunction of Inverter Radiating Fin Temperature Rise Sensor

See Figure 30 on page 96

www.DaikinApplied.com 95 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

Figure 30: P4 – Malfunction of Inverter Radiating Fin Temperature Rise Sensor

Thermistor Resistance/Temperature
Characteristics

OM 1263 • MICROTECH UNIT CONTROLLER 96 www.DaikinApplied.com


Troubleshooting

ERROR CODE: PJ – Faulty Field Setting after Replacing Main PC Board or Faulty Combination of PC Board

Remote
Controller
Display PJ
Method of
Malfunction This malfunction is detected according to communications with the inverter.
Detection
Malfunction Make judgment according to communication data on whether or not the type of the
Decision
Condition inverter PC board is correct.

Supposed ●●Faulty (or no) field setting after replacing main PC board
Causes ●●Mismatching of type of PC board

Recommended
Action ●●Contact the replacement parts supplier for resolution

www.DaikinApplied.com 97 OM 1263 • MICROTECH UNIT CONTROLLER


Troubleshooting

ERROR CODE: U2 – Power Supply Insufficient or Instantaneous Failure

Remote
Controller
Display U2
Method of
Malfunction Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Detection
When the voltage aforementioned is not less than 780V or not more than 320V, or when
Malfunction
Decision the current-limiting voltage does not reach 200V or more or exceeds 740V.
Condition
For 230V units: When the voltage aforementioned is not more than 190V.
●●Power supply insufficient
●●Instantaneous power failure
●●Open phase
●●Defect of inverter PC board
Supposed
Causes ●●Defect of outdoor control PC board
●●Main circuit wiring defect
●●Faulty compressor
●●Faulty fan motor
●●Faulty connection of signal cable

OM 1263 • MICROTECH UNIT CONTROLLER 98 www.DaikinApplied.com


Troubleshooting

Figure 31: U2 – Power Supply Insufficient or Instantaneous Failure

See CHECK3
on page 75

See CHECK3
on page 75

www.DaikinApplied.com 99 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – General

Appendix – General

Supply Fan Failure Codes


HLL = Hall Sensor Error
First occurrence:
Power fluctuations may be responsible.
Corrective: Reset the failure; re-start the motor and observe it. If applicable, filter out the source of the disturbing voltage.
Repeated occurrence:
Question: Do other fans show the same failure?
Yes: Systematically search for voltage peaks.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

TFEI = Electronics Interior Overheated


First occurrence:
Too high ambient temperature may be responsible.
Question: • Could ambient temperature have been too high?
• Is it possible to connect the fan to EC Control in order to display the temperature? If so, is the displayed
temperature within the expected temperature range?
Corrective: If the displayed temperature is above 95°C (the electronics switches off at 105°C,) double-check the ambient
temperature in each operating mode.
Reset the failure; re-start the motor and observe it.

Repeated occurrence:
Question: Do other fans show the same failure?
Yes: Systematically search for the cause of excessive ambient temperature. Perhaps use a data logger or read out
the electronics temperature via EC Control.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

TFM = Motor Overheated


First occurrence:
Excessive ambient temperature may be responsible.
Question: Could ambient temperature have been too high? Or is the motor overloaded?
• Is it possible to connect the fan to EC Control in order to display the motor temperature?
• Is the displayed temperature within the expected temperature range?
Corrective: If the displayed temperature is too high:
• Double-check the motor temperature in each operating mode.
• Check of the fan load: Measure the input power at max. load/ operating point and compare the measured value
with nominal data on the label. Is there any discrepancy?
• Reset the failure; re-start the motor and observe it.

Repeated occurrence:
Question: Do other fans show the same failure?
Yes: systematically search for the cause of excessive ambient temperature. Perhaps use a data logger or read out
the electronics temperature via EC Control.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

OM 1263 • MICROTECH UNIT CONTROLLER 100 www.DaikinApplied.com


Appendix – General

TFE = Power Mod Overheated


First occurrence:
Excessive ambient temperature may be responsible.
Question: • Do other fans (temporarily) show the same failure within the arrangement? Could ambient temperature have been
too high? Or is the motor overloaded?
• Is it possible to connect the fan to EC Control in order to display the temperature?
• Is the displayed temperature within the expected temperature range?
Corrective: If the displayed temperature is too high:
• Check the module temperature during operation in each operating mode (Tmodule <110°C; switching-off
temperature 115°C)
• Check the fan load and supply voltage: Measure the input power at max. load/ operating point and compare the
measured value with nominal data on the label. Is there any discrepancy?
• Reset the failure; re-start the motor and observe it.

Repeated occurrence:
Question: Do other fans show the same failure?
Yes: Systematic search for the reason of too high ambient temperature, overload, overvoltage or low voltage.
Perhaps use a data logger.
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

BLK = Locked Motor


First occurrence:
Question: • Is it possible that the motor was locked by an obstruction or ice?
• Do other fans show the same behaviour?
Corrective: Remove the reason for blocking. Caused by ice: activate the shake-loose functionality (starting with ModBus 5) or
increase the starting phase control factor.

Repeated occurrence:
Question: • Does increasing the starting phase control factor improve the situation?
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

SKF = Communication Error


First occurrence:
Power fluctuations may be responsible.
Corrective: Reset the failure; re-start the motor and observe it. If applicable, filter out the source of the disturbing signal.

Repeated occurrence:
Question: • Do other fans show the same failure?
Yes: systematic search for peaks of disturbance voltage
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

www.DaikinApplied.com 101 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – General

PHA = Phase failure


UzLow = DC-Link Undervoltage
UzHigh = DC-Link Overvoltage
UeHigh = Mains Overvoltage
UeLow = Mains Undervoltage
Question: • Can the main voltage be measured at any spot; a data logger may be helpful.
No: Measure the voltage at the power supply input of the concerned fan.
Corrective: • Reset the failure; re-start the motor and observe it.
• If applicable, filter out the source of disturbing signal.

Repeated occurrence:
Question: • Do other fans show the same failure?
• How often does the failure occur?
• Get big electrical consumer loads switched at the same time when the failure occurs in the surrounding area?
• Are compressors or large asynchronous motors applied within the arrangement?
Yes: Systematic search for external disturbance voltage peaks; If applicable, usage of data logger for a longer
period and analysis of the measured values.
• Are the voltage values within the specified range?
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

OM 1263 • MICROTECH UNIT CONTROLLER 102 www.DaikinApplied.com


Appendix – General

Trending Selection Lists


Table 73: Primary Trending Select List
HMI Name Select Abbreviation Type ID
Bldg Press= BSP 2203 F0AFC4BB
Clg State= ClgSt 230B F0AF3991
Clg Status= ClgSts 230B F0AFF6A6
Clg Press Lmtg= ClPLmtg 230B F0AF3B4E
Cmp Ratio Lmtg= CpRLmtg 230B F0AF7BA2
DAT Clg Spt= DAClgSp 2300 F0AF64FD
Dehum Status= DeHmSts 230B F0AF56EA
DFT= DFT 2203 F0AFCA19
Ref DLT Lmtg= DLLmtg 230B F0AFB273
DRT1= DRT1 2203 F0AFD8D7
DRT3= DRT3 2203 F0AFF895
Duct Press= DSP 230A F0AF143C
Econo Status= EcoSts 230B F0AFC1AB
EF/LC Temp= EFT/LCT 2203 F0AF356B
ER EAT= EREAT 2203 F0AF0DBB
ER LAT= ERLAT 2203 F0AFFD44
EVI Pos= EVI% 2203 F0AF3028
EVO Pos= EVO% 2203 F0AF17B1
EW Temp= EWT 2203 F0AFCD6B
Htg Press Lmtg= HtPLmtg 230B F0AF3FE7
INV Brd Lmtg= IBLmtg 230B F0AFBAB2
INV Cmp Spd= INV% 2203 F0AFDA3E
Mixed Air= MAT 2203 F0AFCD1F
Min OA Pos= MinOA% 230A F0AFEEC9
Occ Clg Spt= OcClgSp 2300 F0AFF8A8
OccSrc= OcSrc 230B F0AFF838
PTD= PTD 2203 F0AF229A
PTS= PTS 2203 F0AF404C
Return Air= RAT 2203 F0AFA24D
Reheat Cap= ReHt% 230A F0AF00F8
RF/EF Cap= RFEF% 2203 F0AFAECF
Subcooling= SbClg 230A F0AF842E
Space Temp= SpaceT 2203 F0AFF74A
SRT= SRT 2203 F0AFC35D
Superheat= SSH 230A F0AFB846
STD3= STD3 2207 F0AF03CC
Sump Temp= SumpT 2203 F0AF503D
UnoccSrc= UnOcSrc 230B F0AFF6B4
Unit Status = UntSts 230B F0AF4FF0
• Not all listed points may be available depending on the specific unit configuration

www.DaikinApplied.com 103 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – General

Table 74: Secondary Trending Select List


HMI Name Select Abbreviation Type ID
Alarm Enumeration Alm 230A F0AFCF76
IAQ PPM= CO2 2203 F0AF7F77
Cmp Ratio Lmtg= CpRLmtg 230B F0AF7BA2
DAT Htg Spt= DAHtgSp 2300 F0AF6054
Dewpoint= Dewpt 230A F0AF532C
Dewpoint Spt= DewptSp 2300 F0AF75C1
Defrost State= DFSt 230B F0AFBD68
Ref DLT Lmtg= DLLmtg 230B F0AFB273
EF/LC Temp= EFT/LCT 2203 F0AF356B
Wheel Speed= ERWhl% 2203 F0AF101D
EVI Pos= EVI% 2203 F0AF3028
EVO Pos= EVO% 2203 F0AF17B1
EW Temp= EWT 2203 F0AFCD6B
Head P Circ 1= HdPr1 2203 F0AFD3C4
Head P Circ 2= HdPr2 2203 F0AFE3A7
Htg State= HtgSt 230B F0AF4BE8
Htg Status= HtgSts 230B F0AFD173
Htg Press Lmtg= HtPLmtg 230B F0AF3FE7
INV Brd Lmtg= IBLmtg 230B F0AFBAB2
INV Cmp Spd= INV% 2203 F0AFDA3E
Mixed Air= MAT 2203 F0AFCD1F
OA Flow= OAFlw 230A F0AFF10A
MinOAFlw Spt= OAFlwSp 2300 F0AF6B95
Occ Htg Spt= OcHtgSp 2300 F0AF8A33
PTD= PTD 2203 F0AF229A
PTS= PTS 2203 F0AF404C
Return Air= RAT 2203 F0AFA24D
Rem ExhF Cap= RemEF% 2300 F0AF1969
Rem RAF Cap= RemRF% 2300 F0AF57A7
Rem SAF Cap= RemSF% 2300 F0AF211F
Rel Humidity= RH 2203 F0AF1DDC
RH Setpoint= RHSp 2300 F0AFFA18
Reheat Spt= RhtSp 230A F0AF335D
Subcooling= SbClg 230A F0AF842E
Space Temp= SpaceT 2203 F0AFF74A
SuplHtgStatus= SpHtSts 230B F0AF7D21
Superheat= SSH 230A F0AFB846
Supl Htg Cap= SupHt% 230A F0AF1FEA
STD3= STD3 2207 F0AF03CC
• Not all listed points may be available depending on the specific unit configuration.

OM 1263 • MICROTECH UNIT CONTROLLER 104 www.DaikinApplied.com


Appendix – Sample Wiring Diagrams: Rebel 3-15 Tons

Appendix – Sample Wiring Diagrams: Rebel 3-15 Tons

Figure 32: DPS005A, 208V with Gas Heat and Exhaust Fan
101
DS1
PB1
102 208V, 3 Phase, 60Hz
L1 T1 103A
L1
103 CUSTOMER L2 T2 104A
SUPPLIED L2
104 POWER
L3 T3 105A
L3
105 Wire for CW 60A GF-I
phase monitor 106A GFR1
MMP1 1
106 PB1 PB1
GLG1 GFR1
107A X3A
107B L1 T1 3
107 T1 T1
TB6
108A L2 T2 106A 2 106A EVB
108 T2 T2 1
(350)
109A L3 T3 107A 3 107A
109 T3 T3 3 X77A
GND2 NB
EVB208-I
110

112D
112A

112C
112B
111
A4PPWR-I
112 CMP1
CMP1-PI
113A U U
U NB
113 L1A L2A L3A E1
V
A4P V
114A V M
114 3
(350) W W GND
115A
W
115

U OFN1
116 BLK U
1 NB
PC0615-2(A)
V V M

X501A
117 WHT
2
3
118 W W CTRL
RED
3

119 1 YEL
P1 1
2 BLU
2

X502A
120 3 ORG
LR1 3
4 PNK
4
121 P2 5 GRY
5

122 X504A
PB1 PVM1 1 2
123A REC1
123 T1 3
LN-H LN-N
124 124A G
T2 4
LD-H LD-N
A4PJMP-I
125 125A
T3 5

126
MMP10 INDOOR_FAN
PB1 IFN-PI
127 NB
128A L1 T1 128B 1 L1
T1
128
T2
129A L2 T2 129B 2 L2 M
3
129 3
130A L3 T3 130B L3
T3
130 GND10 4
131A GND

131

132
MMP51 EXH_FAN1
EXH-PI NB
133 1
L1 T1 134A L1

134
L2 T2 135A 2 L2 M
3
135 3
L3 T3 136A L3

136 GND51 4
137A GND

137

138

139

140

141

142

143

144

145

146

147

148

149 T1PWR1-I PL21 T1PWR2-I F1A


PB1 1
150A 150A 1 2 153A
150 T1 PB1 150B TB6
T1
6A 1
151 R-CCH1 CCH1
F1B 1 9 CCH1-I x1 x2 CCH1-I
3 1 2 T1 152A 152B 150B
152C 152C 153B 208V PRI. T3
152 T3 500VA
MB.HB
6A H2 H3 (305)
153

154
TB1 F1C X1 X2 T1PWR2-I PL21 T1PWR1-I TB1
1 4 XF 5 3
155 160A 160A 155A 155A
120V SEC.
1 6A 3 3
156
1 3
157 6 3G
155A 155A
158
160A 155A
159 SPD
160A

155A

SPD-I
160A 120 COM T2B
1
160 120V CLASS 2 120 COM
120V_H 155A 120V_N
2 120V_N / (160) 75VA 120V
(202) 161A T2C (160)
161 GND TB1 3G
(302) CLASS 2 (202)
24V (302)
TB1 TB1 75VA
162 24 COM 24V
4 163A 163B 5 24 COM
164A

164B

163 5
T2B_24V T2B_N TB2 233 TB2 234
164 (248) (248)
(357) (357)

www.DaikinApplied.com 105 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – Sample Wiring Diagrams: Rebel 3-15 Tons

Figure 32 continued: DPS005A, 208V with Gas Heat and Exhaust Fan
(160) (160)
201 120V_H 120V_N

202

203
160A 155A
120 COM T2A
204
120V CLASS 2
75VA
205
TB1 GF1-I GF1-I TB1 24V TB1
206 6 GFR1 12 7
YEL YEL 207A 24 COM 207B
6 1 4 7
207 (105)
6 7
208 T2A_24V T2A_N
MCB 7G (213)
207C 207B
209 T1-G 207B
T1-G0

210
207B
T11-R3-4
211 T11-DI3
(346)
TB2 T12-+ A1+ /
212 TB2 Mod Bus (358)
218 SMOKE DETECTOR 219 207B Connection
207C 218 (347)
T12-- B1- /
213 (FIELD SUPPLIED) (358)
2 x 5VA AVAILABLE T2A_N / (207) 301G
RS485 (347)
GND1 /
214 (359)
TB2
COMPRESSOR_INTERLOCK 242
215 215A
T11-DI4
T7-AI1
216
DIRTY_FILTER(FIELD)
T10-DI1
217 T7-M1
T10-DI2

218 TB2 T10-M


PC5 TB2 T7-AI2
232A 232B
219 219A 1 3 219B
24VDC
FILTER OAT
220 OAT-I
BLK
T7-M2
221 OAD (FROM FIELD) TB2 NB
BLK
277 222A T7-AI3
(260) / TB2_236 T9-X8
222
0-10 VDC
TB2 TB2 TB2
223 PVM1 SAF_START_STOP (FROM FIELD)
237A 237B 266
224B 224C 224A
X3 TB2_236 / (260)
224
1(123) 8
T8-M2
225
TB2
EAF_START_STOP (FROM FIELD) 274 226A
226 (260) / TB2_236 T9-X5 SAF_CAP (FROM FIELD)
TB2
T9-M1 227A
227 X4 TB2_236 / (260)
267
0-10VDC
228
COMP_ACTUAL_CAP (TO FIELD) TB2
229 250 229A
(260) / TB2_236 T8-X2

230 0-10VDC
T8-M1
EAF_CAP (FROM FIELD) TB2
231
275 232A
(260) / TB2_236 T9-X6
232 COMP_CAP (FROM FIELD)
0-10 VDC TB2
233A
233 T8-X1 TB2_236 / (260)
247
0-10 VDC
234

235 TB2 ALARM OUTPUT


216 T5-C9-10 DO9 T5-D09 TB2 TB2
236A 236B
236
DO10 215 216
T5-DO10
237 ACT3-I
PL7
RED 1 RED TB8 207C
1
238 ACT3 GRY 3 WHT 310
NB 3 X7-AO
239 BLK 2 BLK
2
301G
DRN
240

241

242

243

244

245

246
(163) (163)
T2B_24V EXPD T2B_N
247

C2 DO2 DO2
248

249
DO4 DO4
250

251
SVB-I SVB SVB-I
C3-4 DO3 DO3
252 163A 252A 1 2 163B
PTS-I
253 WHT MB.HB
PTS S X1
NB BLK 254A
254 - T4-M1
TB8 304 R-HP1
RED DO1
+ +5V / (259) DO1 255C
255 12 8 RED
DRN 301G 255 / (354)
PTD-I (303)
256 PTD BLK C1
- WHT
NB 256 / (354)
WHT
257 S X2 SRT
SRT-I
RED BLK
+ +5V / (259) X6
258 301G TB8
DRN 305 255A 259A TB2 NB
(255) BLK (222)
/ +5V +5VDC T5-M1
259 DRT1 (258) 236 236 236 (224)
DRT1-I
BLK DIP SWITCH (226)
X3
260 ON TB2_236 / (227)
MB.HB BLK OFF (229)
T4-M2 (232)
261 1 2 3 4 5 6
(233)
SW6 MUST
262 BE ON
WHEN LAST
263

264

OM 1263 • MICROTECH UNIT CONTROLLER 106 www.DaikinApplied.com


Appendix – Sample Wiring Diagrams: Rebel 3-15 Tons

Figure 32 continued: DPS005A, 208V with Gas Heat and Exhaust Fan
(160) (160)
301 120V_H 120V_N
HP1
PL4 PL4 R-HP1

NO NC
302 HP1-I NB HP1-I
160A 1 H C 2 303A 13 14 155A

(307)
(255)
303
MCB

(152)
304 R-CCH1

NO NC
T2-C1 DO1 T2-DO1B
160A 305A 13 14 155A
305

306 R-HP1 DO2


9 5 T3-C2 T3-DO2B
160A
307
(303)

308 308A 155A


T6-DI5 T6-R5-6

309

T3-C3 DO3 DO3


310

311

T3-C4 DO4 DO4


312

313
TB2 TB2 TB2
DO5 248 INV_COMP_RDY_STATUS 245C
314 245C 314A T4-C5-6 T4-D05 314B

315 DO6 T4-D06


316
TB2
240C T4-C7-8 DO7 T4-D07
317 317A

TB2 TB2
318 DO8 LOCAL_REMOTE_STATUS
T4-D08 240 240C
319A
319

320

321

322

323

324

HEAT1
325
POAF(FIELD) TB2 AHL
1 2
326 W
226
GAS_HEAT_ENABLE(FIELD) TB2 NB
327
R HEAT1GM-CI
328 226C PL19
GRN
G
3
329 HEAT1GM-CI
RED 1 WHT
L1 L2
330 TB2 ALARM_RESET(FIELD) TB2 EXPD PL19 2
160A 331A
DI1
HEAT1GM-CI
331 235 231 TB2 3
WHT
+
332 PL18
GAS_HEAT_CAP(FIELD) 222
TB2
333 BLK 4
-
X8-AO 222C TB8 MOD GAS
334 0-10VDC DRN301G
HEATER
T5-M2
NB
335

336
T5-X5
337
155A
R1
338

339

340

341

342

343

344

345

CBL345-I WHT
346 A1+ / (212)
BLK
B1- / (213)
347 DRN
GND1 / (214)
A2+ / (360)
348 EVBJMP-I
B2- / (361)
349 SPL1
GND2 / (362)
EVI EVI-I
350 ORG 1 5 WHT A4P
1 + - GND
RED 2 4 BLK 1 3 EVB/88A-I (112)
2 MOD A4/4-I
351 YEL 3 3 BRN RED 351E
X86A

3 X89A 1 1 1 1
EVI BLK RED
4 2
ACS3

ACS1
X88A

X4A

NB 4
352 GRY 5 1 GRN BLK 352B
5 EVB 2 2 2 2
(108)
353 IFB 255 256 X6A-2I
NB IFBA-I (354)
354B 255D (255) (257) WHT
(363) CHK1_24V 3 1
24VAC

16V
354
TN2

DIP SWITCH
355A BLK
X6A

ON K SD 24
(363) CHK1_N 1 GND 2
355 1234 DIP SWITCH
RED
2
3
356 (163) (163) 1234
T2B_N T2B_24V
IFN_MOTOR
357
IFN-CI NB
WHT 1
163B

163A

(212) / A1+
358 IFB-I BLK 2
(213) / B1-
CHK1 DRN
359 (214) / GND1
1 3 EXH_MOTOR
360 EXH-CI
WHT 1 NB
(348) / A2+
BLK 2
361 3 1 (349) / B2-
DRN
(349) / GND2
362
CHK1_24V / (354)
363
CHK1_N / (355)

364

www.DaikinApplied.com 107 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – Sample Wiring Diagrams: Rebel 3-15 Tons

Figure 32 continued: DPS005A, 208V with Gas Heat and Exhaust Fan

TB2

&D#10.TRILOB &D#10.TRILOB &D#10.TRILOB &D#10.TRILOB &D#10.TRILOB

NOTE:
Only wire to bottom of TB2,
top is for customer connection.

MCB aligned with wireway mounting hole

MMP51 MMP10 MMP1

BUSBAR EXPD
MCB
PC5 GFR1
GND2
TB8 TB1
SPD1
CHK 1
PB1 GND51 GND10
R-HP1
R-CCH1 LOAD
IFB

ACS3
Modbus

LOAD

PVM1 ACS2
ACS1
LINE Top View Mounted on
the side of the
T2A LINE
24V transformer panel

T2B
DS1

H
F1A F1B F1C
TB6 T2C
GLG1

T1

FOR HIGH VOLTAGE WIRING X


DO NOT RUN HIGH VOLTAGE
WIRES INSIDE WIRE TRACK

ID: Description: ID: Description:


4WV Four Way Valve MMP51 Manual Motor Protector, Exhaust Fan
WARNING/ ADVERTISSEMENT
A4P Compressor 1 Inverter MMP60 Manual Motor Protector, Energy Recovery Wheel
A4PF Compressor 1 Inverter Electrical Noise Filter MPB1 Contactor, Circuit 1 Dual Supply
A5P Outdoor Fan 1 Inverter OAE Enthalpy Sensor, Outside Air
A5P+ Outdoor Fan 2 Inverter OAER Relay, Outside Air Enthalpy
DANGER/WARNING A5PF Outdoor Fan Electrical Noise Filter OAT Temperature Sensor, Outside Air
LABEL TO BE LABELS TO BE SHIPPED ACT12 Actuator Motor, Heat Wheel OF1F Outdoor Fan Electrical Noise Filter 1
SHIPPED LOOSE LOOSE AND PLACED ACT3 Actuator Motor, Economizer OF2F Outdoor Fan Electrical Noise Filter 2
AND APPLIED TO ON OUTSIDE OF UNIT AHL Auxiliary High Limit ORT Outdoor Refrigerant Temperature Sensor
DANGER DOOR.
INNER DOOR OF CCH
CHV1
Crankcase Heater
Valve, Condenser Coil
PB1
PB2
Power Block, Power Distribution
Power Block 2,Circuit 2 Dual Supply
McQUAY'S UNIT. Comm Mod. Communication Module (BACnet, Lonworks, ...) PB1F Power Block Electrical Noise Filter
PLACE SOFTWARE D3 DIII-NET Communication Gateway PC5 Pressure Control, Dirty Filter Switch
LABEL IN AREA DAT Temperature Sensor, Discharge Air PC7 Pressure Control, Proof Airflow Switch
SHOWN ON LABEL. DFT Defrost Temperature Sensor PTD Discharge Refrigerant Pressure Sensor
DHL Duct Hi-limit, Switch PTS Suction Refrigerant Pressure Sensor

REC1 DRT1,3
DS1
Discharge Refrigerant Temperature Sensor
Disconnect Switch, Unit Power
PVM1
R63
Phase Voltage Monitor
Relay, Duct High Limit Switch
DS2 Disconnect Switch, Supply Fan / Circuit 2 RAE Enthalpy Sensor, Return Air
DS6 Disconnect Switch, Powered GFCI Receptacle RAT Temperature Sensor, Return Air
ECB1 Ebtron Control Board R-CCH1 Crankcase Heater Relay
RECEPTACLE TO EVB Expansion Valve Board REC1 Receptacle, GFCI
BE SHIPPED LOOSE EVBF Expansion Valve Board Electrical Noise Filter RES3,4 Resistor
EVI Indoor Expansion Valve RHB1 Reheat Board, Hot Gas
EVO Outdoor Expansion Valve R-HP1 High Pressure Compressor 1 Relay
EXPB,D Expansion Control Board RHV1 Valve, Reheat Coil
F1A,B Fuse, Control Circuit Transformer (T1), Primary SD1/SD2 Smoke Detector, Supply Air/Return Air
F1C,D Fuse, Control Circuit Transformer (T1), Secondary SHS1 Space Humidity Sensor
F4A,B,C Fuse, 460V 3-Phase Transformer (T4), Primary SPD Surge Protective Device
F6C Fuse, Powered GFCI Transformer (T6), Secondary SPS1 Static Pressure Sensor, Duct
GFR1 Ground Fault Relay SPS2 Static Pressure Sensor, Building
HEAT1 Heater Module SRT Suction Refrigerant Temperature Sensor
HL Hi-Limit Switch, Gas Heat SVB Refrigerant Bypass Solenoid Valve
HP1,3 Hi-Pressure Switch, Refrigeration Circuits 1, 3 SVR Refrigerant Receiver Solenoid Valve
IFB Interface Board T1 Transformer, Main Control
IFBF Interface Board Electrical Noise Filter T12 575/460V Primary Power Transformer
IRT Indoor Refrigerant Temperature Sensor T1F Main Transformer Electrical Noise Filter
Field Wiring
LCT Temperature Sensor, Leaving Coil T2A,B Transformer, Control Input (115/24VAC)
LR1 Compressor Line Reactor T4 Transformer, 230V Single Phase (460/397VAC)
Factory Wiring M1F Compressor 1 Electrical Noise Filter T6 Transformer, Powered GFCI Receptacle (Line/115VAC)
M3 Contactor, Compressor 3 T7 Transformer, Reheat Control Board (115/24VAC)
Factory Terminal M60 Contactor, Constant Speed Recovery Wheel TB1 Terminal Block, Internal Power Distribution
MCB Main Control Board TB2 Terminal Block, Field -24V
Field Terminal MJ Mechanical Jumper TB8 Terminal Block, Internal Signal Distribution
MMP1 Manual Motor Protector, A4P Board VFD60 Variable Frequency Drive, Energy Recovery Wheel
MMP10 Manual Motor Protector, Supply Fan
Plug Connection MMP3 Manual Motor Protector, Compressor 3

OM 1263 • MICROTECH UNIT CONTROLLER 108 www.DaikinApplied.com


Appendix – Sample Wiring Diagrams: Rebel 16-28 Tons

Appendix – Sample Wiring Diagrams: Rebel 16-28 Tons

Figure 33: DPS020A, 208V with Hot Water Heat

www.DaikinApplied.com 109 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – Sample Wiring Diagrams: Rebel 16-28 Tons

Figure 33 continued: DPS020A, 208V with Hot Water Heat

OM 1263 • MICROTECH UNIT CONTROLLER 110 www.DaikinApplied.com


Appendix – Sample Wiring Diagrams: Rebel 16-28 Tons

Figure 33 continued: DPS020A, 208V with Hot Water Heat

www.DaikinApplied.com 111 OM 1263 • MICROTECH UNIT CONTROLLER


Appendix – Sample Wiring Diagrams: Rebel 16-28 Tons

Figure 33 continued: DPS020A, 208V with Hot Water Heat

OM 1263 • MICROTECH UNIT CONTROLLER 112 www.DaikinApplied.com


Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com
and click on Training, or call 540-248-9646 and ask for the Training Department.

Warranty

All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied Representative for warranty details. To find your
local Daikin Applied Representative, go to www.DaikinApplied.com.

Aftermarket Services

To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.

Products manufactured in an ISO Certified Facility.

OM 1263 (06/18) ©2018 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com

You might also like