Innovair Prestige Inverter Service Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 120

SERVICE MANUAL

SERVICE MANUAL

Table of Contents

Part Ⅰ : Technical Information........................................................................1


1. Summary.......................................................................................................................1
2. Specifications...........................................................................................................3
2.1 Specification Sheet............................................................................................................3
2.2 Operation Characteristic Curve.......................................................................................13
2.3 Capacity Variation Ratio According to Temperature........................................................13
2.4 Cooling and Heating Data Sheet in Rated Frequency....................................................14
2.5 Noise Curve.....................................................................................................................14
3. Outline Dimension Diagram.......................................................................15
3.1 Indoor Unit.......................................................................................................................15
3.2 Outdoor Unit....................................................................................................................16
4. Refrigerant System Diagram.....................................................................17
5. Electrical Part.........................................................................................................19
5.1 Wiring Diagram................................................................................................................19
5.2 PCB Printed Diagram......................................................................................................23
6. Function and Control.......................................................................................26
6.1 Remote Controller Introduction of YV1FB7F...................................................................26
6.2 Remote Controller Introduction of YAN1F1F...................................................................30
6.3 Operation of Smart Control (Smart Phone, Tablet PC) For Gree....................................34
6.4 Operation of Smart Control (Smart Phone, Tablet PC) ..................................................47
6.5 Brief Description of Modes and Functions.......................................................................60

Part Ⅱ : Installation and Maintenance ..................................................69


7. Notes for Installation and Maintenance...........................................69
8. Installation.................................................................................................................72
8.1 Installation Dimension Diagram.......................................................................................72
8.2 Installation Parts-checking .............................................................................................74
8.3 Selection of Installation Location.....................................................................................74
8.4 Requirements for Electric Connection ............................................................................74
8.5 Installation of Indoor Unit.................................................................................................74
8.6 Installation of Outdoor Unit..............................................................................................77
8.7 Vacuum Pumping and Leak Detection............................................................................78
8.8 Check after Installation and Test Operation....................................................................78

w w w . i n n o v a i r . c o m
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

9. Maintenance.............................................................................................................79
9.1 Error Code List................................................................................................................79
9.2 Troubleshooting for Main Malfunction.............................................................................80
9.3 Troubleshooting for Normal Malfunction..........................................................................95
10. Exploded View and Parts List...............................................................97
10.1 Indoor Unit.....................................................................................................................97
10.2 Outdoor Unit................................................................................................................ 112
11. Removal Procedure......................................................................................121
11.1 Removal Procedure of Indoor Unit..............................................................................121
11.2 Removal Procedure of Outdoor Unit...........................................................................126

Appendix:.......................................................................................................................131
Appendix 1: Reference Sheet of Celsius and Fahrenheit...................................................131
Appendix 2: Configuration of Connection Pipe....................................................................131
Appendix 3: Pipe Expanding Method..................................................................................132
Appendix 4: List of Resistance for Temperature Sensor.....................................................133
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Outline Dimension Diagram

Indoor Unit for KIN310C2V31, KIN413C2V31

W D

6 5/8 18 3/16 6 5/16


09K

Φ2 3/16 Φ2 3/16

2 1/8 2 1/8
6 3 1/2

4 11/16 21 5/16 7 1/4

12K

Φ2 3/16 Φ2 3/16

1 3/8 1 3/8
5 3 5/16

Unit:inch
MODEL W H D
09K 31 1/8 10 7/8 7 7/8
12K 33 1/4 11 3/8 8 1/4

w w w . i n n o v a i r . c o m 1
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Outdoor Unit for KIN310C2V31, KIN413C2V31

10 1/8 28
21 1/4

12 5/8 30 9/16

11 1/4
Unit:inch
20

2
SERVICE MANUAL

Indoor Unit for KIN321C2V31, KIN824C2V31

W D

H
4 27 7 3/16
18K

Φ2 3/16 Φ2 3/16

1 1/2
7 1/2 5 1/2

8 1/8 27 7 5/16

24K
Φ2 3/4 Φ2 3/4

1 11/16

6 3 1/8
Unit:inch

Models W H D
18K 38 3/16 11 13/16 8 13/16
24K 42 7/16 12 13/16 9 11/16

w w w . i n n o v a i r . c o m 3
SERVICE MANUAL

Outdoor Unit for KIN321C2V31, KIN824C2V31

13 3/8 35

27 9/16
38 15 5/8

22

14 5/16
Unit: inch

4
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Refrigerant System Diagram


KIN310C2V31 , KIN413C2V31

Indoor unit Outdoor unit

Gas pipe
side
Valve

Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compressor Heat
exchanger
(condenser)
Liquid pipe
side
Valve Electron Strainer
expansion
valve

COOLING

Connection pipe specification:


Liquid pipe:1/4"
Gas pipe:3/8"

w w w . i n n o v a i r . c o m 5
SERVICE MANUAL

KIN321C2V31, KIN824C2V31

Indoor unit Outdoor unit

Gas pipe
side
Valv
e

Discharge
Heat
exchanger
(evaporator) Suction Accumlator
Compresso Heat
r exchanger
(condenser)
Liquid pipe
side
Valv Electron
e Strainer
expansion
valve

COOLING

Connection pipe specification:


Liquid pipe:1/4"
Gas pipe:1/2" for 18K
Gas pipe:5/8" for 24K

6
SERVICE MANUAL

Electrical Part
Wiring Diagram

● Instruction

Symbol Symbol Color Symbol Symbol Color Symbol Name


WH White GN Green CAP Jumper cap
YE Yellow BN Brown COMP Compressor
RD Red BU Blue Grounding wire
YEGN Yellow/Green BK Black / /
VT Violet OG Orange / /

Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.

● Indoor Unit for KIN310C2V31 , KIN413C2V31

:,5('
7(036(1625

7(036(1625

&21752//(5
5(&(,9(5$1' $3
5220

78%(

',63/$<%2$5'
$3
­ ­
&211(&725
57 57 7(50,1$/
%/2&.
%8 :+ %8
1 1 
287'22581,7

76(1625 ',63 ',63 &200$18$/


%. %.
&20287 
&$3
%1 5' %1
$30$,1%2$5' $&/ 
-803 <(*1 *1 <(*1

3*) 3* 6:,1*8' :,), ;7

<(*1
; (9$325$725 *
0
0
)$1 67(33,1* :,),02'8/( *
(/(&75,&%2;
02725 02725 237,21$/ 600007000575

w w w . i n n o v a i r . c o m 7
SERVICE MANUAL

● Outdoor Unit for KIN310C2V31, KIN413C2V31

:$51,1* (/(&7521,& 5($&725


28778%( 2875220 (;+$867 (;3$16,21
3OHDVHGRQ WWRXFKDQ\ 7(03 7(03 7(03 9$/9( /
WHUPLQDOZKHQWKHPDFKLQHLV 6(1625 6(1625 6(1625 :+ 2*

0$*1(7,&
UXQQLQJVWRSSLQJRUKDVEHHQ (.9 / /

5,1*
SRZHUHGRIIIRUOHVVWKDQ ­ ­ ­
PLQXWHVWRSUHYHQWWKHULVN 57 57 57
N N N
RIHOHFWULFVKRFN
/; /;
;7 0$*1(7,&5,1* &1 &1
,1'22581,7

:+ %8 %8 /
/ 1  1
%.

%. /
&208 $30DLQ%RDUG
5' %1 %1 /
/  $&/
*1 <(*1 <(*1 <(*1 3( 29&&203 2)$1
8 9 :
7(50,1$/ %8 <( 5'
:+ %8 %/2&.
/
0$*1(7,&

/ %. %1 ; 5' 5'
5,1*

*1 <(*1 (/(&75,&$/ / / /
32:(5 %2; * 0 <(*1
%8 <( 5' 6$7
9 *
8 :
<(*1 &203 )$1 02725 *
* 29(5/2$'
&203 3527(&725 127( 0RWRU
JURXQGRQO\
<(*1 0,',62/$7,21 DSSOLHVWRWKH
6+((7 * LURQVKHOOPRWRU
60000700092101

8
SERVICE MANUAL

● Indoor Unit for KIN321C2V31, KIN824C2V31

:,5('

7(036(1625

7(036(1625
&21752//(5
5(&(,9(5$1' $3
5220

78%(
',63/$<%2$5'
$3
­ ­
&211(&725
57 57 7(50,1$/
%/2&.
%8 :+ %8
1 1 

287'22581,7
76(1625 ',63 ',63 &200$18$/
%. %.
&20287 
&$3
%1 5' %1
$30$,1%2$5' $&/ 
-803 <(*1 *1 <(*1

3*) 3* 6:,1*8' :,), ;7

<(*1
; (9$325$725 *
0
0
)$1 67(33,1* :,),02'8/( *
(/(&75,&%2;
02725 02725 237,21$/ 600007000575

● Outdoor Unit for KIN321C2V31, KIN824C2V31

29(5/2$' 3527(&725
:$51,1* 3OHDVHGRQ WWRXFKDQ\WHUPLQDOZKHQ 6$7
7(036(1625

7(036(1625

7(036(1625

WKHYROWDJHRIWHUPLQDO3 '& DQG &203


8 &203 *
1 '& DW$3LVKLJKHUWKDQ9WR
28778%(

2875220

(;+$867

9 :
SUHYHQWWKHULVNRIHOHFWULFDOVKRFN 0$*1(7,& <(*1
5,1*
57 57 57 / / /
:+ :+
­ ­ ­ %8 <( 5' *
*1 <(*1 &211(&725 ;
7(50,1$/
* :+ %. %8 <( 5'
0$*1(7,&
,1'22581,7

%/2&.
:+ %8 5,1* 8 %8 9 <( : 5'
1
/
%. %. 7B6(1625 29&B&203
 &20B,11(5
5' %1 %8

%1 /
%. %1
/ %1
$&B/ $3
:+ %8 /
/ %8
*1 <(*1
*
1
35,17('&,5&8,7%2$5'
;7 <(*1
)$ 2)$1
*
3(

/ /

32:(5 0$*1(7,& /
5,1* 0 *
(.9 <(*1
<(*1

(/(&7521,& )$102725 *
(;3$16,21 1RWH0RWRUJURXQG
* 9$/9( RQO\DSSOLHVWRWKH
60000700023002 LURQVKHOOPRWRU

w w w . i n n o v a i r . c o m 9
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

PCB Printed Diagram


Indoor Unit for KIN310C2V31, KIN413C2V31, KIN321C2V31, KIN824C2V31
● Top view
3 4 5 6 7 8 9 10

No Name
Interface of communication wire for
1
indoor unit and outdoor unit
11 2 Interface of live wire
Interface of health function neutral
3
wire
4 Interface of neutral wire
16
5 Interface of fan
6 Interface of health function live wire
2
7 Jumper cap
8 Auto button
12 9 Up&down swing interface
1
10 Feedback interface of indoor unit
13 11 left&right swing interface
12 Interface of wifi
13 Interface of tube temperature sensor
14 14 Wired controller
15 Display interface
16 Fuse

15

● Bottom view

10
SERVICE MANUAL

Outdoor Unit for KIN310C2V31, KIN413C2V31

● Top view
3 4

Compressor UVW three phase


1
input interface
2 Interface of reactor
3 Interface of fan
4 4-way valve
5 Interface of earthing wire
6 Interface of live wire
7 Interface of netural wire
2
8 Interface of communication
Interface of electronic expansion
9
valve
Overload interface of
5 10
compressor
11 Interface of temperature sensor

6
7

8
1

11 10 9
● Bottom view

w w w . i n n o v a i r . c o m 11
SERVICE MANUAL

Outdoor Unit for KIN321C2V31, KIN824C2V31

● Top view

1 2 3 4 5 6 7 8 9 10

No. Name
Compressor three phase input
1
11 interface
Terminal of system high pressure
2
protection
Compressor overload protection
3
terminal
4 Interface of temperature sensor
Terminal of electronic expansion
5
valve
6 Terminal for low pressure protection
12 7 Interface of fan
13
8 4-way valve terminal
9 2-way valve terminal
14
10 Terminal of compressor electric heater
11 Terminal of chassis electric heater
12 Live wire
13 Communication wire
14 Grounding wire
15
15 Neutral wire

● Bottom view

12
SERVICE MANUAL

Function and Control


Remote Controller Introduction of Prestige

1 ON/OFF button

2 MODE button
WIFI

3 FAN button

4 SWING button
1
3 5 TURBO button
2
5 6 ▲/ button

4
6
7 7 SLEEP button
8
9 8 TEMP button
11 10
9 I FEEL button

12 10 LIGHT button

11 CLOCK button

TIMER ON / TIMER OFF


12
button

Introduction for icons on display screen

I feel Set fan speed


Operation mode Send signal
Turbo mode
Auto mode
8℃ heating function
Cool mode
Set temperature
Dry mode
WIFI
Fan mode WIFI

Heat mode Set time


TIMER ON / TIMER OFF
Clock
Sleep mode Child lock
Light Up & down swing
Temp. display type
:Set temp. :Indoor ambient temp.
:Outdoor ambient temp.

Introduction for buttons on remote controller


Note:
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the
model doesnt have, if press the corresponding button on the remote controller that the unit will keep the original running status.
● After putting through the power, the air conditioner will give out a sound. Operation indictor " " is ON (red indicator). After that,
you can operate the air conditioner by using remote controller.
● Under on status, pressing the button on the remote controller, the signal icon " "on the display of remote controller will blink once
and the air conditioner will give out a “de” sound, which means the signal has been sent to the air conditioner.
● Under off status, set temperature and clock icon will be displayed on the display
of remote controller (If timer on, timer off and light functions are set, the corre- sponding icons will be displayed on the display of
remote controller at the same time); Under on status, the display will show the corresponding set function icons.

w w w . i n n o v a i r . c o m 13
SERVICE MANUAL

1. ON/OFF button
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, operation indicator " "on indoor units
display is ON (green indicator. The colour is different for different models), and indoor unit will give out a sound.

2. MODE button
Press this button to select your required operation mode.

AUTO COOL DRY FAN HEAT

● When selecting auto mode, air conditioner will operate automatically according to ex-factory setting. Set temperature cant be adjusted and
will not be displayed as well. Press "FAN" button can adjust fan speed. Press "SWING" button can adjust fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " "on indoor unit is ON. Press "▲" or " " button

to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON. Under dry
mode, fan speed cant be adjusted. Press "SWING" button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. All indicators are OFF. Press "FAN" button to
adjust fan speed. Press "SWING" button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode. Heat indicator " " on indoor unit is ON. Press "▲" or " "

button to adjust set temperature. Press "FAN" button to adjust fan speed. Press "SWING" button to adjust fan blowing angle. (Cooling only
unit wont receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button cant start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor
ambient temperature).
● Set temperature range from remote controller: 16~30℃ (60.8~86.0OF); Fan speed: auto, low speed, medium speed, high speed.

3. FAN button
Pressing this button can set fan speed circularly as: auto (AUTO), low( ) ,medium( ), high( ).

Auto

Caution:
● Under AUTO speed, air conditioner will select proper fan speed automatically according to ex-factory setting.
● Fan speed under dry mode is low speed.
4. SWING button
Press this button can select up&down swing angle. Fan blow angle can be selected circularly as below:

no display
(horizontal louvers stops at current position)

● When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
● When selecting " 、 、 、 、 ", air conditioner is blowing fan at fixed position. Horizontal louver will stop at the fixed position.
● When selecting " 、 、 " , air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
● Hold " "button above 2s to set your required swing angle. When reaching your required angle, release the button.
Note:
● " 、 、 " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically.

5. TURBO button
Under COOL or HEAT mode, press this button to turn to quick COOL or quick HEAT mode. " " icon is displayed on remote controller.
Press this button again to exit turbo function and " " icon will disappear.

6. ▲/ button

● Press "▲" or " " button once increase or decrease set temperature 1℃ (33.8OF). Holding "▲" or " " button, 2s later, set temperature
▲ ▲

on remote controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change
accordingly. (Temperature cant be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons) When setting TIMER ON, TIMER OFF or CLOCK, press "▲" or "▲" button to adjust time. (Refer to CLOCK, TIMER ON, TIMER
OFF buttons)

14
SERVICE MANUAL

7. SLEEP button
Under COOL, HEAT or DRY mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this button
again to cancel sleep function and " " icon will disappear.

8. TEMP button
By pressing this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor units
display. The setting on remote controlleris selected circularly as below:

no display

● When selecting " " or no display with remote controller, temperature indicator on indoor unit displays set temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambient temperature.
● When selecting " " with remote controller, temperature indicator on indoor unit displays outdoor ambient temperature.
Note:
● Outdoor temperature display is not available for some models. At that time, indoor unit receives " "signal, while it displays indoor set
temperature.
● Its defaulted to display set temperature when turning on the unit.There is no display in the remote controller.
● Only for the models whose indoor unit has dual-8 display.
● When selecting displaying of indoor or outdoor ambient temperature, indoor temperature indicator displays corresponding temperature and
automatically turn to display set temperature after three or five seconds.

9. I FEEL button
Press this button to start I FEEL function and " " will be displayed on the remote controller. After this function is set, the remote controller
will send the detected ambient temperature to the controller and the unit will automatically adjust the indoor temperature according to the
detected temperature. Press this button again to close I FEEL function and " " will disappear.
● Please put the remote controller near user when this function is set. Do not put the remote controller near the object of high temperature
or low temperature in order to avoid detecting inaccurate ambient temperature.
10. LIGHT button
Press this button to turn off display light on indoor unit. " " icon on remote controller disappears. Press this button again to turn on
display light. " " icon is displayed.

11. CLOCK button


Press this button to set clock time. " " icon on remote controller will blink. Press "▲" or " " button within 5s to set clock time. Each

pressing of "▲" or " " button, clock time will increase or decrease 1 minute. If hold "▲" or " " button, 2s later, time will change quickly.
▲ ▲

Release this button when reaching your required time. Press "CLOCK" button to confirm the time. " " icon stops blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation cant exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER ON/TIMER
OFF is the same.

12. TIMER ON / TIMER OFF button


● TIMER ON button
"TIMER ON" button can set the time for timer on. After pressing this button, " " icon disappears and the word "ON" on remote controller
blinks. Press "▲" or " "button to adjust TIMER ON setting. After each pressing "▲" or " " button, TIMER ON setting will increase or
▲ ▲
decrease 1min. Hold "▲" or " " button, 2s later, the time will change quickly until reaching your required time. Press "TIMER ON" to

confirm it. The word "ON" will stop blinking. " " icon resumes displaying. Cancel TIMER ON: Under the condition that TIMER ON is
started up, press "TIMER ON" button to cancel it.
● TIMER OFF button
"TIMER OFF" button can set the time for timer off. After pressing this button," " icon disappears and the word "OFF" on remote
controller blinks. Press "▲" or " " button to adjust TIMER OFF setting. After each pressing "▲" or " " button,
▲ ▲
TIMER OFF setting will increase or decrease 1min. Hold "▲" or " " button, 2s later, the time will change quickly until reaching your

required time. Press "TIMER OFF" word "OFF" will stop blinking. " " icon resumes displaying. Cancel TIMER OFF. Under the condition
that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
Note:
● Under on and off status, you can set TIMER OFF or TIMER ON simultaneously.
● Before setting TIMER ON or TIMER OFF, please adjust the clock time.
● After starting up TIMER ON or TIMER OFF, set the constant circulating valid. After that, air conditioner will be turned on or turned off
according to setting time. ON/OFF button has no effect on setting. If you dont need this function, please use remote controller to cancel it.

w w w . i n n o v a i r . c o m 15
SERVICE MANUAL

Function introduction for combination buttons


1. Energy-saving function
Under cooling mode, press "TEMP" and " CLOCK" buttons simultaneously to start up or turn off energy-saving function. When energy-saving
function is started up, "SE" will be shown on remote controller, and air conditioner will adjust the set temperature automatically according to
ex-factory setting to reach to the best energy-saving effect. Press "TEMP" and "CLOCK"buttons simultaneously again to exit energy-saving
function.
Note:
● Under energy-saving function, fan speed is defaulted at auto speed and it cant be adjusted.
● Under energy-saving function, set temperature cant be adjusted. Press "TURBO" button and the remote controller wont send signal.
● Sleep function and energy-saving function cant operate at the same time. If energy-saving function has been set under cooling mode,
press sleep button will cancel energy-saving function. If sleep function has been set under cooling mode, start up the energy-saving
function will cancel sleep function.

2. 8 ℃ heating function
Under heating mode, press "TEMP" and "CLOCK" buttons simultaneously to start up or turn off 8℃ heating function. When this function is
started up, " " and "8℃ " will be shown on remote controller, and the air conditioner keep the heating status at 8℃ . Press "TEMP" and
"CLOCK" buttons simultaneously again to exit 8℃ heating function.
Note:
● Under 8℃ heating function, fan speed is defaulted at auto speed and it cant be adjusted.
● Under 8℃ heating function, set temperature cant be adjusted. Press "TURBO" button and the remote controller wont send signal.
● Sleep function and 8℃ heating function cant operate at the same time. If 8℃ heating function has been set under cooling mode, press
sleep button will cancel 8℃ heating function. If sleep function has been set under cooling mode, start up the 8℃ heating function will
cancel sleep function.
● Under ℉ temperature display, the remote controller will display 46 ℉ heating.

3. Child lock function


Press "▲" and " " simultaneously to turn on or turn off child lock function. When child lock function is on, " " icon is displayed on remote

controller. If you operate the remote controller, the " " icon will blink three times without sending signal to the unit.

4. Temperature display switchover function


Under OFF status, press " " and "MODE" buttons simultaneously to switch temperature display between ℃ and ℉ .

5. WIFI fuction
Under ON status, press "Mode" and "Turbo" button simultaneously,the "WiFi" icon will be displayed on remote controller.
press "Mode"and"Turbo" button simultaneously,the "WiFi" icon will disppear.

Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN, HEAT.
3. Press "▲" or " " button to set your required temperature. (Temperature cant be adjusted under auto mode).

4. Press "FAN" button to set your required fan speed: auto, low, medium and high speed.
5. Press "SWING" button to select fan blowing angle.

Replacement of batteries in remote controller

1. Press the back side of remote controller marked with " ", as shown in the fig, and then push signal sender battery
out the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar reinstall
are correct.
3. Reinstall the cover of battery box. remove

Note:
Cover of battery box
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp or wireless telephone; remote controller should be close to
indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you dont use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or theres no display, please replace batteries.

16
SERVICE MANUAL

Operation of Smart Control (Smart Phone, Tablet PC)


Operation Instructions
Download and install APP
Scan the following QR code with your smart phone and download Wifi Smart.

Install the APP according to its guidance. When successfully installed, your smart phone homepage will show this icon
User of IOS system can search for the Wifi Smart in Apple store to download the Apple version APP. Android user can search "WiFi
Smart" on Google Play to download it.
Configuration
NOTE: Select either the original configuration or AP configuration according to the APP functions.
1.Original configuration
Before operation, please finish the following configuration in order to realize Wifi control and the connection between air conditioner and
intelligent device.
(1).Short-distance control setting for air conditioner using wifi hotspot
Step 1: Air conditioner wifi is set in APP mode in factory.
You can search the air conditioner wifi hotspot through your smart phone.The name of wifi hotspot is the last 8 numbers of the air
conditioner mac address. Password is 12345678.

gree-a

gr-cn

gr-cn gr-dh

Step 2: Open APP and the screen will show the air conditioner that you just connected. Tap the name of this air conditioner on your
phone to enter and realize short-distance control, as shown below. Please refer to "Functions introduction" for specific control methods.

NOTE:One AC can be controlled by 4 cell phone in maximun at the same time.

w w w . i n n o v a i r . c o m 17
SERVICE MANUAL
2.Configuration method for Android phones 4 steps of configuration
Step 1: Enter homepage "Device", and then tap at the top right corner.
Select "Add device" and enter the page "Add device".
Tap "Manual configuration" and enter the page "Manual configuration".

Step 2: Tap "Next" in the First Step.

Step 3: Select the wireless network of air conditioner. APP will show the password 12345678 (default password of the network of air
conditioner). Then tap "Next"; select the name of home WiFi router, then enter the correct password and select a server.

Step 4: If configuration is successful, a window will pop up and read “WIFI module starts to connect the configured wireless router”.Then
configuration is completed.

18
SERVICE MANUAL
NOTE: After configuration is completed, the air conditioner hot spot connected to your phone will disappear. You should reconnect your
phone to the home WiFi router to realize long-distance control.The above configuration only needs onephone. Other types of phones
shall install this APP, connect with the air conditioner hot spot or wireless router of WiFi air conditioner. When connection is done, open
the APP to use short-distance operation to control the air conditioner and then you can use the long-distance control.
3.Configuration method for Apple phones
Step 1: Turn on Wi-Fi “Settings” on the phone.

Step 2: In general, the hot spot signal of air conditioner is the last 8 bits of MAC address. Eg: Select “a0b41737” and enter
the defaulted password “12345678” to connect it.

Step 3: Turn on APP, press “+” button, press “Add device” to enter into the page of “Add device” and then select “Manual configuration”.
Enter wireless router’s SSID and PSW on the page of “Manual configuration”. The display on the server will be the same as the selection
when registering the account ( server selection in “Setting”).
Eg: WiFi name: Tenda_XXX;
WiFi password:123456789
Server: Europe
Check whether the filled information is correct. If the information is wrong, configuration will fail. Press “Configuration” to start
configuration.

Notice:
Finally, press “Configuration”, and APP will send the filled information to Wifi Smart. At this time, the buzzer will give out a sound, which
indicates it has started to connect the wireless router.

w w w . i n n o v a i r . c o m 19
SERVICE MANUAL

If the name of router or the password is wrong, Wifi Smart can’t connect to the wireless router. 2 mins later, please conduct the
configuration operation again. starts to connect the wireless router.
Wrong server selection will cause long-distance control invalid. Therefore, please make sure thatthe server selection when registering
the account is the same as this one.
If the password is blank, no password is defaulted for the wireless router, which is the OPEN mode.
Configuration should be conducted at one time. As for other phones, they can automatically search for the device after connecting to the
wireless router (such as Tenda_XXX) and turning on the APP.

Functions introduction

1.User registration
Purpose: To realize long-distance control.
Operation instruction: For the first time login, you have to register a new username. If you already have a username, skip the registration
step and enter email address and password on the "Login Page" to log in. If password is forgotton, you can reset the password.
Operation steps:
(1) Select the sever address.

(2) Account login: Slide the page "Device", and enter the menu page on the left.Tap "Login" to enter the page "Register username". New
user must first register a username. Tap "Register”.

(3) If password is forgotten, you can reset the password with your email address.
Tap "Forgot password" and enter the page "Forgot password". Enter your registered email account the first. Tap "Get verification code" to
get an email verification code. Enter a new password and tap "OK" to log in.

20
SERVICE MANUAL
2.Personal settings
Purpose: Set name (device name, preset name, etc.) and images (device image) in order to identify a user easily.
(1) Set device name
After quick configuration, a list of controllable smart devices will be generated. Default name for air conditioner is the last 8 numbers of
the air condtioner mac address.

Step 1: Tap and hold the Wifi model name, such as “a0b417ac”, to enter the page "Edit device". Tap "Image" to select the source of
image. Select from "Default images " or " Take photo" or "Choose from photos" and save an image.

Step 2: Tap "Name" to change device name. Save it and the new device name will be shown. Enable button ''Lock device''to lock the
device so that other smart phones can’t search the device. Tap "Temperature unit" to change the temperature unit.

Step 3: Tap "Firmware updated" to upgrade the Firmware of the device, Tap"1.7" the device will upgraded auto.

w w w . i n n o v a i r . c o m 21
SERVICE MANUAL

(2) Set preset name


Step 1: Tap at the top right corner of the homepage "Device". Select "Add preset" and enter the page "Preset edit".

Step 2: Choose the time. Tap "Name". As shown in the picture, its name is "baby room". For timer type, select "On". Then select the
repeating days. Save the setting of preset name.

(3) Set device image


Please refer to step 1 in 2(1)
3.Control functions
(1) Common control functions: General control on the operation of smart devices (On/Off, temperature, fan speed, mode, etc.) and the
setting of advanced functions (air exchange, dry, health, light, sleep, energy saving upper limit).
Step 1: General control
Enter the homepage "Device" first. Take "babyroom" as an example.

22
SERVICE MANUAL

Tap "babyroom" and enter the page of air conditioner control. Tap to turn on the control switch.

Tap or to increase or decrease temperature. Tap to change working mode. Tap to enter the page of fan speed
adjustment.

Tap and go around the circle to adjust fan speed.

Step 2: Advanced settings


Tap to enter advanced settings. You may select "Air", "Dry", "Health", "Light", "Sleep" or "Energy saving".

(2) Advanced control functions; Set scene; Preset; Link: Infrared control(only applicable to smart phones with infrared emitter)
Set scene: Preset the operation of several smart devices by one tap. On the page "Device", tap the image of "Device" to enter the page
"Edit scene".

Tap "Add scene" and edit the scene name, for example, "Back home". Add execution devices.
Tap to add commands. On the page "Select execution device", select the air conditioner named "babyroom". Then select "ON" or
"OFF".

w w w . i n n o v a i r . c o m 23
SERVICE MANUAL

Continue to select the next execution device as instructed above. Tap to set the interval.

Tap "Save". Tap the scene picture displayed on homepage "Device" to send the command. Then the scene "Back home"
will be in execution. You may view the execution condition of the scene.

(3) Preset includes single-device preset and multi-device preset


Single-device preset: This can preset a certain device to be On/Off at a specific time.
On the homepage "Device", take air conditioner "babyroom" as an example. Tap at the bottom of the page "babyroom".
Then you will enter the page "Preset edit".

Slide up and down to set the time. If you need to synchronize the time, tap " synchronize". IIf such "Hint" interface hasn’t appeared,
please skip this operation procedure.

24
SERVICE MANUAL
Tap "Name" to customize the preset name.
Preset device can’t be selected and it will default to "babyroom". Select "On" for the timer type. Select repeating days to complete the
preset.

Multi-device preset: This can preset multiple devices to execute a command at a specific time.
Please refer to the instructions as how to set preset time, name, timer type and repeating days for a single device.
Tap "Preset device" to select one or more devices. Then return to the page "Device".

(4) Link(This function is applicable to some models)


Select a master device. When the environment satisfies the parameters as set in the master device, slave devices will execute
commands to realize devices linkage.
Step 1: Set the parameters of master device (Select master device, select environment parameters, select master device status).
Tap at the top right corner of the homepage "Device". Select "Link" and enter the page "Add linkage". Tap "Device/Param" to enter
the page "Select device". Take "baby room" as an example. Tap "babyroom".

Enter the page "Select environment parameters".

w w w . i n n o v a i r . c o m 25
SERVICE MANUAL

Tap "Temperature" to enter the page "Select temperature parameter". Slide up or down to adjust temperature. Tap "Upper limit" or "Lower
limit".
Tap "Mode" and "On/Off" to select the status of master device. Then tap "Save".

Step 2: Set time parameter for linkage. Tap "Time parameter" to enter the page "Set time". Slide rightwards to turn on the setting
time.

Tap "Execution time"; then tap "Start" and "Stop" to set start time and stop time respectively. Tap "OK" at the top right corner to save the
setting.

Tap the days below "Repeat" to select the repeating days. Then tap "Save".

Step 3: Select "Execute command" Tap "Execute command" and enter the page "Select device".

26
SERVICE MANUAL

Tap the name of device that you want to control. Tap "ON" or "OFF" and then tap "Save" to complete the linkage.

Tap "Save" and then repeat the above steps to set linkage of several scenes.

4.Menu functions
Menu functions (Share, Set, History, Feedback)
(1) Share: To share quick configuration information and unit’s information, including local export and local import.
For local import, you just need to tap "Local import" and wait for the data download.
Local export
Step 1: Export local data to another smart phone.
Enter menu page on the left side and tap "Share" to enter the page "Share". Then tap "Local export".

w w w . i n n o v a i r . c o m 27
SERVICE MANUAL
Step 2: Another smart phone to be imported.
Tap the model name and wait for the download.

Notice:
This function requires that the two phones are of the same operating system. They are either Android phones or Apple phones,and are
connecting to the same wireless router.
(2) Backup: To keep backup of the quick configuration information and unit’s information, including backup to cloud and backup list on
the cloud.
Backup to cloud
Enter the menu page on the left and tap "Backup".

Tap "Backup to cloud" and then tap "Yes". Then wait for the data download.

Select "Backup list on the cloud". Then backup records will appear. Tap "Record" to download data and recover data to local unit.

28
SERVICE MANUAL

(3) Settings
User can set vibration, message alerts, server, updates, etc. The server setting here must be the same as the server setting in
"Configuration" mentioned before.
Otherwise, remote control will be invalid.

(4) Help
Please refer to “Help” of APP for the instruction of the latest functions.

w w w . i n n o v a i r . c o m 29
SERVICE MANUAL

Brief Description of Modes and Functions


● Indoor Unit

1.Basic function of system


(1)Cooling mode
(1) Under this mode, fan and swing operates at setting status. Temperature setting range is 60.8~86.0OF.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(2)Drying mode
(1) Under this mode, fan operates at low speed and swing operates at setting status. Temperature setting range is 60.8~86.0OF.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(3) Protection status is same as that under cooling mode.
(4) Sleep function is not available for drying mode.
(3)Heating mode
(1) Under this mode, Temperature setting range is 60.8~86.0OF.
(2) Working condition and process for heating mode:
When turn on the unit under heating mode, indoor unit enters into cold air prevention status. When the unit is stopped or at OFF status,
and indoor unit has been started up just now, the unit enters into residual heat-blowing status.
(4)Working method for AUTO mode:
1.Working condition and process for AUTO mode:
a.Under AUTO mode, standard heating Tpreset=68.0OF and standard cooling Tpreset=77.0OF. The unit will switch mode automatically
according to ambient temperature.
2.Protection function
a. During cooling operation, protection function is same as that under cooling mode.
b. During heating operation, protection function is same as that under heating mode.
3. Display: Set temperature is the set value under each condition. Ambient temperature is (Tamb.-Tcompensation) for heat pump unit
and Tamb. for cooling only unit.
4. If theres I feel function, Tcompensation is 0. Others are same as above.
(5)Fan mode
Under this mode, indoor fan operates at set fan speed. Compressor, outdoor fan, 4-way valve and electric heating tube stop operation.
Indoor fan can select to operate at high, medium, low or auto fan speed. Temperature setting range is 60.8~86.0OF.

2. Other control
(1) Buzzer
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(2) Auto button
If press this auto button when turning off the unit, the complete unit will operate at auto mode. Indoor fan operates at auto fan speed
and swing function is turned on. Press this auto button at ON status to turn off the unit.
(3) Auto fan
Heating mode: During auto heating mode or normal heating ode, auto fan speed will adjust the fan speed automatically according to
ambient temperature and set temperature.
(4) Sleep
After setting sleep function for a period of time, system will adjust set temperature automatically.
(5) Timer function:
General timer and clock timer functions are compatible by equipping remote controller with different functions.
(6) Memory function
memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, set fan speed, general timer (clock timer cant be memorized).
After power recovery, the unit will be turned on automatically according to memory content.
(7) Health function
During operation of indoor fan, set health function by remote controller. Turn off the unit will also turn off health function.
Turn on the unit by pressing auto button, and the health is defaulted ON.

30
SERVICE MANUAL

(8)I feel control mode


After controller received I feel control signal and ambient temperature sent by remote controller, controller will work according to the ambient
temperature sent by remote controller.
(9)Compulsory defrosting function
(1) Start up compulsory defrosting function
Under ON status, set heating mode with remote controller and adjust the temperature to 60.8OF. Press “+, -, +, -, +,-” button successively
within 5s and the complete unit will enter into compulsory defrosting status. Meanwhile, heating indicator on indoor unit will ON 10s and OFF
0.5s successively. (Note: If complete unit has malfunction or stops operation due to protection, compulsory defrosting function can be started
up after malfunction or protection is resumed.
(2) Exit compulsory defrosting mode
After compulsory defrosting is started up, the complete unit will exit defrosting operation according to the actual defrosting result, and the
complete unit will resume normal heating operation.
(10)Refrigerant recovery function:
(1) Enter refrigerant recycling function
Within 5min after energizing (unit ON or OFF status is ok), continuously press LIGHT button for 3 times within 3s to enter refrigerant
recycling mode; Fo is displayed and refrigerant recycling function is started. At this moment, the maintenance people closes liquid valve.
After 5min, stick the thimble of maintenance valve with a tool. If there is no refrigerant spraying out, close the gas valve immediately and
then turn off the unit to remove the connection pipe.
(2) Exit refrigerant recycling function
After entering refrigerant recycling mode, when receive any remote control signal or enter refrigerant recycling mode for 25min, the unit will
exit refrigerant recycling mode automatically If the unit is in standby mode before refrigerant recycling, it will be still in standby mode after
finishing refrigerant recycling; if the unit is in ON status before refrigerant recycling, it will still run in original operation mode.
(11)Ambient temperature display control mode
1. When user set the remote controller to display set temperature (corresponding remote control code: 01), current set temperature will be
displayed.
2. Only when remote control signal is switched to indoor ambient temperature display status (corresponding remote control code: 10) from
other display status (corresponding remote control code: 00, 01,11),controller will display indoor ambient temperature for 3s and then turn
back to display set temperature.
Under this mode, indoor fan operates at set fan speed. Compressor, outdoor fan, 4-way valve and electric heating tube stop operation.
Indoor fan can select to operate at high, medium, low or auto fan speed. Temperature setting range is 60.8~86.0OF.
(12)Off-peak energization function:
Adjust compressors minimum stop time. The original minimum stop time is 180s and then we change to:
The time interval between two start-ups of compressor cant be less than 180+T s(0≤T≤15). T is the variable of controller. Thats to say
the minimum stop time of compressor is 180s~195s. Read-in T into memory chip when refurbish the memory chip each time. After power
recovery, compressor can only be started up after 180+T s at least.
(13) SE control mode
The unit operates at SE status.
(14) X-fan mode
When X-fan function is turned on, after turn off the unit, indoor fan will still operate at low speed for 2min and then the complete unit will be
turned off. When x-fan function is turned off, after turn off the unit, the complete unit will be turned off directly.
(15) 8º heating function
Under heating mode, you can set 8º heating function by remote controller. The system will operate at 8ºset temperature.
(16) Turbo fan control function
Set turbo function under cooling or heating mode to enter into turbo fan speed. Press fan speed button to cancel turbo wind.
No turbo function under auto, dry or fan mode.

w w w . i n n o v a i r . c o m 31
SERVICE MANUAL

Outdoor Units
1. Input Parameter Compensation and Calibration
(1) Check the ambient temperature compensation function Indoor ambient temperature compensation function.
a. In cooling mode, the indoor ambient temperature participating in computing control = (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature
compensation)

b. In heating mode, the indoor ambient temperature participating in computing control= (Tindoor ambient temperature – ⊿ Theating indoor ambient temperature
compensation)

(2) Check effective judgment controls of parameters


Effective judgment function of the outdoor exhaust temperature thermo-bulb When conditions a and b are satisfied, the outdoor exhaust
temperature thermo-bulb is judged not to be connected into place, the mainboard of outer units will display failure of the outdoor exhaust
temperature thermo-bulb (not connected into place), stop the machine for repairing, and resume the machine by remote controls of ON/
OFF.
a. Judgment of exhaust detection temperature change:
After the compressor starts up and runs for 10 minutes, if the compressor frequency f ≥ 40Hz, and the rising value Texhaust (Texhaust (after start-
up for 10 minutes) - Texhaust (before start-up)) <35.6ºF , the outdoor exhaust temperature thermo-bulb can be judged not to be connected into place (judging

once when the power is on the first time).


b. Comparative judgment of exhaust detection temperature and condenser detection temperature (Tpipe temperature = Toutdoor pipe temperature in cooling
mode, Tpipe temperature = Tindoor pipe temperature in heating mode): After the compressor starts up and runs for 10 minutes, if the compressor frequency f ≥

40Hz, and Tpipe temperature ≥(Texhaust+37.4), the outdoor exhaust temperature thermobulb can be judged not to be connected into place (judging
once when power is on the first time).
2. Basic Functions
(1) Cooling Mode
1. Conditions and processes of cooling operation:
(1) If the compressor is shut down, and [Tsetup – (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature compensation)] ≤ 32.9ºF , start up the
machine for cooling, the cooling operation will start;
(2) During operations of cooling, if 32ºF ≤ [Tsetup – (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature compensation)] < 35.6ºF , the cooling
operation will be still running;
(3) During operations of cooling, if 35.6ºF ≤ [Tsetup – (Tindoor ambient temperature – ⊿ Tcooling indoor ambient temperature compensation)], the cooling operation
will stop after reaching the temperature point.
2. Temperature setting range
(1) If Toutdoor ambient temperature ≥ [Tlow-temperature cooling temperature], the temperature can be set at: 60.8~86ºF (Cooling at room temperature);
(2) If Toutdoor ambient temperature < [Tlow-temperature cooling temperature], the temperature can be set at: 77~86ºF (Cooling at low temperature), that is, the
minimum setting temperature for outer units judgment is 77ºF .
(2) Dehumidifying Mode
1. Conditions and processes of dehumidifying operations: Same as the cooling mode;
2. The temperature setting range is: 60.8~86ºF;
(3) Air-supplying Mode
1. The compressor, outdoor fans and four-way valves are switched off;
2. The temperature setting range is: 60.8~86ºF.
(4) Heating Mode
1. Conditions and processes of heating operations: (Tindoor ambient temperature is the actual detection temperature of indoor environment
thermo-bulb, Theating indoor ambient temperature compensation is the indoor ambient temperature compensation during heating
operations)
(1) If the compressor is shut down, and [(Tindoor ambient temperature – ⊿ Theating indoor ambient temperature compensation) –Tsetup] ≤ 32.9ºF , start the machine
to enter into heating operations for heating;
(2) During operations of heating, if 32ºF ≤ [(Tindoor ambient temperature – ⊿ Theating indoor ambient temperature compensation) –Tsetup] < 35.6ºF , the heating
operation will be still running;
(3) During operations of heating, if 35.6ºF ≤ [(Tindoor ambient temperature – ⊿ Theating indoor ambient temperature compensation) –Tsetup], the heating operation
will stop after reaching the temperature point.
2. The temperature setting range in this mode is: 60.8~86ºF .

32
SERVICE MANUAL

3. Special Functions
Defrosting Control
① Conditions for starting defrosting
After the time for defrosting is judged to be satisfied, if the temperature for defrosting is satisfied after detections for continuous 3minutes,
the defrosting operation will start.
② Conditions of finishing defrosting
The defrosting operation can exit when any of the conditions below is satisfied:
③ Toutdoor pipe temperature ≥ (Toutdoor ambient temperature – [Ttemperature 1 of finishing defrosting];
④ The continuous running time of defrosting reaches [tmax. defrosting time].
4. Control Logic
(1) Compressor Control
Start the compressor after starting cooling, heating, dehumidifying operations, and the outer fans start for 5s; When the machine is
shutdown, in safety stops and when switching to air-supplying mode, the compressor will stop immediately. In all modes: once the
compressor starts up, it will not be allowed to stop until having run for the [tmin. compressor running time] (Note: including cases of
shutdown when the temperature point is reached; except the cases requiring stopping the compressor such as fault protection, remote
shutdown, mode switching etc.); In all modes: once the compressor stops, it will be allowed be restart after 3-minute delay (Note: The
indoor units have a function of power memory, the machine can be restarted after remote shutdown and powering up again without
delay).
1. Cooling mode
Start the machine to enter into cooling operation for cooling, the compressor is switched on.
2. Dehumidifying mode
Same as the cooling mode.
3. Air-supplying mode
The compressor is switched off.
4. Heating mode
(1) Start the machine to enter into heating operation for heating, the compressor is switched on.
(2) Defrosting:
a. Defrosting starts: the compressor is shut down, and restarts it after 55-second delay.
b. Defrosting ends: the compressor stops, then starts it after 55-second delay.
(2) Outer Fans Control
Notes:
Only the outer fans run for at least 80s in each air flow speed can the air flow be switched;
After the outer fans run compulsively in high speed for 80s when the machine starts up, control the air flow according to the logic.
After remote shutdown, safety stops, and when the machine stops after reaching the temperature point, as well as after the compressor
stops, extend 1 minute, the outer fans will stop (During the period in the 1 minute, the air flow of outer fans can be changed according to
the outdoor ambient temperature changes); When running with force, the outdoor fans shall run in the highest air flow.
(3) 4-way valve control
1. The 4-way valve control under the modes of Cooling, dehumidification and supplying air: closing;
2. The status of 4-way valve control under the heating mode: getting power;
(1) 4-way valve power control under heating mode
a. Starts the machine under heating mode, the 4-way valve will get power immediately.
(2) 4-way valve power turn-off control under heating mode
a. When you should turn off the power or switch to other mode under heating mode, the power of 4-way valve will be cut after 2 minutes
of the compressor stopped.
b. When all kinds of protection stops, the power of 4-way valve will be cut after delaying 4 minutes.
(3) Defrosting control under heating mode:
a. Defrosting begins: The power of 4-way valve will be cut after 50s of entering into the defrosting
compressor.
b. Defrosting stops: The 4-way valve will get power after 50s of exiting the defrosting compressor.
(4) Evaporator frozen-preventing protection function
At the mode of Cooling, dehumidifying:
Evaporator frozen-preventing protection function is allowed to begin after 6 min of starting the compressor.

w w w . i n n o v a i r . c o m 33
SERVICE MANUAL

1. Starting estimation:
After the compressor stopped working for 180s, if Tinner pipe> [Tfrozen-preventing frequency-limited temperature (the temperature of hysteresis is 35.6ºF )],
the machine is only allowed to start for operating, otherwise it should not be started, and should be stopped to treat according to the frozen-
preventing protection: Clear the trouble under the mode of power turn-off / heating, and the protection times are not counted.
2. Frequency limited
[Tfrozen-preventing normal speed frequency-reducing temperature] ≤[Tinner pipe T frozen-preventing frequency-limited temperature] , you should limit the frequency raising of
compressor.
3. Reducing frequency at normal speed:
If [Tfrozen-preventing high speed frequency-reducing temperature] ≤[Tinner pipe T frozen-preventing normal speed frequency-reducing temperature], you should adjust the compressor
frequency by reducing 8Hz/90s till the lower limit;
4. Reducing frequency at high speed:
If [Tfrozen-preventing power turn-off temperature] ≤T inner pipe [Tfrozen-preventing high speed frequency-reducing temperature] you should adjust the compressor frequency by
reducing 30Hz/90s till the lower limit;
5. Power turn-off:
If the Tinner pipe <[Tfrozen-preventing power turn-off temperature], then frozen-preventing protect to stop the machine; If T[frozen-preventing frequency-limited temperature]
<Tinner pipe , and the compressor has stopped working for 3 minutes, the whole machine should be allowed to operate.
6. If the frozen-preventing protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should
press the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t
evaporator frozen-preventing protection times zero clearing time , the times of frozen-preventing power turn-off should be cleared to recount.
The mode of stopping the machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed,
mode transferring will not clear it).
(5) Overload protection function
Overload protection function at the mode of Cooling and dehumidifying
1. Starting estimation:
After the compressor stopped working for 180s, if Touter pipe <[TCooling overload frequency-limited temperature] (the temperature of hysteresis is 35.6ºF ), the
machine is allowed to start, otherwise it should not be started, and should be stopped to treat according to the overload protection: Clear the
trouble at the mode of power turn-off / heating, and the protection times are not counted.
2. Frequency limited
If [TCooling overload frequency-limited temperature] ≤[Touter pipe T Cooling overload frequency reducing temperature at normal speed], you should limit the frequency raising of
compressor.
3. Reducing frequency at normal speed and power turn-off:
If [TCooling overload frequency reducing temperature at high speed] ≤T outer pipe< [TCooling overload power turn-off temperature] , you should adjust the compressor frequency
by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [TCooling overload frequency reducing temperature at normal speed]≤Touter pipe,
then Cooling overload protects machine stopping;
4. Reducing frequency at high speed and stop machine:
If [TCooling overload frequency reducing temperature at high speed]≤Touter pipe [TCooling overload power turn-off temperature], you should adjust the compressor frequency by
reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if [TCooling overload frequency reducing temperature at normal speed] ≤[T outer pipe],
then Cooling overload protects machine stopping;
5. Power turn-off:
If the [TCooling overload power turn-off temperature] ≤Touter pipe, then Cooling overload protects machine stopping; If [Touter pipe]<[TCooling overload frequency-limited
temperature]and the compressor has been stopped working for 3 minutes, the machine should be allowed to operate.

6. If the Cooling overload protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should
press the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t
overload protection times zero clearing time , the times of overload protection power turn-off should be cleared to recount. The mode of
stopping the machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring
mode will not clear it).
Overload protection function at the mode of heating
Starting estimation :
After the compressor stopped working for 180s, if T inner pipe T heating overload frequency-limited temperature (the temperature of
hysteresis is 35.6ºF ), the machine is allowed to start, otherwise it should not be started, and should be stopped to treat according to the
overload protection:
Clear the trouble at the mode of power turn-off / heating, and the protection times are not counted.

34
SERVICE MANUAL

1. Frequency limited
If [Theating overload frequency-limited temperature]≤Tinner pipe <[Theating overload frequency reducing temperature at normal speed] , you should limit the frequency raising of
compressor.
2. Reducing frequency at normal speed and stopping machine:
If T[heating overload frequency reducing temperature at normal speed]≤Tinner pipe<[Theating overload frequency reducing temperature at high speed], you should adjust the compressor
frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if T heating overload frequency reducing
temperature at normal speed ≤T inner pipe, then overload protects machine stopping;
3. Reducing frequency at high speed and power turn-off:
If [Theating overload frequency reducing temperature at high speed]≤Tinner pipe<[Theating overload power turn-off temperature], you should adjust the compressor frequency by
reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if T heating overload frequency reducing temperature at normal
speed ≤T outer pipe, then Cooling overload protects machine stopping;
4. Power turn-off:
If the [Theating overload power turn-off temperature] ≤Tinner pipe, then overload protects machine stopping; If T inner pipe T heating overload frequency-limited
temperature and the compressor has been stopped working for 3 minutes, the machine should be allowed to operate.
5. If the overload protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should press
the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t overload
protection times zero clearing time , the times of overload protection power turn-off should be cleared to recount. The mode of stopping the
machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring mode will not clear
it). Protective function for discharge temperature of compressor
1. Starting estimation:
After the compressor stopped working for 180s, if TDischarge <TDischarge limited temperature (the temperature of hysteresis is 35.6ºF ), the machine is
allowed to start, otherwise it should not be started, and should be stopped to treat according to the discharge temperature:
The machine should be stopped or transferred to supply air, the trouble should be cleared immediately, and the protection times are not
counted.
2. Frequency limited
If [TLimited frequency temperature during discharging] ≤TDischarge<[Tfrequency reducing temperature at normal speed during discharging] , you should limit the frequency raising of
compressor.
3. Reducing frequency at normal speed and stopping machine:
If [Tfrequency reducing temperature at normal speed during discharging] ≤TDischarge<[Tfrequency reducing temperature at high speed during discharging], you should adjust the compressor
frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [Tfrequency reducing temperature at normal speed during discharging]
≤TDischarge, you should discharge to protect machine stopping;
4. Reducing frequency at high speed and power turn-off:
If [Tfrequency reducing temperature at high speed during discharging] ≤TDischarge <[TStop temperature during discharging], you should adjust
the compressor frequency by reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if [Tfrequency reducing temperature at normal
speed during discharging] ≤TDischarge, you should discharge to protect machine stopping;

5. Power turn-off:
If the [TPower turn-off temperature during discharging] ≤TDischarge, you should discharge to protect machine stopping; If [TDischarge]<[TLimited frequency temperature during
discharging] and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.

6. If the discharging temperature protection of compressor continuously occurs for six times, it should not be resumed automatically, and you
should press the ON/OFF button to resume. During the process of running, if the running time of compressor exceeds the t Protection times
clearing of discharge , the discharge protection is cleared to recount. Stopped or transferred to supply air mode will clear the trouble times
immediately (if the trouble can not be resumed, mode transferring also will not clear it).
7. Frequency limited
If [ILimited frequency when overcurrent] ≤IAC Electric current <[I frequency reducing when overcurrent], you should limit the frequency raising of compressor.
8. Reducing frequency:
If [IFrequency reducing when overcurrent] ≤[IAC Electric current I Power turn-off when overcurrent] , you should reduce the compressor frequency till the lower limit or exit
the frequency reducing condition;
9. Power turn-off:
If [IPower turn-off machine when overcurrent] ≤[IAC Electric current] , you should carry out the overcurrent stopping protection; If I AC Electric current<[T Limited frequency when
overcurrent] and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.

10. If the overcurrent protection continuously occurs for six times, it should not be resumed automatically, and you should press the ON/OFF
button to resume. During the process of running, if the running time of compressor exceeds the [t Protection times clearing of over current] , the discharge
protection is cleared to recount.

w w w . i n n o v a i r . c o m 35
SERVICE MANUAL

(6)Voltage sag protection


After start the compressor, if the time of DC link Voltage sag [USagging protection voltage] is measured to be less than t Voltage sag protection time ,
the machine should be stop at once, hand on the voltage sag trouble, reboot automatically after 30 minutes.
(7)Communication fault
When you have not received any correct signal from the inner machine in three minutes, the machine will stop for communication fault. When
you have not received any correct signal from driver IC (aim to the controller for the separating of main control IC and driver IC), and the
machine will stop for communication fault. If the communication is resumed, the machine will be allowed to operate.
(8)Module protection
Testing the module protective signal immediately after started, once the module protective signal is measured, stop the machine with module
protection immediately. If the module protection is resumed, the machine will be allowed to operate. If the module protection continuously
occurs for three times, it should not be resumed automatically, and you should press the ON/OFF button to resume. If the running time of
compressor exceeds the [t Protection times clearing of module] , the module protection is cleared to recount.
(9)Module overheating protection
1. Starting estimation:
After the compressor stopped working for 180s, if TModule<[TModule frequency limited temperature](the temperature of hysteresis is 35.6ºF ), the machine
is allowed to start, otherwise it should not be started, and should be stopped to treat according to the module overheating protection: The
machine should be stopped or transferred to supply air, the trouble should be cleared immediately, and the protection times are not counted.
2. Frequency limited
If [TLimited frequency temperature of module] ≤TModule <[Tfrequency reducing temperature at normal speed of module] , you should limit the frequency raising of compressor.
3. Reducing frequency at normal speed and power turn-off:
If [Tfrequency reducing temperature at normal speed of module] ≤TModule<[Tfrequency reducing temperature at high speed of module], you should adjust the compressor frequency by
reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [T frequency reducing temperature at normal speed of module] ≤T Module, you should
stop the machine for module overheating protection;
4. Reducing frequency at high speed and power turn-off:
If [Tfrequency reducing temperature at high speed of module]≤TModule <[TPower turn-off temperature of module] you should adjust the compressor frequency by reducing 30Hz/90s
till the lower limit; After it was running 90s at the lower limit, if [T frequency reducing temperature at normal speed of module] ≤T Module, you should stop the machine for
module overheating protection;
5. Power turn-off:
If the [TPower turn-off temperature of module] ≤TModule, you should stop the machine for module overheating protection; If TModule <[TLimited frequency temperature of module]
and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.
6. If protection continuously occurs for six times, it should not be resumed automatically, and you should press the ON/OFF button to resume.
During the process of running, if the running time of compressor exceeds the [t Protection times clearing of module] , the discharge protection is cleared
to recount. Stopped or transferred to supply air mode will clear the trouble times immediately (if the trouble can not be resumed, mode
transferring also will not clear it).
(10)Compressor overloads protection
If you measure the compressor overload switch action in 3s, the compressor should be stopped for overloading. The machine should be
allowed to operate after overload protection was measured to resume. If the overloading protection continuously occurs for three times, it
should not be resumed automatically, and you should press the ON/OFF button to resume. The protection times of compressor is allowed to
clear after the compressor run [t Protection times clearing of compressor overloading] 30 minutes.
(11)Phase current overcurrent protection of compressor
During the running process of compressor, you could measure the phase current of the compressor, and control it according to the following
steps:
1. Frequency limited
If [I Limited frequency phase current] ≤[I Phase current T frequency reducing phase current] , you should limit the frequency raising of compressor.
2. Reducing Frequency
If [I Frequency Reducing Phase Current]≤I Phase Current<[I Power Turn-Off Phase Current], the compressor shall continue to reduce frequency till the lowest frequency
limit or out of the condition of reducing frequency;
3. Power turn-off
If [I Phase Current]≥[I Power Turn-Off Phase Current], the compressor phase current shall stop working for overcurrent protection; if [I Phase Current]≤[I Frequency Reducing
Phase Current], and the compressor have stopped working for 3 min, the machine shall be allowed to operate;

4. If the overcurrent protection of compressor phase current continuously occurs for six times, it should not be resumed automatically, and
you should press the ON/OFF button to resume. During the process of running, if the running time of compressor exceeds the [t Clearing Time of
Compressor Phase Current Times] , the overcurrent protection is cleared to recount.

36
SERVICE MANUAL

(12) Starting-up Failure Protection for Compressor


Stop the compressor after its starting-up fails, restart it after 20s if the fault doesnt shows, and if they are all failing for the successive start 3
times, it shall be reported as Starting-up Failure, and then restart up it after 3 min. When it still not be able to operate through carry out the
above process for 5 times, it is available if press ON/OFF. And the compressor should be cleared the times after it run 2 min.
(13) Out-of-Step Protection for Compressor
The out-of-step protection signal should be detected immediately after starting-up compressor, and once find the out-of-step protection signal,
the out-of-step protection shall be stopped; if it can run for lasting power turn-off 3 min, the machine shall be allowed to operate. If it still cant
run automatically when the out-of-step protection for compressor happens to stop working for 6 times in succession, it needs to press ON/OFF
to operate. And if the running time is more than 10 min, the power turn-off times for out-of-step protection shall be cleared and recounted.
(14) Voltage Abnormity Protection for DC Bus
To detect voltage abnormity protection for dc bus after completing the pre-charge:
1.Over-High Voltage Protection for DC Bus:
If it found the DCbus voltage UDC >[UDC Jiekuangchun Protection], turn off PFC and stop the compressor at once, and it shall show the DC over-high
voltage failure; it should clear out the failure when the voltage dropped to UDC <[UDC Jiekuangchun Recovery] and the compressor stopped for 3 min.
2.Over-Low Voltage Protection for DC Bus:
If it found the DC bus voltage UDC <[UDC Wantuochun Protection], turn off PFC and stop the compressor at once, and it shall show the DC over-low
voltage; and it should clear out the failure when the voltage raised to UDC >[UDC Wantuochun Recovery] and the compressor stopped for 3 min.
3.To detect voltage abnormity protect for DC bus when getting electricity:
If it found the DC bus voltage UDC >[UDC——Over-High Voltage], turn off the relay at once, and shows voltage abnormity failure for DC Bus. And the
failure cant recover except to break off and get the electricity.
(15)Abnormity Protection for Four-way Valve
Under the model of heating operation in good condition: the compressor is detected [TInner Tube <(TInner Ring-T Abnormity Temperature Difference For Four-Way Valve
Reversion)], during the running, it should be regarded as four-way valve reversion abnormity. And then it can run if stop the reversion abnormity

protection for four-way valve 3 min; and if it still cant run when the reversion abnormity protection for four-way valve happens to stop working
for 3 times in succession, it is available if presses ON/OFF.
Attention: the protection shall be shielded during the testing mode and defrosting process, and it shall be cleared out the failure and its times
immediately when turning off or delivering wind / cooling / dehumidifying mode conversed (the inverted mode dont clear out the failure when it
cant recover to operate).
(16) PFC Protection
1. After start up the PFC, it should detect the protection signal of PFC immediately; under the condition of PFC protection, it should turn off the
PFC and compressor at one time;
2. It shows the failure is cleared out if PFC Protection stopped working 3 min and recovers to run automatically;
3. If it still cant run when it occurs PFC protection for 3 times in succession, it is available if presses ON/OFF; and clear the PFC Protection
times when start up PFC for 10min.
(17) Failure Detection for Sensor
1. Outdoor Ambient Sensor: detect the failure of sensor at all times.
2. Outdoor Tube Sensor: You should not detect the failure of outdoor tube sensor within 10 minutes heating
operation compressor except the defrosting, and you could detect it at other time.
3. Outdoor Exhaust Sensor:
(a) The compressor only detect the sensor failure after it start up 3 min in normal mode;
(b) It should detect the exhaust sensor failure immediately in the testing mode.
4. Module Temperature Sensor:
(a) Short-Circuit Detection: the compressor should be detected immediately when the module temperature
sensor occurs short-circuits;
(b) Open-Circuit Detection: the compressor should be detected on open-circuit when it runs 3min (it neednt 30s
avoiding the module over-heated).
(c) Detect the sensor failure at all times in the testing mode.
5. Disposal for Sensor Protection
(1) When the short-circuit of sensor is detected within 30s, It is regarded as the temperature of sensor over-high (or infinitely high), and now
according to the over-high sensor, the machine should carry out the corresponding protection to stop working, and show the corresponding
temperature shutdown protection and sensor failure at the same time (for example: the compressor stops immediately when the outdoor tube
sensor short-circuit, and the machine shall show the overload protection and outdoor tube sensor failure).
(2) When the open-circuit of sensor is detected within 30s, The protection shall be stopped and it shall show the corresponding sensor failure.

w w w . i n n o v a i r . c o m 37
SERVICE MANUAL

6. Electric Heating Function of Chassis


(1) When Toutdoor amb.≤32ºF , the electric heating of chassis will operate;
(2) When Toutdoor amb.>35.6ºF , the electric heating of chassis will stop operation;
(3)When 32ºF <Toutdoor amb.≤35.6ºF, the electric heating of chassis will keep original status.
7. Electric Heating Function of Compressor
(1) When Toutdoor amb.≤≤23ºF , compressor stops operation, while the electric heating of compressor starts operation;
(2) When Toutdoor amb.>28.4ºF , the electric heating of compressor stops operation;
(3) When 23ºF <Toutdoor amb.≤28.4ºF , the electric heating of compressor will keep original status.

38
SERVICE MANUAL

Installation and Maintenance


Notes for Installation and Maintenance
Safety Precautions: 10. If the power cord or connection wire is not long enough,
please get the specialized power cord or connection wire
Important! from the manufacture or distributor. Prohibit prolong the wire
by yourself.
Please read the safety precautions carefully before 11. For the air conditioner without plug, an air switch must
installation and maintenance. be installed in the circuit. The air switch should be all-pole
The following contents are very important for installation parting and the contact parting distance should be more than
and maintenance. 1/8 inch.
12. Make sure all wires and pipes are connected properly and
Please follow the instructions below. the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes,
●The installation or maintenance must accord with the please eliminate the electric leakage.
instructions. 14. Replace the fuse with a new one of the same specification
●Comply with all national electrical codes and local if it is burnt down; dont replace it with a cooper wire or
electrical codes. conducting wire.
●Pay attention to the warnings and cautions in this 15. If the unit is to be installed in a humid place, the circuit
manual. breaker must be installed.
●All installation and maintenance shall be performed by
distributor or qualified person.
●All electric work must be performed by a licensed Installation Safety Precautions:
technician according to local regulations and the
instructions given in this manual. 1. Select the installation location according to the require-
●Be caution during installation and maintenance. Prohibit ment of this manual.(See the requirements in installation
incorrect operation to prevent electric shock, casualty and part)
other accidents. 2. Handle unit transportation with care; the unit should not
be carried by only one person if it is more than 44.09lb.
3. When installing the indoor unit and outdoor unit, a suffi-

Warnings
cient fixing bolt must be installed; make sure the installation
support is firm.
4. Ware safety belt if the height of working is above 78 3/4
inch.
5. Use equipped components or appointed components dur-
Electrical Safety Precautions: ing installation.
6. Make sure no foreign objects are left in the unit after fin-
1. Cut off the power supply of air conditioner before ishing installation.
checking and maintenance.
2. The air condition must apply specialized circuit and Refrigerant Safety Precautions:
prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable 1. Avoid contact between refrigerant and fire as it generates
location and ensure the power plug is touchable. poisonous gas; Prohibit prolong the connection pipe by
4. Make sure each wiring terminal is connected firmly welding.
during installation and maintenance. 2. Apply specified refrigerant only. Never have it mixed with
5. Have the unit adequately grounded. The grounding wire any other refrigerant. Never have air remain in the refrigerant
cant be used for other purposes. line as it may lead to rupture or other hazards.
6. Must apply protective accessories such as protective 3. Make sure no refrigerant gas is leaking out when installation
boards, cable-cross loop and wire clip. is completed.
7. The live wire, neutral wire and grounding wire of power 4. If there is refrigerant leakage, please take sufficient measure
supply must be corresponding to the live wire, neutral to minimize the density of refrigerant.
wire and grounding wire of the air conditioner. 5. Never touch the refrigerant piping or compressor without
8. The power cord and power connection wires cant be wearing glove to avoid scald or frostbite.
pressed by hard objects.
9. If power cord or connection wire is broken, it must be Improper installation may lead to fire hazard, explosion,
replaced by a qualified person. electric shock or injury.

w w w . i n n o v a i r . c o m 39
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Safety Precautions for Installing


and Relocating the Unit:
To ensure safety, please be mindful of the following precautions.

Warnings
1. When installing or relocating the unit, be sure to keep the
refrigerant circuit free from air or substances other than the
specified refrigerant.
Any presence of air or other foreign substance in the refrigerant
circuit will cause system pressure rise or compressor rupture,
resulting in injury.
2.When installing or moving this unit, do not charge the
refrigerant which is not comply with that on the nameplate or
unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action,
mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating
or repairing the unit, be sure that the unit is running in
cooling mode.Then, fully close the valve at high pressure
side (liquid valve).About 30-40 seconds later, fully close the
valve at low pressure side (gas valve), immediately stop
the unit and disconnect power. Please note that the time for
refrigerant recovery should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in
and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and
gas valve are fully closed and power is disconnected before
detaching the connection pipe.
If compressor starts running when stop valve is open and
connection pipe is not yet connected, air will be sucked in and
cause pressure rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is
securely connected before the compressor starts running.
If compressor starts running when stop valve is open and
connection pipe is not yet connected, air will be sucked in and
cause pressure rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be
leaked corrosive gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and
other accidents.
7.Do not use extension cords for electrical connections. If
the electric wire is not long enough, please contact a local
service center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
8.Use the specified types of wires for electrical connections
between the indoor and outdoor units. Firmly clamp the
wires so that their terminals receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections
and insecure wire terminals may cause electric shock or fire.

40
SERVICE MANUAL

Main Tools for Installation and Maintenance


1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill

4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner


hexagon spanner

7. Electronic leakage detector 8. Vacuum pump 9. Pressure meter

10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container

w w w . i n n o v a i r . c o m 41
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Installation
Installation Dimension Diagram

Space to the ceiling

At least 5 7/8 inch

Space to the wall


Space to the wall
At least 5 7/8 inch
At least 5 7/8 inch
n

Space to the floor


At least 98 7/16 inch
tio
uc

ch
str

8 in
ob

t 11
he

eas
ot

At l
et
ac
Sp

Space to the obstruction


At least 19 11/16 inch

n
io
ct
t ru
obs
e
th h
Sp to inc
ac
et c e 3 /16
ot
he Spa 111
At l wa st
eas ll lea
t 11 At
13/
16
inch

Drainage pipe
ti o
st ruc nch
ob /8 i Sp
he t7 85 ac
ot eas At et
c et At
l lea ot
S pa st 1
91
he
1/1 ob
6 in str
ch uc
tio
n

42
SERVICE MANUAL

Start installation

Preparation before installation

Read the requirements select installation Prepare tools


for electric connection location

Select indoor unit Select outdoor unit


installation location installation location

Install wall-mounting Install the support of outdoor unit


frame, drill wall holes (select it according to the actual situation)

Connect pipes of indoor Fix outdoor unit


unit and drainage pipe

Connect wires of indoor unit Install drainage joint of outdoor unit


(only for cooling and heating unit)

Bind up pipes and


hang the indoor unit

Make the bound pipes pass


through the wall hole and then
connect outdoor unit

Connect pipes of outdoor unit

Connect wires of outdoor unit

Neaten the pipes

Vacuum pumping and leakage detection

Check after installation and test operation

Finish installation

Note: this flow is only for reference; please find the more detailed installation steps in this section.

w w w . i n n o v a i r . c o m 43
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Installation Parts-checking Requirements for Electric Connection


1. Safety Precaution
No. Name No. Name (1) Must follow the electric safety regulations when installing
1 Indoor unit 8 Sealing gum the unit.
2 Outdoor unit 9 Wrapping tape (2) According to the local safety regulations, use qualified
Support of outdoor power supply circuit and air switch.
3 Connection pipe 10
unit (3) Make sure the power supply matches with the requirement
4 Drainage pipe 11 Fixing screw of air conditioner. Unstable power supply or incorrect wiring
Wall-mounting Drainage plug(cooling may result in electric shock,fire hazard or malfunction. Please
5 12
frame and heating unit) install proper power supply cables before using the air
Connecting Owners manual, conditioner.
6 13
cable(power cord) remote controller (4) Properly connect the live wire, neutral wire and grounding
7 Wall pipe wire of power socket.
Note: (5) Be sure to cut off the power supply before proceeding any
1.Please contact the local agent for installation. work related to electricity and safety.
2.Dont use unqualified power cord. (6) Do not put through the power before finishing installation.
(7) If the supply cord is damaged,it must be replaced by the
manufacturer,its service agent or similarly qualified persons in
Selection of Installation Location order to avoid a hazard.
(8) The temperature of refrigerant circuit will be high, please
1. Basic Requirement: keep the interconnection cable away from the copper tube.
Installing the unit in the following places may cause (9) The appliance shall be installed in accordance with national
malfunction. If it is unavoidable, please consult the local dealer: wiring regulations.
(1) The place with strong heat sources, vapors, flammable or (10) Installation must be performed in accordance with the
explosive gas, or volatile objects spread in the air. requirement of NEC and CEC by authorized personnel only
(2) The place with high-frequency devices (such as welding
machine, medical equipment). 2. Grounding Requirement:
(3) The place near coast area. (1) The air conditioner is first class electric appliance. It must
(4) The place with oil or fumes in the air. be properly grounding with specialized grounding device
(5) The place with sulfureted gas. by a professional. Please make sure it is always grounded
(6) Other places with special circumstances. effectively, otherwise it may cause electric shock.
(7) Do not use the unit in the immediate surroundings of a (2) The yellow-green wire in air conditioner is grounding wire,
laundry a bath ashower or a swimming pool. which cant be used for other purposes.
(3) The grounding resistance should comply with national
2. Indoor Unit: electric safety regulations.
(1) There should be no obstruction near air inlet and air outlet. (4) The appliance must be positioned so that the plug is
(2) Select a location where the condensation water can be accessible.
dispersed easily and wont affect other people. (5) An all-pole disconnection switch having a contact separation
(3) Select a location which is convenient to connect the of at least 1/8 inch in all poles should be connected in fixed
outdoor unit and near the power socket. wiring.
(4) Select a location which is out of reach for children. (6) Including an air switch with suitable capacity, please note
(5) The location should be able to withstand the weight of the following table. Air switch should be included magnet
indoor unit and wont increase noise and vibration. buckle and heating buckle function, it can protect the circuit-
(6) The appliance must be installed 72inch above floor. short and overload. (Caution: please do not use the fuse only
(7) Dont install the indoor unit right above the electric for protect the circuit)
appliance. Air-conditioner Air switch capacity
(8) Please try your best to keep way from fluorescent lamp. 09/12K 15A

3. Outdoor Unit:
(1) Select a location where the noise and outflow air emitted by Installation of Indoor Unit
the outdoor unit will not affect neighborhood.
1. Choosing Installation Iocation
(2) The location should be well ventilated and away from
Recommend the installation location to the client and then
strong wind.
confirm it with the client.
(3) The location should be able to withstand the weight of
outdoor unit. 2. Install Wall-mounting Frame
(4) Make sure that the installation follows the requirement of (1) Hang the wall-mounting frame on the wall; adjust it in
installation dimension diagram. horizontal position with the level meter and then point out the
(5) Select a location which is out of reach for children and far screw fixing holes on the wall.
away from animals or plants.If it is unavoidable, please add (2) Drill the screw fixing holes on the wall with impact drill (the
fence for safety purpose. specification of drill head should be the same as the plastic
expansion particle) and then fill the plastic expansion particles

44
SERVICE MANUAL

in the holes. 5. Connect the Pipe of Indoor Unit


(3) Fix the wall-mounting frame on the wall with tapping screws (1) Aim the pipe joint at the corresponding bellmouth.(As show
(ST4.2X25TA) and then check if the frame is firmly installed by in Fig.5)
pulling the frame. If the plastic expansion particle is loose, (2) Pretightening the union nut with hand.
please drill another fixing hole nearby. (3) Adjust the torque force by referring to the following sheet.
3. Install Wall-mounting Frame Place the open-end wrench on the pipe joint and place the
(1) Choose the position of piping hole according to the direction torque wrench on the union nut. Tighten the union nut with
of outlet pipe. The position of piping hole should be a little torque wrench.(As show in Fig.6)
lower than the wall-mounted frame.(As show in Fig.1) (4) Wrap the indoor pipe and joint of connection pipe with
insulating pipe, and then wrap it with tape.(As show in Fig.7)
Wall Wall
Mark in the middle of it Level meter
Space Space
to the to the Open-end
wrench
wall wall
above above Union nut
5 7/8 5 7/8 Pipe joint Union nut Pipe
inch inch Torque wrench Pipe
Left Righ
Φ2 3/16inch Φ2 3/16inch
Rear piping hole Fig.1 Rear piping hole
Fig.5 Indoor pipe Fig.6

(2) Open a piping hole with the diameter of 2 3/16inch on the


selected outlet pipe position.In order to drain smoothly, slant
the piping hole on the wall slightly downward to the outdoor
side with the gradient of 5-10°.(As show in Fig.2) Insulating pipe Fig.7
Indoor Outdoor Refer to the following table for wrench moment of force:

Hex nut diameter(inch) Tightening torque(ft·Ibf)


2 3/16 inch Φ1/4 11.10~14.75
5-10° Φ3/8 22.12~29.50
Fig.2 Φ1/2 33.19~40.56
Φ5/8 44.24~47.94
Note: Φ3/4 51.32~55.31
(1) Pay attention to dust prevention and take relevant safety
measures when opening the hole. 6. Install Drain Hose
(2) The plastic expansion particles are not provided and should (1) Connect the drain hose to the outlet pipe of indoor unit.(As
be bought locally. show in Fig.8)
(2) Bind the joint with tape.(As show in Fig.9)
4. Outlet Pipe
(1) The pipe can be led out in the direction of right, rear right,
left or rear left.(As show in Fig.3)
Drain hose
(2) When selecting leading out the pipe from left or right, please Outlet pipe
cut off the corresponding hole on the bottom case.(As show in
Fig.4)
Tape
Outlet Drain hose
pipe Fig.9
Fig.8

Note:

Left Rear left (1) Add insulating pipe in the indoor drain hose in order to
Rear right
prevent condensation.
Fig.3 Right (2) The plastic expansion particles are not provided.
(As show in Fig.10)

Left Right Drain hose

Cut off
Insulating pipe
the hole Fig.10
Fig.4

w w w . i n n o v a i r . c o m 45
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

7. Connect Wire of Indoor Unit 8. Bind up Pipe


(1) Open the panel, remove the screw on the wiring cover and (1) Bind up the connection pipe, power cord and drain hose
then take down the cover.(As show in Fig.11) with the band.(As show in Fig.14)
(2) Reserve a certain length of drain hose and power cord
Screw for installation when binding them. When binding to a certain
Panel
degree, separate the indoor power and then separate the drain
hose.(As show in Fig.15)
(3) Bind them evenly.
(4) The liquid pipe and gas pipe should be bound separately at
Fig.11 the end.
Wiring cover

(2) Fix the wire crossing board on connection wire sleeve at Indoor and
the bottom case; let the connection wire sleeve go through the outdoor power cord
Indoor unit Gas
wire crossing hole at the back of indoor unit, and then pull it out pipe
from the front.(As show in Fig.12)

Liquid
Fig.14 Band pipe
Drain hose

Connection pipe Drain hose


connection wire sleeve Band
Fig.12

(3) Remove the wire clip; connect the power connection wire Fig.15
to the wiring terminal; tighten the screw and then fix the power Indoor power cord
connection wire with wire clip.(As show in Fig.13)
Note:
(1) The power cord and control wire cant be crossed or
winding.
N(1) 2 3 (2) The drain hose should be bound at the bottom.
white black red green
(blue) (brown) (yellow- 9. Hang the Indoor Unit
green)
(1) Put the bound pipes in the wall pipe and then make them
pass through the wall hole.
Outdoor unit connection (2) Hang the indoor unit on the wall-mounting frame.
(3) Stuff the gap between pipes and wall hole with sealing gum.
(4) Fix the wall pipe.(As show in Fig.16)
Note: the wiring board is for reference only,please refer to the
(5) Check if the indoor unit is installed firmly and closed to the
actual one.
wall.(As show in Fig.17)
Fig.13

(4) Put wiring cover back and then tighten the screw.
(5) Close the panel. Indoor Outdoor
Wall pipe Fig.17
Note: Sealing gum
(1) All wires of indoor unit and outdoor unit should be Upper hook
connected by a professional.
(2) If the length of power connection wire is insufficient, please
contact the supplier for a new one. Avoid extending the wire by
yourself.
(3) For the air conditioner with plug, the plug should be Fig.16
Lower hook of
reachable after finishing installation. wall-mounting frame
(4) For the air conditioner without plug, an air switch must be
installed in the line. The air switch should be all-pole parting Note:
and the contact parting distance should be more than 3mm. Do not bend the drain hose too excessively in order to prevent
blocking.

46
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Installation of Outdoor Unit Refer to the following table for wrench moment of force:

1. Fix the Support of Outdoor Unit(Select it according to Hex nut diameter(inch) Tightening torque(ft·Ibf)
the actual installation situation) Φ1/4 11.10~14.75
Φ3/8 22.12~29.50
(1) Select installation location according to the house structure.
Φ1/2 33.19~40.56
(2) Fix the support of outdoor unit on the selected location with
Φ5/8 44.24~47.94
expansion screws.
Φ3/4 51.32~55.31
Note:
5. Connect Outdoor Electric Wire
(1) Take sufficient protective measures when installing the (1) Let the connection wire sleeve go through the two holes of
outdoor unit. baffle; tighten the connection joint of sleeve and baffle; remove
(2) Make sure the support can withstand at least four times the the wire clip; connect the power connection wire and power
unit weight. cord to the wiring terminal according to the color; fix them with
(3) The outdoor unit should be installed at least 1 3/16 inch screws.(As show in Fig.23)
above the floor in order to install drain joint.(As show in Fig.18)
(4) For the unit with cooling capacity of 2300W~5000W, 6
N(1) 2 3
expansion screws are needed; for the unit with cooling capacity L1 L2
of 6000W~8000W, 8 expansion screws are needed; for the white
(blue)
black red green
(brown) (yellow- green(yellow-green)
green) black(brown)
unit with cooling capacity of 10000W~16000W, 10 expansion white(blue)
L2
L1
POWER
screws are needed.
Fig.23 Indoor unit connection

Note: the wiring board is for reference only,please refer to the actual one.

(2) Fix the power connection wire and power cord with wire clip.
(3) Fix the stopper on handle with screw.
Drain vent Chassis Note:
At least 1 1/6 inch above the floor Outdoor drain joint
Drain hose (1) After tightening the screw, pull the power cord slightly to
Fig.18 Fig.19 check if it is firm.
2. Install Drain Joint(only for cooling and heating unit) (2) Never cut the power connection wire to prolong or shorten
(1) Connect the outdoor drain joint into the hole on the chassis. the distance.
(2) Connect the drain hose into the drain vent. (3)The connecting wire and connection pipe cannnot touch
(As show in Fig.19) each other,
(4)Top cover of outdoor unit and electric box assembly should
3. Fix Outdoor Unit be fixec by the screw.Otherwise,it can cause a fire,or short
(1) Place the outdoor unit on the support. circuit caused by water or dust.
(2) Fix the foot holes of outdoor unit with bolts. Install the over line pipe
(As show in Fig.20)
Foot holes Cable cross plate 2 wire-passing
hole
wire pipe

valve cover Fixed nut Finish


Foot holes
6. Neaten the Pipes
Fig.20 Fig.21
(1) The pipes should be placed along the wall, bent reasonably
4. Connect Indoor and Outdoor Pipes and hidden possibly. Min. semidiameter of bending the pipe is 3
(1) Remove the screw on the cable cross plate 2 and valve 15/16inch.
cover of outdoor unit and then remove the cable cross plate 2 (2) If the outdoor unit is higher than the wall hole, you must set
and valve cover.(As show in Fig.21) a U-shaped curve in the pipe before pipe goes into the room,
(2) Remove the screw cap of valve and aim the pipe joint at the in order to prevent rain from getting into the room.(As show in
bellmouth of pipe.(As show in Fig.22) Fig.24)
Liquid pipe Pipe joint
The drain hos
Liquid gas pipe can't raise
valve
upwards
Union nut
gas valve
Wall
Fig.22

(3) Pretightening the union nut with hand. U-shaped curve Fig.25
(4) Tighten the union nut with torque wrench .
Fig.24
Drain hose

w w w . i n n o v a i r . c o m 47
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Note:
Check after Installation and Test
(1) The through-wall height of drain hose shouldnt be higher
than the outlet pipe hole of indoor unit.(As show in Fig.25) Operation
(2) Slant the drain hose slightly downwards. The drain hose 1. Check after Installation
cant be curved, raised and fluctuant, etc.(As show in Fig.26) Check according to the following requirement after finishing
installation.
(3) The water outlet cant be placed in water in order to drain
smoothly.(As show in Fig.27) NO. Items to be checked Possible malfunction
Has the unit been The unit may drop, shake or
1
installed firmly? emit noise.
Have you done the It may cause insufficient cooling
2
The drain hose can't be fluctuant refrigerant leakage test? (heating) capacity.
Is heat insulation of It may cause condensation and
3
pipeline sufficient? water dripping.
The water outlet It may cause condensation and
can't be placed 4 Is water drained well?
The drain hose
in water water dripping.
can't be fluctuant
The water Is the voltage of power
outlet can't be
fluctuant Fig.27 supply according to the It may cause malfunction or
Fig.26 5
voltage marked on the damage the parts.
nameplate?
Is electric wiring and
It may cause malfunction or
6 pipeline installed
damage the parts.
Vacuum Pumping and Leak Detection correctly?
1. Use Vacuum Pump Is the unit grounded
7 It may cause electric leakage.
(1) Remove the valve caps on the liquid valve and gas valve securely?
and the nut of refrigerant charging vent. Does the power cord It may cause malfunction or
8
follow the specification? damage the parts.
(2) Connect the charging hose of piezometer to the refrigerant
Is there any obstruction It may cause insufficient cooling
charging vent of gas valve and then connect the other charging 9
in air inlet and air outlet? (heating) capacity.
hose to the vacuum pump.
The dust and
(3) Open the piezometer completely and operate for 10-15min sundries caused It may cause malfunction or
to check if the pressure of piezometer remains in -14.5ISP. 10
during installation are damaging the parts.
(4) Close the vacuum pump and maintain this status for 1-2min removed?
to check if the pressure of piezometer remains in -14.5ISP. If The gas valve and liquid
It may cause insufficient cooling
the pressure decreases, there may be leakage. 11 valve of connection pipe
(heating) capacity.
(5) Remove the piezometer, open the valve core of liquid valve are open completely?
and gas valve completely with inner hexagon spanner. Is the inlet and outlet It may cause insufficient cooling
(6) Tighten the screw caps of valves and refrigerant charging 12 of piping hole been (heating) capacity or waster
vent.(As show in Fig.28) covered? eletricity.
2. Test Operation
Liquid valve Piezometer (1) Preparation of test operation
Lo Hi

Gas valve ● The client approves the air conditioner installation.


Valve cap
● Specify the important notes for air conditioner to the client.
Refrigerant charging
vent (2) Method of test operation
● Put through the power, press ON/OFF button on the remote
Nut of refrigerant
controller to start operation.
Charging vent
● Press MODE button to select AUTO, COOL, DRY, FAN and
Vacuum pump HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16℃ , the air
Inner hexagon
spanner conditioner cant start cooling.

Close
Fig.28
Open

2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air
bubbles coming out of this position, theres a leakage.

48
SERVICE MANUAL
SERVICE MANUAL

Troubleshooting for KIN310C2V31 , KIN413C2V31


Error Code List

Display of lamp
(the times of blinking)
Display of
Name of malfunction Indoor Outdoor
indoor unit
R C H Y R G
Anti-freezing protection E2 2 3
Block or Low pressure of refrigerant system E3 3 9
Compressor exhaust high temperature protection E4 4 7
AC over-current protection E5 5 5
Communication failure between indoor unit and outdoor unit E6 6 O/U
E8 8 6
Anti-high temperature protection
H4 4 6
No feedback of indoor fan motor H6 11
Jumper cap malfunction protection C5 15
Indoor unit and outdoor unit doesn't match LP 19 16
Outdoor DC fan motor malfunction L3 23 14
Power protection L9 20 9
Gathering refrigerant Fo 1 1
Indoor ambient sensor open or short circuit F1 1
Indoor tube sensor open or short circuit F2 2
Outdoor ambient sensor open or short circuit F3 3 6
Outdoor tube sensor open or short circuit F4 4 5
Exhaust sensor open or short circuit F5 5 7
Overload limit / drop frequency F6 6 3
Over current limit / drop frequency F8 8 1
High exhaust temperature limit / drop frequency F9 9 2
Refrigerant leakage protection F0 10 9
Anti-freezing limit / drop frequency FH 2 2 4
Defrosting H1 1 2
Compressor overload protection H3 3 8
IPM protection H5 5 4
Module temperature is too high H5 5 10
PFC protection HC 6 14
Loading EEPROM malfunction EE 15 11
High PN voltage protection PH 11 13
Low PN voltage protection PL 21 12
4-way valve reversal abnormal U7 20
DRED1 / DRED2 / DRED3 d1/d2/d3
Compressor Min frequence in test state P0
Compressor rated frequence in test state P1
Compressor maximum frequence in test state P2
Compressor intermediate frequence in test state P3
Compressor is running(normal) 1
The temperature for turning on the unit is reached(normal) 8
Frequency limiting (module temperature ) EU 6 6 11
Frequency limiting (power) LU 24 13
Malfunction of detecting plate(WIFI ) JF
Insufficient fluorine protection F0
Notes: R(Indoor)--Running C--Cooling H--Heating Y--Yellow R(Outdoor)--Red G--Green
O/U--OFF or Unblink The display difference between Fo and F0 is 'o' is the bottom part of figure 8

w w w . i n n o v a i r . c o m 49
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Troubleshooting for Main Malfunction


●Indoor unit:
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
Start
● Is mainboard broken?
Malfunction diagnosis process:

Is the wiring terminal between the


temperature sensor and the controller Yes
loosened or poorly contacted?

Insert the temperature


sensor tightly

No
No Is malfunction
eliminated

Is there short circuit due to trip- Yes


over of the parts

Make the parts upright

No

No Is malfunction Yes
eliminated

Is the temperature sensor normal No Yes


according to the resistance table?

Replace it with a
temperature sensor with
the same model

Yes

No Is malfunction
eliminated

Replace the mainboard with


the same model.

Yes

End

50
SERVICE MANUAL
SERVICE MANUAL

2. Malfunction of Blocked Protection of IDU Fan Motor H6


Main detection points:
● SmoothlyIs the control terminal of PG motor connected tightly?
● SmoothlyIs the feedback interface of PG motor connected tightly?
● The fan motor cant operate?
● The motor is broken?
● Detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:
Start

While power is off stir the blade


with a tool to see whether the No
blade rotates smoothly
Tighten the screw; reassemble the blade, motor
and shaft bearing rubber base sub-assy to make
sure there is no foreign object between them
Yes

No Is malfunction Yes
eliminated

Check if the connection of PG No


motor feedback terminal is firm
Insert the control terminal
of PG motor tightly

Yes
No Is malfunction Yes
eliminated

Check if the connection of PG No


motor control terminal is firm

Reinstall the blade


and motor correctly
Yes

No Is malfunction Yes
eliminated

Turn on the unit again; measure


whether the output voltage on Yes
control terminal for PG motor is Yes
more than 50V within 1 min after
the louvers are opened

Yes
Is the motor started up

No
Measure the voltage of this foot to
neutral wire on the mainboard Replace PG motor
No

No Is malfunction Yes
eliminated

Replace the mainboard


with the same model

End

w w w . i n n o v a i r . c o m 51
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

3. Malfunction of Protection of Jumper Cap C5


Main detection points:
● Is there jumper cap on the mainboard?
● Is the jumper cap inserted correctly and tightly?
● The jumper is broken?
● The motor is broken?
● Detection circuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

No Appearance of the
Is there jumper cap on the mainboard?
jumper cap

Assemble the jumper


cap with the same model
Yes

No Is malfunction
eliminated

Is the jumper cap inserted correctly No


and tightly?

Insert the jumper


cap tightly
Yes

No Is malfunction Yes
eliminated

Replace the jumper cap with


the same model

Is malfunction Yes
eliminated

Yes
No

Replace the mainboard


with the same model

End

52
SERVICE MANUAL
SERVICE MANUAL

4. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8


Main detection points:
● Instant energization afte de-energization while the capacitordischarges slowly?
● The zero-cross detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

Turn power off for


1minute,the turn
back on

The unit returns to normal.


U8 is still No Conclusion:U8 is displayed due to
displayed power off/on while the
capacitor discharges slowly.

Yes

The zero-cross detection circuit


of the mainboard is defined
abnormal.Replace the mainboard
with the same model

End

w w w . i n n o v a i r . c o m 53
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
5. Malfunction of detecting plate(WIFI) JF

Start

check if the connection wire


are correctly connected

Yes

Replace the detecting


plate with the same model

Is malfunction
eliminated

Replace the mainboard No Yes


with the same model

The end

54
SERVICE MANUAL
SERVICE MANUAL
6. Malfunction
(4) 㕪≏᭵䳌 F0ᧂḕ⍱〻of Insufficient fluorine protection F0

Troubleshooting
for F0 malfunction

Heat exchangers are Clean the heat exchangers and remove


Yes Malfunction is Yes
too dirty or the air inlet/outlet eliminated.
is blocked.
blockage of air inlet/outlet.

No No

Compressor doesn't work Malfunction is


normally. Strange noise or leakage occurs. Yes Make compressor run normally. eliminated.
Yes
Casing is too hot.

No No

System is blocked inside


(dirt block, ice block, oil block, Y-valve no Yes Remove blockage in the system Malfunction is Yes
eliminated.
fully open).

No No

Check the leaking status of refrigerant Malfunction is Yes


The refrigerant is leaking Yes eliminated.
and charge refrigerant

No No

Replace a main
board with the
same model.

End

w w w . i n n o v a i r . c o m 55
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

●Outdoor unit:

(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:

Turn on the unit


and wait 1 minute

Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor

Fault with the voltage


testing circuit on Replace the control
Voltage higher than 200V? Y
control panel AP1 panel AP1

Measure the AC voltage between


terminalL and N on wiring board
XT(power supply)

Shut down the power


Voltage within and repair the power power on and If the fault is
210VAC~250VAC? N supply to restore the restart the unit Y
eliminated?
range
210VAC~250VAC

Shut down the power and wait 20 minutes;


or use DC voltmeter to measure the voltage
N
on the two ends of capacitor , until the
voltage is lower than 20V

Check the
connection of reactor
(L in the Electrical
Wiring Diagram)

Connect the reactor


If the wiring of Laccording to Elec- Re-energize and If the fault is
reactor Lis normal? N trical Wiring Diagr- Y
turn on the unit eliminated?
am correctly

Replace the control


panel AP1 N

End

56
SERVICE MANUAL
SERVICE MANUAL

(2) IPM Protection, Out-of-step Fault, Compressor Phase Overcurrent (AP1 below refers to the outdoor control
panel)
Main check points:
●Is the connection between control panel AP1 and compressor COMP secure? Loose? Is the connection in correct order?
●Is the voltage input of the machine within normal range? (Use AC voltmeter to measure the voltage between terminal L and N on the
wiring board XT)
●Is the compressor coil resistance normal? Is the insulation of compressor coil against the copper tube in good condition?
●Is the working load of the machine too high? Is the radiation good?
●Is the charge volume of refrigerant correct?
Fault diagnosis process:

w w w . i n n o v a i r . c o m 57
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Energize and
switch on

Use AC voltmeter If the voltage


to measure the Check the supply
IPM protection between terminal L
occurs after the voltage between and N on wiring voltage and
machine has run for Y terminal L and N N restore it to
board XT is within
a period of time? on the wiring 210VAC~250VAC? 210VAC~250VAC
board XT)

Restart the unit. Before


Voltage between protection occurs,
use DC voltmeter to If the unit can
Y the two ends of celectrolytic measure the voltage N Y
capacitor is between the two work
higher than ends of electrolytic normally?
capacitor on control
250V panel AP1
Please confirm:
1. If the indoor and N
outdoor heat
exchangers are Stop the unit and Reconnect the
dirty? If they are disconnect the power capacitor C2 according
obstructed by other supply. Then, check The connection to Electrical Wiring
objects which affect the connection of of capacitor C2 Y Diagram. Then,
the heat exchange capacitor C2 Restart the
of indoor and according to Electrical is loose.
outdoor unit. Wiring Diagram. unit.
2. If the indoor and N
outdoor fans are
working normally?
3. If the environment Remove the wires Stop the unit and
temperature is too on the two ends of disconnect the power
high, resulting in capacitor C2. Then, supply. Wait 20 minutes,
that the system use capacitance or use DC voltmeter to If the unit can
pressure is too high meter to measure measure the voltage N work normallv? Y
and exceeds the the capacitor C2. between the two ends of
permissible range? Verify as per the capacitor C2, until the
4. If the charge Parameters Sheet. voltage is lower than 20V
volume of
refrigerant is too
much, resulting in
that the system Replace the capacitor
pressure is too If capacitor If the unit can Y
high? C2 is failed? Y C2. Then, energize work normally?
5. Other conditions and start the unit.
resulting in that the
system pressure
becomes too high. Replace the
N N
control panel AP1
Refer to the
Electrical Wiring Take corrective actions
Diagram and check If there is any according to Technical
if the connection abnormality Y Service Manual, and If the unit can
between AP1 and described above? Y
COMP is loose and if then energize and start work normally?
the connection order the unit.
is correct.
N Replace the
control panel AP1 N

If the connection Connect the control panel


between AP1 and AP1 and compressor
COMP is unsecure Y COMP correctly according
or the connection to the Electrical Wiring
order is wrong? Diagram. Then, energize
and start the unit. If the unit can
work Y
normally?

Use ohmmeter to
measure the resistance
between the three If the Replace the
terminals on compressor resistance is compressor
COMP, and compare the normal? N
measurements with the COMP
compressor resistance on
Service Manual.
N
Use ohmmeter to
measure the resistance Resistance higher
between the two than 500MΩ?
terminals of compressor
COMP and copper tube.
Y

Replace the
control panel
AP1

END

58
SERVICE MANUAL
SERVICE MANUAL

(3) High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the
outdoor unit)
Mainly detect:
●Is outdoor ambient temperature in normal range?
●Are the outdoor and indoor fans operating normally?
●Is the heat dissipation environment inside and outside the unit good?
Fault diagnosis process:

Overheat and high


temperature protection

Normal protection, please operate


Is outdoor ambient temperature higher than 53? Y it after the outdoor ambient temp-
erature is normalized.

20 minutes after the complete


unit is powered off.

Improve the heat


Is heat dissipation of the indoor unit Y dissipation environ-
and outdoor unit abnormal? ment of the unit

1. Check if the fan terminal OFAN


is connected correctly
Does the outdoor fan work normally? N 2. Resistance between any two
terminals is measure by an ohm
gauge and should be less than 1K
Ohm.

Replace the fan


capacitor C1
Replace the
control panel AP1

Replace the
outdoor fan

End

w w w . i n n o v a i r . c o m 59
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:

Power on the unit

Is stop time of the compressor N Restart it up after


longer than 3 minutes? 3 minutes

Does startup fail?

Connect the wires as


Are the wires for the compressor connected N per the connection
correctly? Is connection sequence right? diagram

Replace the control panel AP1

If the fault is eliminated?

Replace the
compressor

End

60
SERVICE MANUAL
SERVICE MANUAL

(5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:

Out of step occurs once the Out of step occurs in


unit is powered on. operation

Is stop time of the Check if the fan terminal Replace the fan
Is the outdoor fan working
compressor longer than N OFAN is connected correctly capacitor C1
normally?
3 minutes?

Y
Y Replace the
outdoor fan
Is the outdoor unit blocked Remove foreign objects
by foreign objects? Y

Are the wires for the compressor connected


correctly? Is connection sequence right? N
Is the connection made in clockwise
direction?
Replace the
N control panel AP1
Connect the Y
wires correctly

Replace the control


panel AP1

If the fault is eliminated? Y

Y If the fault is eliminated? N

N Replace the
compressor
Replace the
compressor

End
End

w w w . i n n o v a i r . c o m 61
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

(6) Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:

20 minutes after the


complete unit is
powered off

Is the terminal FA for the Connect the


electronic expansion valve N wires correctly
connected correctly?

Resistances between the first four pins


close to the terminal hole and the fifth
pin are almost the same, less than 100
ohm.

Replace the electronic


expansion valve

If the fault is eliminated? Y

Replace the
control panel
AP1

If the fault is eliminated?

Coolant leakage, refilling


the coolant

End

62
SERVICE MANUAL
SERVICE MANUAL

(7) Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the
outdoor unit)
Mainly detect:
●Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken
Fault diagnosis process:

Start

Check wiring of the


reactor (L) of the
outdoor unit and the
PFC capacitor

Replace it as per the


Whether there is any wiring diagram and
damage or Y If the fault is eliminated?
reconnect the wires
short-circuit?

Remove the PFC capacitor


and measure resistance N
between the two terminals.

The capacitor is
Is the resistance around zero? Y short circuited and Restart the unit If the fault is eliminated? Y
the capacitor
should be repla-
ced
N

Disconnect the terminals for the


reactor and measure the resistance N
between the two terminals of the
reactor by an ohm gauge

Whether there is any damage Y Replace the reactor Restart the unit If the fault is eliminated? Y
or short-circuit?

Replace the control


N
panel AP1

End

w w w . i n n o v a i r . c o m 63
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

(8) Communication malfunction: (following AP1 for outdoor unit control board)
Mainly detect:
●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is there any
damage?
Fault diagnosis process:

Start

Did the equipment operate


N
normally before the failure
Y occurs?

Check the wiring of the indoor and


outdoor units with reference to the
wiring diagram

Check wiring inside of


the indoor and outdoor Y Is the connection right?
units N

Correctly connect the


The AP1 voltage corresponding wires for
detection circuit Y Are wires broken? the indoor and outdoor
is at fault units with reference to
the wiring diagram
N

Check the communication


If the fault is eliminated? N
circuit of the outdoor unit

If the fault is eliminated?

The communication Replace the main board


Y
circuit is abnormal AP1 of the outdoor unit

N
If the fault is eliminated?

N
Replace the main board
of the indoor unit

Y
Y End

64
SERVICE MANUAL
SERVICE MANUAL

9.3 Troubleshooting for Normal Malfunction


1. Air Conditioner Cant be Started Up
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Confirm whether its due to power failure. If yes,
No power supply, or poor After energization, operation indicator isnt bright wait for power recovery. If not, check power
connection for power plug and the buzzer cant give out sound supply circuit and make sure the power plug is
connected well.
Wrong wire connection between
Check the circuit according to circuit diagram
indoor unit and outdoor unit, Under normal power supply circumstances,
and connect wires correctly. Make sure all
or poor connection for wiring operation indicator isnt bright after energization
wiring terminals are connected firmly
terminals
Make sure the air conditioner is grounded
reliably
Make sure wires of air conditioner is connected
After energization, room circuit breaker trips off at
Electric leakage for air conditioner correctly
once
Check the wiring inside air conditioner. Check
whether the insulation layer of power cord is
damaged; if yes, place the power cord.
Model selection for air switch is
After energization, air switch trips off Select proper air switch
improper
After energization, operation indicator is bright,
Replace batteries for remote controller
Malfunction of remote controller while no display on remote controller or buttons
Repair or replace remote controller
have no action.

2. Poor Cooling (Heating) for Air Conditioner

Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting


Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature
Rotation speed of the IDU fan
Small wind blow Set the fan speed at high or medium
motor is set too low
Filter of indoor unit is blocked Check the filter to see its blocked Clean the filter
Check whether the installation postion is proper
Installation position for indoor unit Adjust the installation position, and install the
according to installation requirement for air
and outdoor unit is improper rainproof and sunproof for outdoor unit
conditioner
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is Find out the leakage causes and deal with it.
Refrigerant is leaking
lower than normal discharged wind temperature; Add refrigerant.
Units pressure is much lower than regulated
range
Malfunction of 4-way valve Blow cold wind during heating Replace the 4-way valve
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is
Malfunction of capillary lower than normal discharged wind temperature; Replace the capillary
Unitt pressure is much lower than regulated
range. If refrigerant isnt leaking, part of capillary
is blocked
Flow volume of valve is The pressure of valves is much lower than that
Open the valve completely
insufficient stated in the specification
Refer to point 3 of maintenance method for
Malfunction of horizontal louver Horizontal louver cant swing
details
Refer to troubleshooting for H6 for maintenance
Malfunction of the IDU fan motor The IDU fan motor cant operate
method in details
Refer to point 4 of maintenance method for
Malfunction of the ODU fan motor The ODU fan motor cant operate
details
Refer to point 5 of maintenance method for
Malfunction of compressor Compressor cant operate
details

3. Horizontal Louver Cant Swing


Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Stepping motor is damaged Stepping motor cant operate Repair or replace stepping motor
Others are all normal, while horizontal louver cant
Main board is damaged Replace the main board with the same model
operate

w w w . i n n o v a i r . c o m 65
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
4. ODU Fan Motor Cant Operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Measure the capacity of fan capacitor with an
Capacity of the ODU fan motor is universal meter and find that the capacity is out of
Replace the capacity of fan
damaged the deviation range indicated on the nameplate of
fan capacitor.
Power voltage is a little low or Use universal meter to measure the power supply
Suggest to equip with voltage regulator
high voltage. The voltage is a little high or low
When unit is on, cooling/heating performance
Change compressor oil and refrigerant. If no
Motor of outdoor unit is damaged is bad and ODU compressor generates a lot of
better, replace the compressor with a new one
noise and heat.

5. Compressor Cant Operate


Possible causes Discriminating method (air conditioner status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Measure the capacity of fan capacitor with an
Capacity of compressor is universal meter and find that the capacity is out of
Replace the compressor capacitor
damaged the deviation range indicated on the nameplate of
fan capacitor.
Power voltage is a little low or Use universal meter to measure the power supply
Suggest to equip with voltage regulator
high voltage. The voltage is a little high or low
Use universal meter to measure the resistance
Coil of compressor is burnt out Repair or replace compressor
between compressor terminals and its 0
Cylinder of compressor is blocked Compressor cant operate Repair or replace compressor

6. Air Conditioner is Leaking


Possible causes Discriminating method (air conditioner status) Troubleshooting
Eliminate the foreign objects inside the drain
Drain pipe is blocked Water leaking from indoor unit
pipe
Drain pipe is broken Water leaking from drain pipe Replace drain pipe
Water leaking from the pipe connection place of
Wrapping is not tight Wrap it again and bundle it tightly
indoor unit

7. Abnormal Sound and Vibration

Possible causes Discriminating method (air conditioner status) Troubleshooting


When turn on or turn off the unit,
the panel and other parts will Normal phenomenon. Abnormal sound will
Theres the sound of "PAPA"
expand and theres abnormal disappear after a few minutes.
sound
When turn on or turn off the
unit, theres abnormal sound due Normal phenomenon. Abnormal sound will
Water-running sound can be heard
to flow of refrigerant inside air disappear after a few minutes.
conditioner
Foreign objects inside the indoor Remove foreign objects. Adjust all parts position
unit or therere parts touching Theres abnormal sound fro indoor unit of indoor unit, tighten screws and stick damping
together inside the indoor unit plaster between connected parts
Foreign objects inside the outdoor Remove foreign objects. Adjust all parts position
unit or therere parts touching Theres abnormal sound fro outdoor unit of outdoor unit, tighten screws and stick
together inside the outdoor unit damping plaster between connected parts
Short circuit inside the magnetic During heating, the way valve has abnormal
Replace magnetic coil
coil electromagnetic sound
Adjust the support foot mat of compressor,
Abnormal shake of compressor Outdoor unit gives out abnormal sound
tighten the bolts
If add too much refrigerant during maintenance,
Abnormal sound inside the
Abnormal sound inside the compressor please reduce refrigerant properly. Replace
compressor
compressor for other circumstances.

66
SERVICE MANUAL
SERVICE MANUAL

Troubleshooting for KIN321C2V31 , KIN824C2V31


Precautions before Maintenance
There are high-capacity electrolytic capacitors on the outdoor mainboard. Thus, even the power is cut off, there is high voltage inside the
capacitors and it needs more than 20min to reduce the voltage to safety value. Touching the electrolytic capacitor within 20min after
cutting the power will cause electric shock. If maintenance is needed, follow the steps below to discharge electricity of electrolytic ca-
pacitor after power off.

(1) Open the top cover of outdoor unit and then remove the cover of electric box.

cover of electric box

outdoor mainboard

(2) As shown in the fig below, connect the plug of discharge resistance (about 100ohm, 20W) (if there is no discharge resistance, you
can use the plug of soldering iron) to point A and B of electrolytic capacitor. There will be sparks when touching them. Press them forc-
ibly for 30s to discharge electricity of electrolytic capacitor.

(3) After finish discharging electricity, measure the voltage between point A and B with universal meter to make sure if electricity dis-
charging is completed, in order to prevent electric shock. If the voltage between the two points is below 20V, you can perform mainte-
nance safely.

w w w . i n n o v a i r . c o m 67
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Error Code List

(Only for the mode with this function)

Malfunction
of detecting JF
13
plate(WIFI )

68
SERVICE MANUAL
SERVICE MANUAL

Complete unit
Off 3s
current
U5 and blink
detection
13 times
malfunction

Off 3s
Defrosting will occur in
and blink
heating mode.Compressor
once
will operate while indoor It’s the normal state
(during
fan will stop.
blinking,
ON 10s
and Off
05s)

w w w . i n n o v a i r . c o m 69
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

70
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Troubleshooting for Main Malfunction


●Indoor unit:
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process: Start

Is the wiring terminal between the


temperature sensor and the controller Yes
loosened or poorly contacted?

Insert the temperature


sensor tightly

No
No Is malfunction
eliminated

Is there short circuit due to trip- Yes


over of the parts

Make the parts upright

No

No Is malfunction Yes
eliminated

Is the temperature sensor normal No Yes


according to the resistance table?

Replace it with a
temperature sensor with
the same model

Yes

No Is malfunction
eliminated

Replace the mainboard with


the same model.

Yes

End

w w w . i n n o v a i r . c o m 71
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
2. Malfunction of Blocked Protection of IDU Fan Motor H6
Main detection points:
● SmoothlyIs the control terminal of PG motor connected tightly?
● SmoothlyIs the feedback interface of PG motor connected tightly?
● The fan motor cant operate?
● The motor is broken?
● Detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:
Start

Turn the fan blades


by hand under
power-off condition

Adjust the motor and blade


Whether the fan blades assembly so that rotor can run
No
can run smoothly? smoothly.

Turn unit on
Yes to check whether the
No malfunction is
eliminated.

Under power-off condition,


check whether the wiring terminal Reinsert the wiring
between indoor fan and main
Yes terminal of indoor fan.
board is loose.

Turn unit on
No No to check whether the Yes
malfunction is
eliminated.

Connect power and restart the unit. It's the malfunction of main board.
Test whether the voltage between terminal 1 and terminal 2 No Replace a new main board that is
of motor interface is within 280~310VDC. of the same model.

Yes

Yes

Then check whether the voltage It's the malfunction of main board.
between terminal 2 and terminal 3 No Replace a new main board that is
of the same model.
of the motor interface is 15VDC.

Yes

Then check whether there is voltage It's the malfunction of main board.
between terminal 2 and terminal 4 No Replace a new main board that is
of the same model.
of the motor interface.

Yes

It's the malfunction of motor.


Replace a new motor that is End
of the same model.

72
SERVICE MANUAL
SERVICE MANUAL

3. Malfunction of Protection of Jumper Cap C5


Main detection points:
● Is there jumper cap on the mainboard?
● Is the jumper cap inserted correctly and tightly?
● The jumper is broken?
● The motor is broken?
● Detection circuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Start

No Appearance of the
Is there jumper cap on the mainboard?
jumper cap

Assemble the jumper


cap with the same model
Yes

No Is malfunction
eliminated

Is the jumper cap inserted correctly No


and tightly?

Insert the jumper


cap tightly
Yes

No Is malfunction Yes
eliminated

Replace the jumper cap with


the same model

Is malfunction Yes
eliminated

Yes
No

Replace the mainboard


with the same model

End

w w w . i n n o v a i r . c o m 73
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

4. Communication malfunction E6

Start

Cut off power supply. Check if


connection line of IDU and ODU
and the wire inside electric box
are correctly connected.

Connect the line


Correct connection? no according to Malfunction eliminated?
wiring diagram.

yes
no

Main board matches


Match correctly
with display board? Main board of no Malfunction eliminated? yes
IDU matches with that of ODU? according to product
specification

yes
no

Replace
Communication cord is damaged? yes communication Malfunction eliminated? yes
cord

no
no

Replace IDU's
main board

yes

Replace ODU's
Malfunction eliminated? no
main board.

yes

End

74
SERVICE MANUAL
SERVICE MANUAL

5. Malfunction of detecting plate(WIFI) JF

Start

check if the connection wire


are correctly connected

Yes

Replace the detecting


plate with the same model

Is malfunction
eliminated

Replace the mainboard No Yes


with the same model

The end

w w w . i n n o v a i r . c o m 75
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

●Outdoor unit:

Key detection point

"Test point NO." Test point Related elements Test value under normal condition
Test 1 Between A and C Neutral wire ,live wire 160V-265V
Test 2 Between B and C Neutral wire ,live wire 160V-265V
Test 3 Between D and E Electrolytic capacitor of DC bas bar DC 180V-380V
Test 4 Between F and G Electrolytic capacitor of switch power DC 180V-380V
Test 5 Both ends of diode D59 D59(IPM module +15V) DC 14.5V-15.5
Both ends of electrolytic
Test 6 C47(+12V power) DC 12V-13V
capacitor C47
Both ends of electrolytic
Test 7 C60(+5V power) DC 5V
capacitor C60
Both ends of electrolytic
Test 8 C73(+3.3V power) DC 3.3V
capacitor C73
Test 9 Between S and T Communication circular current DC 56V
C50 to N terminal (ground) (signal receiving terminal of
Test 10 Between point N and GND Jumping between 0V and 3.3V
outdoor unit)
Test 11 U7 Between 1 and 2 at leading foot of U7 Jumping between 0V and 3.3V
R77 to N terminal (ground) (signal receiving terminal of
Test 12 Between point M and GND Jumping between 0V and 3.3V
outdoor unit)
Test 13 U8 Between 3 and 4 at leading foot of U8 Jumping between 0V and 3.3V

76
SERVICE MANUAL
SERVICE MANUAL

1.Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit)

Main detection point:

● Detect if the voltage of L and N terminal of wiring board is between 210AC-240AC by alternating voltage meter;
● Is reactor (L) well connected? Is connection wire loosened or pull-out? Is reactor (L) damaged?

Malfunction diagnosis process:

Turn on the unit


and wait 1 minute

Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor

Fault with the voltage


Voltage higher than 200V? testing circuit on Replace the control
Y
control panel AP1 panel AP1

Measure the AC voltage between


terminalL and N on wiring board
XT(power supply)

Shut down the power


Voltage within and repair the power power on and If the fault is
210VAC~250VAC? N supply to restore the restart the unit Y
eliminated?
range
210VAC~250VAC

Shut down the power and wait 20nutes;


mi or
use DC voltmeter to measure the voltage
N
on the two ends of capacitor (test3), until
the voltage is lower than 20V

Check the
connection of reactor
(L in the Electrical
Wiring Diagram)

Connect the reactor


If the wiring of Laccording to Elec- Re-energize and If the fault is
reactor Lis normal? N trical Wiring Diagr- Y
turn on the unit eliminated?
am correctly

Replace the control


panel AP1 N

End

w w w . i n n o v a i r . c o m 77
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

2.IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (AP1 below is control board
of outdoor unit)

Main detection point:

● If control board AP1 and compressor COMP is well connected? If they are loosened? If the connection sequence is correct?
● Is voltage input in the normal range (Test the voltage between L, N of wiring board XT by DC voltage meter)?
● If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
● If the work load of unit is heavy? If radiating of unit is well?
● If the refrigerant charging is appropriate?

Malfunction diagnosis process:

78
SERVICE MANUAL
SERVICE MANUAL

Energize and
switch on

Use AC voltmeter If the voltage


to measure the Check the supply
IPM protection between terminal L
occurs after the voltage between and N on wiring voltage and
machine has run for Y terminal L and N N restore it to
board XT is within
a period of time? on the wiring 210VAC~250VAC? 210VAC~250VAC
board XT)

Restart the unit. Before


Voltage between protection occurs,
use DC voltmeter to If the unit can
Y the two ends of celectrolytic measure the voltage N Y
capacitor (test3) is between the two work
higher than ends of electrolytic normally?
capacitor on control
250V panel AP1 (test3)
Please confirm:
1. If the indoor and N
outdoor heat
exchangers are Stop the unit and Reconnect the
dirty? If they are disconnect the power capacitor C2 according
obstructed by other supply. Then, check The connection to Electrical Wiring
objects which affect the connection of of capacitor C2 Y Diagram. Then,
the heat exchange capacitor C2 Restart the
of indoor and according to Electrical is loose.
outdoor unit. Wiring Diagram. unit.
2. If the indoor and N
outdoor fans are
working normally?
3. If the environment Remove the wires Stop the unit and
temperature is too on the two ends of disconnect the power
high, resulting in capacitor C2. Then, supply. Wait 20 minutes,
that the system use capacitance or use DC voltmeter to If the unit can
pressure is too high meter to measure measure the voltage N work normallv? Y
and exceeds the the capacitor C2. between the two ends of
permissible range? Verify as per the capacitor C2, until the
4. If the charge Parameters Sheet. voltage is lower than 20V
volume of
refrigerant is too
much, resulting in
that the system Replace the capacitor
pressure is too If capacitor If the unit can Y
high? C2 is failed? Y C2. Then, energize work normally?
5. Other conditions and start the unit.
resulting in that the
system pressure
becomes too high. Replace the
N N
control panel AP1
Refer to the
Electrical Wiring Take corrective actions
Diagram and check If there is any according to Technical
if the connection abnormality Y Service Manual, and If the unit can
between AP1 and described above? Y
COMP is loose and if then energize and start work normally?
the connection order the unit.
is correct.
N Replace the
control panel AP1 N

If the connection Connect the control panel


between AP1 and AP1 and compressor
COMP is unsecure Y COMP correctly according
or the connection to the Electrical Wiring
order is wrong? Diagram. Then, energize
and start the unit. If the unit can
work Y
normally?

Use ohmmeter to
measure the resistance
between the three If the Replace the
terminals on compressor resistance is compressor
COMP, and compare the normal? N
measurements with the COMP
compressor resistance on
Service Manual.
N
Use ohmmeter to
measure the resistance Resistance higher
between the two than 500MΩ?
terminals of compressor
COMP and copper tube.
Y

Replace the
control panel
AP1

END

w w w . i n n o v a i r . c o m 79
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

3.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit)

Main detection point:

● If the outdoor ambient temperature is in normal range;


● If the indoor and outdoor fan is running normal;
● If the radiating environment of indoor and outdoor unit is well.

Malfunction diagnosis process:

Anti-high temperature,
overload protection

Normal protection, please use


If the outdoor ambient temperature is Y it after improve the outdoor
higher than 127.4 °F? ambient temperature

After the unit de-


energized for 20min

Improve the
If the radiating of outdoor Y radiating
and indoor unit is well? environment of
unit

1. Check if fan terminal


OFAN is connected well
If the indoor and outdoor N 2. Test if resistance value
fan work well? of any two terminals is less
than 1k with ohmic meter

Replace fan
Replace capacitor C1
control board
AP1

Replace
outdoor fan

End

80
SERVICE MANUAL
SERVICE MANUAL

4.Diagnosis for failure start up malfunction (AP1 below is control board of outdoor unit)

Main detection point:

● If the compressor wiring is correct?


● If the stop time of compressor is enough?
● If the compressor is damaged?
● If the refrigerant charging is too much?

Malfunction diagnosis process:

Energize the unit


and start it

If the stop time is not enough and the


If the stop time of compressor N high and low pressure of system is not
is more than 3min? balance , please start it after 3min

Improve the connection situation


If the compressor wire COMP(UVW) is of control board AP1 and
well connected and connection sequence
N compressor COMP, connect it
is correct with wiring diagram

Does the unit start


up normally?
If the refrigerant charging is
N
too much?

Charge the
refrigerant according
to service manual

Does the unit start Y


up normally?

Replace control board AP1

If malfunction is
removed?

Replace the
compressor

End

w w w . i n n o v a i r . c o m 81
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

5. Diagnosis for compressor synchronism (AP1 below is control board of outdoor unit)

Main detection point:

● If the system pressure is over-high?


● If the work voltage is over-low?

Malfunction diagnosis process:

Synchronism after Synchronism


energize the unit occurred during
and start it operation

Check if the fan


If the stop time of If the outdoor fan works Replace fan
N terminal OFAN is
compressor is more than normally? capacitor C1
connected well
3min
Y
Y Replace
Improve the radiating
of unit (clean heat outdoor fan
If the radiating of unit is Y
well? exchanger and
If the compressor wire COMP(UVW) is well
increase ventilation)
connected, the connection sequence N
forwards to clockwise direction?

N Start to run until the


If the input voltage of unit N power resume normal
Connect Y is normal? voltage
wire well
Replace Y
control board
AP1 Charge the
If the refrigerant is too Y refrigerant with
much? service manual
Remove
Y N
malfunction?
Replace
N control board
AP1
Replace
compressor

Remove
malfunction?
End
N Y

Replace
compressor

End

82
SERVICE MANUAL
SERVICE MANUAL

6.Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit)

Main detection point:

● If the electron expansion valve is connected well? Is the expansion valve damaged?
● If the refrigerant is leakage?
● If the overload protector is damaged?

Malfunction diagnosis process:


After the unit
de-energized
for 20min

If the overload protector SAT N


is well connected?

Under ambient temperature, test the


resistance of overload protector with ohmic

Connect wire
If the wiring terminal FA of electron N well with wiring
N expansion is well connected?
diagram
Y

The resistance value of


firs t 4 l e ad fo ot an d th e
fif th lead fo ot is similar,
less than 100

Replace Replace EKV


overload
protector SAT
coil of electron
expansion valve

Remove
malfunction?

Check refrigerant, if there is


leakage, please refer to
specification

Remove
Y
malfunction?

Replace
control board
AP1

End

w w w . i n n o v a i r . c o m 83
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

7.Communication malfunction (AP1 below is control board of outdoor unit)

Main detection point:

● Check if the connection wire and the built-in wiring of indoor and outdoor unit is connected well and no damaged;
● If the communication circuit of indoor mainboard is damaged? If the communication circuit of outdoor mainboard (AP1) is dam-
aged

Malfunction diagnosis process:

Start

If the unit is operation


N
normal before malfunction
Y
Check connection
wire of indoor and
outdoor unit with
circuit diagram

Check built-
in wiring of Connection
Y
indoor and N
correct?
outdoor unit
N

Malfunction of Check connection


circuit is
If the wiring is wire of indoor and
detected with Y
outdoor unit with
control board damaged?
circuit diagram
AP1 voltage

If the malfunction Check communication


N
is removed? circuit of outdoor unit
If the malfunction
is removed?

Problem of
Replace outdoor
communication Y
mainboard AP11
circuit

N If the
malfunction is
removed?
N
Replace indoor
board

Y End Y

84
SERVICE MANUAL
SERVICE MANUAL

8.Diagnosis process for outdoor communication circuit

Start

Test voltage
value with Test
10 position in
diagram with
voltage meter

Number jumping
N

Y
Test voltage
value with Test
13 position in
diagram with
voltage meter

Number jumping N

Y
Outdoor unit
End
Test voltage malfunction
value with Test
11 position in
diagram with
voltage meter

Number jumping N

Y
Test voltage
value with Test
12 position in
diagram with
voltage meter

Number jumping

The circuit of
outdoor unit
communication
is normal

w w w . i n n o v a i r . c o m 85
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Troubleshooting for Normal Malfunction


1. Air conditioner cant be started up
Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Confirm whether its due to power failure. If yes,
No power supply, or poor After energization, operation indicator isnt bright wait for power recovery. If not, check power
connection for power plug and the buzzer cant give out sound supply circuit and make sure the power plug is
connected well.
Wrong wire connection between
Check the circuit according to circuit diagram
indoor unit and outdoor unit, Under normal power supply circumstances,
and connect wires correctly. Make sure all
or poor connection for wiring operation indicator isnt bright after energization
wiring terminals are connected firmly
terminals
Make sure the air conditioner is grounded
reliably
Make sure wires of air conditioner is connected
After energization, room circuit breaker trips off at
Electric leakage for air conditioner correctly
once
Check the wiring inside air conditioner. Check
whether the insulation layer of power cord is
damaged; if yes, place the power cord.
Model selection for air switch is
After energization, air switch trips off Select proper air switch
improper
After energization, operation indicator is bright,
Replace batteries for remote controller
Malfunction of remote controller while no display on remote controller or buttons
Repair or replace remote controller
have no action.
2. Poor cooling (heating) for air conditioner

Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting


Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature
Rotation speed of the IDU fan
Small wind blow Set the fan speed at high or medium
motor is set too low
Filter of indoor unit is blocked Check the filter to see its blocked Clean the filter
Check whether the installation postion is proper
Installation position for indoor unit Adjust the installation position, and install the
according to installation requirement for air
and outdoor unit is improper rainproof and sunproof for outdoor unit
conditioner
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is Find out the leakage causes and deal with it.
Refrigerant is leaking
lower than normal discharged wind temperature; Add refrigerant.
Units pressure is much lower than regulated
range
Malfunction of 4-way valve Blow cold wind during heating Replace the 4-way valve
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is
Malfunction of capillary lower than normal discharged wind temperature; Replace the capillary
Unitt pressure is much lower than regulated
range. If refrigerant isnt leaking, part of capillary
is blocked
Flow volume of valve is The pressure of valves is much lower than that
Open the valve completely
insufficient stated in the specification
Refer to point 3 of maintenance method for
Malfunction of horizontal louver Horizontal louver cant swing
details
Refer to troubleshooting for H6 for maintenance
Malfunction of the IDU fan motor The IDU fan motor cant operate
method in details
Refer to point 4 of maintenance method for
Malfunction of the ODU fan motor The ODU fan motor cant operate
details
Refer to point 5 of maintenance method for
Malfunction of compressor Compressor cant operate
details

3. Horizontal louver cant swing


Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Stepping motor is damaged Stepping motor cant operate Repair or replace stepping motor
Others are all normal, while horizontal louver cant
Main board is damaged Replace the main board with the same model
operate

86
SERVICE MANUAL
SERVICE MANUAL
4. ODU fan motor cant operate
Possible causes Discriminating method (air conditioner status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Measure the capacity of fan capacitor with an
Capacity of the ODU fan motor is universal meter and find that the capacity is out of
Replace the capacity of fan
damaged the deviation range indicated on the nameplate of
fan capacitor.
Power voltage is a little low or Use universal meter to measure the power supply
Suggest to equip with voltage regulator
high voltage. The voltage is a little high or low
When unit is on, cooling/heating performance
Change compressor oil and refrigerant. If no
Motor of outdoor unit is damaged is bad and ODU compressor generates a lot of
better, replace the compressor with a new one
noise and heat.

5. Compressor cant operate


Possible causes Discriminating method (air conditioner status) Troubleshooting
Connect wires according to wiring diagram to
Wrong wire connection, or poor Check the wiring status according to circuit
make sure all wiring terminals are connected
connection diagram
firmly
Measure the capacity of fan capacitor with an
Capacity of compressor is universal meter and find that the capacity is out of
Replace the compressor capacitor
damaged the deviation range indicated on the nameplate of
fan capacitor.
Power voltage is a little low or Use universal meter to measure the power supply
Suggest to equip with voltage regulator
high voltage. The voltage is a little high or low
Use universal meter to measure the resistance
Coil of compressor is burnt out Repair or replace compressor
between compressor terminals and its 0
Cylinder of compressor is blocked Compressor cant operate Repair or replace compressor

6. Air conditioner is leaking


Possible causes Discriminating method (air conditioner status) Troubleshooting
Eliminate the foreign objects inside the drain
Drain pipe is blocked Water leaking from indoor unit
pipe
Drain pipe is broken Water leaking from drain pipe Replace drain pipe
Water leaking from the pipe connection place of
Wrapping is not tight Wrap it again and bundle it tightly
indoor unit
7. Abnormal sound and vibration

Possible causes Discriminating method (air conditioner status) Troubleshooting


When turn on or turn off the unit,
the panel and other parts will Normal phenomenon. Abnormal sound will
Theres the sound of "PAPA"
expand and theres abnormal disappear after a few minutes.
sound
When turn on or turn off the
unit, theres abnormal sound due Normal phenomenon. Abnormal sound will
Water-running sound can be heard
to flow of refrigerant inside air disappear after a few minutes.
conditioner
Foreign objects inside the indoor Remove foreign objects. Adjust all parts position
unit or therere parts touching Theres abnormal sound fro indoor unit of indoor unit, tighten screws and stick damping
together inside the indoor unit plaster between connected parts
Foreign objects inside the outdoor Remove foreign objects. Adjust all parts position
unit or therere parts touching Theres abnormal sound fro outdoor unit of outdoor unit, tighten screws and stick
together inside the outdoor unit damping plaster between connected parts
Short circuit inside the magnetic During heating, the way valve has abnormal
Replace magnetic coil
coil electromagnetic sound
Adjust the support foot mat of compressor,
Abnormal shake of compressor Outdoor unit gives out abnormal sound
tighten the bolts
If add too much refrigerant during maintenance,
Abnormal sound inside the
Abnormal sound inside the compressor please reduce refrigerant properly. Replace
compressor
compressor for other circumstances.

w w w . i n n o v a i r . c o m 87
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Removal Procedure Warning: Be sure to wait for a minimum of 20 minutes


after turning off all power supplies and discharge the
for KIN310C2V31 , KIN413C2V31
refrigerant completely before removal.
Removal Procedure of Indoor Unit

Step Procedure

1. Remove filter assembly


Front panel

Open the front panel. Push the left filter


and right filter until they are separate from
the groove on the front panel. Front
Remove the left filter and right filter case
respectively. Left filter

Groove Right filter

2. Remove horizontal louver

Push out the axile bush on horizontal


louver. Bend the horizontal louver with
hand and then separate the horizontal
louver from the crankshaft of step motor
to remove it.
Location of step motor
Horizontal louver
Axile bush

3. Remove panel and display A1/A5/B6 display

a
(1)A1/A5 panel display: Screw off the 2
screws that are locking the display board.
Separate the display board from the front
panel. Panel
(2)B2/A5/D2 panel display: Screw off Front panel A5/B2/D2 display
the 2 screws that are locking the display
board.

Separate the panel rotation shaft from


b the groove fixing the front panel and then
removes the front panel.
Panel rotation

Groove

88
SERVICE MANUAL
SERVICE MANUAL

Step Procedure

4. Remove detecting plate and electric box cover 2 Screw


Electric box cover2

Remove the screw fixing detecting plate


and then remove the detecting plate.
Detecting plate
Note:The position of detection board(WIFI)
may be different for -different models. Screw
for 09K
Detecting plate

Remove the screw fixing electric box


cover 2 and then remove the electric box
for 12K
cover 2.

5. Remove front case sub-assy


Screws

a Remove the screws fixing front case.

Note:
1.Open the screw caps before removing
the screws around the air outlet.
2.The quantity of screws fixing the front
Front case
case sub-assy is different for different
sub-assy Screw caps
models.
Screw
Clasp
b Loosen the connection clasps between
front case sub-assy and bottom case. Lift Front case
up the front case sub-assy and take it out. sub-assy

6. Remove vertical louver

Loosen the connection clasps between


vertical louver and bottom case to remove
vertical louver. Bottom
case

Vertical
louver

Clasps Vertical
louver

w w w . i n n o v a i r . c o m 89
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Step Procedure

7. Remove electric box assy


Screw

a Loosen the connection clasps between


shield cover of electric box sub-assy and Clasps
electric box, and then remove the shield
cover of electric box sub-assy.
Remove the screw fixing electric box assy .

Electric box
Shield cover of electric
box sub-assy

Indoor tube
temperature
Grounding screw sensor Electric box assy
b ① Take off the water retaining sheet.
Remove the cold plasma generator by
screwing off the locking screw on the
generator.
② Take off the indoor tube temperature Cold plasma
sensor. generator
③ Screw off 1 grounding screw. Wiring
④ Remove the wiring terminals of motor and terminal
stepping motor. Screw
of motor
⑤ Remove the electric box assy.
Water retaining Wiring
sheet terminal
of stepping
motor

Screw
Main board
c Twist off the screws that are locking
each lead wire and rotate the electric
box assy.
Twist off the screws that are locking the
wire clip. Loosen the power cord and
remove its wiring terminal. Lift up the
main board and take it off.

Power cord

Screw

Wire clip

90
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Step Procedure

Instruction: Some wiring terminal of this


product is with lock catch and other devices. circlip
The pulling method is as below:
holder
1.Remove the soft sheath for some terminals
at first, hold the circlip and then pull out the
terminals.
soft sheath connector
2.Pull out the holder for some terminals at
first (holder is not available for some wiring
terminal), hold the connector and then pull the
terminal.

8. Remove evaporator assy Screws Evaporator assy

a Remove 3 screws fixing evaporator assy.

Connection pipe clamp


b At the back of the unit, remove the Screw
screw fixing connection pipe clamp and
then remove the connection pipe clamp.

Groove
Bottom case
c First remove the left side of the evaporator
from the groove of bottom case and then
remove the right side from the clasp on
the bottom case.
Clasp
Evaporator assy

Connection pipe

d Adjust the position of connection pipe


on evaporator slightly and then lift the
evaporator upwards to remove it.

w w w . i n n o v a i r . c o m 91
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Step Procedure

9. Remove motor and cross flow blade

a Remove the screws fixing motor clamp


Screws
and then remove the motor clamp.

Motor clamp

Cross flow
b Remove the screws at the connection Screw
place of cross flow blade and motor; lift Holder Motor
the motor and cross flow blade upwards sub-assy
to remove them.
Remove the bearing holder sub-assy.
Remove the screw fixing step motor and
then remove the step motor.

Screws
Step motor

92
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Removal Procedure of Outdoor Unit

Warning: Be sure to wait for a minimum of 20 minutes


after turning off all power supplies and discharge the
refrigerant completely before removal.

NOTE: Take GWH12QC-D3DNA6E/O for example.

Steps Procedure

1.Remove cable cross plate 2 and valve cover

Before disassamble.

Cable cross plate 2

screw
Remove 3 connection screw fixing cable
cross plate 2 and then remove the Cable
cross plate 2.

Remove 1 connection screw fixing valve cover


and then remove the valve cover. Valve Cover

2.Remove top cover


screw
top cover plate

Remove 3 connection screws among


top cover plate, front panel and right
side plate. Then remove top cover
plate.

w w w . i n n o v a i r . c o m 93
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

3.Remove grille and front panel

Remove connection screws between the front grille


and the front panel. Then remove the front grille.
Remove connection screws connecting the front
panel with the chassis and the motor support, and
then remove the front panel.

Grille
Panel

4.Remove axial flow blade

Axial flow blade

Remove the nut fixing the blade and then


remove the axial flow blade.

5.Remove right side plate

Remove connection screws connecting the right Right side plate


side plate with the valve support and the electric
box. Then remove the right side plate.

94
SERVICE MANUAL
SERVICE MANUAL

6.Remove electric box assy


Electric box assy

Remove the 2 screws fixing the cover of elec-


tric box. Lift to remove the cover. Loosen the
wire and disconnect the terminal. Lift to re-
move the electric box assy.

7.Remove 4-way valve assy

Unscrew the fastening nut of the 4-way Valve


Assy coil and remove the coil. Wrap the 4- 4-way Valve Assy
way Valve Assy with wet cotton and unsolder
the 4 weld spots connecting the 4-way Valve
Assy to take it out.(Note: Refrigerant should
be discharged firstly.) Welding process
should be as quickly as possible and keep
wrapping cotton wet all the time. Be sure not
to burn out the lead-out wire of compressor.

8.Remove capillary sub-assy

Unsolder weld point of capillary Sub-assy, Capillary Sub-assy


valve and outlet pipe of condensator. Then
remove the capillary Sub-assy. Do not block
the capillary when unsoldering it. (Note: be-
fore unsoldering,discharge refrigerants
completely)

w w w . i n n o v a i r . c o m 95
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

9.Remove motor and motor support

Motor support

Remove the 4 tapping screws fixing the motor.


Pull out the lead-out wire and remove the
Motor
motor. Remove the 2 tapping screws fixing
the motor support. Lift motor support to re-
move it.

10.Remove clapboard sub-assy

Clapboard Sub-Assy

Loosen the screws of the Clapboard Sub-Assy .


The Clapboard Sub-Assy has a hook on the
lower side. Lift and pull the Clapboard Sub-Assy
to remove.

96
SERVICE MANUAL
SERVICE MANUAL

11.Remove Compressor

a Remove the 2 screws fixing the gas valve.


Unsolder the welding spot connecting gas valve
and air return pipe and remove the gas valve.
(Note: it is necessary to warp the gas valve when
unsoldering the welding spot.) Remove the 2
screws fixing liquid valve. Unsolder the weld- Liquid valve
ing spot connecting liquid valve and remove the
liquid valve.

Gas valve

b Remove the 3 footing screws of the compressor


and remove the compressor.
Compressor

w w w . i n n o v a i r . c o m 97
SERVICE MANUAL

Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25

Appendix 2: Configuration of Connection Pipe


1.Standard length of connection pipe
● 16.40ft, 24.61ft, 26.25ft.
2.Min. length of connection pipe is 9.84ft.
3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications)
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 32.81ft at the basis of standard length, you should add 0.0013gal of refrigerant
oil for each additional 16.40ft of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional
refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter

Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(inch) Gas pipe(inch) Cooling only(oz/ft.) Cooling and heating(oz/ft.)
Ф1/4 Ф3/8or Ф1/2 0.2 0.2
Ф1/4 or Ф3/8 Ф5/8 or Ф3/4 0.2 0.6
Ф1/2 Ф3/4 or Ф7/8 0.3 1.3
Ф5/8 Ф1 or Ф1 1/4 0.7 1.3
Ф3/4 / 2.7 2.7
Ф7/8 / 3.8 3.8

98
SERVICE MANUAL
SERVICE MANUAL

Appendix 3: Pipe Expanding Method


Pipe
Note:

Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.

B:Remove the burrs Pipe

● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper

Downwards
C:Put on suitable insulating pipe

D:Put on the union nut Union pipe


● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe. Pipe

E:Expand the port


● Expand the port with expander.
Hard
Note: mold
Expander
● "A" is different according to the diameter, please refer to the sheet below:
Outer A(inch) Pipe
diameter(inch) Max Min
Ф0.24 - 0.25 (1/4") 0.05 0.03
Ф0.37 (3/8") 0.06 0.04
Ф0.47 - 0.50 (1/2") 0.07 0.04
Ф0.63 - 0.625 (5/8") 0.09 0.09

Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.

leaning damaged crack uneven


surface thickness
The length is equal

w w w . i n n o v a i r . c o m 99
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Appendix 4: List of Resistance for Temperature Sensor

Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor(15K)

Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ)


-2.2 138.1 68 18.75 138.2 3.848 208.4 1.071
-0.4 128.6 69.8 17.93 140 3.711 210.2 1.039
1.4 121.6 71.6 17.14 141.8 3.579 212 1.009
3.2 115 73.4 16.39 143.6 3.454 213.8 0.98
5 108.7 75.2 15.68 145.4 3.333 215.6 0.952
6.8 102.9 77 15 147.2 3.217 217.4 0.925
8.6 97.4 78.8 14.36 149 3.105 219.2 0.898
10.4 92.22 80.6 13.74 150.8 2.998 221 0.873
12.2 87.35 82.4 13.16 152.6 2.896 222.8 0.848
14 82.75 84.2 12.6 154.4 2.797 224.6 0.825
15.8 78.43 86 12.07 156.2 2.702 226.4 0.802
17.6 74.35 87.8 11.57 158 2.611 228.2 0.779
19.4 70.5 89.6 11.09 159.8 2.523 230 0.758
21.2 66.88 91.4 10.63 161.6 2.439 231.8 0.737
23 63.46 93.2 10.2 163.4 2.358 233.6 0.717
24.8 60.23 95 9.779 165.2 2.28 235.4 0.697
26.6 57.18 96.8 9.382 167 2.206 237.2 0.678
28.4 54.31 98.6 9.003 168.8 2.133 239 0.66
30.2 51.59 100.4 8.642 170.6 2.064 240.8 0.642
32 49.02 102.2 8.297 172.4 1.997 242.6 0.625
33.8 46.6 104 7.967 174.2 1.933 244.4 0.608
35.6 44.31 105.8 7.653 176 1.871 246.2 0.592
37.4 42.14 107.6 7.352 177.8 1.811 248 0.577
39.2 40.09 109.4 7.065 179.6 1.754 249.8 0.561
41 38.15 111.2 6.791 181.4 1.699 251.6 0.547
42.8 36.32 113 6.529 183.2 1.645 253.4 0.532
44.6 34.58 114.8 6.278 185 1.594 255.2 0.519
46.4 32.94 116.6 6.038 186.8 1.544 257 0.505
48.2 31.38 118.4 5.809 188.6 1.497 258.8 0.492
50 29.9 120.2 5.589 190.4 1.451 260.6 0.48
51.8 28.51 122 5.379 192.2 1.408 262.4 0.467
53.6 27.18 123.8 5.197 194 1.363 264.2 0.456
55.4 25.92 125.6 4.986 195.8 1.322 266 0.444
57.2 24.73 127.4 4.802 197.6 1.282 267.8 0.433
59 23.6 129.2 4.625 199.4 1.244 269.6 0.422
60.8 22.53 131 4.456 201.2 1.207 271.4 0.412
62.6 21.51 132.8 4.294 203 1.171 273.2 0.401
64.4 20.54 134.6 4.139 204.8 1.136 275 0.391
66.2 19.63 136.4 3.99 206.6 1.103 276.8 0.382

100
SERVICE MANUAL
SERVICE MANUAL

Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)

Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ)


-2.2 181.4 68 25.01 138.2 5.13 208.4 1.427
-0.4 171.4 69.8 23.9 140 4.948 210.2 1.386
1.4 162.1 71.6 22.85 141.8 4.773 212 1.346
3.2 153.3 73.4 21.85 143.6 4.605 213.8 1.307
5 145 75.2 20.9 145.4 4.443 215.6 1.269
6.8 137.2 77 20 147.2 4.289 217.4 1.233
8.6 129.9 78.8 19.14 149 4.14 219.2 1.198
10.4 123 80.6 18.13 150.8 3.998 221 1.164
12.2 116.5 82.4 17.55 152.6 3.861 222.8 1.131
14 110.3 84.2 16.8 154.4 3.729 224.6 1.099
15.8 104.6 86 16.1 156.2 3.603 226.4 1.069
17.6 99.13 87.8 15.43 158 3.481 228.2 1.039
19.4 94 89.6 14.79 159.8 3.364 230 1.01
21.2 89.17 91.4 14.18 161.6 3.252 231.8 0.983
23 84.61 93.2 13.59 163.4 3.144 233.6 0.956
24.8 80.31 95 13.04 165.2 3.04 235.4 0.93
26.6 76.24 96.8 12.51 167 2.94 237.2 0.904
28.4 72.41 98.6 12 168.8 2.844 239 0.88
30.2 68.79 100.4 11.52 170.6 2.752 240.8 0.856
32 65.37 102.2 11.06 172.4 2.663 242.6 0.833
33.8 62.13 104 10.62 174.2 2.577 244.4 0.811
35.6 59.08 105.8 10.2 176 2.495 246.2 0.77
37.4 56.19 107.6 9.803 177.8 2.415 248 0.769
39.2 53.46 109.4 9.42 179.6 2.339 249.8 0.746
41 50.87 111.2 9.054 181.4 2.265 251.6 0.729
42.8 48.42 113 8.705 183.2 2.194 253.4 0.71
44.6 46.11 114.8 8.37 185 2.125 255.2 0.692
46.4 43.92 116.6 8.051 186.8 2.059 257 0.674
48.2 41.84 118.4 7.745 188.6 1.996 258.8 0.658
50 39.87 120.2 7.453 190.4 1.934 260.6 0.64
51.8 38.01 122 7.173 192.2 1.875 262.4 0.623
53.6 36.24 123.8 6.905 194 1.818 264.2 0.607
55.4 34.57 125.6 6.648 195.8 1.736 266 0.592
57.2 32.98 127.4 6.403 197.6 1.71 267.8 0.577
59 31.47 129.2 6.167 199.4 1.658 269.6 0.563
60.8 30.04 131 5.942 201.2 1.609 271.4 0.549
62.6 28.68 132.8 5.726 203 1.561 273.2 0.535
64.4 27.39 134.6 5.519 204.8 1.515 275 0.521
66.2 26.17 136.4 5.32 206.6 1.47 276.8 0.509

w w w . i n n o v a i r . c o m 101
SERVICE MANUAL

Resistance Table of Discharge Temperature Sensor for Outdoor(50K)

Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ)


-20.2 853.5 50 98 120.2 18.34 190.4 4.754
-18.4 799.8 51.8 93.42 122 17.65 192.2 4.609
-16.6 750 53.6 89.07 123.8 16.99 194 4.469
-14.8 703.8 55.4 84.95 125.6 16.36 195.8 4.334
-13 660.8 57.2 81.05 127.4 15.75 197.6 4.204
-11.2 620.8 59 77.35 129.2 15.17 199.4 4.079
-9.4 580.6 60.8 73.83 131 14.62 201.2 3.958
-7.6 548.9 62.6 70.5 132.8 14.09 203 3.841
-5.8 516.6 64.4 67.34 134.6 13.58 204.8 3.728
-4 486.5 66.2 64.33 136.4 13.09 206.6 3.619
-2.2 458.3 68 61.48 138.2 12.62 208.4 3.514
-0.4 432 69.8 58.77 140 12.17 210.2 3.413
1.4 407.4 71.6 56.19 141.8 11.74 212 3.315
3.2 384.5 73.4 53.74 143.6 11.32 213.8 3.22
5 362.9 75.2 51.41 145.4 10.93 215.6 3.129
6.8 342.8 77 49.19 147.2 10.54 217.4 3.04
8.6 323.9 78.8 47.08 149 10.18 219.2 2.955
10.4 306.2 80.6 45.07 150.8 9.827 221 2.872
12.2 289.6 82.4 43.16 152.6 9.489 222.8 2.792
14 274 84.2 41.34 154.4 9.165 224.6 2.715
15.8 259.3 86 39.61 156.2 8.854 226.4 2.64
17.6 245.6 87.8 37.96 158 8.555 228.2 2.568
19.4 232.6 89.6 36.38 159.8 8.268 230 2.498
21.2 220.5 91.4 34.88 161.6 7.991 231.8 2.431
23 209 93.2 33.45 163.4 7.726 233.6 2.365
24.8 198.3 95 32.09 165.2 7.47 235.4 2.302
26.6 199.1 96.8 30.79 167 7.224 237.2 2.241
28.4 178.5 98.6 29.54 168.8 6.998 239 2.182
30.2 169.5 100.4 28.36 170.6 6.761 240.8 2.124
32 161 102.2 27.23 172.4 6.542 242.6 2.069
33.8 153 104 26.15 174.2 6.331 244.4 2.015
35.6 145.4 105.8 25.11 176 6.129 246.2 1.963
37.4 138.3 107.6 24.13 177.8 5.933 248 1.912
39.2 131.5 109.4 23.19 179.6 5.746 249.8 1.863
41 125.1 111.2 22.29 181.4 5.565 251.6 1.816
42.8 119.1 113 21.43 183.2 5.39 253.4 1.77
44.6 113.4 114.8 20.6 185 5.222 255.2 1.725
46.4 108 116.6 19.81 186.8 5.06 257 1.682
48.2 102.8 118.4 19.06 188.6 4.904 258.8 1.64

102
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

11. Removal Procedure


Warning: Be sure to wait for a minimum
for KIN321C2V31 , KIN824C2V31 of 20 minutes after turning off all power
supplies and discharge the refrigerant
11.1 Removal Procedure of Indoor Unit completely before removal.

1. Remove filter as s y
Front panel

Open the front panel. Push the left and right


filters to make them break away from the
groove on the front case. Then remove the left
and right filters one by one. Front
Left filter case

Groove Right filter

Screw off the 2 screws that are locking the


display board. Separate the display board from
the front panel.

w w w . i n n o v a i r . c o m 103
SERVICE MANUAL

Electric box cover 2


4. Remove electric box cover 2 and detecting plate(WIFI)
Screw

Remove the screws on the electric box


cover 2 and detecting plate(WIFI), then
remove the electric box cover 2 and Screws
detecting plate(WIFI).

Detecting plate
(WIFI)

Loosen the connection clasps between


front case sub-assy and bottom case.
Lift up the front case sub-assy and take
it out.

Screw off the screws that are locking S wing motor


the swing motor and take the motor off.

104
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Indoor tube
Cut off the wire binder and pull out the temperature s ensor
indoor tube temperature sensor.
Screw off one grounding screw.
Main
Remove the wiring terminals of motor and
stepping motor. board
Remove the electric box assy. G rounding
Screw off the screws that are locking each s c rew Wi ring
lead wire. terminal
of motor
Wire binder

Wiring
terminal
of stepping
S crew motor

Rotate the electric box assy. Twist off the screws


that are locking the wire clip and loosen the S crew
power cord. Remove the wiring terminal of
power cord. Lift up the main board and take it off. P ower cord

Wire clip

w w w . i n n o v a i r . c o m 105
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

G roove
R ear case ass y

First remove the left side of evaporator from


the groove on the rear case assy. Then
remove the right side from the clasp on the
rear case assy. C lasp

106
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

w w w . i n n o v a i r . c o m 107
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

11.2 Removal Procedure of Outdoor Unit


Warning: Be sure to wait for a minimum of 20 minutes after
turning off all power supplies and discharge the refrigerant
completely before removal.
NOTE: Take GWH24QE-D3DNA6E/O for example.

Steps Procedure

1. Remove big handle,valve cover and top cover

a Remove the screw connecting the big handle and big handle
right side plate, and then remove the big handle.
Remove the screw connecting the valve cover and
right side plate, and then remove the valve cover.

valve cover

b Remove the screws connecting the top cover with


top cover
outer case, right side plate and left side plate; lift
the top cover upwards to remove it.

2. Remove grille and outer case

Remove the 4 screws connecting the grille and


outer case, and then remove the panel grille.

grille

108
SERVICE MANUAL
SERVICE MANUAL

Steps Procedure

Remove the screws connecting the outer case with


motor support, isolation plate and chassis; lift the
outer case upwards; loosen the clasps of outer
case with right side plate and left side plate, and
then remove the outer case.

outer case

3. Remove right&left side plate

a Remove the screws connecting the right side plate


with electric box assy, valve support, chassis and
condenser side plate, and then remove the right
side plate.

right side plate

b Remove the screws connecting the left side plate


with chassis, and then remove the left side plate.

left side plate

w w w . i n n o v a i r . c o m 109
SERVICE MANUAL

Steps Procedure
4. Remove axial flow blade

a Remove the nut fixing axial flow blade and then


remove the blade. axial flow fan

motor support

b Remove the 6 screws fixing the motor and then


remove the motor.
Remove the 2 screws connecting the motor support
and chassis, and then loosen the stopper to remove
the motor support.

fan motor

5. Remove electric box

electric box

Remove the screws fixing the electric box sub-assy;


loosen the wire bundle; pull out the wiring terminals
and then pull the electric box upwards to remove it.

110
SERVICE MANUAL
SERVICE MANUAL

Steps Procedure
6. Remove the soundproof sponge

Tear off the sticking stripe and then remove the


soundproof sponge.

soundproof sponge

7. Remove isolation plate

Remove the 2 screws connecting the isolation plate


and condenser side plate; remove the 3 screws
connecting the isolation plate and chassis, and then
remove the isolation plate.

isolation plate

8. Remove 4-way valve assy

Unsolder the welding joints connecting the 4-way 4-way valve assy
valve assy with capillary sub-assy, compressor and
condenser; remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.

w w w . i n n o v a i r . c o m 111
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Steps Procedure
9. Remove compressor

Remove the 3 foot nuts fixing compressor and then compressor


lift the compressor upwards to remove the
compressor and damping cushion.
Note:
Keep the ports of discharge pipe and suction pipe
from foreign objects.

10. Remove condenser sub-assy

support
a Remove the screws connecting the support
(condenser) and condenser assy,and then remove
the support(condenser).

condenser
sub-assy
b Remove the 2 screws fixing the condenser and
chassis, and then lift the condenser upwards to
remove it.

chassis subassy

112
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL
SERVICE MANUAL

Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25

Appendix 2: Configuration of Connection Pipe


1.Standard length of connection pipe
● 16.40ft, 24.61ft, 26.25ft.
2.Min. length of connection pipe is 9.84ft.
3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications)
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 32.81ft at the basis of standard length, you should add 5ml of refrigerant oil
for each additional 16.40ft of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional
refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter

Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(inch) Gas pipe(inch) Cooling only(oz/ft.) Cooling and heating(oz/ft.)
Ф1/4 Ф3/8or Ф1/2 0.53 0.71
Ф1/4 or Ф3/8 Ф5/8 or Ф3/4 0.53 1.76
Ф1/2 Ф3/4 or Ф7/8 1.06 4.23
Ф5/8 Ф1 or Ф1 1/4 2.12 4.23
Ф3/4 / 8.82 8.82
Ф7/8 / 12.35 12.35

w w w . i n n o v a i r . c o m 113
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Appendix 3: Pipe Expanding Method


Pipe
Note:

Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.

B:Remove the burrs Pipe

● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper

Downwards
C:Put on suitable insulating pipe

D:Put on the union nut Union pipe


● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe. Pipe

E:Expand the port


● Expand the port with expander.
Hard
Note: mold
Expander
● "A" is different according to the diameter, please refer to the sheet below:
A(inch) Pipe
Outer diameter(inch)
Max Min
Ф1/4 2/39 1/36
Ф3/8 1/16 1/51
Ф1/2 1/14 1/51
Ф5/8 5/53 2/23

Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.

leaning damaged crack uneven


surface thickness
The length is equal

114
SERVICE MANUAL
SERVICE MANUAL

Appendix 4: List of Resistance for Temperature Sensor


Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K)

Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ)


-2.2 138.1 68 18.75 138.2 3.848 208.4 1.071
-0.4 128.6 69.8 17.93 140 3.711 210.2 1.039
1.4 121.6 71.6 17.14 141.8 3.579 212 1.009
3.2 115 73.4 16.39 143.6 3.454 213.8 0.98
5 108.7 75.2 15.68 145.4 3.333 215.6 0.952
6.8 102.9 77 15 147.2 3.217 217.4 0.925
8.6 97.4 78.8 14.36 149 3.105 219.2 0.898
10.4 92.22 80.6 13.74 150.8 2.998 221 0.873
12.2 87.35 82.4 13.16 152.6 2.896 222.8 0.848
14 82.75 84.2 12.6 154.4 2.797 224.6 0.825
15.8 78.43 86 12.07 156.2 2.702 226.4 0.802
17.6 74.35 87.8 11.57 158 2.611 228.2 0.779
19.4 70.5 89.6 11.09 159.8 2.523 230 0.758
21.2 66.88 91.4 10.63 161.6 2.439 231.8 0.737
23 63.46 93.2 10.2 163.4 2.358 233.6 0.717
24.8 60.23 95 9.779 165.2 2.28 235.4 0.697
26.6 57.18 96.8 9.382 167 2.206 237.2 0.678
28.4 54.31 98.6 9.003 168.8 2.133 239 0.66
30.2 51.59 100.4 8.642 170.6 2.064 240.8 0.642
32 49.02 102.2 8.297 172.4 1.997 242.6 0.625
33.8 46.6 104 7.967 174.2 1.933 244.4 0.608
35.6 44.31 105.8 7.653 176 1.871 246.2 0.592
37.4 42.14 107.6 7.352 177.8 1.811 248 0.577
39.2 40.09 109.4 7.065 179.6 1.754 249.8 0.561
41 38.15 111.2 6.791 181.4 1.699 251.6 0.547
42.8 36.32 113 6.529 183.2 1.645 253.4 0.532
44.6 34.58 114.8 6.278 185 1.594 255.2 0.519
46.4 32.94 116.6 6.038 186.8 1.544 257 0.505
48.2 31.38 118.4 5.809 188.6 1.497 258.8 0.492
50 29.9 120.2 5.589 190.4 1.451 260.6 0.48
51.8 28.51 122 5.379 192.2 1.408 262.4 0.467
53.6 27.18 123.8 5.197 194 1.363 264.2 0.456
55.4 25.92 125.6 4.986 195.8 1.322 266 0.444
57.2 24.73 127.4 4.802 197.6 1.282 267.8 0.433
59 23.6 129.2 4.625 199.4 1.244 269.6 0.422
60.8 22.53 131 4.456 201.2 1.207 271.4 0.412
62.6 21.51 132.8 4.294 203 1.171 273.2 0.401
64.4 20.54 134.6 4.139 204.8 1.136 275 0.391
66.2 19.63 136.4 3.99 206.6 1.103 276.8 0.382

w w w . i n n o v a i r . c o m 115
INNOVAIR INVERTER PRESTIGE SERVICE MANUAL

Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)

Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ)


-2.2 181.4 68 25.01 138.2 5.13 208.4 1.427
-0.4 171.4 69.8 23.9 140 4.948 210.2 1.386
1.4 162.1 71.6 22.85 141.8 4.773 212 1.346
3.2 153.3 73.4 21.85 143.6 4.605 213.8 1.307
5 145 75.2 20.9 145.4 4.443 215.6 1.269
6.8 137.2 77 20 147.2 4.289 217.4 1.233
8.6 129.9 78.8 19.14 149 4.14 219.2 1.198
10.4 123 80.6 18.13 150.8 3.998 221 1.164
12.2 116.5 82.4 17.55 152.6 3.861 222.8 1.131
14 110.3 84.2 16.8 154.4 3.729 224.6 1.099
15.8 104.6 86 16.1 156.2 3.603 226.4 1.069
17.6 99.13 87.8 15.43 158 3.481 228.2 1.039
19.4 94 89.6 14.79 159.8 3.364 230 1.01
21.2 89.17 91.4 14.18 161.6 3.252 231.8 0.983
23 84.61 93.2 13.59 163.4 3.144 233.6 0.956
24.8 80.31 95 13.04 165.2 3.04 235.4 0.93
26.6 76.24 96.8 12.51 167 2.94 237.2 0.904
28.4 72.41 98.6 12 168.8 2.844 239 0.88
30.2 68.79 100.4 11.52 170.6 2.752 240.8 0.856
32 65.37 102.2 11.06 172.4 2.663 242.6 0.833
33.8 62.13 104 10.62 174.2 2.577 244.4 0.811
35.6 59.08 105.8 10.2 176 2.495 246.2 0.77
37.4 56.19 107.6 9.803 177.8 2.415 248 0.769
39.2 53.46 109.4 9.42 179.6 2.339 249.8 0.746
41 50.87 111.2 9.054 181.4 2.265 251.6 0.729
42.8 48.42 113 8.705 183.2 2.194 253.4 0.71
44.6 46.11 114.8 8.37 185 2.125 255.2 0.692
46.4 43.92 116.6 8.051 186.8 2.059 257 0.674
48.2 41.84 118.4 7.745 188.6 1.996 258.8 0.658
50 39.87 120.2 7.453 190.4 1.934 260.6 0.64
51.8 38.01 122 7.173 192.2 1.875 262.4 0.623
53.6 36.24 123.8 6.905 194 1.818 264.2 0.607
55.4 34.57 125.6 6.648 195.8 1.736 266 0.592
57.2 32.98 127.4 6.403 197.6 1.71 267.8 0.577
59 31.47 129.2 6.167 199.4 1.658 269.6 0.563
60.8 30.04 131 5.942 201.2 1.609 271.4 0.549
62.6 28.68 132.8 5.726 203 1.561 273.2 0.535
64.4 27.39 134.6 5.519 204.8 1.515 275 0.521
66.2 26.17 136.4 5.32 206.6 1.47 276.8 0.509

116
SERVICE MANUAL
SERVICE MANUAL

Resistance Table of Discharge Temperature Sensor for Outdoor(50K)

Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ) Temp.(oF) Resistance(kΩ)


-20.2 853.5 50 98 120.2 18.34 190.4 4.754
-18.4 799.8 51.8 93.42 122 17.65 192.2 4.609
-16.6 750 53.6 89.07 123.8 16.99 194 4.469
-14.8 703.8 55.4 84.95 125.6 16.36 195.8 4.334
-13 660.8 57.2 81.05 127.4 15.75 197.6 4.204
-11.2 620.8 59 77.35 129.2 15.17 199.4 4.079
-9.4 580.6 60.8 73.83 131 14.62 201.2 3.958
-7.6 548.9 62.6 70.5 132.8 14.09 203 3.841
-5.8 516.6 64.4 67.34 134.6 13.58 204.8 3.728
-4 486.5 66.2 64.33 136.4 13.09 206.6 3.619
-2.2 458.3 68 61.48 138.2 12.62 208.4 3.514
-0.4 432 69.8 58.77 140 12.17 210.2 3.413
1.4 407.4 71.6 56.19 141.8 11.74 212 3.315
3.2 384.5 73.4 53.74 143.6 11.32 213.8 3.22
5 362.9 75.2 51.41 145.4 10.93 215.6 3.129
6.8 342.8 77 49.19 147.2 10.54 217.4 3.04
8.6 323.9 78.8 47.08 149 10.18 219.2 2.955
10.4 306.2 80.6 45.07 150.8 9.827 221 2.872
12.2 289.6 82.4 43.16 152.6 9.489 222.8 2.792
14 274 84.2 41.34 154.4 9.165 224.6 2.715
15.8 259.3 86 39.61 156.2 8.854 226.4 2.64
17.6 245.6 87.8 37.96 158 8.555 228.2 2.568
19.4 232.6 89.6 36.38 159.8 8.268 230 2.498
21.2 220.5 91.4 34.88 161.6 7.991 231.8 2.431
23 209 93.2 33.45 163.4 7.726 233.6 2.365
24.8 198.3 95 32.09 165.2 7.47 235.4 2.302
26.6 199.1 96.8 30.79 167 7.224 237.2 2.241
28.4 178.5 98.6 29.54 168.8 6.998 239 2.182
30.2 169.5 100.4 28.36 170.6 6.761 240.8 2.124
32 161 102.2 27.23 172.4 6.542 242.6 2.069
33.8 153 104 26.15 174.2 6.331 244.4 2.015
35.6 145.4 105.8 25.11 176 6.129 246.2 1.963
37.4 138.3 107.6 24.13 177.8 5.933 248 1.912
39.2 131.5 109.4 23.19 179.6 5.746 249.8 1.863
41 125.1 111.2 22.29 181.4 5.565 251.6 1.816
42.8 119.1 113 21.43 183.2 5.39 253.4 1.77
44.6 113.4 114.8 20.6 185 5.222 255.2 1.725
46.4 108 116.6 19.81 186.8 5.06 257 1.682
48.2 102.8 118.4 19.06 188.6 4.904 258.8 1.64

w w w . i n n o v a i r . c o m 117

You might also like