Intecont - Tersus Operating Manual
Intecont - Tersus Operating Manual
Instruction Manual
BV-H2464 GB
PASS - Service you can rely on
Fast, comprehensive, anywhere in the world
Table of Contents
2 Safety notes................................
notes................................................................
................................................................................................
................................................................................................
..........................................................................
..........................................3
..........3
2.1 Signal Words .........................................................................................................................................4
2.1.1 Signal Words for Safety Warnings ................................................................................................4
2.1.2 Signal Words for Application Notes ..............................................................................................5
2.2 Five Safety Rules of Electrical Engineering ..........................................................................................5
2.3 Damaged / Defective Electrical Components ........................................................................................6
4 Operation................................................................
................................................................................................
................................................................................................
............................................................................
............................................15
4.1 Quick guide ......................................................................................................................................... 15
4.2 Function block..................................................................................................................................... 17
4.3 Operating in Normal Operation........................................................................................................... 18
13 Parameters ................................................................
................................................................................................
................................................................................................
.........................................................................
.........................................49
13.1 Abbreviations ...................................................................................................................................... 50
13.2 Configuring Event Messages.............................................................................................................. 50
13.3 Parameter Listing .............................................................................................................................. 51
13.3.1 Parameter Overview .................................................................................................................. 51
13.3.2 Parameter Details ...................................................................................................................... 60
13.3.2.1 Parameter Block 01 - Dialog Behaviour ..................................................................................... 60
13.3.2.2 Parameter Block 02 - Rated Data .............................................................................................. 64
13.3.2.3 Parameter Block 03 - Calibration Data ...................................................................................... 67
13.3.2.4 Parameter Block 04 - Calibrat. Results ...................................................................................... 68
13.3.2.5 Parameter Block 05 - Analog Outputs ....................................................................................... 69
13.3.2.6 Parameter Block 06 - Limit Values ............................................................................................. 71
13.3.2.7 Parameter Block 07 - Filters....................................................................................................... 73
13.3.2.8 Parameter Block 08 - AUTO Zero Set ....................................................................................... 74
13.3.2.9 Parameter Block 09 - Batch Mode ............................................................................................. 76
13.3.2.10 Parameter Block 10 - Printer Setting ......................................................................................... 79
13.3.2.11 Parameter Block 11 - Maintenance interval ............................................................................... 82
13.3.2.12 Parameter Block 12 - Feeder Control ........................................................................................ 83
13.3.2.13 Parameter Block 13 - Belt Monitoring ........................................................................................ 84
13.3.2.14 Parameter Block 14 - Events ..................................................................................................... 87
13.3.2.15 Parameter Block 15 - Linearization ............................................................................................ 90
13.3.2.16 Parameter Block 16 - Digital Inputs ........................................................................................... 92
13.3.2.17 Parameter Block 17 - Digital Outputs ......................................................................................... 93
13.3.2.18 Parameter Block 18 - Communication EasyServe ..................................................................... 95
13.3.2.19 Parameter Block 19 - Communication Fieldbus......................................................................... 96
13.3.2.20 Parameter Block 20 - Fixed mode configuration ...................................................................... 101
13.3.2.21 Parameter Block 21 - Ethernet ................................................................................................. 103
13.3.2.22 Parameter Block 22 - Data Logging ......................................................................................... 104
13.3.2.23 Parameter Block 23 - Configuration HMI Values ..................................................................... 106
13.3.2.24 Parameter Block 24 - Second Display ..................................................................................... 108
14 Event
Event messages ................................................................
................................................................................................
...............................................................................................
............................................................... 111
15 Events ................................................................
................................................................................................
................................................................................................
..............................................................................
.............................................. 113
15.1 Events Details ................................................................................................................................... 113
15.1.1 Event Group: Calibration .......................................................................................................... 113
15.1.2 Event Group: Controller ........................................................................................................... 114
15.1.3 Event Group: Electrical System ............................................................................................... 114
15.1.4 Event Group: Interlock ............................................................................................................. 115
15.1.5 Event Group: Material Flow...................................................................................................... 115
15.1.6 Event Group: MAX ................................................................................................................... 115
18 Appendix ................................................................
................................................................................................
................................................................................................
..........................................................................
.......................................... 137
18.1 Service Values .................................................................................................................................. 137
18.2 Set option.......................................................................................................................................... 138
18.3 Function Check ................................................................................................................................. 139
18.4 Test Connector ................................................................................................................................. 140
18.5 Starting and Stopping ....................................................................................................................... 141
18.6 Measuring at the Discharge Point VAP ............................................................................................ 142
18.7 Belt Monitoring .................................................................................................................................. 142
18.8 BIC belt impact compensation .......................................................................................................... 143
18.9 Linearization ..................................................................................................................................... 143
Index ................................................................
................................................................................................
................................................................................................
................................................................................
................................................ 145
This operating manual for belt weighersis intended for the service technician. It describes the functionality
of the VBW 20650-xxx software.
2 Safety notes
To avoid personal injury and material damage, follow the safety regulations stated below.
Additionally you should also observe:
▪ Safety information given in order-specific documentation
▪ Safety information relating to mechanical components
▪ Instructions and safety instructions for parts manufactured by thrid-party suppliers or parts that are not
part of Schenck's scope of delivery.
When performing installation, commissioning and service work, observe all applicable local regulations.
Intended Application
The measuring system and its connected mechanical components are exclusively designed for weighing
and controlling tasks. Any use other than originally intended is considered inappropriate.
Sources of Risk
If the measuring system has been correctly installed and commissioned, it does not pose any danger during
weigh operations.
Hazards may arise when the system is used for control operations or for transporting weighed goods. Po-
tential hazards may then arise from e.g. additional devices through which the weighed goods are passed or
metered. Minor risks may arise in these situations if the measuring system is used or operated by untrained
personnel.
The measuring system can be part of a more complex plant. The system operating company is fully respon-
sible for the operating safety of the system.
Personnel
Preparation, assembly, commissioning, operation, maintenance and servicing may only be carried out by
qualified personnel.
All persons working on the system are required to observe the safety hints and know the parts of the tech-
nical documentation relevant to their work.
The operating company is responsible for instructing his operators to observe all regulations and instruc-
tions given.
Changing Parameters
The measuring system's functionality is determined by parameters. Only personnel familiar with the device's
mode of operation may alter these parameters (e.g. after training by Schenck Process). Incorrectly set pa-
rameters may cause injury or material damage. Furthermore they may also cause considerable disruption to
weigh operations.
Password
Passwords safeguard the parameters against unauthorized alteration. The measuring system operating
company must ensure that the password is handled safely.
Design Modifications
Unauthorized modifications to the system and/or use of replacement parts not supplied by Schenck Process
voids Schenck Process's liability for any resulting damages. This especially applies to alterations which
could affect the operating safety of the system.
Replacing Components
Spare parts must meet the technical specifications indicated by Schenck Process. To ensure this require-
ment is met, only genuine Schenck Process spare parts should be used. When using other spare parts, the
warranty will be void.
In this manual the following signal words will indicate hazards that may arise when using this machine:
DANGER
This signal word indicates a danger that can immediately cause the
most severe injuries up to and including death.
Follow all instructions to prevent this from occurring.
WARNING
This signal word indicates a danger that can cause serious injuries up
to and including death.
Follow all instructions to prevent this from occurring.
CAUTION
This signal word indicates a danger that can cause slight or medium
injuries.
Follow all instructions to prevent this from occurring.
Signal words for information on material damages and on the optimal use of the machine
STRICTLY OBSERVE
Signal word used to identify situations in which material or environ-
mental damage could occur.
Follow all instructions to prevent this from occurring.
HINT
Signal word used to identify information on using the product eco-
nomically and at an optimal level of efficiency.
These fives safety rules must be followed in the order shown before work is begun on electrical systems.
Once the work is finished, they are to be applied in reverse order.
DANGER
Electric shock from live components.
There is a danger of life from an electric shock.
– Take all possible precautions to ensure safety before work is begun on
live components. Observe, among other things, the following:
1. Disconnect the components.
2. Secure them against inadvertent restart.
3. Ensure that the components have been de-energized.
4. Above 1 KV: earth and bypass the cables.
5. Cover or shield adjacent, live components.
DANGER
Live damaged or defective components
There is a danger of life from an electric shock.
– Always have qualified personnel ensure that the components are nei-
ther damaged nor defective.
1. Qualified personnel must immediately replace or, if possible, repair
damaged or defective electrical components.
3 General Diagram
INTECONT Tersus is an extension of and improvement on the INTECONT system that has proven its worth
for years and has been used in more than 50,000 scales all over the world.
INTECONT Tersus is a measuring and measurement processing system of continuous weighing and feed-
ing equipment for
▪ weighfeeders
▪ conveyor belt scales
▪ differential feeding scales
▪ Coriolis mass flow equipment and
▪ solids flow equipment.
A belt weigher or weighfeeder continuously weighs the quantity of material transported by a conveyor belt.
The feed rate is regulated on a weighfeeder according to a setpoint. A belt weigher only measures and it
cannot influence the feed rate.
Definitions
Belt load Q and speed v are continuously measured and factored together. The result is the feed rate I, from
which the flow rate is determined.
Fig. 2: The belt load of the weighbridge is not legal for trade
The material is transported over a weighing platform located beneath the belt, limited by 2 carrying idlers.
The load on the platform exerts a force on the load cell LC through one or more weighing idlers. The mea-
suring displacement is approximately 0.2 mm. The measuring rolls are linked with the frame construction via
parallel plate springs. The load cell output voltage is proportional to the platform load. It is recorded with a
suitable measuring amplifier.
The load distribution on a single-roll weighbridge is shown by the white triangle. Only half of the force from
the weight of the material is passed into the measuring idler. The following conversion formula applies to the
effective bridge length with single-roll weighbridges:
Weighing platforms with more than one weighing idler will have a different factor than 1/2.
Therefore the belt load in kg/m totals:
Belt speed
The belt speed is recorded using velocity sensor D and converted into a corresponding pulse frequency.
Feed rate
The readings Q and v are standardized in the unit to the physical quantities kg/m and m/s and multiplied
with one another. The product is feed rate I.
I in kg/s
Q in kg/m
v in m/s
QB in kg
Leff in m
I in kg/h
3.4 Characteristics
Displays
The display of INTECONT Tersus consists of 4 parts:
1. You can give the technical name at the installation location in the header. A rotating symbol on the left
edge shows whether the weighfeeder is on or off.
2. The second line of the display is reserved for event messages.
3. The following two lines show readings that can be selected with the cursor buttons. These lines cor-
respond to the lines of the INTECONT PLUS display.
The lower half of the display is used for various visualizations: the large-scale display of an individual read-
ing, displaying 4 readings in line font size or displaying as many as 9 adjustable readings in the parameters
block Configuration HMI Values. They adapt their font size over 3 levels.
Event messages
▪ Events and malfunctions are shown by an alphanumerical shorthand symbol and title.
▪ The appropriate "uncoded text" for all subsequent events can be called up via the operating keyboard.
▪ This distinguishes alarms (red) and warnings that either have to be acknowledged (orange) or do not
have to be acknowledged (yellow). Alarms will shut down the scales, warnings will not. All alarms are al-
so indicated with a relay output.
Operating philosophy
▪ Operator guidance through menus on several levels. Important configuration and calibration functions
are secured via password.
The dialog language for fault messages, operation and service programs
▪ DEUTSCH, ENGLISH, FR-FRANCAIS, ES-ESPANOL, IT-ITALIANO, CN-CHINESE, JP-JAPANESE,
RU-RUSSIAN, HU-HUNGARIAN, NL-NETHERLAND at your choice or a loadable language (OTHER /
XX-NEW).
Dimensions
▪ SI units (Metric): kg, kg/h, t, t/h, m and cm
▪ NON SI units (English): lb, lb/h, t, t/h, f and inches
▪ This can be selected with the P02.06 Feeder Start and FALSE Feedrate Setpoint parameters (howev-
er, only with charging systems).
Belt speed
▪ The belt speed is recorded with a speed pick-up.
Zero settings
▪ The zero point fault of the belt weigher comes from soiling that adheres permanently or from other con-
stant factors. The zero setting records the zero point fault on an empty belt over one or several whole-
number belt circuits. This corrects the regular measurement in normal operation.
▪ Zero setting takes place with an empty belt conveyor with a program which runs automatically.
▪ Zero setting should be started manually at regular intervals if automatic operation is not preselected.
▪ The maximum permitted zero setting correction is monitored.
Tare
▪ Taring is a calibration procedure that determines the impact that the empty belt has on the measuring
signal, the basic tare. After taring, the total remains unchanged over one belt circuit with the empty belt.
Call-up is password protected.
Batching mode
▪ Batch mode conveys a preset amount of material. The conveying process ends once the batch setpoint
has been reached. The batching process can be controlled via the belt conveyor drive or bin feeder.
▪ The turn-off point and dribble feed utilization can be adapted automatically.
Display filters
▪ For feed rate, belt load and belt speed
Calibration
▪ It is not necessary to calibrate the pick-up input. Certain design data such as on the load cells, velocity
sensors and conveyor belt inclination must be entered. The system uses this data to calculate all stan-
dardizations required for the displays. It can be controlled or readjusted using two different methods.
▪ Control with material: the result of a material inspection is entered into the system and it serves to cor-
rect the measurement result.
▪ Control with calibration weight: standardization is controlled or can also be corrected if the technical data
(such as the lever ratio or belt conveyor inclination) is not precisely known.
In later operation, the program also becomes suitable for verifying mechanical changes such as the
weighing platform being twisted due to movement of the foundations.
4 Operation
Line 1: header rotating cross as a progress indicator. The scales are switched on; feed rate and flow
rate are being recorded. In belt-based systems, only the belt load and belt speed are
measured when the device is switched off (single point displayed).
Ɖ : with activated batching mode
local designation of the feeder. This can be changed with EasyServe using the parame-
ter P01.05.
Line 2: event line event information with a code and plain text
Upper display area two lines of actual values. These lines correspond to the two lines of INTECONT PLUS.
Lower display area Actual values that can be selected for display with buttons 0 - 9. The functions of buttons
4 - 7 depend on the application software and parameterization.
Operating elements:
SCROLL
▪ Pre-select which data will be displayed in the upper line
▪ Select a parameter group or a single parameter
Select the desired function for the first level. This field has a yellow back-
ground.
Change to the second level. The field selected for the first level has an
orange background.
Select the desired function of the second level. This field has a yellow
background.
Select function. Only those functions that can be called up at that moment
will be displayed.
You will return to the normal display if no key is pressed in the function distributor within 60 seconds.
Setup
Totals
Mode
Calibration
Parameter
Printer Set-
ting
Batch
Configuration and parameter functions are only accessible via password. The password is queried once the
function has been called up.
Access to some functions can be configured in the Dialog Behaviour block. Certain entries may be missing
depending upon this setting.
The feeder drive can be switched on and off with the keys in this field if the mode of operation and the pa-
rameterization permit it.
WARNING
A start signal will actuate the motors!
There is the danger of injury if persons are in the area of the drives. Bulk
solids can be transported and cover the following equipment.
The switch-off command is not an emergency-off, but rather is normal op-
erational shutdown.
Totals
Reset Totalizer 1 or
Reset Totalizer 2
Calibration
>0< Zero Set
Call up other functions such as displaying event information, adjustment, etc. and return from the func-
tion distributor
……
Acknowledge input
5 Service Functions
Service functions help get an overview of the status of the unit and the weighing system.
Service Values activates the display of other internal status information in the lower line of the display Ser-
vice Values. This line has a grey background. The return from this display takes place from Standard Values
.
The other functions operate the routines set in the parameter block Data Logging.
This function displays the software version and tests the display.
Setup
Display Check Overlay the software version number
Overlay the Schenck Process Logo
The test ends automatically
6 Counter functions
Reset Totalizer 1
Reset Totalizer 2 Totals
Totalizer Record
The Totalizer Record function starts a printout of the counter. The printout is made to a file that can be read
using the web server. For beltweighers and legal-for-trade beltweighers a protocol can also be sent to a
connected printer.
7 Mode functions
There are functions brought together in the Mode menu for switching over into various operating modes.
Functions: Mode
Display:
One part of the actual value display in the upper display area is the line containing information on the status
and process of the program. Here OP signifies that OP Mode is active.
7.2 Prefeeder
The Particip. Prefeeder or Stop Prefeeder functions determine the impact of INTECONT on the prefeeder.
This function is activated in normal operation and INTECONT takes on controlling the prefeeder. The ma-
terial flow is interrupted when it is off and the scale can be tared, etc.
7.3 Simulation
In simulation mode, all functions of the scales can be tested without material during start-up. The scales
cannot be used for normal operation during simulation.
Display:
▪ Event message SY14 Event: Simulation active
▪ One part of the actual value display in the upper display area is the line containing information on the
status and process of the program: Here 'SIM' signifies that Simulation Mode is active.
▪ This function can be turned off again with Stop Simulation in the same fashion.
Characteristics:
1. All operation functions can be executed
2. The actual feed rate is set at the setpoint feed rate for feeder systems. This value will be set as per
P02.02 Nominal Flow Rate for measuring systems.
3. Belt load and speed measuring are active for belt-based systems.
4. All inputs and outputs operate as set.
8 Calibration functions
Functions: Calibration
Calibration
Afterwards you will be shown the dialog of the selected adjustment program.
The amount of impulses given by the speed sensor for one belt circuit is calculated. Afterwards, the number
of impulses acts as a belt circuit identifier for the TW: Tare, CW: Span Calibration programs and zeroing.
This program should be called up at initial calibration as the first of all adjustment programs. This also ap-
plies to scales without speed measurement.
Preconditions:
1. Measure the time for a belt circuit as precisely as possible and key in as theP03.02 Belt Circuit Time
parameters before calling up
2. The conveyor belt has to run
3. Volumetric mode (weighfeeders only)
4. Switch off batch mode
Note:
Belt drive and prefeeder are not controlled by the set-up program. The setup program will be interrupted
with a corresponding message if one of the conditions is not met.
Sequence:
Calibration
LB: Pulses/Belt
While the program is running, the remaining seconds of the program running time and the impulses added
up with the velocity sensor are shown in the display.
LB: Calibration active is shown in the header.
After ending the program, the mean belt speed is shown in the display over the entire running period
along with the final result of impulses/belt circuit.
There is the request 'LB: wait for Confirmation' in the header.
The results are accepted and filed in P04.06 Belt Circuit No. parameters.
Specific Messages:
Start ! if the belt is not running
Aborted !
Note:
The program routine is slightly different if there is a P13.03 Belt Sensor Active belt sensor:
The new reading is shown for impulses/belt circuit after every belt circuit.
If the sensor is not correctly identified, it gives the Error Sensor message and the adjustment program is
cancelled.
8.3 Tare TW
The taring program uses one or several whole-number belt circuits to record the zero point error of the belt-
weigher or weighfeeder. This value is used to correct the ongoing measuring results in normal operation.
We should distinguish taring from zeroing.
Taring: Recording of the base tares (i.e., the weight of such things as the mechanism or
belt conveyor) when starting up, servicing and doing maintenance
Conditions:
1. Under no circumstances may there be any material on the belt. The prefeeder can be controlled with
'Feeder ON/OFF' function
2. The mechanical equipment within the scales area must be cleaned. You may leave deposits that will
develop again immediately in regular operation
3. Switch off batch mode
4. The belt conveyor must be running. Notice is given automatically
Sequence:
Calibration
TW: Tare
While the program is running, the display shows the remaining running period in % of the entire running
period and the constantly meaned tare in % of the rated belt load.
TW: Calibration active is shown in the header.
After ending the program, the display shows how much tare departs from prior taring in % of the rated belt
load and the mean of the entire tare in % of the rated belt load.
Dev = + : tare has increased
Dev = - : tare has decreased
The TW: wait for Confirmation message in the header reports the end of the program and requests user
input.
The result is accepted and stored in the P04.04Basic Tare parameters. At the
same time, P04.05 Tare Correction is set to zero.
The result is not accepted and the scales are not tared.
Specific Messages:
Start ! if the belt is not running
Aborted !
NOTE!
Tare may exceed 100 % by using the rated belt load as reference.
CAUTION
If the deviation (Dev) is substantial (>20 %), this may indicate a me-
chanical fault.
The weighbridge must then be checked for stuck material particles.
Preconditions:
1. Tare or zero
2. Key in the calibration weight in P03.08 parameters. The calibration weight should be between 30 % and
100 % of the Qo rated bridge load.
Sequence:
Function Distributor
Calibration
CW: Span Calibration
While the program is running the remaining running period is shown in the display as a % of the total ad-
justment period along with the continual measuring result Set/Act.
'CW: Calibration active' will be displayed in the header.
After ending the program, the fictitiously conveyed quantity of material is shown in the display along with
the mean of KOR of the Set/Act.
The CW: wait for Confirmation message in the header reports the end of the program and requests user
input.
Exiting the program. Either button may be used AS THE RESULT IS NOT
ACCEPTED AUTOMATICALLY.
Specific Messages:
Start ! if the belt is not running
Aborted !
NOTE!
If no test weight is used the quality after a taring or the zeroing of the scales can be checked with this pro-
gram. In the results display the fictitious quantity conveyed over the runtime of the adjustment program -
which after a taring or a zeroing ought to be practically 0.00 kg - is shown in kg. The scales mechanics must
be checked if the error is too large.
The current value of the P04.02 Range Correction parameter is not taken into account in the check.
This is why the control program will show the same KOR fault quotients after correcting with the value input in
P04.02.
The date and time are among the Service Values status information for the scale and
they can be changed at any time.
Calibration
Set Time
…
Confirm each entry.
After the seconds have been entered and confirmed, the new time will be
accepted.
Then it shows the new setting for a couple of seconds as Current Time.
The internal clock will run for a further approx. 5 days in case of a mains failure.
9 Parameter functions
Functions: Parameter
Read Parameters
Enter Parameters
Print Parameters
Load Factory Defaults
Load Custom Defaults Parameter
Option activate
Additional functions can be activated by the Option activate function (Set option [➙ 138]).
Parameter are changeable characteristics or data with which the device can be adapted to its special weigh-
ing task.
You can find the meaning of the parameters in the detailed parameter description.
The input of parameters is protected by a password. They can inspected without any hazard with the Read
Parameters function. The parameters are broken down into functional blocks and numbered within a block.
Parameters are composed as follows:
Reading parameters:
Parameter
Read Parameters
10 Printer functions
Totalizer Record
Print Parameters
Print Status Report
Batch Record
Printer Set-
ting
When printing with the Batch Record function, the Totalizer Record function adds the batch setpoint and
actual batch value to the print-out and Totalizer Printout is printed out as the heading.
The batch protocol can only be printed after completing the batch. The counter protocol is available at any
time.
The complete parameter list is printed out with the current readings using the Print Parameters function. All
inputs departing from the default readings are marked with an *. The list of all possible event messages and
the current hardware allocation is printed out as an appendix.
The printing procedure can be cancelled at any time.
The Print Status Report can be printed out at any time. It provides information on the events and configura-
tion results that have occurred to date, etc. The Service Values chapter explains the specific data in detail.
The printing procedure can be cancelled at any time.
Software version
Own Address EasyServe address information
IP Address Ethernet address information
OP Mode Status information
Simulation Mode
Feeder On
Volumetric Mode
Summary Alarm
Maintenance Electric Overall duty cycle of mains voltage.
Maintenance Feeder Run Overall duty cycle of the belt conveyor and the device.
Totalizer 1 The readings of the total counter
Totalizer 2
Totalizer 3
The events since Power ON The number and type of events from Power ON or since the last print-out ofPrint
Status Report.
11 Batching functions
Functions: Batch
Display:
If Batch Mode is selected, the summation symbol Ɖ appears in the header.
Relevant data in the middle and lower display zone: Batch Setpoint, Batch Actual Value and Batch Residual
Amount.
Before starting a batch, Batch Actual Value and Batch Residual Amount show the amounts reached by the
previous batch. Deselecting Batch Mode means that the displays are no longer accessible, although they
appear again with the new preselection.
The format of the display is determined by P02.07 Counter 1 Unit and also by P02.13 Z1-Numberstep, de-
pending on the application.
Batch
Select Batch
A Batch Setpoint query occurs automatically upon preselection or can be manually initiated with after
a batch has been finished (scales OFF).
No entry can be made if batch mode is deselected or if a batch is in process.
No input is possible if the Batch Setpoint is specified with the fieldbus (Batch Setpoint Source P09.09 = FB).
For beltweigher VWF and loss-in-weight A query of the Setpoint of the Feedrate will be first made if Feedrate
feeder VLW only: Setpoint is set to OP or keyboard mode is active.
…
Acknowledge input
Interrupting a batch
The batch is continued with the next start command
Deselect Batch
This function deselects batching mode, i.e. it is taken out of the active
scope of functions. The summation symbol disappears from the header and the batching values can no
longer be called up again. However, they will not be cleared.
Conditions: the batch is ended or cancelled via Abort Batch function, scales OFF.
Batch
Deselect Batch
Batching mode can be re-activated with the Select Batch function and you can inspect the old batching val-
ues again.
Abort Batch
This function cancels a current batch and the conveying process is ended immediately.
Operation remains in batch mode.
The next start command will begin a new batch; the previous batch will not be resumed.
Batch
Abort Batch
▪ The batch has to be ended or cancelled. This function is only available in batching mode.
▪ It can be printed out with the Batch Record function or automatically after every finished batch
(P09.10 Batch Automatic Record = YES).
▪ The printing procedure can be cancelled at any time.
12 Startup operation
The effective weighing platform length "L" is an important value for calibration. It is determined by the design
of the weighing platform and can usually be found in the technical data sheets. However, it is always expe-
dient to measure the length manually and to enter the exact value as a parameter. The hatched area shows
the load distribution on the weighing platform.
Single-Idler Platform
The load on the weighing platform is conducted via a weighing idler into the load cell. This can be done by
means of a lever system or without levers by means of a parallel leaf-spring system.
Multiple-Idler Platform
Several weighing idlers are combined into one mechanical unit, the measuring bridge.
Buckled Platform
The weighing platform consists of two parts. The force is conducted centrally into the load cell. A split mea-
suring table can also be used in place of the weighing idlers.
Single-idler platform
tan(α)» 0.018 * a
Angle α = 0 : K = 0
Angle α = neg : K = neg
Multiple-idler platform
Buckled platform
The calibration weight usually has an effect in the center.
QPRF = QP
The following applies if the entire belt issupported on one side only:
If the belts are inclined, the extension or shortening of the calibration lever corresponding to the single-idler
platform must be taken into account.
0° must be entered as angle α. The full force Q acts on the load cells.
A technical data sheet is part of the scope of delivery. It contains all important nominal and calibration data
acc. specification. We will therefore list only a few important pieces of information and some recommenda-
tions at this point. It makes sense to go through all of the parameters and consider the value entered.
The inclination of the belt can be determined easily using a spirit level and a measuring tape. It is advanta-
geous to measure multiple times and to take the mean value of these measurements (h1, h2, …) as the
value 'h'.
-1
The Angle P03.07 angle is then a = tan (h/l)
For angle < 20°, a = 55 h/l applies
F = Qo * L * H * cos(a)
Qo Nominal Belt Load P04.01 kg/m
L Effective Platform Length P03.05 m
H Lever Ratio P03.06
a Angle P03.07 Degrees
F Force on the load cell kg
F should be less than or equal to the total of LC Rated Capacity P03.04. Otherwise, the load cells are too
small for the required Nominal Flow Rate.
1. Switch on the belt conveyor and scales. The switch-on process depends on the preselected Feeder
Start P02.06 source.
2. A rotating cross appears in the header as a progress indicator. If not, there is no clearance or the ON
button was not pressed.
3. Take any event messages which appear into account and remove the error.
4. Check the following:
Tachometer: The output frequency of the tachometer generator has to be less than 3,000 Hz with acti-
vated measurement. The value must approximately correspond to the information in the data sheet.
Load cell: The non-standardized initial value for the load cell amplifier may not be larger than
2.85 mV/V even at nominal load of the weighing platform. It must change if the weighing platform is
placed under load (e.g. the calibration weight). If the value is too large, the load cell is overloaded. If the
value is negative, the load cell may be wrongly connected.
The load cell load in percent, sourced from the sum of the load cell nominal capacities, should not be
larger than 100 % with nominal belt load.
The calibration weight should be between 30 % ... 100 % of the platform nominal load and be accurate.
1. Enter Calibration Weight P03.08.
On beltweighers with parallel leaf-spring guides, the effective calibration weight is the same as the ac-
tual value. In other cases, the effective calibration weight can be taken from the data sheet, or can be
calculated according to the chapter details/data flow images. The inclination of the conveyor belt has no
effect on the effective calibration weight.
2. Call up the CW: Span Calibration program.
The velocity sensor frequency generator can be actuated in a number of different ways.
1. with a frictional wheel on the lower carrying run of the belt or
2. with the shaft of the drive motor
In the first case, the value Pulses per length P02.04 depends on the exact diameter of the frictional wheel; in
the second case, it depends on the gear and looping factor of the belt. So the velocity measurement accu-
racy should be checked.
1. Establish the velocity of the conveyor belt using a stopwatch and a tape measure. Make several mea-
surements to be sure and then calculate the mean.
2. Read the speed display over the same period of time wherever feasible.
3. Compare these readings with one another and correct P02.04 wherever necessary. (new value = prior
value * speed measured/speed read)
5. The containers or vehicles in which the material is transported onto a (legal-for-trade) commercial scales
must be cleaned and re-weighed (tared) before each filling. The commercial scales must be sufficiently
accurate to measure the quantity MW.
The new value P04.02new is calculated from the old value P04.02old using the counter progression MA from
the continuous measurement and the mass MW calculated from the control scales as follows:
P04.02new = P04.02old * MW / MA
For example:
Old value of P04.02 = 1
A material quantity of MW = 4.9 t is conveyed over a period of 15 minutes. The counter progression MA
read off the device is 5.0 t.
13 Parameters
The INTECONT Tersus is adapted to each application by means of parameters. No special programing
knowledge is therefore necessary.
Backup set Pre-setting for a group of Use EasyServe or the unit Only using EasyServe in
applications or a setting to copy into the active pa- expert mode
stored during commis- rameter set
sioning
Tab. 1 : Using parameter sets
Note: Parameters not required for an application can be faded out or declared 'read only' using EasyServe
in expert mode. EasyServe compiles a list of visible parameters that form an integral part of the system do-
cumentation. Together with the operating manual they make up the relevant control system documentation
for an application. The parameter list contained in the operating manual contains all of the parameters re-
gardless of their actual use in an application.
In addition to the parameter set stored in the scales, we recommend that after commissioning you keep a
copy of the parameter set in a mass storage medium using EasyServe.
The parameters are arranged into blocks to for clarity. A parameter is uniquely identified by its block and
number within that block in the respective scales software version, e.g. 'P01.03' means 'parameter block 1,
parameter no.3'.
Notes:
▪ Gaps can appear between block numbers and parameters within the blocks. In rare cases, the number
of a parameter may change.
▪ Furthermore, each parameter has a unique ID with which it can be addressed via an interface (serial,
fieldbus). This ID can be seen as a 'Tooltip' in EasyServe when passing over the parameter and can be
output in the parameter printout.
13.1 Abbreviations
Source Description
FB Fieldbus
OP Operating panel
DI Digital Input
DO Digital Output
AI Analog Inputs
AO Analog Outputs
LS Logical signal for using internally available signals
Event Event. The reaction to an event can be configured
W1 Warning 1 (requires acknowledgement)
W2 Warning 2 (does not require acknowledgement)
ALARM Alarm (requires acknowledgement)
IGNORE Ignore: do not show any event message but switch the corresponding contact outputs
LC Load cell
I Feed rate
v Belt speed
VCU VCU 20100 system unit of DISOCONT Tersus. Refer to manual BVH2406 for details.
VHM DISOCONT Tersus operating panel. Refer to manual BVH2406 for details.
VMO Machine operating console for service work. Refer to manual BVH2488 for details.
Tab. 2 : List of commonly used parameter-related abbreviations
Note: An external binary output channel that may have been assigned to an event is set, independent of the
event class.
A newly pending alarm or warning 1-class event will be shown on the operating panel blinking and in color.
The blinking stops when acknowledged. Acknowledged event messages are cleared from the display for
currently pending events when the event is no longer pending. Each event is stored with a time-stamp in the
internal memory for later analysis.
01 - Dialog Behaviour
Number: Name Default Customer Sys ID
P01.01 [➙ 60] Language * DEUTSCH 4224
02 - Rated Data
Number: Name Default Customer Sys ID
P02.01 [➙ 64] Flow Rate Units ------ t/h 4229
03 - Calibration Data
Number: Name Default Customer Sys ID
P03.01 [➙ 67] Belt Circuit No. 1 6145
04 - Calibrat. Results
Number: Name Default Customer Sys ID
P04.01 [➙ 68] Nominal Belt Load 111.11 kg/m 6146
05 - Analog Outputs
Number: Name Default Customer Sys ID
P05.01 [➙ 69] AO: Actual Flow Rate AO 4388
06 - Limit Values
Number: Name Default Customer Sys ID
P06.01 [➙ 71] Limit: Actual Flow Rate MIN 5 % Io 4337
07 - Filters
Number: Name Default Customer Sys ID
P07.01 [➙ 73] Filter: Actual Flow Rate 3s 4328
09 - Batch Mode
Number: Name Default Customer Sys ID
P09.01 [➙ 76] Pre-cut-off Amount 100 kg 6156
10 - Printer Setting
Number: Name Default Customer Sys ID
P10.01 [➙ 79] Baud rate 9600 4512
11 - Maintenance interval
Number: Name Default Customer Sys ID
P11.01 [➙ 82] Maintenance Electric 3000 h 4465
12 - Feeder Control
Number: Name Default Customer Sys ID
P12.01 [➙ 83] Feeder Active NO 6187
13 - Belt Monitoring
Number: Name Default Customer Sys ID
P13.01 [➙ 84] VAP Active NO 4480
14 - Events
Number: Name Default Customer Sys ID
P14.01 [➙ 87] Event: Power Failure A 4297
15 - Linearization
Number: Name Default Customer Sys ID
P15.01 [➙ 90] Linearization ON NO 4577
16 - Digital Inputs
Number: Name Default Customer Sys ID
P16.01 [➙ 92] Source Run Enable * DI 4245
17 - Digital Outputs
Number: Name Default Customer Sys ID
P17.01 [➙ 93] DO: ALARM DO 4436
18 - Communication EasyServe
Number: Name Default Customer Sys ID
P18.01 [➙ 95] Own Address 1 4520
19 - Communication Fieldbus
Number: Name Default Customer Sys ID
P19.01 [➙ 96] Protocol Type NO 4528
21 - Ethernet
Number: Name Default Customer Sys ID
P21.01 [➙ 103] IP Address 192.168.240.1 6235
22 - Data Logging
Number: Name Default Customer Sys ID
P22.01 [➙ 104] Hourly Total Time 0 min 5743
24 - Second Display
Number: Name Default Customer Sys ID
P24.01 [➙ 108] Second Display active NO 4525
Letters and characters can be used. The name appears in the upper row of the operating
console and when searching through networks for controllers.
Remark: The characters ";" and "=" are not accepted. During the saving procedure these
characters will automatically be deleted.
Using this parameters, access to the basic function prefeeder ON/OFF can be controlled.
The following options are available:
active: Access is always permitted.
not active: Access is never allowed. This function is not visible in the block.
Password: Access is available with the standard password.
2nd password: Access is available with the 2nd password.
Confirm: The access must be confirmed for security reasons.
The digital input is flank-controlled, i.e. the ON signal must be removed and then reapplied
if the scales becomes inoperative because of e.g. an alarm.
If the impulse duration is shorter than 10 ms the impulse output is disabled. All impulses not
issued yet are cleared.
Also refer to: P05.02 Flow Rate Offset, P05.03 Flow Rate Range
Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.
The actual feed rate is lower than the minimum value Limit: Actual Flow Rate MIN.
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low
Actual feed rate higher than the maximum value set in P06.03 Limit: Actual Flow Rate MAX
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too large
The belt load is less than the minimum value set in Limit: Load MIN
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
The belt load is greater than the maximum value set in P06.07 Limit: Load MAX
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
The belt speed is less than the minimum value set in Limit: Speed MIN
The belt speed is greater than the maximum value set in Limit: Speed MAX
Note: filtering the load cell signal also effects the regulating action.
Conditions:
- v > vmin
- no setup program active
- no parameter input active
This event is identified if the change in tare identified by the automatic zeroing system ex-
ceeds the threshold value in P08.04 Zeroing Limit.
Possible causes:
- low quantities of bulk material on the belt
- error in the weighing mechanics
Steps:
- visual inspection of the belt and the weighing system.
- run the base tare adjustment program
- check weight measuring using test weights
Interim values result in filtered adjustment; this should be used in particular for systems with
poor reproducibility.
The result of the event is stored in P09.02 Correction Amount.
Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces
YES:
Batch and empty the belt. Batching is ended by switching off the material prefeeder. The
bin feeder has to be active.
Refer to P12.01.
The actual batch value currently reached is past the setpoint by the amount of the P09.04
tolerance.
The CO09 message is given and monitoring for the current batch has expired after ac-
knowledging (including the alarm).
The printout can be made only after a batch has ended automatically or manually. The
printout is stored to a file that can be read using the Web-Server.
The printout can be made only after a batch has ended automatically or manually.
The printout is made in a file that can be read using the web server.
With an INTECONT Tersus it can also be sent to a connected printer.
Form feed is not issued at value 128 at the end of the sheet.
The sum of the times during which the mains voltage is on is greater than the time P11.01
Maintenance Electric.
A message occurs after each expired time interval. The message may indicate service work
required.
The sum of the runtimes of the conveying elements is greater than the time P11.03 Main-
tenance Feeder Run.
A message occurs after each expired time interval. The message may indicate service work
required.
P09.07 = YES: run the belt empty and P12.05 does not have a function.
P09.07 = NO: do not run the belt empty and you can decide with P12.05 between coarse
and fine control over the belt conveyor (NO) or on the prefeeder (YES).
The belt sensor must be activated and the signal input defined in order to apply adaptive
belt influence compensation (P13.05 BIC Active), basic slip control (P13.14 Event: Slip) and
basic belt motion monitoring (4504).
Note:
Initial startup is made without active BIC.
Characteristics:
After belt influence compensation is activated the influence that the conveyor belt has on
weight measurement is offset after approximately ten belt circuits.
This event is identified if the belt motion does not correspond to that predicted by the motor
revolutions.
Possible causes:
- belt is slipping at the drive pulley
- withdrawal forces are too high
- gearing is defective
- belt or drive pulley heavily soiled
Steps:
- visual inspection of the belt and the bulk material flow
The output operates independently of the event class of the corresponding event.
The output operates independently of the event class of the corresponding event.
The output operates independently of the event class of the corresponding event.
The scales will not switch on automatically, regardless of the event class. The event must
first be acknowledged and the command to start given again before the scales will restart.
The program and parameters memory are checked cyclically. An error has occurred during
that. The scales will no longer function correctly.
Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.
The signals at the feeder drive's impulse speedometer input are outside of the specified
range.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wiring).
- the sensor has been incorrectly calibrated
The event message has to be set to IG if connecting up other equipment (not NAMUR).
External NAMUR adapters, resistor circuitry etc. are not required.
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Steps to take:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales still cannot be switched
on even after the error has been rectified.
No release signal from the source determined by P16.01 Source Run Enable.
If this event is pending then the downstream transport equipment is most likely not switched
on.
The load acting on the load cell is greater than 110 % of the sum of the nominal loads of
the load cells.
Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell
The load cell load is less than 3 % of the sum of the load cell nominal loads.
Possible causes:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
Possible cause: depends on the external cabling. Usually: an error in the main drive
The option selected in the P19.01 Protocol Type parameter is not activated.
It has to be cleared. Refer to the Option activate function.
Caution: the level is static and may not be on permanently (otherwise continuous acknowl-
edgement).
The input is also linked to the internal interference logic (block: interlocking).
All devices connected to the communicatio bus must have disjunct addresses.
Data transfer speed. This parameter is used for information only. The speed cannot be
changed.
Formats the serial data. The value is used for information only and cannot be altered.
NO: It is possible to read via Modbus-TCP, although writing access is not processed.
Modbus: Modbus-RTU protocol; RS232, RS422 or RS485 interface; the VSS 28020 field-
bus interface card has to be installed.
A telegram from the host system will be expected within the time set if the timeout value in
P19.02 is greater than zero.
Cyclical serial communication with the higher-order plant control system has been inter-
rupted for longer than the timeout-period in P19.02.
YES: Ident-No. 0524 is valid and GSD-file of INTECONT PLUS has to be used.
NO: Ident-No. 0C9B is valid and GSD-file of INTECONT Tersus has to be used.
The configuration bytes correspond to INTECONT PLUS if the parameter is on bytes. Oth-
erwise, the data are written in words. Consistency always refers to a data word or double
data word.
This parameter together with P19.19 PA32 compatible guarantees that there is no problem
exchanging with PROFIBUS Master in an existing system without having to adapt Master.
NO: No restrictions
FIRST WRITE: The subscriber that transmits the first write access gets the control rights.
The other subscribers may read only.
REMOTE IP: Control commands from the subscriber with the IP address given in P19.23
Remote IP Address FB only will be carried out.
13.3.2.20 Parameter
Parameter Block 20 - Fixed mode configuration
Configuration of the data in fieldbus communication 'FIXED' mode that were exchanged with the host com-
puter via serial interface.
Selecting the first control command with ID 320 (decimal) in the Fieldbus telegram.
The other values can be configured as per the ID list in the Data Communication manual.
Selecting the first value to be read from weighing electronics in the fieldbus telegram. The
number of the value (ID) can be found in the Data Communication manual (BV-H2448).
IP address of the weighing electronics. If the control system is integrated into an Ethernet
network, the address must be chosen in agreement with the network administrator. In iso-
lated networks we recommend the factory setting 192.168.240.x. "x" allows for selection of
the system on the bus.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.
The settings can be comfortably made with EasyServe or using the operating panel with the help of the allo-
cation map in the data description of the serial interface.
The display shows the value selected in the upper line of INTECONT Tersus.
If the letter space is illuminated as a full-surface block, this is an indication that the value
shown is invalid.
Either it is not possible to show the desired format or the unit is in the operator dialog.
Beyond this, the block is also shown to indicate that printing is active.
14 Event messages
DANGER
Events register abnormal states, e.g. malfunctions or exceeded thre-
shold values.
A running feeder can be a hazard to people or to property.
The cause of event messages must be corrected before events are ac-
knowledged!
Note:
In the following list, parameters related to the indicated event are shown in parentheses.
15 Events
Steps to take:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales still cannot be
switched on even after the error has been rectified.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wir-
ing).
- the sensor has been incorrectly calibrated
Possible causes:
- low quantities of bulk material on the belt
- error in the weighing mechanics
Steps:
- visual inspection of the belt and the weighing system.
- run the base tare adjustment program
- check weight measuring using test weights
The scales will not switch on automatically, regardless of the event class. The event
must first be acknowledged and the command to start given again before the scales
will restart.
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
If this event is pending then the downstream transport equipment is most likely not
switched on.
Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces
Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too large
Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
Possible causes:
- belt is slipping at the drive pulley
- withdrawal forces are too high
- gearing is defective
- belt or drive pulley heavily soiled
Steps:
- visual inspection of the belt and the bulk material flow
Possible causes:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too low
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
A message occurs after each expired time interval. The message may indicate ser-
vice work required.
A message occurs after each expired time interval. The message may indicate ser-
vice work required.
Possible cause: depends on the external cabling. Usually: an error in the main drive
Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.
Front-of-panel unit with VBW 20650 software for the weighfeeder VEG 20650
Basic equipment V082002.B01
with Modbus option V082002.B02
with PROFIBUS option V082002.B03
with DeviceNet option V082002.B04
with Ethernet/IP option V082002.B05
Front-of-panel unit with VLW 20650 software for the loss-in-weight feeder VEG 20650
Basic equipment V082003.B01
with Modbus option V082003.B02
with PROFIBUS option V082003.B03
with DeviceNet option V082003.B04
with Ethernet/IP option V082003.B05
Front-of-panel unit with VMC 20650 software for MULTICOR VEG 20650
Basic equipment V082004.B01
with Modbus option V082004.B02
with PROFIBUS option V082004.B03
with DeviceNet option V082004.B04
with Ethernet/IP option V082004.B05
Front-of-panel unit with VIF 20650 software for MULTISTREAM VEG 20650
Basic equipment V082005.B01
Front-of-panel unit with VBW 20660 software for legal-for-trade weighfeed- VEG 20650
er
Basic equipment V082007.B01
with Modbus option V082007.B02
with PROFIBUS option V082007.B03
with DeviceNet option V082007.B04
with Ethernet/IP option V082007.B05
Further Options
Installed power supply and mounting set V082050.B01
Analog signal card with 2 analog inputs and 2 analog outputs VEA 20451 V054098.B01
IP65 protection type for front-side control panel installation V082039.B01
Software
EasyServe VPC 20150 E144541.01
Large-scale displays
Large-scale 5-digit display, LED, 100 mm digit height VLD 20100 V090252.B01
Large-scale 6-digit display, LCD, 45 mm digit height VLZ 20045 V067304.B01
Large-scale 5-digit display, LCD, 100 mm digit height VLZ 20100 V066611.B01
In the beginning, INTECONT PLUS equipment was produced as the FIP model and then as the VEG 206xx
model starting in 2003.
INTECONT Tersus as the follow-up unit was also kept very similar to its predecessors in terms of its hard-
ware connections.
The EasyServe adjustment program (VPC 20150) can be used for INTECONT Tersus from version 19
which makes it possible to conveniently change over from VEG to INTECONT Tersus.
The following tables show the connector pin assignment of FIP, VEG and INTECONT Tersus opposite one
another for all physical signals.
Power Supply
Signal FIP and
VEG and
INTECONT Tersus
0V X2 1
24 V in X2 2
0V X2 3
24 V out X2 4
Load cell
Signal FIP VEG INTECONT Tersus
OUT1 X5 3 X7 3 X10 3
REF1 X5 4 X7 4 X10 4
IN2 X5 5 X7 6 X10 6
IN1 X5 6 X7 5 X10 5
REF2 X5 7 X7 7 X10 7
OUT2 X5 8 X7 8 X10 8
Digital Outputs, DO
Signal FIP VEG INTECONT Tersus
DO1 X1 1,2
DO2 X1 3,4
DO3 X1 5,6
DO4 X6 1,2 X8 1,2 X13 9,10
DO5 X6 3,4 X8 3,4 X13 7,8
DO6 X6 5,6 X8 5,6 X13 5,6
DO7 X6 7,8 X8 7,8 X13 3,4
DO8 X6 9,10 X8 9,10 X13 1,2
Digital Inputs, DI
Signal FIP VEG INTECONT Tersus
Analog outputs AO
Signal FIP VEG INTECONT Tersus
Analog inputs AI
Signal FIP VEG INTECONT Tersus
Printer
Shield X8 1 X10 1 X7 1
TX X8 2 X10 2 X7 2
RX X8 3 X10 3 X7 3
Large-scale display
Signal FIP VEG INTECONT Tersus
Shield —- —- X11
TX —- —- Pin assignment
RX —- —- after RSxxx selec-
tion
EasyServe
Signal FIP VEG INTECONT
Tersus
Shield —- X4 5 or X5 1 X6 1
TX —- X4 2 or X5 2 X6 2
RX —- X4 3 or X5 3 X6 3
Pulse output
Signal FIP VEG INTECONT Tersus
24 V X9 5 X6 8 —-
Open collector X9 6 X6 9 X3 1
Open Emitter X9 7 X6 10 —-
0V X9 8 X6 11 X3 2
The module may be attached to the basic board of the device to create an interface to the PROFIBUS.
Module properties
Isolation: Optocoupler
Power supply: +5 VDC internal
Current supply: max. 310 mA
Connector to bus activation: XP1: D-Sub 9-pole
XP3: Terminal 5-pole
Settings
*)
Wire color red
**)
Wire color green
***)
Bus termination supply
Status Display
Status Display
Disconnection Optocoupler
Power supply +5 VDC internal
Power supply max. 250 mA
Plug connector to the bus activation XC1: Terminal 5-pole
XC3: Terminal 5-pole
Settings
1 V-
2 CAN_L
Ditto:
3 Shielding
4 CAN_H
5 V+
Tab. 8 : 'Bus activation' connector
The interface card is an isolated, serial interface. The type of the interface is set using control unit parame-
ters and using jumpers in the plug. Both plugs are electrically parallel.
Module properties
Disconnection Optocoupler
Power supply +5 VDC internal
Power supply Max. 250 mA
Plug connector to the bus activation XS2: Terminal 7-pole
XS3: Terminal 7-pole
Tab. 11 : Modbus module properties
Establishing a connection:
▪ Enter into the address bar of the browser the IP address of the control unit.
Various data from the controller can be called up in the left-hand navigation bar.
Navigation entry Function
Memory depth is approx. 1,000 entries. All entries are recorded with the entry time. The table is refreshed
only when it is called up. The values can be exported into a PC file for analysis with standard programs us-
ing select-copy-paste.
The event display is highlighted by a colored rectangle. There are 3 colors, each of which has a different
meaning.
The system data are provided here. You can find files such as the software version, hardware version, IP
address. "Serial No." or "MAC-ID" are the names of the serial number on the CPU board.
Together with the 'mainboard' data, this data also supplies the user with the 'fieldbus' configurations and
settings. In particular the amount of bytes for the read and transmitted data.
This page is still undergoing development and may differ from the image shown here.
18 Appendix
Detailed information on the system is contained in the service table. The call-up does not interfere with any
weigh functions.
Setup
Service Values
Setup
Standard Values
Readouts:
Parameter
Option activate
Key in password
…
Abort possible at any time
a) tachometer
The output frequency of the tachometer generator has to be less than 3,000 Hz when the measurement is
activated. The value must approximately correspond to the information in the data sheet. If the frequency
fluctuates substantially at a constant belt speed, the Namur sensor of the tachometer generator is probably
too far away.
b) wz
The non-standardized output value of the load cell amplifier may not be greater than 2.85 mV/V even at the
rated load of the weighbridge. It must change if the weighing platform is placed under load (e.g. the calibra-
tion weight).
Negative Value:
– load cell connected incorrectly
– tare equalization weight incorrectly set
c) aw
Load of the load cell in percents with reference to the total of the rated loads of the load cell.
The value can be analyzed as per item b). aw should not be greater
than 100 % at the rated belt load.
If it is not possible to bring about a reasonable operational state in spite of all efforts, the test plug chapter
might help.
A basic function control of the INTECONT can be carried out using a simple test connector. In this way an
error can be limited between the load cell with wiring and electrical equipment.
1. Connect the connector as shown in the diagram
2. Disconnect load cell connector X7 and plug in the test connector instead
Note:
With other resistances R1 and R2, the LC Raw is calculated to 500 * R2 / R1 [mV/V].
The test plug is available as an accessory.
An effective switch-off command does not turn off totalizing immediately, but only after the P07.06 After-
flow Totalizer time. Stop commands have the highest priority.
Various control modes can be configured as per the P02.06 Feeder Start parameters.
Comments:
▪ No batching is possible after selecting v.
▪ The n/a setting in the P16.01 Source Run Enable parameters turns off the input. Then the scale is al-
ways released.
Measuring on the VAP discharge point shifts the measuring point of the weighbridge to the discharge point
of the material by means of a time-lag device. The totalized amount of material dispatched is directly rec-
orded.
Preconditions:
▪ The length ratio from the centerline of the weighing platform to the material dispatch to the overall belt
conveyor length is known.
▪ Key in the length ratio in percent in parameters Platform Dis.Length P13.02.
▪ Activate VAP via VAP Active P13.01 parameters.
Drift and slippage monitoring is built into the functions. Monitoring is activated with the P13.03 Belt Sensor
Active parameter.
The programs can only be used for belt monitoring if there is a belt circuit sensor (Namur transmitter) and a
triangular metallic sensor surface in the conveyor belt. Otherwise, the aforementioned parameter and
P13.05 BIC Active parameters have to be on NO.
Even excellent conveyor belts are never completely even and they become heavier and stiffer especially on
the seams. This is why it is normally only possible to guarantee a high level of accuracy over entire belt
circuits (i.e. over the mean).
An additional belt circuit sensor and metallic marking flag in the belt enable the unit to record this impact and
constantly correct it.
That substantially boosts the short-term accuracy of the scale.
Belt impact measurement is constant to take changes in regular operation into account. Compensation
adapts itself whenever material is conveyed.
Relevant parameters P13.05 BIC Active, P13.03 Belt Sensor Active, P13.04 DI: Source Belt Sensor.
18.9 Linearization
The belt loading does not usually need to be linearized. It only makes sense with major belt load fluctua-
tions.
Repeat work processes 1 - 3 with increasingly large calibration weights for the other linearization points.
▪ Read the mean of the belt load q1(a) on the equipment and key it into the Linearization I1 parameters.
▪ Key in the result of the formula q1(s) = q1(a) * Ms / Ma into the Linearization S1 parameters.
Where:
– Ms: conveyed quantity of material in kg
– Ma: quantity of material read on the equipment in kg
Repeat work processes 1 - 3 with increasingly large calibration weights for the other linearization points.
Index
>0 Zero ON/OFF ............................................................................................................................................................. 63
2. Password ..................................................................................................................................................................... 62
Abbreviations ................................................................................................................................................................... 50
About This Manual ............................................................................................................................................................. 1
Access Rights Limitation FB........................................................................................................................................... 101
acknowledge event information ........................................................................................................................................ 19
Activation code ............................................................................................................................................................... 138
Adaptation Factor ............................................................................................................................................................. 77
Address .............................................................................................................................................................. 98, 99, 100
Afterflow Totalizer ............................................................................................................................................................ 74
An overview of the INTECONT Tersus............................................................................................................................... 7
Analog Outputs ................................................................................................................................................................ 69
Angle ................................................................................................................................................................................ 68
AO Actual Flow Rate ....................................................................................................................................................... 69
AO Belt Load ................................................................................................................................................................... 70
AO Speed........................................................................................................................................................................ 70
Appendix ........................................................................................................................................................................ 137
Auto Zero Active ............................................................................................................................................................... 74
AUTO Zero Set .................................................................................................................................................... 74, 75, 76
Basic Tare ........................................................................................................................................................................ 69
Batch Actual Value Column.............................................................................................................................................. 80
Batch Actual Value Line ................................................................................................................................................... 80
Batch Automatic Record................................................................................................................................................... 78
Batch control .................................................................................................................................................................... 63
Batch Mode ...................................................................................................................................................................... 76
Batch Setpoint Column..................................................................................................................................................... 80
Batch Setpoint Line .......................................................................................................................................................... 80
Batch Setpoint Source...................................................................................................................................................... 78
Batch Tolerance - ............................................................................................................................................................. 77
Batch Tolerance + ............................................................................................................................................................ 77
Batching functions ............................................................................................................................................................ 37
Batching mode ................................................................................................................................................................. 37
Batchnumber Column....................................................................................................................................................... 81
Batchnumber Line ............................................................................................................................................................ 81
Baud rate.................................................................................................................................................... 79, 99, 100, 108
Baud Rate ........................................................................................................................................................................ 96
Belt Circuit No. ........................................................................................................................................................... 67, 69
Belt Circuit Time ............................................................................................................................................................... 67
Belt Drift ........................................................................................................................................................................... 85
Belt Empty ........................................................................................................................................................................ 78
Belt inclination .................................................................................................................................................................. 44
belt load.............................................................................................................................................................................. 8
Belt Load Offset ............................................................................................................................................................... 70
Belt Load Range .............................................................................................................................................................. 70
Belt Monitoring ............................................................................................................................................................... 142
Belt Monitoring ............................................................................................................................................... 84, 85, 86, 87
Belt Sensor Active ............................................................................................................................................................ 84
Belt Skew ......................................................................................................................................................................... 85
Belt Velocity Check .......................................................................................................................................................... 47
BIC Active ........................................................................................................................................................................ 84
BIC belt impact compensation........................................................................................................................................ 143
Byte Sequence ................................................................................................................................................................. 98
CA01 Event Error LC Input........................................................................................................................................... 113
CA02 Event Tachometer Input ..................................................................................................................................... 113
CA05 Event Linearization Error .................................................................................................................................... 113
CA06 Event Tare Correction ........................................................................................................................................ 113
CA12 Event Tare Difference > MAX............................................................................................................................. 114
CA13 Event Time elapsed............................................................................................................................................ 114
Calibrat. Results ......................................................................................................................................................... 68, 69
Calibration ...................................................................................................................................................................... 113
Calibration Data ......................................................................................................................................................... 67, 68
Calibration functions ......................................................................................................................................................... 27
calibration switch ............................................................................................................................................................ 137
MIN................................................................................................................................................................................. 117
Modbus Interface VSS8020 ........................................................................................................................................... 132
Mode functions ................................................................................................................................................................. 25
Motor STOP immediately ................................................................................................................................................. 83
Net Mask ........................................................................................................................................................................ 103
Nominal Belt Load ............................................................................................................................................................ 68
Nominal Flow Rate ........................................................................................................................................................... 64
Nominal Speed................................................................................................................................................................. 65
Operating in Normal Operation ........................................................................................................................................ 18
operating sources ............................................................................................................................................................. 25
Operation ......................................................................................................................................................................... 15
Output current ................................................................................................................................................................ 137
Own Address.................................................................................................................................................................... 95
P01 - Dialog Behaviour .................................................................................................................................................... 60
P01.01 - Language ........................................................................................................................................................... 61
P01.02 - Userdefined Text ............................................................................................................................................... 61
P01.03 - Font ................................................................................................................................................................... 61
P01.04 - Units .................................................................................................................................................................. 61
P01.05 - Scale Name ....................................................................................................................................................... 61
P01.06 - Password ........................................................................................................................................................... 62
P01.07 - 2. Password ....................................................................................................................................................... 62
P01.08 - Feeder ON/OFF ................................................................................................................................................. 62
P01.09 - Switch Keyboard-/Normal Mode ........................................................................................................................ 62
P01.10 - Batch control ...................................................................................................................................................... 63
P01.11 - >0 Zero ON/OFF............................................................................................................................................... 63
P01.12 - Reset Counter 1................................................................................................................................................. 63
P01.13 - Reset Counter 2................................................................................................................................................. 63
P01.14 - Route Tot. ON/OFF ........................................................................................................................................... 63
P01.15 - Data Log ON/OFF.............................................................................................................................................. 64
P02 - Rated Data ........................................................................................................................................... 64, 65, 66, 67
P02.01 - Flow Rate Units ................................................................................................................................................. 64
P02.02 - Nominal Flow Rate ............................................................................................................................................ 64
P02.03 - Speed Measurement ......................................................................................................................................... 64
P02.04 - Pulses per length ............................................................................................................................................... 65
P02.05 - Nominal Speed .................................................................................................................................................. 65
P02.06 - Feeder Start ....................................................................................................................................................... 65
P02.07 - Counter 1 Unit.................................................................................................................................................... 65
P02.08 - Pulse Length Total ............................................................................................................................................. 66
P02.09 - Counter 2 Unit.................................................................................................................................................... 66
P02.10 - Counter 3 Unit.................................................................................................................................................... 66
P02.11 - DO Pulse Counter............................................................................................................................................. 66
P02.12 - Totalizer Increment ............................................................................................................................................ 67
P02.13 - Z1-Numberstep .................................................................................................................................................. 67
P03 - Calibration Data ................................................................................................................................................ 67, 68
P03.01 - Belt Circuit No. ................................................................................................................................................... 67
P03.02 - Belt Circuit Time ................................................................................................................................................ 67
P03.03 - LC Characteristic Value ..................................................................................................................................... 67
P03.04 - LC Rated Capacity............................................................................................................................................. 67
P03.05 - Effective Platform Length ................................................................................................................................... 68
P03.06 - Lever Ratio ........................................................................................................................................................ 68
P03.07 - Angle ................................................................................................................................................................. 68
P03.08 - Calibration Weight ............................................................................................................................................. 68
P04 - Calibrat. Results ............................................................................................................................................... 68, 69
P04.01 - Nominal Belt Load ............................................................................................................................................. 68
P04.02 - Range Correction............................................................................................................................................... 68
P04.03 - Total Tare .......................................................................................................................................................... 69
P04.04 - Basic Tare ......................................................................................................................................................... 69
P04.05 - Tare Correction .................................................................................................................................................. 69
P04.06 - Belt Circuit No. ................................................................................................................................................... 69
P05 - Analog Outputs ....................................................................................................................................................... 69
P05.01 - AO Actual Flow Rate ........................................................................................................................................ 69
P05.02 - Flow Rate Offset ................................................................................................................................................ 69
P05.03 - Flow Rate Range ............................................................................................................................................... 70
P05.04 - AO Belt Load .................................................................................................................................................... 70
P05.05 - Belt Load Offset ................................................................................................................................................. 70
P05.06 - Belt Load Range ................................................................................................................................................ 70