Acoustic Barrier Mat

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

KINETICS® KNM-AL

ACOUSTIC BARRIER MATERIAL

Description and Application Specification


Fire-resistant noise barrier material for wrapping The barrier shall be constructed of a 0.12" or 0.24"
ducts, valves and pipelines. Designed for indoor or (3 or 6 mm) thick, mass-loaded, limp vinyl sheet
outdoor use, Kinetics KNM-AL noise barrier material bonded to a thin layer of reinforced aluminum foil on
reduces risks due to burning, and retards smoke one side. The barrier shall have a nominal density of
development and flame spread. The material is 1.0 or 2.0 psf (4.88 or 9.76 kg/sq. m.).
designed to reduce sound transmission from HVAC
duct, process piping, fluid or gas pulsations in pipe- Product not meeting minimum test standards will
lines for chemical, petrochemical, and waste water not be accepted. Barrier shall have surface burning
treatment plants and gas utility pressure-reducing characteristics as follows: Flame Spread Index: 25 or
stations. less, and Smoke Development Index: 450 or less, per
ASTM E84-15b (reports using standard test methods
The material is constructed of mass-loaded, limp prior to ASTM E84-15b will not be accepted). Barrier
vinyl with a layer of reinforced aluminum foil facing on shall be tested with reinforced foil scrim face exposed
one side. The vinyl provides mass and flexibility, while to flame.
the aluminum adds increased mechanical strength,
weatherability, and improved fire retardancy. The barrier shall be model KNM-100AL or KNM-200AL
as manufactured by Kinetics Noise Control, Inc.
The non-lead composition of the material allows for
safe handling and easy installation. When applied
over an insulation material such as fiberglass, foam,
ceramic fiber or mineral wool, Kinetics fire-resistant
barrier material is simply cut to length, wrapped
around the pipe or duct, and fastened with tape,
mechanical fasteners, or bands.

®
Sound Transmission Loss, dB
ASTM E90-09: Tested as free hanging barrier

Product 125 250 500 1000 2000 4000 STC


KNM-100AL 15 17 21 26 31 36 26
KNM-200AL 21 22 27 32 37 42 31

Insertion Loss (IL)


2.0 psf Model KNM-200AL tested as wrapping over 2" thick, 5
pcf fiberglass around steel retangular duct.

Product 125 250 500 1000 2000 4000


KNM-200AL 5 9 18 34 37 37

Fire Test per ASTM E84-15b


KNM-100AL
Pipe/Duct Wrap Detail - Butt Joint Method
Flame Spread- 25
Smoke Developed- 250
Kinetics Barrier Tape
Class A
Kinetics Barrier
Pipe/Duct
KNM-200AL Material KNM-100AL

Flame Spread- 25 Butt Joint


Smoke Developed- 450
Class A Insulation

Material Thickness:
KNM-100AL - 0.12" (3 mm) Pipe/Duct Wrap Detail - Overlap Method
KNM-200AL - 0.24" (6 mm) Insulation

Material Roll Size:


KNM-100AL - 54" x 60' (1.4 m x 18 m)
Pipe/Duct
KNM-200AL - 54" x 30' (1.4 m x 9 m)
Kinetics Barrier
Material KNM-100AL
Service Temperature:
-40°F to 220°F (-40°C to 104°C)

Corrosion Resistance:
Excellent for most oils, grease, acids, and mild alkalis.

kineticsnoise.com/knm
[email protected]
® 1-800-959-1229

MADE IN USA Kinetics Noise Control, Inc. is continually upgrading the quality of our products. KNM-AL │ 11/18
We reserve the right to make changes to this and all products without notice.
ADDITIONAL 6MM THICK
MASS LOAD BARRIER

AIR DUCT THERMO


INSULATION IF ANY

INSTALLATION DETAIL -DUCT LAGGING