Technical Information
iTEMP TMT84
Dual Input Temperature Transmitter
PROFIBUS® PA communication
Measuring system
m n
A0007667
Application examples
m Two sensors with measuring input (RTD or TC) in remote installation with the following advantages: drift warning,
sensor backup function and temperature-dependent switching
n Built-in head transmitter - 1 x RTD/TC or 2 x RTD/TC as redundancy
Device architecture
PLC
Visualisation and monitoring
e. g. P View, FieldCare
and diagnostic software
PROFIBUS-DP
0 - 10 bar 0 - 10 bar
2 Endress+Hauser
TMT84
The temperature transmitter is a two-wire device with two measuring inputs. Using PROFIBUS® PA,
the device transfers converted signals from resistance thermometers and thermocouples in addition to
other resistance and millivolt signals. The device is powered via the PROFIBUS® PA bus and can be
installed as an intrinsically safe apparatus in zone 1 hazardous areas. The device is used for
instrumentation purposes in the terminal head form B as per DIN EN 50446. Data transfer takes place
via 4 analog input (AI) function blocks:
Sensor diagnosis functions
Sensor diagnoses such as cable open circuit, short-circuit, cable corrosion, wiring error and device
hardware error are supported. In addition, the work area of the sensor and the ambient temperature
are monitored.
2-channel functions
These functions increase the reliability and availability of the process values:
• Sensor backup switches to the second sensor if the primary sensor fails.
• Drift warning or alarm if the deviation between sensor 1 and sensor 2 is less than or greater than a
predefined limit value.
• Temperature-dependent switching between sensors which have advantages in different ranges.
Compatibility mode
For a easy replacement of the previous model iTEMP TMT184 with the TMT84 a compatibility mode
is available. The switching between the standard mode and compatibility mode in the iTEMP TMT84
is done automatically during the connection establishment of the cyclic communication.
The Following points have to receive attention:
• Only PROFIBUS® PA-Profile 3.0 is supported.
• Only 1-channel operation possible.
• The diagnostics and status handling is equal to the previous model TMT184.
• The previous model TMT184 software locking is not available.
Input
Measured variable Temperature (temperature linear transmission behavior), resistance and voltage.
Measuring range The transmitter records different measuring ranges depending on the sensor connection and input
signals (see "Type of input").
Endress+Hauser 3
TMT84
Type of input It is possible to connect two sensors which are independent of each other. The measuring inputs are
not galvanically isolated from each other.
as per Edison Copper Winding Cu10 -100 to 260 °C (-148 to 500 °F)
No.15 (α = 0.004274)
as per Edison Curve Ni120 -70 to 270 °C (-94 to 518 °F)
(α = 0.006720)
as per GOST Pt50 -200 to 1100 °C (-328 to 2012 °F)
(α = 0.003911) Pt100 -200 to 850 °C (-328 to 1562 °F)
as per ASTM E988 Type C (W5Re-W26Re) (32) 0 to +2315 °C (32 to 4199 °F) 0 to +2000 °C (+32 to +3632 °F)
Type D (W3Re-W25Re) (33) 0 to +2315 °C (32 to 4199 °F) 0 to +2000 °C (+32 to +3632 °F)
as per DIN 43710 Type L (Fe-CuNi) (41) -200 to +900 °C (-328 to 1652 °F) -150 to +900 °C (-238 to +1652 °F)
Type U (Cu-CuNi) (42) -200 to +600 °C (-328 to 1112 °F) -150 to +600 °C (-238 to +1112 °F)
as per GOST Type L (NiCr-CuNi) (43) -200 to +800 °C (-328 to 1472 °F) -200 to +800 °C (-328 to +1472 °F)
R8.8585-2001
• Internal cold junction (Pt100)
• External cold junction: value adjustable from -40 to +85 °C (-40 to +185 °F)
• Maximum sensor resistance 10 kΩ (if the sensor resistance is greater than 10 kΩ, an error message is output in
accordance with NAMUR NE89)
4 Endress+Hauser
TMT84
When assigning both sensor inputs, the following connection combinations are possible:
Sensor input 1
RTD or resistance
transmitter, 2-wire
-
RTD or resistance
transmitter, 3-wire
-
Sensor
input 2 RTD or resistance
- - - -
transmitter, 4-wire
Thermocouple (TC),
voltage transmitter
Input signal Input data: The transmitter is able to receive a cyclic value and its status sent by a master via
PROFIBUS® PA. That value and status is represented and can be read acyclically.
Output
Output signal • PROFIBUS® PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically isolated;
• FDE (Fault Disconnection Electronic) = 0 mA
• Data transmission rate: supported baud rate = 31.25 kBit/s
• Signal coding = Manchester II
• Output data:
Available values via AI blocks: temperature (PV), temp sensor 1 + 2, terminal temperature
• In a control system the transmitter always operates as a slave and, dependent on the application, can
exchange data with one or more masters.
• In accordance with IEC 60079-27, FISCO/FNICO
Breakdown information Status message in accordance with PROFIBUS® PA Profile 3.01/3.02 specification.
Current consumption ≤ 11 mA
Switch-on delay 8s
Endress+Hauser 5
TMT84
PROFIBUS® PA basic data Manufacturer spec. ID-no.: Profile 3.0 ID-no.: Manufacturer specific GSD
If the TMT84 operates in the compatibily mode, the device is identifying with the manufactu-
rer specific ID-no.: 1523 (Hex) - TMT184 in the cyclic data exchange.
Power supply
Electrical connection
6 Endress+Hauser
TMT84
Performance characteristics
Response time 1 s per channel
Maximum measured error Typical values, according to DIN EN 60770, 25 °C ± 3 °C (77 °F ± 5,4 °F), supply voltage
24 VDC. The data concerning the various measured errors correspond to a standard deviation
of 2 σ (Gaussian normal distribution). These data include nonlinearity and repeatability.
Thermocouples (TC)
according to standard
Digital1)
Standard Designation Measuring range
Maximum Relating to measured
value
Pt100 (1) ≤ 0.12 °C (0.21 °F) 0.06 °C (0.11 °F) + ≤ 0.05 °C (0.09 °F)
IEC 60751:2008
-200 to +850 °C 0.006% x (MW - MBA)
IEC 60751:2008 Pt100 (2) (-328 to +1562 °F) ≤ 0.30 °C (0.54 °F) 0.11 °C (0.2 °F) + 0.018% ≤ 0.13 °C (0.23 °F)
x (MW - MBA)
IEC 60751:2008 Pt500 (3) -200 to +510 °C ≤ 0.16 °C (0.29 °F) 0.05 °C (0.09 °F) + ≤ 0.08 °C (0.14 °F)
(-328 to +950 °F) 0.015% x (MW - MBA)
IEC 60751:2008 -200 to +250 °C 0.03 °C (0.05 °F) + ≤ 0.05 °C (0.09 °F)
Pt1000 (4)
(-328 to +482 °F) 0.013% x (MW - MBA)
≤ 0.09 °C (0.16 °F)
JIS C1604:1984 Pt100 (5) -200 to +510 °C 0.05 °C (0.09 °F) + ≤ 0.04 °C (0.07 °F)
(-328 to +950 °F) 0.006% x (MW - MBA)
GOST 6651-94 Pt50 (8) -185 to +1100 °C ≤ 0.20 °C (0.36 °F) 0.1 °C (0.18 °F) + 0.008% ≤ 0.11 °C (0.2 °F)
(-301 to +2012 °F) x (MW - MBA)
GOST 6651-94 Pt100 (9) -200 to +850 °C ≤ 0.11 °C (0.2 °F) ≤ 0.05 °C (0.09 °F)
(-328 to +1562 °F)
0.05 °C (0.09 °F) +
DIN 43760 IPTS-68 Ni100 (6) -60 to 250 °C ≤ 0.05 °C (0.09 °F) 0.006% x (MW - MBA)
≤ 0.03 °C (0.05 °F)
DIN 43760 IPTS-68 Ni120 (7) (-76 to 482 °F)
Endress+Hauser 7
TMT84
OIML R84:2003 / GOST Cu50 (10) ≤ 0.11 °C (0.2 °F) 0.09 °C (0.16 °F) + ≤ 0.05 °C (0.09 °F)
6651-2009 -60 to +250 °C 0.006% x (MW - MBA)
OIML R84:2003 / GOST Cu100 (11) (-76 to +482 °F) ≤ 0.06 °C (0.11 °F) ≤ 0.04 °C (0.07 °F)
6651-2009
OIML R84:2003 / GOST Cu50 (14) -50 to +200 °C ≤ 0.11 °C (0.2 °F) 0.1 °C (0.18 °F) + 0.004% ≤ 0.07 °C (0.13 °F)
6651-94 (-58 to +392 °F) x (MW - MBA)
MW = Measured value
MBA = Measuring range start of the respective sensor
Type A (30) 0 to +2500 °C ≤ 1.33 °C (2.39 °F) 0.8 °C (1.44 °F) + 0.021% x ≤ 0.52 °C (0.94 °F)
IEC 60584-1
(+32 to +4532 °F) MW
IEC 60584-1 Type B (31) +500 to +1820 °C ≤ 1.50 °C (2.7 °F) 1.5 °C (2.7 °F) - 0.06% x ≤ 0.67 °C (1.21 °F)
(+932 to +3308 °F) (MW - MBA)
IEC 60584-1 / ASTM Type C (32) ≤ 0.66 °C (1.19 °F) 0.55 °C (1 °F) + 0.0055% x ≤ 0.33 °C (0.59 °F)
E988-96 0 to +2000 °C MW
ASTM E988-96 (+32 to +3632 °F) ≤ 0.75 °C (1.35 °F) 0.75 °C (1.44 °F) - 0.008% ≤ 0.41 °C (0.74 °F)
Type D (33)
x MW
IEC 60584-1 Type E (34) -150 to +1000 °C ≤ 0.22 °C (0.4 °F) 0.22 °C (0.40 °F) - 0.006% ≤ 0.07 °C (0.13 °F)
(-238 to +2192 °F) x (MW - MBA)
IEC 60584-1 Type J (35) ≤ 0.27 °C (0.48 °F) 0.27 °C (0.49 °F) - 0.005% ≤ 0.08 °C (0.14 °F)
-150 to +1200 °C x (MW - MBA)
IEC 60584-1 Type K (36) (-238 to +2192 °F) ≤ 0.35 °C (0.63 °F) 0.35 °C (0.63 °F) - 0.005% ≤ 0.11 °C (0.20 °F)
x (MW - MBA)
IEC 60584-1 Type N (37) -150 to +1300 °C ≤ 0.48 °C (0.86 °F) 0.48 °C (0.86 °F) - 0.014%
≤ 0.16 °C (0.29 °F)
(-238 to +2372 °F) x (MW - MBA)
IEC 60584-1 Type R (38) ≤ 1.12 °C (2.0 °F) 1.12 °C (2 °F) - 0.03% x ≤ 0.76 °C (1.37 °F)
+50 to +1768 °C MW
IEC 60584-1 Type S (39) (+122 to +3214 °F) ≤ 1.15 °C (2.07 °F) 1.15 °C (2.07 °F) - 0.022% ≤ 0.74 °C (1.33 °F)
x MW
IEC 60584-1 Type T (40) -150 to +400 °C ≤ 0.36 °C (0.47 °F) 0.36 °C (0.47 °F) - 0.04% x ≤ 0.11 °C (0.20 °F)
(-238 to +752 °F) (MW - MBA)
DIN 43710 Type L (41) -150 to +900 °C ≤ 0.29 °C (0.52 °F) 0.29 °C (0.52 °F) - 0.009%
≤ 0.07 °C (0.13 °F)
(-238 to +1652 °F) x (MW - MBA)
DIN 43710 Type U (42) -150 to +600 °C ≤ 0.33 °C (0.6 °F) 0.33 °C (0.6 °F) - 0.028% x ≤ 0.10 °C (0.18 °F)
(-238 to +1112 °F) (MW - MBA)
GOST R8.8585-2001 Type L (43) -200 to +800 °C ≤ 2.2 °C (4.0 °F) 2.2 °C (4 °F) - 0.015% x ≤ 0.15 °C (0.27 °F)
(-328 to +1472 °F) (MW - MBA)
8 Endress+Hauser
TMT84
Sample calculation with Pt100, measuring range 0 to +200 °C (32 to +392 °F), ambient temperature
+25 °C (+77 °F), supply voltage 24 V:
Measured error = 0.06 °C + 0.006% x (200 °C - (-200 °C)): 0.084 °C (0.151 °F)
Sample calculation with Pt100, measuring range 0 to +200 °C (32 to +392 °F), ambient temperature
+35 °C (+95 °F), supply voltage 30 V:
Measured error = 0.06 °C + 0.006% x (200 °C - (-200 °C)): 0.084 °C (0.151 °F)
Influence of ambient temperature = (35 - 25) x (0.002% x 200 °C - (-200 °C)), 0.08 °C (0.144 °F)
min. 0.005 °C
Influence of supply voltage = (30 - 24) x (0.002 % x 200 °C - (-200 °C)), 0.048 °C (0.086 °F)
min. 0.005 °C
Total measured error: √(Measured error² + influence of ambient temperature² + 0.126 °C (0.227 °F)
influence of supply voltage²:
Sensor transmitter matching RTD sensors are one of the most linear temperature measuring elements. Nevertheless, the output
must be linearized. To improve temperature measurement accuracy significantly, the device enables
the use of two methods:
• Callendar-Van Dusen coefficients (Pt100 resistance thermometer)
The Callendar-Van Dusen equation is described as:
-100 3
The coefficients A, B and C are used to match the sensor (platinum) and transmitter in order to
improve the accuracy of the measuring system. The coefficients for a standard sensor are specified
in IEC 751. If no standard sensor is available or if greater accuracy is required, the coefficients for
each sensor can be determined specifically by means of sensor calibration.
-100 3
These coefficients A, B and C are used for the linearization of nickel or copper resistance
thermometers (RTD). The exact values of the coefficients derive from the calibration data and are
specific to each sensor.
Sensor transmitter matching using one of the above-named methods significantly improves the
temperature measurement accuracy of the entire system. This is due to the fact that to calculate the
temperature measured, the transmitter uses the specific data pertaining to the connected sensor
instead of using the standardized sensor curve data.
Endress+Hauser 9
TMT84
Operational influences The data concerning the various measured errors correspond to a standard deviation of 2 σ (Gaussian
normal distribution)
Pt100 (1) ≤ 0.02 °C (0.036 °F) 0.002% x (MW - MBA). ≤ 0.12 °C (0.21 °F) 0.002% x (MW - MBA).
min. 0.005 °C (0.009 °F) min. 0.005 °C (0.009 °F)
Pt500 (3) IEC60751:2008 ≤ 0.014 °C (0.025 °F) 0.002% x (MW - MBA), ≤ 0.014 °C (0.025 °F) 0.002% x (MW - MBA),
min. 0.009 °C (0.016 °F) min. 0.009 °C (0.016 °F)
Pt50 (8) ≤ 0.03 °C (0.054 °F) 0.002% x (MW - MBA), ≤ 0.03 °C (0.054 °F) 0.002% x (MW - MBA),
min. 0.01 °C (0.018 °F) min. 0.01 °C (0.018 °F)
GOST 6651-94
Pt100 (9) ≤ 0.02 °C (0.036 °F) 0.002% x (MW - MBA), ≤ 0.02 °C (0.036 °F) 0.002% x (MW - MBA),
min. 0.005 °C (0.009 °F) min. 0.005 °C (0.009 °F)
Cu50 (10) - -
Cu100 (11) ≤ 0.008 °C (0.014 °F) 0.002% x (MW - MBA), ≤ 0.008 °C (0.014 °F) 0.002% x (MW - MBA),
OIML R84:2003 / min. 0.004 °C (0.007 °F) min. 0.004 °C (0.007 °F)
GOST 6651-2009
Ni100 (12) - -
≤ 0.004 °C (0.007 °F) ≤ 0.004 °C (0.007 °F)
Ni120 (13) - -
Digital1) Digital1)
Thermocouples (TC)
Type A (30) IEC 60584-1 ≤ 0.14 °C (0.25 °F) 0.0055% x MW, ≤ 0.14 °C (0.25 °F) 0.0055% x MW,
min. 0.03 °C (0.05 °F) min. 0.03 °C (0.005 °F)
Type B (31) IEC 60584-1 ≤ 0.06 °C (0.11 °F) - ≤ 0.06 °C (0.11 °F) -
Type C (32) IEC 60584-1 / ≤ 0.09 °C (0.16 °F) 0.0045% x MW, ≤ 0.09 °C (0.16 °F) 0.0045% x MW,
ASTM E988-96 min. 0.03 °C (0.05 °F) min. 0.03 °C (0.05 °F)
10 Endress+Hauser
TMT84
Digital1) Digital1)
Type D (33) ASTM E988-96 ≤ 0.08 °C (0.14 °F) 0.004% x MW, ≤ 0.08 °C (0.14 °F) 0.004% x MW,
min. 0.035 °C (0.063 °F) min. 0.035 °C (0.063 °F)
Type E (34) ≤ 0.03 °C (0.05 °F) 0.003% x (MW - MBA), ≤ 0.03 °C (0.05 °F) 0.003% x (MW - MBA),
min. 0.016 °C (0.029 °F) min. 0.016 °C (0.029 °F)
Type J (35) ≤ 0.02 °C (0.04 °F) 0.0028% x (MW - MBA), ≤ 0.02 °C (0.04 °F) 0.0028% x (MW - MBA),
min. 0.02 °C (0.036 °F) min. 0.02 °C (0.036 °F)
Type K (36) ≤ 0.04 °C (0.07 °F) 0.003% x (MW - MBA), ≤ 0.04 °C (0.07 °F) 0.003% x (MW - MBA),
min. 0.013 °C (0.023 °F) min. 0.013 °C (0.023 °F)
IEC 60584-1
Type N (37) ≤ 0.04 °C (0.07 °F) 0.0028% x (MW - MBA), ≤ 0.04 °C (0.07 °F) 0.0028% x (MW - MBA),
min. 0.020 °C (0.036 °F) min. 0.020 °C (0.036 °F)
Type R (38) ≤ 0.06 °C (0.11 °F) 0.0035% x MW, ≤ 0.06 °C (0.11 °F) 0.0035% x MW,
min. 0.047 °C (0.085 °F) min. 0.047 °C (0.085 °F)
Type L (41) DIN 43710 ≤ 0.02 °C (0.04 °F) - ≤ 0.02 °C (0.04 °F) -
Type U (42) DIN 43710 ≤ 0.01 °C (0.02 °F) - ≤ 0.01 °C (0.02 °F) -
Type L (43) GOST R8.8585- ≤ 0.02 °C (0.04 °F) - ≤ 0.02 °C (0.04 °F) -
2001
-20 to 100 mV - ≤ 3 μV - ≤ 3 μV -
MW = Measured value
MBA = Measuring range start of the respective sensor
Maximum
Pt100 (1) IEC 60584-1 ≤ 0.03 °C (0.05 °F) + 0.024% x ≤ 0.042 °C (0.076 °F)+ 0.035% x ≤ 0.051 °C (0.092 °F) + 0.037% x
measuring span measuring span measuring span
Pt200 (2) IEC 60584-1 ≤ 0.17 °C (0.31 °F) + 0.016% x ≤ 0.28 °C (0.5 °F) + 0.022% x ≤ 0.343 °C (0.617 °F) + 0.025% x
measuring span measuring span measuring span
Pt500 (3) IEC 60584-1 / ≤ 0.067 °C (0.121 °F) + 0.018% x ≤ 0.111 °C (0.2 °F)+ 0.025% x ≤ 0.137 °C (0.246 °F) + 0.028% x
ASTM E988-96 measuring span measuring span measuring span
Pt1000 (4) ASTM E988-96 ≤ 0.034 °C (0.06 °F) + 0.02% x ≤ 0.056 °C (0.1 °F) + 0.029% x ≤ 0.069 °C (0.124 °F)+ 0.032% x
measuring span measuring span measuring span
Endress+Hauser 11
TMT84
Pt100 (5) ≤ 0.03 °C (0.054 °F)+ 0.022% x ≤ 0.042 °C (0.076 °F) + 0.032% x ≤ 0.051 °C (0.092 °F) + 0.034% x
measuring span measuring span measuring span
Pt50 (8) ≤ 0.055 °C (0.01 °F) + 0..023% x ≤ 0.089 °C (0.16 °F) + 0.032% x ≤ 0.1 °C (0.18 °F)+ 0.035% x
measuring span measuring span measuring span
Pt100 (9) ≤ 0.03 °C (0.054 °F)+ 0.024% x ≤ 0.042 °C (0.076 °F) + 0.034% x ≤ 0.051 °C (0.092 °F) + 0.037% x
measuring span measuring span measuring span
Ni100 (6) ≤ 0.025 °C (0.045 °F) + 0.016% x ≤ 0.042 °C (0.076 °F) + 0.02% x ≤ 0.047 °C (0.085 °F) + 0.021% x
IEC 60584-1
measuring span measuring span measuring span
Ni120 (7) ≤ 0.02 °C (0,036 °F) + 0.018% x ≤ 0.032 °C (0.058 °F) + 0.024% x ≤ 0.036 °C (0.065 °F) + 0.025% x
measuring span measuring span measuring span
Cu50 (10) ≤ 0.053 °C (0.095 °F) + 0.013% x ≤ 0.084 °C (0.151 °F) + 0.016% x ≤ 0.094 °C (0.169 °F) + 0.016% x
measuring span measuring span measuring span
Cu100 (11) ≤ 0.027 °C (0.049 °F) + 0.019% x ≤ 0.042 °C (0.076 °F) + 0.026% x ≤ 0.047 °C (0.085 °F) + 0.027% x
measuring span measuring span measuring span
Ni100 (12) DIN 43710 ≤ 0.026 °C (0.047 °F)+ 0.015% x ≤ 0.04 °C (0.076 °F) + 0.02% x ≤ 0.046 °C (0.083 °F) + 0.02% x
measuring span measuring span measuring span
Ni120 (13) DIN 43710 ≤ 0.021 °C (0.038 °F) + 0.017% x ≤ 0.034 °C (0.061 °F) + 0.022% x ≤ 0.038 °C (0.068 °F) + 0.023% x
measuring span measuring span measuring span
Cu50 (14) GOST R8.8585- ≤ 0.056 °C (0.1 °F)+ 0.009% x ≤ 0.089 °C (0.16 °F) + 0.011% x ≤ 0.1 °C (0.18 °F) + 0.011% x
2001 measuring span measuring span measuring span
10 to 2000 Ω - ≤ 144 mΩ + 0.019% x measuring ≤ 238 mΩ + 0.026% x measuring ≤ 294 mΩ + 0.028% x measuring
span span span
Maximum
Type A (30) ≤ 0.17 °C (0.306 °F) + 0.021% x ≤ 0.27 °C (0.486 °F) + 0.03% x ≤ 0.38 °C (0.683 °F) + 0.035% x
measuring span measuring span measuring span
Type B (31) ≤ 0.5 °C (0.9 °F) ≤ 0.75 °C (1.35 °F) ≤ 1.0 °C (1.8 °F)
Type C (32) IEC60751:2008 ≤ 0.15 °C (0.27 °F) + 0.018% x ≤ 0.24 °C (0.43 °F) + 0.026% x ≤ 0.34 °C (0.61 °F) + 0.027% x
measuring span measuring span measuring span
Type D (33) ≤ 0.21 °C (0.38 °F) + 0.015% x ≤ 0.34 °C (0.61 °F)+ 0.02% x ≤ 0.47 °C (0.85 °F)+ 0.02% x
measuring span measuring span measuring span
Type E (34) JIS C1604:1984 ≤ 0.06 °C (0.11 °F) + 0.018% x ≤ 0.09 °C (0.162 °F) + 0.025% x ≤ 0.13 °C (0.234 °F) + 0.026% x
measuring span measuring span measuring span
Type J (35) ≤ 0.06 °C (0.11 °F) + 0.019% x ≤ 0.1 °C (0.18 °F) + 0.025% x ≤ 0.14 °C (0.252 °F) + 0.027% x
measuring span measuring span measuring span
GOST 6651-94
Type K (36) ≤ 0.09 °C (0.162 °F) + 0.017% x ≤ 0.14 °C (0.252 °F) + 0.023% x ≤ 0.19 °C (0.342 °F) + 0.024% x
(MW + 150 °C (270 °F)) measuring span measuring span
Type N (37) ≤ 0.13 °C (0.234 °F) + 0.015% x ≤ 0.2 °C (0.36 °F) + 0.02% x ≤ 0.28 °C (0.5 °F) + 0.02% x
(MW + 150 °C (270 °F)) measuring span measuring span
DIN 43760 IPTS-68
Type R (38) ≤ 0.31 °C (0.558 °F) + 0.011% x ≤ 0.5 °C (0.9 °F) + 0.013% x ≤ 0.69 °C (1.241 °F) + 0.011% x
(MW - 50 °C (90 °F)) measuring span measuring span
12 Endress+Hauser
TMT84
Type S (39) ≤ 0.31 °C (0.558 °F) + 0.011% x ≤ 0.5 °C (0.9 °F) + 0.013% x ≤ 0.7 °C (1.259 °F) + 0.011% x
measuring span measuring span measuring span
Type T (40) ≤ 0.09 °C (0.162 °F) + 0.011% x ≤ 0.15 °C (0.27 °F)+ 0.013% x ≤ 0.2 °C (0.36 °F) + 0.012% x
OIML R84:2003 / measuring span measuring span measuring span
Type L (41) GOST 6651-2009 ≤ 0.06 °C (0.108 °F) + 0.017% x ≤ 0.1 °C (0.18 °F)+ 0.022% x ≤ 0.14 °C (0.252 °F) + 0.022% x
measuring span measuring span measuring span
Type U (42) ≤ 0.09 °C (0.162 °F) + 0.013% x ≤ 0.14 °C (0.252 °F)+ 0.017% x ≤ 0.2 °C (0.360 °F)+ 0.015% x
measuring span measuring span measuring span
Type L (43) OIML R84:2003 / ≤ 0.08 °C (0.144 °F) + 0.015% x ≤ 0.12 °C (0.216 °F) + 0.02% x ≤ 0.17 °C (0.306 °F) + 0.02% x
GOST 6651-94 measuring span measuring span measuring span
-20 to 100 mV - ≤ 2 μV + 0.022% x measuring ≤ 3.5 μV + 0.03% x measuring ≤ 4.7 μV + 0,033% x measuring
span span span
Influence of reference point Pt100 DIN EN 60751 Cl. B, internal reference point for thermocouples TC
(cold junction)
Installation
Installation instructions • Mounting location:
A B
12
0
(4 mm
.72
in)
12
0
C (4 mm
.72
in)
A0016762
A: Terminal head as per DIN EN 50446 form B, direct installation onto insert with cable entry (middle hole 7 mm (0.28 in))
B: Separated from process in field housing, wall or pipe mounting
C: With DIN rail clip on top-hat rail as per IEC 60715 (TH35)
• Orientation:
No restrictions
Endress+Hauser 13
TMT84
Environment
Ambient temperature range -40 to +85 °C (-40 to +185 °F), for hazardous areas see Ex documentation (XA, CD)
Altitude up to 4000 m (4374.5 yd) above mean sea level in accordance with IEC 61010-1, CSA 1010.1-92
Degree of protection • IP00 with screw terminals. In the installed state, it depends on the terminal head or field housing
used.
• IP30 with spring terminals
• IP66/67 (NEMA Type 4x encl.) when installed in field housing TA30A, TA30D or TA30H
Electromagnetic CE compliance
compatibility (EMC) EMC to all relevant requirements of the IEC/EN 61326- series and NAMUR NE21. For details see
declaration of conformity.
Maximum measured error <1% of measuring range
Interference immunity: as per IEC/EN 61326 series (industrial environment) / NAMUR NE21
Interference emissions: as per IEC 61326-1 Class B
Measuring category Measuring category II as per IEC 61010-1. The measuring category is provided for measuring on power
circuits that are directly connected electrically with the low-voltage network.
14 Endress+Hauser
TMT84
Mechanical construction
Design, dimensions Specifications in mm (in)
Head transmitter
5 (0.2)
C
7 (0.28)
A
44 (1.73)
33 (1.3)
B
24.1 (0.95)
A0007301
28.1 (1.11)
A0007672
Model with spring terminals. The same dimensions except for height of housing.
Field housings
All terminal heads have an internal shape and size in accordance with DIN EN 50446, flat face and a
thermometer connection of M24x1.5. Cable glands: M20x1.5
TA30A Specification
Seals: silicone
15.5 (0.6)
Endress+Hauser 15
TMT84
91.6 (3.61)
• Cable entry incl. glands: ½"NPT und M20x1.5
15.5 (0.6)
• Head color: blue RAL 5012
• Cap color: gray RAL 7035
• Weight: 420 g (14.81 oz)
28
(1.1)78 (3.1)
A0009821
TA30H Specification
28
(1.1)
78 (3.01)
A0009832
28
(1.1)
78 (3.01)
A0009831
16 Endress+Hauser
TMT84
TA30D Specification
110 (4.3)
• Two head transmitters can be mounted. In the standard ver-
sion, one transmitter is mounted in the terminal head cover
15.5 (0.6)
and an additional terminal block is installed directly on the
insert.
• Head color: blue RAL 5012
• Cap color: gray RAL 7035
• Weight: 390 g (13.75 oz)
28
(1.1) 78 (3.1)
A0009822
Cable gland polyamide ½" NPT, M20x1.5 (non-Ex) -40...+100 °C (-40...+212 °F)
Cable gland polyamide M20x1.5 (for dust ignition-proof area) -20...+95 °C (-4...+203 °F)
Cable gland brass ½" NPT, M20x1.5 (for dust ignition-proof area) -20...+130 °C (-4...+266 °F)
Terminals Choice of screw or spring terminals (see "Design, dimensions" diagram) for sensor and fieldbus wires:
Screw terminals (with latches at the Rigid or flexible ≤ 2.5 mm2 (14 AWG)
fieldbus terminals for easy connection
of a handheld terminal, e.g. DXR375)
Endress+Hauser 17
TMT84
Operability
Display and operating There are no display or operating elements present at the transmitter.
elements Optional the plug-on display TID10 can be used in connection with the transmitter. It will display
information regarding the actual measured value and the measurement point identification. In the
event of a fault in the measurement chain this will be displayed in inverse color showing the channel
ident and diagnostics code. DIP-switches can be found on the rear of the display. This enables the
hardware set-up such as the PROFIBUS® device address.
a0009818
If the transmitter is installed in a field housing and used with a display, a housing with glas window
needs to be used.
Remote operation The configuration of PROFIBUS® PA functions and of device-specific parameters is performed via
fieldbus communication. Special configuration systems provided by various manufacturers are
available for this purpose.
Configuration software
Sources of supply of the device data files (GSD) and device drivers:
• GSD-file: www.endress.com (→ Download → Software)
• Profile GSD-file: www.profibus.com
• FieldCare/DTM, SIMATIC PDM (EDD): www.endress.com (→ Download → Software)
Bus address The device address or bus address is set up either with the configuration software or via DIP switches
on the optional display.
18 Endress+Hauser
TMT84
Hazardous area approvals For further details on the ailable Ex versions (ATEX, CSA, FM, etc.), please contact your nearest
Endress+Hauser sales organisation. All relevant data for hazardous areas can be found in separate Ex
documentation. If required, please request copies from us or your Endress+Hauser sales organisation.
Certification PROFIBUS® PA The temperature transmitter is certified and registered by the PNO (PROFIBUS® user organization
e.V.). The device thus meets all the requirements of the specifications following:
• Certified according to PROFIBUS® PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)
Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website:
www.endress.com → Click "Corporate" → Select your country → Click "Products" → Select the product
using the filters and search field → Open product page
→ The "Configure" button to the right of the product image opens the Product Configurator.
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration:
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring
range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Endress+Hauser 19
TMT84
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser
website:www.endress.com.
The following accessories are contained in the scope of delivery:
• Multi-language Brief Operating Instructions as hard copy
• Supplementary documentation ATEX:
ATEX Safety instructions (XA), Control Drawings (CD)
• Mounting material for head transmitter
• Mounting material for field housings (pipe or wall mounting)
DIN rail clip according to IEC 60715 (TH35) for head transmitter 51000856
mounting without securing screws
Standard - DIN mounting set (2 screws + springs, 4 securing disks and 1 71044061
display connector cover)
Documentation
• Operating instructions "iTEMP TMT84" (BA00257R/09/en) and associated Brief Operating
Instructions "iTEMP TMT84" (KA00258R/09/a2)
• Ex supplementary documentation:
ATEX II 1G Ex ia IIC: XA00069R/09/a3
ATEX II 2(1)G Ex ia IIC: XA01012T/09/a3
ATEX II 2G Ex d IIC and ATEX II 2D Ex tb IIIC: XA01007T/09/a3
• Operating instructions "Display TID10" (BA262R/09/c4)
• Guidelines for planning and commissioning "PROFIBUS® DP/PA" (BA034S/04/en)
20 Endress+Hauser
TMT84