BS-685 Waterproof LPG detector for conventional panels

BS-686 Waterproof natural gas-methane detector for conventional panels

TECHNICAL CHARACTERISTICS
BS-685 BS-686
Operation voltage 10-30V AC- DC ( Powered by panel)
Average consumption 0,5W ( 12VDC 40mADC, 24VDC 20mADC)
Sensitivity 5-15 % L.E.L. Propane 5-15 % L.E.L. Methane
Indicators alarm LED
Degrees of cover protection IP 65
Produced in accordance with EN 50194-1, EN 50270
Operation temperature range 0 to 60 oC
Humidity Up to 95% relative humidity
Dimensions 155 x 80 x 43 mm
Sensor life time 5 years
Weight 150 gr
Guarantee 2 years

Thank you for your trust in our products


Olympia Electronics - European manufacturer
OPERATION - USE made safe, and any necessary repair carried out.
BS-685 and BS-686 detectors are used in
combination with gas panels to give us a Placement
warning in case there is a natural gas or LPG Depending on the monitored gas, the unit must be
gas leak. The installation must be done by a placed with the sensor downwards, 30cm from
qualified personnel. Instructions must be read the ceiling (for methane, natural gas) or 30cm
before the installation. from the floor (for propane, LPG). The horizontal
distance should not be more than 4 meters from
Emergency Actions the probable gas leak point and the detectors
It is recommended that the following advice must not be placed in humid or drafty areas.
should be given in the event of an alarm It is suggested that the detector is tested for good
sounding or the smell of gas even without an operation every 6 months or if it is changed
alarm: position.
Keep calm, and carry out the following actions, The unit must should not be sited:
not necessarily in the order given: - directly above cooking appliances
-extinguish all flames, including smoking - directly above sink
material. - adjacent to extractor fans
- turn off all gas appliances. - in any outside location
- do not switch on or off any electrical equipment, -where the environmental conditions are outside
including the gas detection apparatus. the manufacturers operational specification.
- turn off the gas supply at the gas main control
and/or ( with a LPG supply) the storage tank. Installation
-open doors and windows to increase In order to install the device you must first remove
ventilation. the four srews (figure 1). Then with the
- do not use a telephone in the building where the assisstance of figures 2 and 3 you can connect it
presence of a gas is suspected. to the panel.
If the alarm continues to operate, even after an
alarm resetting action where appropriate, and Connection with fire panel of Olympia
the cause of the leak in not apparent and/or Electronics.
cannot be corrected, vacate the premises and Terminals ΖΟΝΕ are used to connect to zone of
IMMEDIATELY NOTIFY the gas supplier in the gas panel, as shown in figure 2. A terminal
order that the installation may be tested and resistor (5,6KÙ) should be installed on the end of

Page 1 from 5 921686000_09_017


the line(see figure 2). of the L.E.L. This is an alarm latch mode. This
mode is helpful to the technician, to locate the
Connection with others fire panel. device which is in alarm condition.
Terminals NO, C are used to connect to the zone When you connect the device to a conventional
of the gas panel, as shown in figure 2. A terminal gas panel, the device must have alarm latch
resistor should be installed on the end of the line mode. If we want to de-activate the alarm latch
(see figure 3). mode, the LD1 jumper must be linked. The link
or the removal should be done when the unit is
Programming Alarm latch mode not operating. The device is shipped with
When the device is in alarm mode, it keeps its activated the alarm latch.
condition even if the contents drop below 5-15%

Gland for cable


connection

These screws must be


unscrewed in order to remove
the plastic cover

LED Alarm The sensor must


faced downwards

Figure 1. Diagram of removing the plastic cover

Terminal Resistor
5Ê6

Ζ1
24V_M

Relay resistance
selection jumper

Fire panel
LED Alarm Olympia Electronics

Jumper for programming


alarm latch mode

Figure 2. Connection diagram of a detector


with a fire panel of Olympia Electronics

Page 2 from 5 921686000_09_017


Terminal Resistor

Ζone 10-30VDC
Relay resistance
selection jumper

Fire panel
LED Alarm

Jumper for programming


alarm latch mode

Figure 3.
Connection diagram of a detector with a fire panel of other company.
Sensitivity Relay resistance Selection (JMP RELAY)
The BS-685 detectors are activated when the There is the capability to select the alarm relays
content of gas (propane), in the monitored area, resistance, with the use of the resistance
exceeds 5 - 15% of the lower explosive level selection Jumper. When a link is used on the
(L.E.L). jumper, then the used resistance is zero, and an
The BS-686 detectors are activated when the external resistence may be used. If there is no
content of gas (methane), in the monitored area, link, then the on board resistence of 440 Ohm is
exceeds 5 - 15% of the lower explosive level used.
(L.E.L).
The devices are connected to 24_M, of a gas ATTENTION!! The devices must not be
panel, as shown in figure 2. When a detector is tested using gas filled lighters because the
activated, it gives an alarm signal to the gas sensor will be destroyed.
panel. The activation stops when:
A) You push the test button or when you cycle the
power of the detector (Alarm latch mode) (figure
4).
B) You push the test button or the gas content
drops below 5-15% of the L.E.L. (Νο alarm latch
mode) (figure 5).

Indication LEDS and Operation


When first installed, you must wait 20 seconds
until the sensor compensates to its surroundings.
When the red LED is lit then the unit is in alarm
mode. Alarm mode can be triggered from the
sensor of the unit. Figure 4 shows a connection
diagram between 4 BS-685 or BS-686 and a gas
panel.

Waterproofing of the device


The package contains a sealing gasket which is
installed on the rim of the front cover in order to
water-proof the unit.

Page 3 from 5 921686000_09_017


Ζ1
BS-685-6 BS-685-6 BS-685-6 BS-685-6

5Κ6

24V_M
Terminal
Resistance

Figure 4. Connection of 4 gas detector BS-685 or BS-686 to a


Olympia Electronics panel. The number of the devices connecting
to a gas panel is depending only to the panel specifications.

BS-690-1 Button Power LED


RED LED Alarm LED
A B Fault LED
1
P2

JMP1
1 JM

Sensor
P3
1 JM

SENSOR
GND

GND
OUT

+VS
NO
NC

EXTERNAL
Z-
Z+
N
C

S
L

BUZZER

RED LED

BS-655

L N
~230 V
BS-685-6

5Κ6

Figure 5. Connection diagram with BS-690 (no alarm latch mode)

Page 4 from 5 921686000_09_017


WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period
of warranty is specified in the official catalogue of Olympia Electronics and also in the
technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer
does not follow the technical instructions included in official documents given by Olympia
Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done
by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that
have been damaged can be returned to the premises of our company for repair or
replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not
charge the buyer depending on the reason of defection. Olympia Electronics reserves the
right to charge or not the buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
[email protected]

Page 5 from 5 921686000_09_017