DESCRIPTION
1. SCOPE
This specification covers circular, single, twin, three or four PVC insulated conductors
with a concentric conductor over the assembly of cores, rated 0.6/1KV, type NYCY to
IEC 60502-1; for use in aerial, direct burial, conduit, open tray and underground duct
installations, These cables offer high resistance to ageing, abrasion, moisture,
chemicals, oils and acids and afford protection of phase conductors against external
ingress.
2. CONSTRUCTION
Conductor STANDARDS
Plain, annealed electrolytic copper conductors, solid, circular stranded, or sectoral International IEC 60228;
stranded conforming to the applicable requirements of IEC 60228. IEC 60502-1
Insulation
Assembly
Insulated conductors are laid up, filled where necessary with non-hygroscopic material
and covered with an additional layer of extruded thermoplastic material or a Polyester
binding tape.
Concentric Conductor
Bare, plain, annealed electrolytic copper wires are layed over the common covering of
cores with a counter helix of copper tape on top.
Sheath
Conductor flexibility Rated Voltage Uo/U (Um) Bending factor when laying Minimum installation temperature Max.conductor temp.in service
Class 2 IEC 60228 0,6/1 kV 10 (xD) 15 °C 70 °C
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 3/14/24 www.libancables.com Page 1 / 5
AntiTheft Power Cable, PVC insulated
PVC sheathed (ENYCY)
CHARACTERISTICS
Construction characteristics
Conductor flexibility Class 2 IEC 60228
Conductor material Copper class 2
Insulating material PVC
Concentric conductor Copper wires and helical copper tape
Outer sheath PVC
Electrical characteristics
Rated Voltage Uo/U (Um) 0,6/1 kV
Usage characteristics
Bending factor when laying 10 (xD)
Minimum installation temperature -15 °C
Max. conductor temperature in service 70 °C
Short-circuit max. conductor temperature 160 °C
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 3/14/24 www.libancables.com Page 2 / 5
AntiTheft Power Cable, PVC insulated
PVC sheathed (ENYCY)
Nom. Perm.
Nom. Nom. Max. DC
Screen outer Approx. current Rodent
Country Conductor insulation overall Resist.
section sheath weight rating resista
Ref. shape thick. diam. Cond. 20°C
[mm²] thick. [kg/km] open air nt
[mm] [mm] [Ohm/km]
[mm] [A]
ENYCY Circular
7*2.5+2.5 stranded 0.8 2.5 1.8 16.5 415 7.41 26 Yes
(AR) (RM)
Circular
NYCY
stranded 0.8 2.5 1.8 20.0 516 7.41 26 Yes
9*2.5+2.5
(RM)
ENYCY Circular
10*2.5 stranded 0.8 2.5 1.8 20.0 555 7.41 26 No
+2.5 (RM)
Circular
NYCY 4*4
stranded 0.8 4 1.8 17.0 444 4.61 32 Yes
+4
(RM)
Circular
NYCY
stranded 0.8 4 1.8 21.0 647 7.41 26 Yes
12*2.5+4
(RM)
Circular
NYCY 4*6
stranded 0.8 6 1.8 18.5 556 3.08 41 Yes
+6
(RM)
Circular
NYCY
stranded 0.8 6 1.8 22.0 733 7.41 26 Yes
14*2.5+6
(RM)
ENYCY Circular
19*2.5+6 stranded 0.8 6 1.8 24.0 919 7.41 26 Yes
(AR) (RM)
Circular
ENYCY
stranded 1.0 4 1.8 18.5 533 4.61 32 No
5*4+4
(RM)
Circular
ENYCY
stranded 1.0 6 1.8 20.0 677 3.08 41 No
5*6+6
(RM)
Circular
ENYCY
stranded 1.0 10 1.8 22.0 961 1.83 57 No
5*10+10
(RM)
Circular
ENYCY
stranded 1.0 16 1.8 25.0 1342 1.15 76 No
5*16+16
(RM)
Circular
ENYCY
stranded 1.2 16 1.8 29.0 1892 0.524 125 No
4*35+16
(RM)
Circular
ENYCY
stranded 1.2 16 1.8 32.0 2286 0.524 125 No
5*35+16
(RM)
Circular
ENYCY
stranded 1.4 50 2.0 34.0 2863 0.387 151 No
4*50+50
(RM)
ENYCY
3*95 Shaped 1.6 50 2.2 38.0 3738 0.193 232 No
+50SM
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 3/14/24 www.libancables.com Page 3 / 5
AntiTheft Power Cable, PVC insulated
PVC sheathed (ENYCY)
Nom. Perm.
Nom. Nom. Max. DC
Screen outer Approx. current Rodent
Country Conductor insulation overall Resist.
section sheath weight rating resista
Ref. shape thick. diam. Cond. 20°C
[mm²] thick. [kg/km] open air nt
[mm] [mm] [Ohm/km]
[mm] [A]
ENYCY
4*95 Shaped 1.6 50 2.3 42.0 4769 0.193 232 No
+50SM
ENYCY
4*150 Shaped 1.8 70 2.6 50.0 7182 0.124 309 No
+70SM
Routine Tests
- Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-1 parag. 15.1 & 15.2
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided .
Sample Tests
- Check of dimensions
These tests will be carried out on one length of each size during each inspection .
Type Tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance
with IEC 60502-1.
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 3/14/24 www.libancables.com Page 4 / 5
AntiTheft Power Cable, PVC insulated
PVC sheathed (ENYCY)
INSULATION COLORS:
All numbered control cables (6 conductors and above), are insulated with white color, and numbered with black digits
LIBAN CABLES DESCRIPTION RATED VOLTAGE SECTION MM2 Year of manufacture meter marking
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.